Annex B3 – Technical Offer Form
Page 1 of 11
Technical Offer Form
FOR ELECTRICAL AND LIGHTNING PROTECTION SYSTEM – Bidders need to
Submit complete catalogue and specification for the system with brand names and
brochures.
TECHNICAL DATA FOR SWITCHBOARDS, DISTRIBUTION BOARDS AND ACCESSORIES
ITEM NO. DESCRIPTION OFFER
A. SWITCHBOARDS
1 MSB & EMSB
a. Manufacturer
b. Country of Manufacture
c. Colour finish
d. Type of sheet metal Electro-galvanised steel sheets
e. Design Ambient Temperature (40C)
2 SUB-SWITCHBOARD
a. Manufacturer
b. Colour Finish
c. Enclosure required: Drip-proof natural ventilated
d. Design Ambient Temperature (40C)
3 DISTRIBUTION BOARDS
a. Manufacturer
b. Colour Finish
c. Enclosure required : Drip proof natural ventilated
d. Design Ambient Temperature (40C)
B. ELECTRICAL COMPONENTS
1 ACB
a. Manufacturer / Origin
b. Model / Type No.
c. Rated Current / Voltage
d. Short-time withstand current (3 sec)
2 MCCBS
a. Manufacturer
b. Model / Type No.
c. Interrupting Capacity
3 MCB
a. Manufacturer
b. Model / Type No.
Annex B3 – Technical Offer Form
Page 2 of 11
c. Interrupting Capacity
Auxiliary Power Supply Voltage
4 SELECTOR SWITCHES
a. No. of Selection Positions (Ammeter)
b. No. of Selection Positions (Voltmeter)
5 INDICATING LAMPS
a. Manufacturer
b. Transformer operated type
c. Watt / Volts
6 PROTECTION RELAYS (OVERCURRENT & EARTH FAULT RELAY)
a. Manufacturer
b. Model No.
c. Type of Description
d. No. of poles
7 ELCB/RCCD
a. Manufacturer
b. Model / Type No.
c. Earth Leakage Sensitivity
8 EARTH FAULT RELAY (STATIC TYPE)
a. Manufacturer
b. Model No.
c. Type Description
d. No. of poles
9 EARTH LEAKAGE RELAY (ELR)
a. Manufacturer
b. Model / Type No.
c. Leakage current setting
d. Time delay setting range
10 CURRENT TRANSFORMERS
a. Manufacturer
b. Ratio
c. Class - Protection
d. Class - Metering
e. Rated Burden
11 CONTACTORS
a. Manufacturer
b. Model / Type No.
c. Duty Category
d. Peak switching current
12 SHORT CIRCUIT TYPE TESTS
Switched type manufactured type tested for short circuits of 50kA of 1 sec.
Annex B3 – Technical Offer Form
Page 3 of 11
TECHNICAL DATA FOR LV CABLES & CABLING INSTALLATIONS
ITEM NO. DESCRIPTION OFFER
1 LV CABLING :
1.1 PVC / PVC Cables
a) Manufacturer
b) Standards
c) Voltage Grade
d) Insulation Material
e) Multi-stranded copper conductors
1.2 XLPE / PVC Cables
a) Manufacturer
b) Standards
c) Voltage Grade
d) Insulation Material
e) Multi-stranded copper conductors
1.3 PVC/SWA/PVC Cables:
a) Manufacturer
b) Standards
c) Voltage Grade
d) Multi-stranded copper conductors
e) Galvanised Steel Wire Armoured
1.4 XLPE/SWA/PVC Cables :
a) Manufacturer
b) Standards
c) Voltage Grade
d) Multi-stranded copper conductors
e) Galvanised Steel Wire Armoured
1.5. Fire Resistant / MICC Cables:
a) Manufacturer
b) Material type
2 CABLING ACCESSORIES :
2.1 Cable Termination Glands:
a) Manufacturer
b) Type
c) State material used for gland
2.2 Cable Sockets / Lugs
a) Manufacturer
b) Method of Cable / Socket Connection
c) Material of Cable Socket
2.3 Cables Cores markers (slip-in type)
a) Manufacturer
Annex B3 – Technical Offer Form
Page 4 of 11
b) Type
c) Material used
2.4 Cable Sleeve Markers:
a) Manufacturer
b) Type
c) Material used
3 GI CONDUITS:
a) Manufacturer
b) Type
c) Material used
4 PVC PIPE:
a) Manufacturer
b) Type
c) Material used
5 CABLE TRUNKING:
a) Manufacturer
b) Type
c) Material used
d) Thickness
e) Standard length
6 CABLES LADDER:
a) Manufacturer Hot dipped galvanised
b) Material used
c) Thickness
d) Standard length
7 CABLES TRAYS:
a) Manufacturer Hot dipped galvanised
b) Material used
c) Thickness
d) Standard length
TECHNICAL DATA FOR LIGHTING, SWITCHES, SOCKET OUTLET, ETC)
ITEM NO. DESCRIPTION OFFER
1 2x4 LED Recessed/Surface Light Fitting c/w LED Tube
a) Name of Manufacturer
b) Model
c) Country of Manufacture
d) Lamp colour
e) Total watt
f) Dimension
2 Double Bare Channel Light Fitting with LED tube (normal/weatherproof type)
Annex B3 – Technical Offer Form
Page 5 of 11
a) Name of Manufacturer
b) Model
c) Country of Manufacture
d) Lamp colour
e) Total watt
f) Dimension
3 Single Bare Channel Light Fitting with LED tube (normal/weatherproof type)
a) Name of Manufacturer
b) Model
c) Country of Manufacture
d) Lamp colour
e) Total watt
f) Dimension
4 LED DOWNLIGHTER :-
a) Name of Manufacturer
b) Model
c) Country of Manufacture
d) Lamp colour
e) Total watt
f) Dimension
5 SWITCHES AND SWITCHES SOCKET OUTLET
5.1 Light Switches
a) Flush Lighting Switch
b) Flush Push Button Switch
c) Flush Dimmer Switch
d) Metalclad Lighting Switch
e) Grid Switch
f) Weather Proof IP56 Lighting Switch
g) Weather Proof IP56 Push Button Switch
h) Surface Mounted 230V 20A IP56 Switch
I) Surface Mounted 400V 20A to 60A IP56 Switch
5.2 Switched Socket Outlet
a) 13A Surface Flush Mounted S/S/O
b) 13A Surface Flush Mounted S/S/O c/w Pilot Light
c) 13A Metalclad Switched Socket Outlet
d) 15A Switched Socket Outlet
e) Weatherproof Switched Socket Outlet
6.1 EMERGENCY LIGHTING LUMINAIRE
a) Name of Manufacturer
b) Country of Manufacture
c) Local Agent
6.2 SELF-CONTAINED EMERGENCY KELUAR SIGN
a) Name of Manufacturer
Annex B3 – Technical Offer Form
Page 6 of 11
b) Country of Manufacture
c) Local Agent
d) Mode of Operation
e) Input Voltage
TECHNICAL DATA FOR LIGHTNING PROTECTION EQUIPMENT
ITEM NO. DESCRIPTION OFFER
LIGHTNING PROTECTION MATERIALS:-
1 COPPER TAPE:
a) Make
b) Model No.
c) Type
d) Material
2 ALUMINIUM TAPE:
a) Make
b) Model No.
c) Type
d) Material
3 SQUARE TAPE CLAMP
a) Make
b) Model No.
c) Type
d) Material
4 TEST CLAMP:
a) Make
b) Model No.
c) Type
d) Material
5 BI-METALLIC CONNECTOR:
a) Make
b) Model No.
c) Type
d) Material
6 ‘U’ BOLT ROD CLAMP :
a) Make
b) Model No.
c) Type
d) Material
7 EARTH POINT :
a) Make
b) Model No.
c) Type
d) Material
Annex B3 – Technical Offer Form
Page 7 of 11
8 CONCRETE INSPECTION EARTH CHAMBER
a) Make
b) Model No.
c) Dimension
d) Material
e) Size of Earth Bar
9 TAPE CLIP :
a) Make
b) Model No.
c) Type
d) Material
TECHNICAL DATA FOR EARTHING
ITEM NO. DESCRIPTION OFFER
1 EARTH POINT:
a) Make
b) Model No.
c) Type
d) Material
2 CONCRETE INSPECTION EARTH CHAMBER
a) Make
b) Model No.
c) Dimension
d) Material
e) Size of Earth Bar
3 EXOTHERMIC WELD :
a) Make
b) Type
c) Type of Weld Powders
4 CONDUCTOR (STRANDED COPPER CONDUCTOR)
a) Make
b) Type
c) Size
d) Strand (No. / Dia.)
e) Wt / kg
f) Model No.
5 25 x 3mm CU TAPE
a) Make
b) Type
c) Size
d) Wt / kg
e) Model No.
6 EARTH ROD:
Annex B3 – Technical Offer Form
Page 8 of 11
a) Make
b) Type
c) Model No.
d) Nom. Diameter
e) Length
TECHNICAL DATA FOR SURGE PROTECTION DEVICE (SPD)
A) POWER SURGE PROTECTOR FOR MAIN SWITCH BOARD (3-PHASE)
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 415V
2 Max. working voltage, Uc 475V
3 Mode of protection 7 Module, Full Mode
(L-N, L-E & N-E)
4 Max. discharge current, Imax (8/20µs) 80kA
(L-N / L-E / N-E)
5 Let - through voltage, Up
at 10kA (8/20µs), 20kV (1.2/50µs) < 1.8kV
at 5kA (8/20µs), 10kV (1.2/50µs) < 1.2kV
at 3kA (8/20µs), 6kV (1.2/50µs) < 950V
6 Response time < 25ns
7 Standard of compliance MS IEC 61643-11
8 Local compliance SIRIM QAS Test Certificate
Manufacture 'MALAYSIA BRAND' Certificate
9 Status of indication LED indicators
10 Type of termination Parallel
11 Type of arrester MARSA - MONOBLOCK / MOV
12 Warranty against manufacturing defects 2 years
B) POWER SURGE PROTECTOR FOR SUB SWITCH BOARD (3-PHASE)
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 415V
2 Max. working voltage, Uc 475V
3 Mode of protection 7 Module, Full Mode
(L-N, L-E & N-E)
4 Max. discharge current, Imax (8/20µs) 40kA
Annex B3 – Technical Offer Form
Page 9 of 11
(L-N / L-E / N-E)
5 Let - through voltage, Up
at 10kA (8/20µs), 20kV (1.2/50µs) < 1.8kV
at 5kA (8/20µs), 10kV (1.2/50µs) < 1.2kV
at 3kA (8/20µs), 6kV (1.2/50µs) < 950V
6 Response time < 25ns
7 Standard of compliance MS IEC 61643-11
8 Local compliance SIRIM QAS Test Certificate
Manufacture 'MALAYSIA BRAND' Certificate
9 Status of indication LED indicators
10 Type of termination Parallel
11 Type of arrester MARSA - MONOBLOCK / MOV
12 Warranty against manufacturing defects 2 years
C) POWER SURGE PROTECTOR FOR DISTRIBUTION BOARD (3-PHASE)
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 415V
2 Max. working voltage, Uc 475V
3 Mode of protection 7 Module, Full Mode
(L-N, L-E & N-E)
4 Max. discharge current, Imax (8/20µs) 20kA
(L-N / L-E / N-E)
5 Let - through voltage, Up
at 10kA (8/20µs), 20kV (1.2/50µs) < 1.7kV
at 5kA (8/20µs), 10kV (1.2/50µs) < 1.2kV
at 3kA (8/20µs), 6kV (1.2/50µs) < 950V
6 Response time < 25ns
7 Standard of compliance MS IEC 61643-11
8 Local compliance SIRIM QAS Test Certificate
Manufacture 'MALAYSIA BRAND' Certificate
9 Status of indication LED indicators
10 Type of termination Parallel
11 Type of arrester MARSA - MONOBLOCK / MOV
12 Warranty against manufacturing defects 2 years
Annex B3 – Technical Offer Form
Page 10 of 11
D) POWER SURGE PROTECTOR FOR DISTRIBUTION BOARD (SINGLE PHASE)
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 240V
2 Max. working voltage, Uc 275V
3 Mode of protection 3 Module, Full Mode
(L-N, L-E & N-E)
4 Max. discharge current, Imax (8/20µs) 20kA
(L-N / L-E / N-E)
5 Let - through voltage, Up
at 10kA (8/20µs), 20kV (1.2/50µs) < 1.7kV
at 5kA (8/20µs), 10kV (1.2/50µs) < 1.2kV
at 3kA (8/20µs), 6kV (1.2/50µs) < 950V
6 Response time < 25ns
7 Standard of compliance MS IEC 61643-11
8 Local compliance SIRIM QAS Test Certificate
Manufacture 'MALAYSIA BRAND' Certificate
9 Status of indication LED indicators
10 Type of termination Parallel
11 Type of arrester MARSA - MONOBLOCK / MOV
12 Warranty against manufacturing defects 2 years
E) POWER SURGE PROTECTOR FOR DISTRIBUTION BOARD (SINGLE PHASE)
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 240V
2 Max. working voltage, Uc 275V
3 Mode of protection 3 Module, Full Mode
(L-N, L-E & N-E)
5 Max. discharge current, Imax (8/20µs) 40kA
(L-N / L-E / N-E)
6 Let - through voltage, Up
at 10kA (8/20µs), 20kV (1.2/50µs) < 1.7kV
at 5kA (8/20µs), 10kV (1.2/50µs) < 1.2kV
at 3kA (8/20µs), 6kV (1.2/50µs) < 950V
7 Response time < 25ns
8 Standard of compliance MS IEC 61643-11
9 Local compliance SIRIM QAS Test Certificate
Annex B3 – Technical Offer Form
Page 11 of 11
Manufacture 'MALAYSIA BRAND' Certificate
10 Status of indication LED indicators
11 Type of termination Parallel
12 Type of arrester MARSA - MONOBLOCK / MOV
13 Warranty against manufacturing defects 2 years
F) POWER LINE SURGE PROTECTOR AT THE EQUIPMENT END
DESCRIPTION TECHNICAL
REQUIREMENT COMPLY / NOT COMPLY
1 Nominal voltage, Un 120Vac / 240Vac
2 Max. working voltage, Uc 130Vac / 275Vac
3 Mode of protection Full Mode
(L-N, L-E & N-E)
4 Max. load Current 13 Amps
5 Max. discharge current, Imax (8/20µs) 20kA
(L-N / L-E / N-E)
6 Let - through voltage, Up <300V
at 1kA (8/20µs), 2kV (1.2/50µs)
7 Working frequency 40-60 Hz
8 Standard of compliance MS IEC 61643-11
9 Local compliance SIRIM QAS Test Certificate Manufacture 'MALAYSIA BRAND' Certificate
10 Status of indication LED indicator
11 Type of termination Series
12 Type of arrester MARSA - MOV
13 Warranty against manufacturing defects 2 years
Supplier Name :