INTELLECT-69INSTALLATION&OPERATINGINSTRUCTIONS
VersionV_41
MODELSINT-69RTINT-69RINT-69T(withRS232&RS422Option)
9931801/27/10
KESSLER-ELLIS PRODUCTS10IndustrialWayEastEatontown,NJ07724
800-631-2165•732-935-1320Fax:732-935-9344
ht tp : / /www.kep.com
ProprietaryNotice
Theinformationcontainedinthispublicationisderivedinpartfromproprietaryandpatentdata.Thisinformationhasbeenpreparedfortheexpressedpurposeofassistingoperatingandmaintenancepersonnelintheefficientuseoftheinstrumentdescribedherein.Publicationofthisinformationdoesnotconveyanyrightstouseorreproduceitortouseforanypurposeotherthaninconnectionwiththeinstallation,operationandmaintenanceoftheequipmentdescribedherein.
Copyright1990PrintedinUSA.AllRightsReserved.
WARNING!This instrument containselectronic components that are susceptible todamageby staticelectricity.Properhandling*proceduresmustbeobservedduringtheremoval,installation,orhandlingofinternalcircuitboardsordevices.
*HandlingProcedure
1.Powertounitmustberemoved.
2.Personnelmustbegrounded,viawriststraporothersafe,suitablemeans,beforeanyprintedcircuitboardorotherinternaldeviceisinstalled,removedoradjusted.
3.Printedcircuitboardsmustbetransportedinaconductivebagorotherconductivecon-tainer.Boardsmustnotberemovedfromprotectiveenclosureuntiltheimmediatetimeofinstallation.Removedboardsmustbeplacedimmediatelyinprotectivecontainerfortransport,storage,orreturntofactory.
Comments
ThisinstrumentisnotuniqueinitscontentofESD(electrostaticdischarge)sensitivecompo-nents.Mostmodernelectronicdesignscontaincomponentsthatutilizemetaloxidetechnology(NMOS,CMOS,etc.).Experiencehasproventhatevensmallamountsofstaticelectricitycandamageordestroythesedevices.Damagedcomponents,eventhoughtheyappeartofunctionproperly,mayexhibitearlyfailure.
!
TABLE OF CONTENTS
SAFETYINSTRUCTIONS........................................................... 1
DESCRIPTION&SPECIFICATIONS........................................... 2
MOUNTING.................................................................................. 3
WIRING........................................................................................ 4
TYPICALWIRING........................................................................ 5
OPENCOLLECTOR&RELAYOPERATION.............................. 5
PROGRAMMINGFLOWCHART.................................................. 6
DEFINITIONS............................................................................... 7
FRONTPANELOPERATIONS.................................................... 10
PROGRAMMING......................................................................... 10
SETTINGPRESETS&PANELLOCK......................................... 15
RS232/422OPERATIONS.......................................................... 16
RS232/422WIRING.................................................................... 20
TROUBLESHOOTINGGUIDE..................................................... 21
WARRANTY................................................................................. 22
DECODINGPARTNUMBER....................................................... 22
1
! SAFETY INSTRUCTIONSThe following instructions must be observed.
• ThisinstrumentwasdesignedandischeckedinaccordancewithregulationsinforceEN60950(“Safetyofinformationtechnologyequipment,includingelectricalbusinessequipment”).
Ahazardoussituationmayoccurifthisinstrumentisnotusedforitsintendedpurposeorisusedincorrectly.Pleasenoteoperatinginstructionsprovidedinthismanual.
• Theinstrumentmustbeinstalled,operatedandmaintainedbypersonnelwhohavebeenproperlytrained.Personnelmustreadandunderstandthismanualpriortoinstallationandoperationoftheinstrument.
• Theuseofanexternallinefuseisrecommended.Addorreplacetheexternalfusewiththefollowingspecifiedtypeandratingonly:
Input Power Recommended Fuse 115VAC 100mAslowblowfuse 230VAC 50mAslowblowfuse 12-24VDC 250mAslowblowfuse
Disconnect power supply before adding or replacing fuse!
• Themanufacturerassumesnoliabilityfordamagecausedbyincorrectuseoftheinstrumentorformodificationsorchangesmadetotheinstrument.
Symbols Used On Unit Number Symbol Publication Description 1 IEC417,No.5031 Directcurrent
2 IEC417,No.5172 EquipmentprotectedthroughoutbyDOUBLEINSULATIONorREINFORCEDINSULATION(equivalenttoClassIIofIEC536–seeannexH)
3 ! ISO3864,No.B.3.1 Caution(refertoaccompanyingdocuments)
Technical Improvements•Themanufacturerreservestherighttomodifytechnicaldatawithoutpriornotice.
2
DESCRIPTION & SPECIFICATIONS
Description:Featuring6digitsofbright,7-segmentLEDdisplays,thisunitisanintegratingtotalizer/ratemeterwhichac-ceptsanalogsignalinputs.Theunitcanbefieldpro-grammedtoaccept0-20mA,4-20mA,0-5V,0-10Vor1-5Vsignals.AnoptionalSquareLawinputisavail-able for inputs that require square root extraction.A 4-20mA output option is available to control striprecorders or other peripherals. Two assignable setpointsarestandardfortwostageshutoff. Thehighand lowscalingsettingsareprogrammable fromthefront panel. By pressing the "view" button, the unitwilldisplay:integratedtotal,rate,peakorvalley.RS-422 or RS-232 serial communications are availableoptionsfordatacommunicationwithahostcomputer.Specifications:Display: 6digit,.55"high,LED.Input Power: 110,220VAC±15%or12to24VDC.Current: maximum 300mADC or 10.0 VA at ratedACvoltage.Output Power: (AC powered units only) + 24VDC.@50mAregulated±5%Temperature:Operating:+41°F(5°C)to+130°F(+54°C).Storage:-40°F(-40°C)to+200°F(93°C).Memory:EEPROMstoresdatafortenyearsifpowerislost.Reset:FrontPanel:resetsdisplayedvaluesandcontrolout-puts.Remote:4-30VDCpositiveedge,resetstotalizerandcontroloutputs.Control Outputs:Standard:Opencollectorsinks250mAfrom30VDCwhenactive.Optional: 2 each FormC SPDT 5Amp@ 120/240VAC or 28 VDC. (Open collector outputs are alsosupplied with 10VDC provided at transistor outputsthroughrelaycoil.Ifgreaterthan2mAisused,relaywillremainenergized.Applyinggreaterthan10VDCmaydestroyunit.Transistorwillsink100mAin"ON"state.)Input:Standard: Linear0-20mA,4-20mA,0-5V,0-10Vor1-5Vselectablefromthefrontpanel.Optional:SquareLaw0-20mA,4-20mA,0-5V,0-10V,or1-5V,isavailableforinputsthatrequiresquarerootextraction.Input Impedance:Current:100Ω;Voltage:115KΩCalibration: Theunitdoesallofthecalibrationsinter-nally.Therearenopotentiometerstoadjustandtheunitneverneedstoberemovedfromthecase.Set Points: Thetwocontrolsetpointscanbesetatany
numberfrom0to59999.Thesetpointoutputscanbeassignedtorateortotal.Theunitcomesstandardwithtwoopencollectorcontroloutputs.Two5Amp,FormCrelaysareoptional.Theoutputsareprogrammablefrom .01 to 599.99 sec or latched until reset whenassigned to the totalandahysteresis (alarmrange)whenassignedtotherate.Rate Display:Updates5timespersecond,Accurateto4.5digits.Set"low"greaterthan"high"forinverteddisplay(LINEARONLY).Totalizer: Integrates from the rate reading and ac-cumulatesupto6digitsoftotalcount.Thetimebase(hours,minutesorseconds)isfieldprogrammablefromthefrontpanel.Analog Out: Theunitcanbeorderedwithanoptional4-20mAoutputwhich isproportional to the instanta-neousrate.(Thenormalizingaveragingfactordoesnotaffecttheanalogoutput)Thehighandlowsettingsareprogrammablefromthefrontpanel.Set"low"greaterthan"high"forinvertedoutput.Asinkingdrivergener-atesacorrespondinglinearcurrentthroughtheexternaldevices.Theoutputupdateswitheachupdateoftherate.Accuracyis50uAworstcase.Forratedaccuracy,loadmustbeconnectedtotheanalogoutputbeforeunitispowered.Compliancevoltagemustbe3to30VDCnoninductive.(TheunitcanprovidetheDCsourceaslongasthedropacrossthedevicesbeingdrivendoesnotexceed21V).Programming: Decimal points, Scaling from 0 to59999unitsperselectedtimebase,setpoints,inputtype,securitylockcode,andassigningoutputsareallprogrammablefromthefrontpanel.Housing:Standard1/8DIN,highimpact94VOplasticcase.Shipping Weight:2lbs.Overvoltage Protection:50VOvercurrent Protection: 50mAResolution: 14.5BitsAccuracy: RANGE %FSERROR %FSERROR (worstcase) (typical)4-20mA 0.1% .05%0-10VDC 0.2% 0.1%0-5VDC .25% .15%1-5VDC .25% .15%
SquareLaw:(above5%ofbottomrange)0.1%(5Vinputs.4%)Worstcaseovercompleterange:2%
Temperature Stability: Willnotdriftmorethan20partspermillionper°Cfrom5°Cto54°C
3
MOUNTINGHOW TO MOUNT:
Slidethebodyoftheunitthroughtherubbergasket.Inserttheunitintothepanel.Slidethebracketsupthegroovetopressagainstthebackofthepanel,asshownin"FIG.A".Insertthescrewsintotherearofthebrackets.
Tightenthescrewsevenlyandalternately.Apanellessthan.1"maydistortiftheclampsarescrewedtootightly.Donotovertighten!Anormalleveloftorqueisrequired.Maximumtorqueshouldbe3"pounds.Thepanelmustbeparalleltothebezeltoas-sureproperseal.UnitsealstoNEMA4/IP65ifproperlymounted.
FIG. A
4.437(112.7)
2.625(66.68)
3.925(99.7)
3.622(92)
1.772(45)
.587 4.245(107.8)
BEZEL
GASKET
CUSTOMER PANELPanel Thickness 0.062" (1.5)to 0.187" (4.7) max.
4
WIRING
WIRING CONNECTIONS
AC/DCCONNECTIONS:NOTE:Connectpoweronlyafterotherconnectionsarefinished.DonottouchtheliveACpowertermi-nals.TheunithasbeendesignedwithanisolatedACinput,thereforepolarityisnotaconcernfortheACpower.Thechassisisplastic,thereforeearthgroundisnotused. ForDCoperation,connect+DCtoterminal10and-DCtoterminal3.
ThisProductcomplieswithrequirementsoftheEu-ropeanCommunityDirective89/336/EEC[Electro-magneticCompatibility].However,electricalnoiseorintenseelectromagneticfieldsinthevicinityoftheunitmaydisturbthemicroprocessor.Usersshouldexercisecareandshouldtakeproperprecautionstoavoidmicroprocessordisturbance.
Fourcommonsourcesofnoiseare:
1)ACpowerlinenoise-Theinputpowerlinesshouldnotbecommontopowerlinesformotors,pumps,contactors,etc.Iftheunitcannotbeconnectedtoanelectricallycleanpowersource,an inductiveloadsuppressingdevice(MOVasGE#V130LA1orResistorCapacitorasPaktron#.2uf/220ohm@400V)canbeinstalled.AlthoughlocatingthesuppressoracrosstheACsupplyattheunitshouldhelp,bestresultsareobtainedbyconnectingthesuppressoracrosstheleadsofthe"load"atthedevicecausingthespikes.
2)Inputlinenoise-ThenoiseiscarriedontheinputandDCgroundlines.Makesuretheinputwiresarenot run into theunit inabundlewithpowerinputlines.Werecommendusingshieldedcable.ConnecttheshieldtoDCgroundoftheunitand"earth"atonepointinthecircuitpreferablyattheDCgroundterminaloftheunit.
3)Outputlines-Theunithastwoopencollectoroutputs and two optional relay outputs. Whentheseoutputsareusedtorunexternalrelaysorsolenoids,spikescanbegenerateduponactiva-tion.Thisnoisecanspreadthroughtheinstrumentcausingoperatingproblems.IfthesourceisaD.C.operateddevice,ageneralpurposediode(IN4004)placedacrossthesolenoidpreventselectricalnoisespikes.Connectthecathode(bandedside)tothemorepositivesideofthecoil.IfthesourceisanA.C.operateddevice,useaResistorCapacitororMOVacrossthecoil.
4)24VDCoutputsupply-Noisecanbegeneratedonthe24VDCoutputsupplyifitisusedtodriveinductiveloadsorifthecurrentdrawexceeds50mA.Insurethatallinductiveloadshaveadiode(suchas IN4004)across thecoil and that thecurrentdoesnotexceed50mA.
NOTE: ForadditionalovercurrentprotectiontheuseofanexternalfuseisrecommendedontheDCoutputaswellasRelayOutputconnections.Itishighlyrecommendedtouseanexternalfuseforthepowerinputconnection(see"TypicalWiring"diagrams.
REAR VIEW1 2 3 4 5 6 7 8 9 10 11 12
13 14 15 15 17 18 RESET INANALOG OUT (SINK)SIGNAL GND (-DC)(CURRENT) +I IN(VOLTAGE) +V INNOT USED+24V OUTPRESET B COLLECTORPRESET A COLLECTOR+D.C. IN110 / 220 VAC110 / 220 VAC
101112
123456789
RELAY B
RELAY A131415161718
COMMON N.C. N.O. COMMON N.C. N.O.
!
5
Theopencollectorandrelayoutputstriggerwhenthetotalorrate(assignable;seeprogrammingstep2)equalsorexceedsthecorrespondingPreset(AorB).Whentheoutputsareassignedtothe"total",theoperatorcanassignadurationoftime(.01to599.99sec.)thattheoutputwillremainenergized.If0.00isassigned,theoutputwilllatchuntilreset.IfoutputAissetataduration(otherthan0.00),thetotalizerwillautorecyclewhenPresetAisreached.Atthistime,outputBwillde-energize(ifitwasenergized).PresetAisthefinalpresetandshouldbesethigherthanPresetB,whenbothoutputsareassignedtothetotal. IfoutputAissetatadurationotherthan0.00andPresetAisset
lessthanPresetB,PresetBwillbeignored(providedthattheyarebothassignedtototal).ThetotalizerwillneverautorecycleatPresetB.Whentheoutputsareassignedtothe"rate",theout-putscanbeassignedahysteresis(alarmrange).Thehysteresisisthenumberofunitsbelowthepresetthattheoutputwillremainenergized.EXAMPLE:Presetset@100;Hysteresisset@10.Theoutputwillenergizewhentherateequals100andde-energizewhentheratefallsbelow90(10belowPreset).
NOTE: Iftheinputscalingisinverted,thecontroloutputfunctionsareinverted(LINEARONLY).
TYPICAL WIRING
OPEN COLLECTOR & RELAY OPERATION
3-Wire0-10VTransmitter2-Wire4-20mATransmitter
•3 -
Sign
al G
ND
(-D
C)•4
- I I
n +
(Cur
rent
). . •1
1 - A C
In•1
2 - A C
In
- +
PowerSupply
Flowmeter(4-20mA Transmitter)
AC
PowerFuse
(user supplied)
•13 Common•14 N.C.•15 N.O.•16 Common•17 N.C.•18 N.O.
Relay A
Relay B
AC Supply
MOVrecommendedfor inductive
loads
Neutral
LOAD
- +DCSupply
LOAD-
+ Dioderecommendedfor inductive
loads
2-Wire4-20mATransmitterwithMultipleDevices RelayOutput
2-Wire4-20mATransmitterwithAnalogOutput
4-Wire4-20mATransmitter
Flowmeter(4-20mA Transmitter)
•3 -
Sign
al G
ND
(-D
C)•4
- I I
n +
(Cur
rent
). •7
- +2
4V O
ut. •1
1 -
AC
InA
C In
•12
-
-+
AC
PowerFuse
(user supplied)Flowmeter
(0-10 V Transmitter)
•3 -
Sign
al G
ND
(-D
C). •5
- V
In +
(Vol
tage
). •7
- +2
4V O
ut.
-
+signal
•11
- AC
InA
C In
•12
-
AC
PowerFuse
(user supplied)
Flowmeter(4-20mA Transmitter)
•2 -
Analo
g Out
•3 -
Sign
al GN
D (-D
C)•4
- I I
n + (C
urre
nt)
. •7 -
+24V
Out
.
+-
-
Strip ChartRecorder
+
•11 -
AC
InAC
In•1
2 -
ACPowerFuse
(user supplied)
Flowmeter(4-20mA Transmitter)
•2 -
Ana
log
Out
•3 -
Sign
al G
ND
(-D
C)•4
- I I
n +
(Cur
rent
). •7
- +2
4V O
ut.
+-
+
Strip ChartRecorder
–
•11
- AC
InA
C In
•12
-
AC
PowerFuse
(user supplied)
NOTE: Theuseofanexternallinefuseisrecommended.Addorreplacetheexternalfusewiththefollowingspecifiedtypeandratingonly.Recommended Fuses:115VAC:100mAslowblowfuse;230VAC: 50mAslowblowfuse;12-24VDC:250mAslowblowfuse
6
V41 & V_41 PROGRAMMING FLOWCHART
Thissymbolindicatesanykey.
PressthiskeytostepthroughMenuchoices
Pressthiskeytoenterdisplayedvalue.
NOTE: SEVERAL PROGRAMMING SELECTIONS WILL NOT APPEAR WITH "RATE ONLY" & "TOTAL ONLY" UNITS OPTIONS NOT ORDERED WILL NOT APPEAR IN PROGRAM SELECTIONS
input
i 4-20
i 0-20
e 0-5
e 1-5
e 0-10
LiNEAR
S9RT
RUN MODE
RELAYS
A RATE A tot
HYS A dur A
XXX.XX
HYS B
XXXXX
dur B
RUN MODE
loC
LC ALL
LC pg
Code
RUN MODE
setup
rDEC
SET lo
SET Hi
lo Cut
nor XX.X
SECS
NNiNS
hours
RUN MODE
opt
out lo
out Hi
B RATE B tot
baud
unit XX
P LiST
total
RATE
PEAC
ually
PRE A
PRE B
SET lo
SET Hi
END
RUN MODE
PRESS"ENTER"TO ADDITEM TO
PRINTLIST
PRESS"PRGM"
TO ADVANCETO NEXT
SELECTION
300
1200
2400
9600
PRGM
ENTER
PRGM
ENTER
PRGM
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTERENTER
PRGM
ENTERENTER
ENTERENTER
PRGM
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
PRGM
ENTER
ENTER
ENTER
ENTER
PRGM
ENTER
ENTER
ENTERPRGM
XXX.XX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
XXXXX
tDEC
tfaCt
ENTER
1
10
100
1000
PRGM
ENTER
PRGM
PRGM
START
*
* ForVersionV41, RDECappearsafterLo Cut.InVersionV_41(withspacebetweenV&41),rdeC appearsasshown
Forbestresults,choosethehighestresolutionpossiblewhenenteringthe"setlo","sethi"and"locut"values.
Entertheproperdecimallocationatthe"rdec"prompt.
For V41 EXAMPLE:Toscaletheunitfrom0.00to100.00,enter0for"set
lo"and10000for"sethi",enterthedecimalat"rdec".
TheVersionnumberisdisplayedatpowerup.NOTE: ModelINT69T&unitswithRS232/RS422optioncanonly
beusedwithV_41.
PRGM
ENTER
7
DEFINITIONS
input -INPUT;Thissectionoftheprogrammenuassignsthetypeofinputtheunitwillbeusing(0-20mA,4-20mA,0-5V,0-10V,1-5V,Linearorsquarerootextraction).
i 4-20-I4-20;Thissetstheunitforacurrentinputof4to20mA.
i 0-20-I0-20;Thissetstheunitforacurrentinputof0to20mA.
E 1-5-E1-5;Thissetstheunitforavoltageinputof1to5volts.
E 0-5-E0-5;Thissetstheunitforavoltageinputof0to5volts.
E 0-10-E0-10;Thissetstheunitforavoltageinputof0to10volts.
LiNEAR-LINEAR;Thissetstheunitforlinearinput.
S9RT-SQUAREROOT;Thissetstheunitforsquarerootextraction.
RELAYS-RELAYS;Thissectionoftheprogrammenusetsthecontroloutputvariables(relays&opencollec-tor).
A RATE-OUTPUTAFORRATE;ThisassignstheAoutputtotherate.
HYS A-HYSTERESISFOROUTPUTA;ThisvalueisthenumberofunitsbelowPresetAthattheoutputwillremain"ON".EXAMPLE:PresetAsetat100,Hyssetat10.OutputAwillactivate(turnon)whentherateequals100;OutputAwilldeactivate(turnoff)whentheratefallsbelow90(10belowPresetA)
A tot-OUTPUTAFORTOTAL;ThisassignstheAoutputtothetotalizer.
DuR A-OUTPUTADURATION;Thisisthedurationoftime(.01to599.99sec)thatOutputAwillremainener-gized.If0.00isenteredtheoutputwilllatchuntilreset.Ifavalueotherthan0.00isenteredtheunitwillautorecycleatPresetA.
B RATE-OUTPUTBFORRATE;ThisassignstheBoutputtotherate.
HYS B-HYSTERESISFOROUTPUTB;SameasHYSA.
b tot-OUTPUTBFORTOTAL;ThisassignstheBoutputtothetotalizer.
DuR B-OUTPUTBDURATION;Thisisthedurationoftime(.01to599.99sec)thatOutputBwillremainener-gized.If0.00isenteredtheoutputwilllatchuntilreset.
loc-LOCK;Thissectionoftheprogrammenusetsupthelockouttypeandcode.
LC ALL-LOCKALL;WhenthisisselectedthelockoutwilllocktheprogramaswellasthePresetsandresetbutton.Thepresetscanbeviewedbutnotchanged.
8
lc pg-LOCKPROGRAM;Whenthisisselectedthelockoutwilllockonlytheprogram.TheResetcanbeactivatedandthepresetscanbeviewedandchanged.
code-CODE;Thisisa5-digitcodewhichwillbeusedtolockandunlockthefrontpanel.
setup-SETUP;Thissectionoftheprogrammenusetsuptheoperatingvariables.
rdec-RATEDECIMALLOCATION;Thisallowstheusertoprogramadecimalpointfortheratedisplay.
set lo-SETLOW;Thisistheratevalueforthelowestinput(0or1Volts;4mA).(i.e.4mA=10lbs/hr.)
SET Hi-SETHIGH;Thisistheratevalueforthehighestinput(5or10Volts;20mA).(i.e.20mA=500lbs/hr.)
lo cut-LOWCUT-OFF;Thisisthelowestratevaluetoberecognized.Allratereadingsbelowthisvaluewillassumethe"setlo"value.
nor-NORMALIZINGFACTOR;Thisisanaveragingfactor(00.0to99.9).Highersettingsprovidemorenor-malizing(averaging)foramorestabledisplay.Derivedfromtheequation:
(OLDDATAx"NOR"+NEWDATA) ("NOR"+1)
SECS-SECONDS;ThistellstheunitthattheHighandLowinputvaluesareenteredinunitspersecond.
NNiNs-MINUTES;ThistellstheunitthattheHighandLowinputvaluesareenteredinunitsperminute.
hours-HOURS;ThistellstheunitthattheHighandLowinputvaluesareenteredinunitsperhours.
tdec-TOTALIZERDECIMALLOCATION;Thisallowstheusertoenteradecimalforthetotalizerdisplay.Thisdecimalisnotadummydecimalandwillscalethetotalizerdisplayaccordingly.(i.e.ifthetdecissetinthetenthsposition(#####.#),100willbedisplayedas100.0)
tfact-TOTALIZERFACTOR;Thisfactordividesthetotalizerdisplayby1,10,100or1000.
opt-OPTIONS;Thissectionoftheprogrammenuisforsettingupoptionalfeatures(analogout,RS232/422serialcommunications).
out lo-OUTLOW;Thedisplayedratevalueatwhichtheunitwilloutput4mA(2lbs./hr=4mAout).
out hi-OUTHIGH;Thedisplayedratevalueatwhichtheunitwilloutput20mA(2000lbs./hr=20mAout).
BAuD-BAUDRATE;ThebaudrateatwhichtheRS232orRS422communicationswilloperate.
9600-9600BAUD;Thissetsthecommunicationsat9600Baud.
2400 -2400BAUD;Thissetsthecommunicationsat2400Baud.
1200-1200BAUD;Thissetsthecommunicationsat1200Baud.
300-300BAUD;Thissetsthecommunicationsat300Baud.
9
unit -UNITNUMBER;ThisassignstheunitanIDnumberfrom1to99.Thisnumberistobeaddressedwhentheunitistobeonline.Aunitwith0assignedwillnevercomeonline.
P LiST-PRINTLIST;Thissetsalistofdatathatwillbetransmittedwheneverthestrobeisactivated.
total-TOTALCOUNT;Whenthisisaddedtotheprintlist,theunitwilltransmitthetotalwhenthestrobeisactivated.
RATE-RATE;Whenthisisaddedtotheprintlist,theunitwilltransmitthepresentratevaluewhenthestrobeisactivated.
PEAK-PEAK;Whenthisisaddedtotheprintlist,theunitwilltransmitthepresentpeakvaluewhenthestrobeisactivated.
uALLEY-VALLEY;Whenthisisaddedtotheprintlist,theunitwilltransmitthepresentvalleyvaluewhenthestrobeisactivated.
PRE A-PRESETA;Whenthisisaddedtotheprintlist,theunitwilltransmitthePresetAvaluewhenthestrobeisactivated.
PRE B-PRESETB;Whenthisisaddedtotheprintlist,theunitwilltransmitthePresetBvaluewhenthestrobeisactivated.
set lo-SETLOW;Whenthisisaddedtotheprintlist,theunitwilltransmittheSetLowvaluewhenthestrobeisactivated.
set hi-SETHIGH;Whenthisisaddedtotheprintlist,theunitwilltransmittheSetHighvaluewhenthestrobeisactivated.
END-END;ThisistheonlyexitfromthePList.IfENDisnotenteredtheunitwillstartatthebeginningofthePListagain.
PXXXXX-P;Thiswillappearinthe6th(furthesttotheleft)digitwhenviewingthePeak.Thepeakvalueisthehighestratereadingthattheunithaddisplayedsincethepeakhadbeenreset.Thepeakisnotretainedinmemorywhenpowerislost.
uXXXXX-U;Thiswillappearinthe6th(furthesttotheleft)digitwhenviewingtheValley.Thevalleyvalueisthelowestratereadingthattheunithaddisplayedsincethevalleyhadbeenreset.Thevalleyisnotretainedinmemorywhenpowerislost.
RXXXXX-R;Thiswillappearinthe6th(furthesttotheleft)digitwhenviewingtheRate.
10
ENTER
A B C D ERST
ENTER LOCK PRE A PRE B VIEW PRGM
8 1 4 2 3 5
PROGRAMMING
REMARKSThis sectionof themenu is used tosetupthetypeofsignaltheunitwillbereceiving.
PressthePRGMkeytostepthroughchoices.PresstheRST/ENTERkeytoenterthedisplayedchoice.
Thissectionwillonlyappearonunitswiththesquarerootextractionoption.PressthePRGMkeytotogglebetweenthechoicesandpresstheRST/ENTERkeytoenterthedesiredchoice.
DISPLAY
iNPuT
i 4-20, i 0-20
E 1-5, E 0-5 or E 0-10
LiNEAR
orS9RT
PRESS
FRONT PANEL OPERATIONS
PresstoRESETinoperatingmode;Pressto"ENTER"inpro-grammingmode.
PresstovieworchangePresetA
PresstovieworchangePresetB
Presstoalter-natelyviewRate,Total,Peak&Valley.
PresstocyclethroughPRO-GRAMchoices;Presstostepthroughsetupchoicesinpro-grammode.
SETTINGINPUT
STEP1
Pressoncetofreezedisplay.Pressanykeytoupdatedisplaynormally.Pressrapidly(3timeswithin5seconds)to"enter"LOCKcodeforpanellock.
PRGM
ENTER
11
PRESS DISPLAY REMARKS
input
RELAYS
A RATE
orA ToT
(IFTOTSELECTED)
DuR A
(hitanykeytovieworchangeexistingdurA
valueXX.X)
(IFRATESELECTED)
HYS A
(hitanykeytovieworchangeexistingHySA
valueXXXXX)
B RATEorB ToT
(IFTOTSELECTED)DuR B
(IFRATESELECTED)HYS B
STEP2
SETTINGRELAYS
NOTE: Ifrelayoutputsare not used,set dur A &dur B at "0.0"to prevent thecounters fromresettingatthepresets.
Thissectionofthemenusetsuptheopencollectoroutputsand/orrelays.
OutputAassignedtotherateortotal.PressthePRGMkeytotogglebetweenchoices,presstheRST/ENTERkeytoenterthedisplayedchoice.
durA = the duration of time (.01 to599.99sec)thatoutputAwillremainonorenergized.WhendurAisdisplayed,hitanykeytovieworchangedurA.Press the RST/ENTER key to enterdisplayedvalue.WhendurAissetat0.00,outputAwilllatchuntilreset;whendurAissetotherthan0.00thecounterwillautorecycleatPresetA.Hys(hysteresis)=Thenumberofunitsbelow thepreset that the outputwillremain"ON".EXAMPLE:Presetset@ 100; HyS set@ 10. Output willactivate(turnon)whenrate=100andturnoffwhenrate fallsbelow90(10belowpreset).Follow instructions for A RATE & ATOT.
FollowinstructionsfordurA
FollowinstructionsforhysA
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTER
ENTER
12
DISPLAY REMARKS
STEP3
SETTINGLOCK
Thissectionofthemenuisusedtosetupthelockouttypeandcode.
LCPG=Locksprogrambutpresets areaccessible.LCALL=Locksprogram&presets.PressthePRGMbuttontotogglebe-tweenchoices;PressRST/ENTERtoenterdisplayedchoice.
WhenCODEisdisplayed,pressanykey to view existing lock code. Tochangethecodepressthekeyundereachdigittobechanged.PressRST/ENTERtoenterdisplayedvalue.
input
RELAYS
LoC
LC PG or LC ALL
CoDE
Pressanykeytovieworchangethelock
code
PRESS
Thissectionofthemenuisusedtosetupimportantoperatingvariables.
RDEC=ratedecimal location;Pressthekeyunderthedigitwiththedesiredlocation.Pressthe"E"keyifadecimalisnotdesired.PressRST/ENTERtoenterthedisplayedlocation.
SET LO=Rate value for the lowestinput(0or1V; 4mA).(i.e.4mA=10lbs/hr.)KeyinthedesiredlowvalueandpressRST/ENTERtoenterdis-playedvalue.
SETHI=Rate value for the highestinput (5or10V;20mA).(i.e.20mA=500lbs/hr.).KeyinthedesiredhighvalueandpressRST/ENTERtoenterdisplayedvalue.
input
RELAYS
LoC
SETuP
rDEC
SET Lo
Pressanykeytovieworchangeexisting
value
SET Hi
Pressanykeytovieworchangeexisting
value
CONTINUEDONNEXTPAGE
STEP4
SETTINGSETUP
ENTER
PRGM
ENTER
ENTER
PRGM
ENTER
ENTER
PRGM
PRGM
PRGM
PRGM
PRGM
13
REMARKSDISPLAYPRESSLO CUT= Low cut-off; Lowest ratevaluetoberecognized.Allrateread-ings below the "cutoff" will assumethe"setlo"value.KeyinthedesiredvalueandpressRST/ENTERtoenterdisplayedvalue.
NOR= Normalizing (averaging) fac-tor(00.0to99.9);KeyinthedesiredvalueandpressRST/ENTERtoenterdisplayedvalue.Highersettingspro-videmorenormalizing(averaging)foramorestabledisplay.
Thissectiontellstheunitthatthehigh&lowsettingareenteredinunitsperMinutes,HoursorSeconds.PressthePRGMkey to step through choices.PressRST/ENTERtoenterdisplayedchoice.
TDEC=TotalizerDecimal;Pressthearrow keys to enter in the desiredtotalizerdecimal.PressRST/ENTERto enter displayed choice. Enteringa decimal will add resolution to thetotal. (i.e. tdec=#####.#; 100will bedisplayedas100.0)
TFACT=TotalizerFactor;Thisfactorallowsyoutodividethetotalizerby1,10,100,1000
Press thePRGMkey to step to thedesiredfactor.PressRST/ENTERtoenterdisplayedchoice.
Lo CuT
Pressanykeytovieworchangeexisting
value
NoR
Pressanykeytovieworchangeexisting
value
NNiNS, HouRS
or SECS
tdec
tfact
Pressanykeytovieworchangeexisting
value
1, 10, 100 or1000
STEP4
CONT...
SETTINGSETUP
ENTER
PRGM ENTER
ENTER
PRGM ENTER
ENTER
ENTER
14
REMARKSDISPLAYPRESS
Thissectionofthemenuisforsettingupthevariablesforanyoptionswhichwere ordered (Analog out or Serialcommunications).
OUTLO=Theratevaluerepresentedbythe4mAendofthe4-20mAoutputKeyinthedesiredvalueandpressRST/ENTERtoenterdisplayedvalue.
OUTHI=Theratevaluerepresentedbythe20mAendofthe4-20mAoutput.KeyinthedesiredvalueandpressRST/ENTERtoenterdisplayedvalue.
BAUD=BaudrateforRS232orRS422 communications option. Pressanykeytoviewexistingvalue.
PressthePRGMkeytoviewavailablebaudrates;PressRST/ENTERtoenterdisplayedvalue.
UNIT=Unit IDnumber. Key in thedesiredunitnumber(1-99)andpressRST/ENTER to enter displayedvalue.
PLIST=Printlist.Press RST/ENTER to add items tolist; Press PRGM to remove itemsfromlist.TOTAL=TotalRATE=RatePEAC=PeakUALLY=ValleyPREA=PresetAPREB=PresetBSETLO=LowInputValueSETHI=HighInputValueEND=PressRST/ENTERtoexit(end)printlist;PressPRGMtorecyclethroughlistchoices.
STEP5
SETTINGOPTIONS
OR
THE PROGRAM SETUP IS COMPLETE! YOU ARE NOW READY TO SET THE PRESETS.
input
RELAYS
LoC
SETuP
oPT
ouT Lo
Pressanykeytovieworchangeexisting
value
ouT Hi
Pressanykeytovieworchangeexisting
value
BAuD
Pressanykeytovieworchangeexisting
value9600, 1200,
2400 or 300
unit
Pressanykeytovieworchangeexisting
value
P LiST
PressanykeytoenterprintlistToTAL
RATE
PEAK
uALLY
PRE A
PRE B
set lo
set hi
END
PRGM
PRGM
PRGM
ENTER
PRGM
PRGM
ENTER
ENTER
ENTER
PRGMENTER
15
REMARKSDISPLAYPRESS
SETTING THE PRESETS & PANEL LOCK
SETTINGTHE
PRESETS
PRE A
Pressanykeytovieworchangeexisting
value
PRE B
Pressanykeytovieworchangeexisting
value
CoDE
Pressanykeytoenterthe5-digitlockcode.
LoCor
UN LoC
PREA=PresetA(FinalPreset);ThesetpointatwhichoutputAwilltrigger.Ifthedisplayedvalueisnotthedesiredpreset,pressthekey(s)underthedigittobechanged.
PREB=PresetB(Prewarn);ThesetpointatwhichoutputBwilltrigger.Ifthedisplayedvalueisnotthedesiredpreset,pressthekey(s)underthedigittobechanged.
Keyinthelockcode(seeprogrammingstep3)bypressingthekeysunderthedigitstobechanged.Eachtimeakeyispressedthedigitwillincrementone.PresstheRST/ENTERkeytoenterthedisplayedcode.
AfterthecodeisenteredtheunitwilldisplayLOC(unitislocked)orUNLOC(unitisun-locked).Thismessagewillbedisplayedforapproximately3sec-ondsbeforetheunitreturnstotherunmode.Ifaninvalidcodeisentered,nomessageisdisplayed;tryagain.
PressLOCK3timeswithin5seconds(IfLOCKispressedonce,unitfreezesdisplay)
SETTINGTHE
LOCKSTATUS
NOTE:Presetscanbesetatanyvalueform0to59999.
PRE A
PRE B
LOCKLOCK
LOCK
ENTER
16
Thissectionappliestounitswhichhavetheserial communications interfaceoption. Upto99unitscanbelinkedtogether.Unitsta-tuscanbeaccessedandmanymenuitemscanbeenteredthroughtheserialport.Datais transmitted at selected baud rates usingstandardeightbitASCIIcharactersandone“stop”bit.Theunitdoesnotcheckortransmitaparitybit.
UNIT I.D. (DEVICE #)Eachunitinthehookupmustbeassignedaunitnumberfrom1to99.Thiscanbeenteredthrough the front panel (see step 5 of theprogramming section). If “00” is assigned,theunitcannotbebroughton line throughthe serial port. The unitswill remain in an“off”highimpedancestateuntiladdressedbytheassignedunitnumber.Onceaunitisad-dressed,donotaddressanotherunituntilthedatahasbeensentandanydatarequestedhasbeentransmittedback.
BAUD RATEThebaudrateisthespeedatwhichdataistransmitted, expressed in bits per second.Baud ratesof300,1200,2400or9600areavailable.Selectthedesiredbaudratefromthemenu. (seestep5of theprogrammingsection).
PRINT LISTTheserial interfacecard isequippedwithastrobeline.Whenthestrobelineisactivateda user selectable set of data (print list) istransmitted.Thistransmissioncanbesenttoacomputerorprinter.Theprintlistconsistsofeightselectableitems:COUNT,RATE,PEAK,VALLEY, PREA, PREB, LOWSET,HIGHSET.Thelistcanbeenteredthroughthefrontpanel(seestep5oftheprogrammingsection)orthroughtheserialport(readon).
HELPAhelpcommandhasbeeninstalledforeasyaccessofthecommandanddatavariables.Whenhelp isneeded, typea “?”andpressreturn(enter)wheneveraunitisonline.Thefollowinglistwillbetransmitted:D#XX:SSetEExamRResetGLockL*ListC*CountR*RateP*PeakV*ValleyA*PreAB*PreBL*LoSetH*HiSetJLoOutKHiOutNNormDUnitEInputGHy/DrAIHy/DrBMTimeTBaudWLockXMeterYATypZBTypOCodeFRDecQTDecUTFactTheunittransmitstheunitID(D#XX)aswellasthevariablesforthecorrespondingcom-mandsanddata.A“*”indicatesthatthedataisavailablefortheprintlist.
RS 232/422 OPERATIONS
17
COMMANDS:
Eachcommandconsistsofaninstructionandanaddress.Eachinstructionandaddressisrepresentedbya letter. Theprefixofeachcommandmustbeaninstructionfollowedbyanaddress(andaddressvariableifapplicable).
INSTRUCTIONS (1st letter of command): [S]Set-Usedtoset thevalueoroperatingparameterofanaddress.(i.e.“SC5000”willsetthecountat5000)
[E]Examine-Usedtoexaminethevalueorstatusofanaddress.(i.e.“ER”willexaminethepresentratereading)[R]Reset-Usedtoresetthecount&controloutput,peakorvalley.(i.e.“RP”willresetthepeakvalue)[G]Lock-usedto lockandunlocktheunit.Type“G”followedbythe“lockcode”tolockandunlocktheunit.[L]*List-Usedtosettheprintlist.(i.e.“LCRVA”willsetthelistforcount,rate,valleyandpresetA.Thesevalueswillbetransmittedwheneverthestrobeisactivated.)
ADDRESSES (2nd letter of command):[C]*Count[R]*Rate[P]*Peak[V]*Valley[A]*PreA[B]*PreB[L]*LoSet[H]*HiSet[J]LoOut[K]HiOut[N]Norm[D]Unit[E]Input[G]DurA[I]DurB[M]Time[T]Baud[W]Lock[X]Meter[Y]AType[Z]BType[O]Code[F]RDec[Q]TDec[U]TFact
18
POSSIBLE COMMANDS:Eachcommandmustbe followedbyacarriagereturnforexecution.
DXX:(device“unitID”#)-UnitXXwillcome“online”andstay“online”untilanotherdeviceisaddressed.
SD XX:(setdevice“unit ID”#)-setsunit ID#atrequestedvalue
ED: (examine device)- Unit will transmit thepresentdevice(unit ID)number(i.e.d=000000XX).
SC XXXXXX:(setcount)-Setscountatrequestedvalue.
EC:(examinecount)-Unitwilltransmitthepresentcountvalue(i.e.c=00XXXXXX).
RC:(resetcount)-Resetsthecounterandcontroloutput.
ER:(examinerate)-Unitwilltransmitthepresentratevalue(i.e.r=000XXXXX).
RR:(resetrate)-ResetsthenormalizationEP:(examinepeak)-Unitwilltransmitthepresent
peakvalue(i.e.p=000XXXXX).RP:(resetpeak)-Unitwillresetthepeak.EV:(examinevalley)-Unitwilltransmitthepresent
valleyvalue(i.e.v=000XXXXX).RV:(resetvalley)-Resetsthevalley.SA XXXXX: (setpresetA)-SetspresetAat re-
questedvalue.EA:(examinepresetA)-Unitwilltransmitpresent
presetAvalue(i.e.a=000XXXXX).SB XXXXX:(setpresetB)-SetspresetBatre-
questedvalue.EB:(examineB)-Unitwilltransmitpresentpreset
Bvalue(i.e.b=000XXXXX).SL XXXXX:(set“Low”)-Sets“setlow”atrequested
value.EL:(examine“Low”)-Unitwilltransmitpresent“set
low”value(i.e.l=000XXXXX).SH XXXXX: (set “High”)- Sets “set high” at re-
questedvalue.EH: (examine“High”)-Unitwill transmitpresent
“sethigh”value.(i.e.h=000XXXXX)SJ XXXXX:(set“lowout”)-Sets“outlow”atre-
questedvalue.OnlyavailablewithANA-LOGOUToption.
EJ:(examine“lowout”)-Unitwilltransmitpresent“outlow”value.(i.e.j=000XXXXX)
SK XXXXX: (set “high out”)- Sets “out high” atrequestedvalue.OnlyavailablewithANA-LOGOUToption
EK:(examine“highout”)-Unitwilltransmitpresent“outhigh”value.(i.e.k=000XXXXX)
SN XX.X: (setnorm)-Sets “norm”at requestedvalue. Must be a 3-digit number withdecimal.
EN: (examine norm)- Unit will transmit present“norm”value(i.e.n=000XX.X).
SE i 4-20, i 0-20, e 0-5, e 1-5ore 0-10:(setin-put)-sets input tooneof the4availabletypes.Entertypeexactlyasitappearsonthedisplay.
EE:(examineinput)-Unitwilltransmitinputtype(i.e.e0-10).
SG XXXXX: (setdurAorhysA)-SetsdurAorhysAatrequestedvalue.(durAwhenAisassignedtototal;hysAwhenAassignedtorate).
EG: (examine durA or hysA)- Unit will trans-mitpresentdurAorhysAvalue(i.e.g=000XXXXX)
SI XXXXX:(setdurBorhysB)-SetsdurBorhysB at requested value. (durBwhenB isassignedtototal;hysBwhenBassignedtorate).
EI: (examinedurBorhysB)-Unitwill transmitpresent dur B or hys B value (i.e.I =000XXXXX)
SM secs, minsorhours:(settimebase)-Setstimebasetodesiredsetting.
EM:(examinetimebase)-Unitwilltransmitpresenttimebase(i.e.secs).
ST XXXX:(setbaud)-Setsbaudatdesiredrate(9600,2400,1200or300).
ET:(examinebaud)-Unitwilltransmitpresentbaudrate(i.e.9600).
EW:(examinelocktype)-unitwilltransmitpresentlocktype(i.e.lcpg).
SX linearor sqrt:(setmetertype)-Setsmeterinputforlinearorsquarerootextraction.Onlyavailablewithsquarelawoption.
EX:(examinemetertype)-Unitwilltransmitpres-entmetertype(i.e.linear).
SY A totorA rate:(setAtype)-AssignscontroloutputAtorateortotal.
EY:(examineAtype)-UnitwilltransmitpresentAtype(i.e.atot).
SZ B totorB rate:(setBtype)-AssignscontroloutputBtorateortotal.
EZ:(examineBtype)-UnitwilltransmitpresentBtype(i.e.btot).
19
Whentheunit isactive(online)itwilloper-ateinanechobackmodesothatdatasentfromtheterminalwillbetransmittedbackforverification.Whentheunitis"online",usetheproperserial transmitcommandstorequestdataorsetanewvalue.Besuretosendonlyonecommandatatimefollowedbyacarriagereturntoinsureproperoperation.Ifanerrorismade,acorrectioncanbemadebybackspacingandretypingcorrectdatabeforethereturn(enter)issent.Onceareturn(enter)issent, theunitbeginsprocessing thedataandwilltransmittherequesteddataonanon-prioritybasisoverthedatatransmitline.TheunitwillnottransmitdataifthePrinterBusylineisactivated(high).WhenthePrinterBusylineisactivatedall transmissionsarehalteduntilthelinegoesloworopen.Thereshouldbeapauseafterdataisrequestedtoinsurethatalldatahasbeentransmittedbeforemak-ing another request or addressing anotherunit. If transmission has not startedwithintwo seconds after data is requested, it canbeassumedthatthereisaproblem.Theunittransmitsacarriagereturnandlinefeedaftereachdatavalue.Theunitwillstay"online"untilanotherunitisaddressed.
RS232/RS422 - PC INTERFACE:ThefollowingBASICprogramisforsettingupRS232/RS422onserialport(#1)at300baud.Runthisprogramafterconnectingtheserialinterfaceconnections.
10SCREEN0,0:WIDTH8020CLS:CLOSE30OPEN"COM1:300,n,8,1,CS,DS,CD"AS#140ONERRORGOTO11050B$=INKEY$60IFB$<>""THENPRINT#1,B$;70IFEOF(1)THEN5080A$=INPUT$(LOC(1),#1)90PRINTA$;100GOTO50110RESUME
SO XXXXX: (set lock code)- Sets lock code atrequestedvalue.
EO: (examine code)- Unit will transmit presentcode(i.e.o=000XXXXX).
SF X:(setratedecimallocation)-Setsratedecimalatrequestedlocation(0to4).
EF:(examineratedecimallocation)-Unitwilltrans-mitthepresentratedecimallocation(i.e.f=0000000X).
G XXXXXX:(lockunit)-Locksandunlocksunit.(XXXXX=code)
SQ X:(settotalizerdecimallocation)-Setstotalizerdecimalatrequestedlocation(0to4)
EQ:(examinetotalizerdecimallocation)-Unitwilltransmitpresenttotaldecimallocation(i.e.Q=0000000X).
SU XXXX:(settotalizerscalefactor)-Setstotal-izerscalefactoratrequestedvalue.Thisfactordivides the totalizerby1,10,100or1000.(i.e.SUXXX100setsthedividerat100where"X"representstherequiredspacecharacters.
EU: (examine totalizer scale factor )- Unit willtransmitpresenttotalscalefactor(i.e.U=XXX100where"X"representsthespacecharacters).
L CRPVABLH:(list)-Thelistcanconsistofanycombinationoftheeightavailableoptions.Anyaddresswitha "*"next to it canbelisted.
SERIAL INTERFACE OPERATION:Data is receivedand transmittedoverstan-dardEIARS232orRS422levels.Eachtenbitcharacterismadeupofastartbit,eightbitASCIIcodeandastopbit.TheinputimpedanceofRS232is3KΩto7KΩworstcase.Theterminaladdressingtheunitmustbecapableofdrivingallloadsintheloop.TheinputimpedanceofRS422ismuchhigherand there should be no problem driving asmanyas99units.Thetransmitlineremainsinahighimpedance"off"stateuntiladdressed.Onlyoneunitistobeonlineatatime!!!Morethanoneunitonlinecoulddamagetheunitordestroythetransmitteddata.
20
RS232 / RS422 WIRING
COMPUTER HOOKUP:RS 232: When connecting the unit to acomputerwithRS232communication,onlythreeconnectionsareneeded.Thesecon-nections are: Receive data, Transmit dataand Ground. The connections should bemadeasfollows:
DB-9CONNECTORCOMPUTERTransmitdata(pin2) ReceivedataReceivedata(pin3) TransmitdataGround(pin5) Ground
RS 422: When connecting the unit to acomputerwithRS422,fiveconnectionsareneeded. These connections are: ReceivedataA(+),ReceivedataB(-),TransmitdataA(+),TransmitdataB(-)andGround.Theconnectionsshouldbemadeasfollows:
DB-9CONNECTORCOMPUTERTrans.dataA(+)(pin2) Rec.dataA(+)Trans.dataB(-)(pin7) Rec.dataB(-)Rec.dataA(+)(pin3) Trans.dataA(+)Rec.dataB(-)(pin8) Trans.dataB(-)Ground(pin5) Ground
PRINTER HOOKUP:When connecting the unit to a printer, youmust first program the desired baud rate,parityandstrobelistwithacomputer.Aftertheunitisprogrammeditcanbeconnectedto theprinter. Connect the transmit line(s)oftheunittothereceiveline(s)oftheprinterandbesurethatbothdeviceshavecommongrounds.Whenthestrobelineistriggeredtheunitwilltransmittheselectedstrobelistwhichyouhadpreviouslyprogrammed.
1-Printerbusy:3to30VDC,Levelactivated.2-TransmitA(+)(RS422);Transmit(RS232)3-ReceiveA(+)(RS422);Receive(RS232)4-NotUsed5-Ground6-Strobe:3to30VDCPositiveEdge7- TransmitB(-)(RS422Only)8-ReceiveB(-)(RS422Only)9-NotUsed
12345
6789
DB - 9 CONNECTOR
RS 232
TRANSMIT PIN (2)GROUND PIN (5)
STROBE PIN (6)
PRINTER BUSY PIN (1)
TRANSMIT A (+) PIN (2)GROUND PIN (5)
TRANSMIT B (-)PIN (7)
STROBE PIN (6)RS 422
PRINTER BUSY PIN (1)
TRANSMIT PIN (2)
GROUND PIN (5)
RECEIVE PIN (3)
RS 232
TRANSMIT A(+)PIN (2)
TRANSMIT B(-) PIN (7)
RECEIVE B(-)PIN (8)RECEIVE A(+)PIN (3)
GROUND PIN (5)
RS 422
21
TROUBLESHOOTING GUIDE
PROBLEM POSSIBLE CAUSES SOLUTIONSPowerisappliedtounitbutthedisplaydoesnotlight.
Unitworksbutoccasionallythedisplayfreezesorskipscounts.
Inputsignalisconnectedbuttheunitdoesnottotalizeorrate.
Displayreadingisinaccurate.
Ratemeterworksproperlybuttotalizerisincorrect.
1.ACorDCpowerwiring isincorrect.
1.Linenoise iseffecting theprocessorduetoacurrentspikeorsurge.
1.Inputwiringisincorrect2.Highandlowscalingsettingsareincorrect.
3.Transmitting device isdefective.
4.Unitisdefective.
1.Inputwiringisincorrect.
1.Timebaseisincorrect.
1.Recheckpowerwiring.
1.Use a different powersupply or install a surgesuppressor.
1.Recheckinputwiring.2.Recheck high and lowscalingsettings.
3.Replace t ransmi t t ingdevice.
4.To confirm set meter for0-10Vinput,low@0;[email protected] the voltage input (pin5).Whenviewingtheratethe meter should displaythe voltage value that isapplied.IfnotcallfactoryforanRMA#.
1.Besurethatvoltagesignalsare connected to voltageinput (pin 5) and currentsignals are connected tocurrentinput(pin4).
1.Rechecktimebasesettingin setup section of theprogrammenu.
IF YOU HAVE ANY OTHER PROBLEMS, PLEASE CALL THE FACTORY.
22
Wehopeyouwillbepleasedwithourproduct.Ifyouhaveanyquestionsconcerningourwarranty,repair,modificationorreturnedgoodsprocess,pleasecontactyourlocaldis-tributor.
WARRANTY Thisproductiswarrantedagainstdefectsinmaterialsandworkmanshipforaperiodoftwo(2)yearsfromthedateofshipmenttoBuyer. TheWarrantyislimitedtorepairorreplacmentofthedefectiveunitattheoptionofthemanufacturer.Thiswarrantyisvoidiftheproducthasbeenaltered,misused,dismantled,orotherwiseabused.
ALLOTHERWARRANTIES,EXPRESSEDORIMPLIED,AREEXCLUDED,INCLUD-INGBUTNOTLIMITEDTOTHE IMPLIEDWARRANTIESOFMERCHANTABILITYANDFITNESSFORAPARTICULARPURPOSE.
Kessler - Ellis Products Co. 10 Industrial Way East Eatontown, NJ 07724
(732) 935- 1320 Toll Free 800 - 631 - 2165
Fax (732) - 935- 9344
SAMPLE: INT69RT A L 1 C1 DECODING PART NUMBER
SeriesINT69RT=Ratemeter/TotalizerINT69R=RatemeterOnlyINT69T=TotalizerOnly
Operating VoltageA=110VAC±15%or12to24VDCB=220VAC±15%or12to24VDC
InputsL=Linear(standard)S=SquareLaw(optional)
Control outputs1=2-OpenCollectorOutputs(standard)2=2-5AmpFormCRelays(optional)
OptionsA=AnalogOutput(4-20mA)C1=RS232communicationsC2=RS422communications
AccessoriesSeparatenonkeyboardpanelorder#34235Separatekeyboardpanelorder#34237
23
Revision History
Revision Changes01/05/05 Original
01/27/10 PG5:Addednotesregardinguseofanexternalfuseforpowerinputwiring PG4:AddedanoteregardingtheuseofanexternalfusefortheDCOutput
andRelayOutputs
KEPLEadErs in industriaL automation tEchnoLogy
Formorethan40years,KesslerEllisProductshasbeensupplyingindustrialautomationandflowinstrumentationproductstoabroadrangeofcustomersworldwide.
KEPoffersautomationsolutionsrangingfromsimplevoltagemeterstosophisticatedflowcomputersandHMIsoftware.WealsoofferOperatorInterfacePanelsthatcanbeinterfacedtoPLCControllers,KEPflowinstrumentsandKEPMarineDisplays.
Ourcommitmenttoprovidingnext-generationsolutionshasallowedustopushexistingperformancelevelsintomorerugged,reliableandconvenientpackages.Butmoreimportantly,ouremphasisonproductqualityandcustomerservicehashelpedusgainthetrustandconfidenceofourcustomersaroundtheworld.
www.kep.com
Flow MeasureMentKEPseekstoservicetheflowmeasurementcommunitybyprovidingversatile,
economicalinstrumentationand“knowhow”toourusers.Ourflowmeasurementproductsinclude:fieldindicators,ratemeter/totalizers,batchers,process&levelindicatorsandsophisticatedflowcomputers.Weofferadvancedcommunicationfeaturessuchas:RS-232,RS-485withModbusRTUprotocol,Modem,ModbusTCPandWirelesssupport.Weareexpertsininterfacingwithalltypesofprimaryflowsensors.Weassistusersbyprovidingeconomicalsolutionsfortheirinstrumentationneeds.
Count/rate MeasureMentNeedlocalcountvalues?Tryourfulllineofhighspeed,ruggedcounters,ratemonitors
andsensors.Theyareperfectfordiscretepartsproductioncounting,ormeasuringmotorRPMorconveyorspeed.Easytoprogram,easytouse,andEASYTOSEE!!
operator InterFaCesPLC'saregreat,buthowdoesanoperatorinteractwiththePLC?OurMMIseriesof
textinterfacesandgraphicaltouchscreensconnecttonearlyallPLC'sandeasilylettheuserviewtheprocessandchangesetupinformation.WealsooffersimpleBCDtoLEDdisplaysandBCDthumbwheelandrotaryinputswitches.
HMI soFtware and CoMMunICatIonInfilink-HMIisafullfeaturedoperatorinterfacepackage,isanOPCclient,andincludes
trendinganddatalogging.Thedevelopmentpackageisfree.AndafreeOPCServerisincludedwhichconnectsusingnearlyanycommunicationprotocoloverRS232,RS485,Ethernet,orotherhardwarelayers.