Automatic Fire Sprinkler Systems
Chapter 5
© 2008 Delmar, Cengage Learning
Learning Objectives
• Describe an automatic fire sprinkler system• Discuss the myths and realities associated with
automatic fire sprinkler system operation• State the factors that determine requirements to
install automatic fire sprinkler systems• Discuss the design concepts behind automatic
fire sprinkler systems
© 2008 Delmar, Cengage Learning
Learning Objectives (continued)
• List and describe different occupancy and commodity classification
• Describe different types of automatic fire sprinkler systems and the best applications for those systems
• Discuss the inspection and test requirements for acceptance of water-based fire protection systems
© 2008 Delmar, Cengage Learning
Introduction• Automatic fire sprinkler system: network of
piping with sprinkler heads at specific intervals– Upon activation, applies water over the fire area
• Common myths:– All sprinkler heads operate simultaneously– Sprinkler heads activate for no reason– Water discharged will cause a flood or drown a
person– Costs more to repair water damage than fire damage– Smoke detector activation will cause sprinkler to
operate
© 2008 Delmar, Cengage Learning
Introduction (continued)
• Facts about sprinkler heads:– Operate independently, only in fire area– Undergo numerous tests by third-party organizations
• Rarely accidentally activate
– Exposure to fire and smoke damage limited• Fire hose could cause substantially more damage
– Majority of smoke detectors operate independently of sprinkler systems
© 2008 Delmar, Cengage Learning
Effectiveness in Property Protection
• Basis for sprinkler system design is to keep a fire at a relatively small size, under control
• Prevents extensive damage that would have closed the facility, injured occupants
• Frequently, businesses never recover from a fire when there are injuries or loss of life
© 2008 Delmar, Cengage Learning
Effectiveness in Life Safety• Primary purpose is to provide property
protection– Not necessarily life safety
• Sprinklers provide some level of life safety– Systems may interact with other building safety
systems
• Residential systems provide higher level of life safety
• Not more than two people have died in a fire where complete sprinkler system installed
© 2008 Delmar, Cengage Learning
Required Installations• Most early requirements came from property
insurance companies• Requirements changed with development of
model codes– Changes were gradual– Code changes only affected new building construction
• Incentives provided for installation of automatic fire sprinkler systems
• Model codes today establish requirements based on use and occupancy conditions
© 2008 Delmar, Cengage Learning
Design and Installation Standards
• Published standards available from model code and insurance organizations
• Three primary standards:– NFPA 13: Installation of Sprinkler Systems– NFPA 13D: Installation of Sprinkler Systems in One-
and Two-Family Dwellings and Manufactured Homes– NFPA 13R: Installation of Sprinkler Systems in
Residential Occupancies Up To and Including Four Stories in Height
© 2008 Delmar, Cengage Learning
NFPA 13, Standard for the Installation of Sprinkler Systems
• First published in 1896• Performance objective: maintain control of a fire• Contain the fire to general area of origin by
applying water• Sprinkler heads cover all spaces in the building
– Includes concealed combustible spaces, attics, above and below ceilings
• In many cases, sprinkler can suppress the fire
© 2008 Delmar, Cengage Learning
NFPA 13D, Standard for the Installation of Sprinkler Systems in
One- and Two-Family Dwellings and Manufactured Homes
• Published in 1975• Addresses residential fire problem
– Places sprinklers in home where fire likely to start– Excludes small bathrooms, closets, unheated areas
• Standard relies on research and testing data
© 2008 Delmar, Cengage Learning
NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies Up to and
Including Four Stories in Height• Concerns hotels, motels, apartments, condos• Loosely follows NFPA 13 requirements• At least one FDC in the building• Places sprinkler heads where fire most likely to
start
© 2008 Delmar, Cengage Learning
Other Fire Sprinkler Standards• Other standards deal with level of hazard
exceeding NFPA 13• Standards state the applicability
– Establish design criteria based on conditions– Specify sprinkler head characteristics and appropriate
types
• Do not specify installation methods or dictate how to lay out a system
• Ultimately the design professional determines the type of system best suited to the hazard
© 2008 Delmar, Cengage Learning
Design Concepts for Automatic Fire Sprinkler Systems
• Design starts with classifying the occupancy, commodities, storage arrangement– Evaluate the combustibility
• System must deliver enough water to absorb energy from the fire
• Design professional decides whether to use a pipe schedule or hydraulic design
© 2008 Delmar, Cengage Learning
Design Concepts for Automatic Fire Sprinkler Systems (continued)
• Density/area curves: graphic representation of a minimum amount of water over a specific area
• Amount of water is minimum design density– Area of coverage is the remote area
• Contractor records system information on hydraulic design information sign
© 2008 Delmar, Cengage Learning
Fire Sprinkler System Components
• Components require listing or approval from third-party testing and certification laboratory– Underwriters Laboratories, FM Global
• Many supporting components are common to all the different types of fire sprinkler systems
• Each type of automatic sprinkler system uses specific type of valve
• Some design and installation objectives require special types of sprinkler heads
© 2008 Delmar, Cengage Learning
Pipe and Fittings• Join together to provide a conduit for water• Must handle maximum permitted system working
pressure of 175 psi• ASTM standard establishes internal and external
pipe dimensions and wall thicknesses• Thinner pipe has larger internal diameter
– Offers hydraulic design advantages because there is less friction loss
• CPVC pipe dominant type of piping used for residential installations
© 2008 Delmar, Cengage Learning
Gauges
• Pressure gauges important• Some systems have water gauges
– Other systems have water and air gauges
• Help to determine whether there is a problem with the system
• Should not be subject to freezing temperatures• Each should have a control valve capable of
draining
© 2008 Delmar, Cengage Learning
Valves• Water control valves permit water to flow into
and through the system when open– Prevent water flow, isolate parts of the system when
closed
• Valves placed in locations that are clearly accessible
• Water control valves must be indicating-type– Must handle 175 psi
• Check valves permit water or air to flow in one direction
© 2008 Delmar, Cengage Learning
Support and Stabilization of Pipe• Majority of piping runs horizontally across ceiling
– Fasteners stabilize the pipe– Riser clamps hold vertical pipes in position
• All supporting materials must be made of ferrous materials for heat resistance
• Spacing and location of hanger components depend on the size and type of piping
• Hanger assembly consists of fastener, threaded rod, ring that holds the pipe– Bracing, guides, restraints provide stability
© 2008 Delmar, Cengage Learning
Automatic Sprinkler Heads
• Spray device that distributes water over a limited area at a designated flow rate
• Reduces heat from a fire– Limits and controls fire’s growth
• Heat-activated– Heat-sensitive element head releases so that the
parts holding back the water fall away
• Each head operates independently
© 2008 Delmar, Cengage Learning
Automatic Sprinkler Heads (continued)
• Frame holds other pieces in place• Heat-sensitive element attach to the frame,
hold orifice cap in place• Orifice is the smooth opening in the head
through which water flows from the pipe• Orifice cap covers the orifice• Deflector creates the spray pattern of the water
© 2008 Delmar, Cengage Learning
Automatic Sprinkler Heads (continued)
• Types of sprinkler heads– Old Style, Standard Spray, Specialty Heads– Pendent, Upright, and Sidewall Heads– Special Application Sprinkler Head Identification– Heads for Particular Conditions and Applications– Heads for Aesthetic Purposes
• K-factor classifies the head by factor number• Modern heads resemble heads of 100 years ago
© 2008 Delmar, Cengage Learning
Types of Systems
• Four basic types of automatic fire sprinkler systems
• Each has characteristics appropriate for particular situations and applications
• Most commonly installed types of systems• Basis for other types of water-based fire
protection systems
© 2008 Delmar, Cengage Learning
Wet Pipe Systems
• Least expensive, most frequently installed– Easiest to maintain, modify, and most reliable
• Limited area sprinkler systems provide protection without installing full building system
• Require dedicated water supply and usually have an alarm check valve
• Clapper inside the valve acts as a check valve• Common in almost every type of building
© 2008 Delmar, Cengage Learning
Figure 5-29 Wet pipe sprinkler system schematic
© 2008 Delmar, Cengage Learning
Dry Pipe Systems• Best system to protect building where temperature
falls below 40 degrees– Unheated warehouses, attics, loading docks, etc.
• Pressurized air maintained in the system piping until system activates
• Dry pipe valves prevents water from entering the system until needed– Operates on water-to-air differential
• Size and layout of system affects time to deliver water
© 2008 Delmar, Cengage Learning
Figure 5-31 Dry pipe sprinkler system schematic
© 2008 Delmar, Cengage Learning
Pre-action Systems
• Similar to dry pipe systems, using closed sprinkler heads
• Normally no water in system piping• Fire detectors release the pre-action valve• Require two separate events before water
discharges– Fire detector activates and releases pre-action valve– Sprinkler head activates to flow water
© 2008 Delmar, Cengage Learning
Figure 5-35 Pre-action sprinkler system schematic
© 2008 Delmar, Cengage Learning
Deluge Systems
• Operate similar to pre-action systems• Open to the atmosphere because sprinkler
heads open to the atmosphere• Open sprinkler heads do not have a heat-
sensing element• Discharge immediate and simultaneous from all
sprinkler heads• Deluge valve receives signal from detection
system
© 2008 Delmar, Cengage Learning
Figure 5-37 Deluge sprinkler system schematic
© 2008 Delmar, Cengage Learning
Residential Sprinkler Systems• Benefits derive from change in emphasis from
property protection to life protection• Design concepts:
– Prevent flashover– Improve occupants chance for rescue or escape
• Vast majority are wet pipe systems• Many share water supplied by domestic water line• Residential sprinkler head satisfies different
testing criteria
© 2008 Delmar, Cengage Learning
Inspection, Testing, and Maintenance Requirements
• Approval process for automatic sprinklers similar to fire lines and standpipes
• Approving authority determines if system installed according to plans
• Requirements are in various standards used to design the systems
• Most periodic inspections, tests and maintenance follow inspection and test protocols
© 2008 Delmar, Cengage Learning
Acceptance Inspections and Tests
• Acceptance inspections during construction similar from system to system
• Flushing: incoming fire line requires flushing before connecting water supply to sprinkler
• Hydrostatic air tests: subjects system to predetermined pressure for minimum duration
• Hydrostatic tests for residential systems: verify no system leaks with source water pressure
© 2008 Delmar, Cengage Learning
Acceptance Inspections and Tests (continued)
• Visual inspection: confirm the design and installation meet standards
• Operation of Components: verify that the system will operate when needed
• Main Drain Test: establishes that the incoming water supply is adequate, with no impairments
© 2008 Delmar, Cengage Learning
Periodic Inspection, Testing, and Maintenance
• Provide a level of certainty that the system will operate when called upon
• Same tests used to accept a system can be used to verify proper operation– Conducted at regular intervals
• Impairments result from a lack of maintenance, component failure, etc.
• Typical impairments: closed control valves, damaged sprinkler heads, broken piping, etc.
© 2008 Delmar, Cengage Learning
Summary
• Sprinkler systems designed to keep a fire small and under control
• Not all automatic sprinkler systems are alike• For well over 100 years, sprinkler systems have
protected property and life• Automatic fire sprinkler systems offer building
owners and homeowners a reliable, effective, economical, and proven protection system