Upload
independent
View
0
Download
0
Embed Size (px)
Citation preview
Building Thermal Network Model
and Application to Temperature Regulation
Qi Luo and Kartik B. Ariyur
Abstract— Residential and commercial facilities account forover 40% of energy consumption in the US. Our work showshow fine grain modeling and sensing of this consumption canlead to substantial savings. We construct a thermal networkmodel of a building with the temperatures of the various roomsas states; with the room thermal capacitances and thermalresistances between the rooms as parameters; the externalor ambient temperatures as uncontrolled input and heatingand cooling loads as control inputs. We show the effects onenergy consumption of the random opening and closing ofdoors or windows. We show that active management of roomtemperature set points saves up to 20% of energy costs . Wealso demonstrate the substantial savings–up to 30%–throughstrategies of keeping certain doors and windows closed.
I. INTRODUCTION
Heating and cooling of both residences and commercial fa-
cilities accounts for the lion’s share of energy consumption–
over 40%–in the United States. Utilities building the Smart
Grid [1], [2] on the one hand and consumers switching to
Smart Appliances [3] on the other hand raise the possibility
of significant savings of energy in a variety of applications.
The availability of real time cost and consumption infor-
mation from smart meters and measurements [4] opens up
several avenues for savings. The utilities can save through
monitoring vulnerability, [5] and electrical [6] or gas loads
in real time; the integration of renewable energy sources
into the grid; and the integration of distributed generation
into the grid. Consumers can save through use of real-time
pricing information and schedule their energy consumption
for intervals of relatively lower prices; they can also use
smart appliances and sensors to keep track of their patterns
of energy use and systematically cut waste.
In this context, we develop a higher fidelity model of
building heat consumption (or equivalently cooling load) that
uses the distributed sensing and data logging expected to be
available, and can account for human habits. The building
is modeled as a thermal network–a passive circuit with room
heaters as heat sources and the ambient environment as the
heat sink. The thermal resistances between rooms or that
between rooms and the ambient can change randomly if
doors or windows are opened or closed. Thus, we have a
stochastic hybrid system that can have any of a finite number
of system dynamics. Our model renders some strategies of
energy savings explicit and gives means to quantify them.
Qi Luo is with the School of Mechanical Engineering, , Purdue Univer-sity, West Lafayette, IN 47906, USA [email protected]
Kartik B. Ariyur is with the School of Mechanical Engineering, , PurdueUniversity, West Lafayette, IN 47906, USA [email protected]
It also opens up several possibilities–such as helping con-
sumers track their consumption precisely and craft strategies
to cut their energy costs. We show that a simple strategy of
closing doors in a building can lead to a saving of 30%in energy costs–which runs counter to the current trend of
cubicle farms in commercial facilities.
The paper is organized as follows: Section II introduces
the thermal network model of the building, Section III details
the thermal connectivity matrix for a building, Section IV
supplies a simple distributed energy saving control strategy
for the building, Section V shows illustrative results from
using the model for temperature regulation for facilities, and
Section VI supplies concluding remarks.
II. THERMAL NETWORK MODEL
In prior work [7], which used a lumped building thermal
model, we showed the potential of energy savings via active
energy management. Here we posit a higher fidelity model
to enable better quantification of those benefits. The model
relates the environmental conditions of a building to its
heating and cooling loads. The model is obtained through
combining convective and conductive heat transfer between
the building and its surroundings. Overall, we have, for a
single room,
miCp
dθi
dt=
m∑
j=1
1
( 1
hini
Aij+
Lij
kijAij+ 1
houtj
Aij)(θout − θi)
+
n∑
k=1
1
( 1
hini
Aik+ Lik
kikAik+ 1
hikAik)(θk − θi) + Qi (1)
where, typically,
m + n = 6 (2)
because a cuboidal (typical room) has only six faces. The
parameters and variables in the differential equations are
room thermal mass mi, specific heat capacity Cp, which
is approximately constant because of small temperature
range, the air temperature inside the room θi, the ambient
temperature θout, the conduction coefficient of the brick
connecting jth wall of room i with ambient environment kij ,
the area of the jth wall connecting room i and the ambient
environment Aij , the thickness of the jth wall connecting
room i and the ambient environment Lij , the convection
coefficient between the outside air and the jth wall houtj ,
the convection coefficient between the inside air and the
wall hini , and in the second part of the equation, kik is the
2010 IEEE International Conference on Control ApplicationsPart of 2010 IEEE Multi-Conference on Systems and ControlYokohama, Japan, September 8-10, 2010
978-1-4244-5363-4/10/$26.00 ©2010 IEEE 2190
TABLE I
THE TABLE OF ROOM PROPERTIES
ρ(kg/m3) c(J/kg − K) k(W/m − K)Room 1.16 1007 —
Walls 2050 — 1.921900 — 1.922050 — 1.922050 — 0.52
Ambient Air — — —
TABLE II
THE TABLE OF ROOM PROPERTIES(CONTINUE)
h(W/m2− K) A(m2) L(cm) V (m3)
Room 5.0 — — 125
Walls 5.0 25 2 —5.0 25 10 —5.0 25 2 —5.0 25 20 —
Ambient Air 18.0 — — —
conduction coefficient of the brick connecting rooms i and
k, Aik is the area of the wall connecting rooms i and k, Lik
is the thickness of the wall connecting rooms i and k, hik
is the convection coefficient between the air of room k and
wall of room i, Qi is the inside wall heating/cooling load.
If we account for the difference in heat transfer coefficient
between situations where the door is open versus situations
where the door is closed into consideration, the equation can
be rewritten as:
miCp
dθi
dt=
6∑
j=1
(DijCij − (1−Dij)Cij)(θj −θi)+ Qi (3)
where the parameter Cij is the heat transfer coefficient
when the door/window/connection between rooms i and j is
closed or there is no connection, the parameter Cij is the
heat transfer coefficient when the door/window/connection
between rooms i and j is open. Dij is an indicator function
defined as follows:
Dij =
{
1 door/window between i and j closed
0 door/window between i and j open(4)
Tables I and II are from references [8], [9] and sum
up the thermal properties of a single room and ambient
environment.
III. EQUIVALENT HEAT TRANSFER
COEFFICIENT MATRIX
In general, a one-to-one mapping may not exist between
heat loss and door/window/connection closures. This is seen
from the simple observation that several rooms can be of
the same size and have the same thermal connections. To
understand the system of differential equations in Eqn (3),
the equivalent heat transfer coefficient connectivity matrix
(EHCM) is introduced and described.
The EHCM C is constructed from Copen, which is
the EHCM when all doors inside the building are open,
and Cclosed, which is the EHCM when all doors inside
the building are closed. To illustrate this, we will use the
examples in Figures 1, 2, and 3.
Fig. 1. Building structure 1
Fig. 2. Building structure 2
The figures give examples of 3 possible 4-room-building
structures, and each of them can be represented by Copen
and Cclosed individually, but the structure and size of the
connectivity matrix are identical:
Cclosed =
C11 C12 C13 C14 C15
C21 C22 C23 C24 C25
C31 C32 C33 C34 C35
C41 C42 C43 C44 C45
C51 C52 C53 C54 C55
(5)
and
2191
Fig. 3. Building structure 3
Copen =
C11 C12 C13 C14 C15
C21 C22 C23 C24 C25
C31 C32 C33 C34 C35
C41 C42 C43 C44 C45
C51 C52 C53 C54 C55
(6)
where the indices 1−4 represent rooms 1−4, and index 5
represents ambient environment. Cij and Cij are constructed
according to the following rules.
Connection: If the rooms i and j (or ambient envi-
ronment) are directly connected, Cij and Cij represents
respectively the equivalent heat transfer coefficient between
rooms i and j (or ambient environment) when the door is
closed or open, Cij and Cij are equation (3). And Cii is
defined to be zero for all i.Non-Connection: If rooms i and j (or ambient environ-
ment) are not directly connected, the equivalent heat transfer
coefficient is zero. The physical meaning is that there is no
direct heat transfer between these regions.
In prior work, we neglected the effect of the open or
closed status of the doors on the building thermal model.
Nevertheless, in a real building, some of the doors are open
and some of them are closed, and the EHCM of the building
C is a combination of elements of Copen and C
closed. We
use the a priori probability of a door being open Popen to
help build up the C matrix for simulation.
Bernoulli distribution of door/window open (closed):
We assume that each door is open (closed) at any time
according to a constant probability Pij (1 − Pij ). Thus,
the doors are either open or closed according to the prob-
abilities in a matrix P, each of whose elements pro-
vides probability of an individual connection being open.
In the frequency interpretation of probability, popenij refers
to the proportion of time in a day in which the door
is open. This also lends itself to simulation, in that we
perform a Monte-Carlo simulation of the building with
C matrices chosen according to the probability matri-
ces and then averaging them to estimate the expected
bill. In doing so, we are assuming ergodicity of stochas-
tic process, i.e., time average, limT→∞
1
T
∫ T
0
∑
Qi dt =
phase space average, E <∑
∫
Qidt >.
In our simulations, we explore the simplest case: Each
room has at most one door and all of them have the same
probability of being open, i.e., all nonzero Pij=Popen, which
can be acquired from the empirical data and used to generate
a random connectivity matrix between the rooms:
Cij =
0 room i and j not directly connected
Cclosedij door between i and j is closed/no door
Copenij open door connecting i and j
(7)
For commercial facilities, some doors open and close more
often and their open probabilities may need to be estimated
individually from data. For residences, however, the C matrix
does not change very often.
IV. CONTROL FOR ENERGY MANAGEMENT
In current building thermal control, the set point of indoor
temperature is always adjusted manually, so it is always the
case that the heater in the room is still on while no one is in
during a specific time period, or the temperature set point can
be relatively high when the real time gas price is at a high
level. Our control goal is to reduce the energy cost of these
situations. The model shows that minimization of heat loss is
equivalent to maximization of energy saving: In steady state,
i.e.
dθi
dt= 0 (8)
for ∀i and
min∑
∫
Qidt ⇔ min∑ ∑
∫
Cij(θi − θj)dt (9)
We assume that temperature control is performed by a
standard on-off controller in the thermostat. The switching
is performed as follows
Qin =
{
Qmax when θseti − θi(t) exceeds δ
0 when θi(t) − θseti exceeds δ
(10)
where δ is the deadzone parameter. In order to maintain
human comfort, we assume that the temperature set-point
θset will lie between a suitable Tmin and Tmax.
Tmin < θset < Tmax (11)
The adaptation of the set-point is performed to reactively
reduce the cost of gas used.
θset = θset + min(0, 1/UA/Pgas(VgasPgas −Cgas)) (12)
The parameters in the above equations are as follows: the
cost of gas per second Cgas; the volume of gas expected
to be consumed Vgas per second; and the cost per volume
2192
unit of gas Pgas, and weighted heat transfer coefficient UA,
which is defined as:
UA =6
∑
i=1
(DijCij − (1 − Dij)Cij) (13)
From these equations, we can set different expected volumes
based on instant gas prices to maintain the bill at a low level.
V. EXAMPLE OF BUILDING THERMAL
NETWORK MODEL
A. An Example of Four Room Building
We first illustrate the advantages of active management for
the 4 room building model in Figure 4. We assume that δ =0.5K in Eqn (10) and Tmin = 288.5K(60F ) and Tmax =300K(80F ) in Eqn (11).
Fig. 4. A simple four room building model
This structure has four rooms with thermal interactions
denoted as Room1-Room4, and have four doors denoted as
Door1-Door4, where Door1 connects Room1 and ambi-
ent, Door2 connects Room2 and Room3, Door3 connects
Room3 and Room4, Door4 connects Room4 and ambient.
If we take into consideration the thermal effect of the
open and closed status of the doors within the building, we
will have the element C15 within the C matrix affected by
the open/closed status of Door1, C12 within the C matrix
affected by the open/closed status of Door2, C35 within the
C matrix affected by the open/closed status of Door3, and
C34 within the C matrix affected by the open/closed status
of Door4. For the purpose of simulation, we assume an
a priori probability Popen = 0.3 that a door is open. We
generate fifty C matrices satisfying the probability condition
and calculate the consumption profile for each of them. We
then calculate the expected consumption profile by averaging
these trajectories. Figures 5 through 8, show the simulation
results. Specifically, Figures 5 and 6 show the building indoor
temperature and gas cost when all doors are closed. Figures 7
and 8 show the building indoor temperature and gas cost
when all doors are open. It can be seen that the thermal
0 100 200 300 400 500 600240
250
260
270
280
290
300
Time, s
T, K
Temperautres of building model (type one) without active control
T(1)T(2)T(3)T(4)T(out)
Fig. 5. Temperatures of building model (all doors closed) without activecontrol
0 100 200 300 400 500 6000
2
4
6
8x 10
4
Time,sH
eat
Com
sum
ption,J
Heat consumption of building model (type one) without active control
0 100 200 300 400 500 6000
1
2
3x 10
−3
Time,s
Bill,$
Bill of advanced building model(type one) with active temperature control
Fig. 6. Heat consumption of building model (all doors closed) withoutactive control
properties of the building have a significant change from all
doors inside closed to all doors inside open. The main reason
is that when the doors open, especially Door1 and Door3,
the major heat exchange method changes from convection
and conduction to diffusion, and the heat loss rate to the
ambient environment increases greatly. Figures 9 and 10
show the building indoor temperature in an instance and
average gas cost when the probability of any door being
open is given by Popen = 0.3.
Figures 11 and 12 show an instance of the inside
temperature of this four room building with active control,
its average heat consumption and gas cost respectively. The
set point is adapted according to Equation (12). Figure 12
shows a cost saving of some 20% compared to Figure 10.
B. Energy Cost vs Number of Open Doors Inside the Build-
ing
In order to analyze the relationship between the energy
cost and the number of open doors inside the building, we
2193
0 100 200 300 400 500 600245
250
255
260
265
270
275
280
285
290
Time, s
T,
K
Temperautres of building model (type two) without active control
T(1)T(2)T(3)T(4)T(out)
Fig. 7. Temperatures of building model (all doors open) without activecontrol
0 100 200 300 400 500 6007.9999
8
8
8
8.0001x 10
4
Time,s
He
at
Co
msu
mp
tio
n,J
Heat consumption of building model (type two) without active control
0 100 200 300 400 500 6000
0.001
0.002
0.003
Time,s
Bill,$
Bill of advanced building model (type two) without active temperature control
Fig. 8. Heat consumption of building model (all doors open) without activecontrol
0 100 200 300 400 500 600240
250
260
270
280
290
300
Time,s
T,
K
Building temperautre without active control
T(1)T(2)T(3)T(4)T(out)
Fig. 9. Building temperature without active control with Popen = 0.3
0 100 200 300 400 500 6000
2
4
6
8x 10
4
Time,s
He
at
Co
msu
mp
tio
n,J
Heat Consumption of Building Without Active Temperature Control
0 100 200 300 400 500 6000
1
2
3x 10
−3
Time,s
Bill,$
Bill of the Building Without Active Temperature Control
Fig. 10. Building heat consumption and bill without active control withPopen = 0.3
0 100 200 300 400 500 600245
250
255
260
265
270
275
280
285
290
295
Time, s
T,
K
Temperautres of advanced building model with active control
T(1)T(2)T(3)T(4)T(out)
Fig. 11. Building temperature with active control with Popen = 0.3
0 100 200 300 400 500 6000
2
4
6
8x 10
4
Time,s
He
at
Co
msu
mp
tio
n,J
Heat consumption of advanced building model with active control
0 100 200 300 400 500 6000
1
2
3x 10
−3
Time,s
Bill,$
Bill of advanced building model with active temperature control
Fig. 12. Building heat consumption and bill with active control withPopen = 0.3
2194
Fig. 13. Building with fifteen Rooms and sixteen Doors
0 2 4 6 8 10 12 14 160.006
0.0065
0.007
0.0075
0.008
0.0085
0.009
Number of doors open
En
erg
y c
ost
$/s
The energy cost vs number of opening doors
Fig. 14. Energy cost vs number of open doors inside the building
simulate a building of fifteen rooms with the structure shown
in Figure 13.
The building has fourteen regular rooms and one corridor
which is treated as the fifteenth room. We plot the energy
cost versus the number of open doors inside the building
in Figure 14. It is clear from the plot that energy cost
increases as the number of doors increases-a whopping 30%in this illustrative example. This is a problem in many
large buildings with a constant traffic at the outside doors,
including the Purdue Mechanical Engineering building. The
specific fast changes of room temperature and overall heater
outputs following door openings and closures, if logged by
a smart building environment control system, will permit
tracking of consumer habits, and indeed specific actions such
as the opening/closing of doors.
VI. CONCLUSIONS AND FUTURE WORK
We have shown how better modeling and more sensors can
help reduce building energy consumption more than 20%.
Our modeling framework, implemented in SIMULINK can
handle arbitrary structures of connectivity within buildings.
It is usable as an optimization tool in smart HVAC systems.
In conjunction with real-time pricing of electricity or gas,
and the temperature preferences of the consumer, the model
can help derive which doors and windows in a building must
be left open or closed.
There are several avenues where we plan to use this model.
The first is to model consumer demand and demand response
of consumers to utility pricing; the second is in identifying
habits of consumption, keeping doors open or closed, from
real-time energy consumption data that may come from smart
metering. The latter will be useful for utilities trying to
balance their loads through the day and night.
However, our assumption of steady state where maximiza-
tion of energy saving is equivalent to minimization of heat
losses may not be valid for commercial facilities where the
EHCM changes randomly and often. That is, commercial
building will always be in a transient; another assumption
we may evaluate is the absence of mass flows and pressure
differences between rooms and between the building and
the ambient, and this becomes important when temperature
differences are large; further analysis needs to be done to
evaluate the building thermal network model in this case.
In the case of central residential heating, flue gas from the
furnace often sent directly into rooms. Hence we may have
to account better for these mass flows.
VII. ACKNOWLEDGMENTS
We wish to acknowledge discussions with Anoop K.
Mathur of Terrafore.
REFERENCES
[1] H. Farhangi, ”The path of the smart grid,” IEEE Power and Energy
Magazine, vol. 8, pp. 18–28, January-February 2010.
[2] Stan M. K., Fred S., Amy A., Jon W., Suedeen G. K., and James J.H., Smart Grid, first edition, The Capitol 2009.
[3] C-Y. Chen, Y-P. Tsou, S-C. Liao, C-T. Lin, ”Implementing thedesign of smart home and achieving energy conservation,” 7th IEEE
International Conference on Industrial Informatics, pp. 273–276,June 23–26, 2009.
[4] R. V. Gerwen, S. Jaarsma and R. W., KEMA, ”SmartMetering”,available at Leonardo Energy Orgnization, July 2006.
[5] Anurag S. and Alexander F., Contingency Screening Techniques And
Electric Grid Vulnerabalities, first edition, VDM Verlag Dr. Muller2008.
[6] Reynaldo N., Electric Power Monitoring with Synchronized Power
Measurements, first edition, VDM Verlag Dr. Muller 2009.
[7] Q. Luo, K. B. Ariyur and A. K. Mathur, ”Real Time EnergyManagement : Cutting the Carbon Footprint and Energy Costs viaHedging, Local Sources and Active Control”, Proceedings of theASME Dynamic Systems and Control Conference, Hollywood, CA,October 2009.
[8] N. Mendes, G. H. C. Oliveira, H. X. Arajo and L. S. Coelho, ”AMATLAB based simulation tool for thermal performance analysis,”8th International IBPSA Conference, pp. 855–862, Eindhoven,Netherlands, August 2003.
[9] M. G. Davies, ”Building Heat Transfer”, John Wiley & Sons,Hoboken, NJ, 2004
2195