ระบบหัวกระจายน้ำดับเพลิง Springkler System

Embed Size (px)

Citation preview

  • 8/14/2019 Springkler System

    1/114

    SPRINKLER SYSTEM

  • 8/14/2019 Springkler System

    2/114

    Laboratory Approvals

    AGENCYAGENCY STANDARDSTANDARD

    UL & c-UL (ULC) NFPA & UL Requirements

    FM FM Requirements(NFPA = minimum)

    LPC LPC StandardVDS VDS Standard

    NYC & LA Specific City approvals

  • 8/14/2019 Springkler System

    3/114

    NFPA

    o 1. NFPA 13 Standard for the installation of sprinkler system.

    o 2. NFPA 14 Standard for the installation of standpipe andhose systems.

    o 3. NFPA 20 Standard for the installation of stationary pumpsfor fire protection

    o 4. NFPA 25 Standard for the inspection, testing, andmaintenance of water base fire protection systems.

    o 5. NFPA 72 National fire alarm code

  • 8/14/2019 Springkler System

    4/114

    WET PIPE SYSTEM (,)

    DRY PIPE SYSTEM (,)

    DELUGE SYSTEM (,)

    PREACTION SYSTEM (,)

  • 8/14/2019 Springkler System

    5/114

    1. ( Control Valve )

    2. ( Sprinkler Head )

    3. Supervisory Switch

    4. Water Motor Alarm Gong

    5. Pressure Guage

    6. Service Valve / Block Valve with position

    Supervisory Switch

  • 8/14/2019 Springkler System

    6/114

    WET PIPE SYSTEM

  • 8/14/2019 Springkler System

    7/114

    WET PIPE SYSTEM

  • 8/14/2019 Springkler System

    8/114

    DRY PIPE SYSTEM

  • 8/14/2019 Springkler System

    9/114

    DRY PIPE SYSTEM

  • 8/14/2019 Springkler System

    10/114

    DELUGE SYSTEM

  • 8/14/2019 Springkler System

    11/114

    DELUGE SYSTEM

  • 8/14/2019 Springkler System

    12/114

    DELUGE SYSTEM

  • 8/14/2019 Springkler System

    13/114

    PREACTION SYSTEM

  • 8/14/2019 Springkler System

    14/114

    PREACTION SYSTEM

  • 8/14/2019 Springkler System

    15/114

    ( Sprinkler Head )

  • 8/14/2019 Springkler System

    16/114

    MATERIALS OF CONSTRUCTIONThe components that make up a sprinkler head are:

    Frame or casting

    Deflector

    Fusible element or frangible bulb

    Pip CapPintle Screw

    Belleville Spring

    Viking Sprinklers utilize low zinc content brass to

    provide a more resilient frame or casting. This low

    zinc content protects the sprinkler from de-

    zincification.

    The Bellville Spring seals the water way of the

    sprinkler. This metal to metal sealing mechanism

    allows the waterway to clear even when no pressure

    is on the inlet of the sprinkler head.

  • 8/14/2019 Springkler System

    17/114

    155F 175F 200or212F 286F 360F 500F(68C) (79C) (93or100C) (141C) (182C) (260C)

    Ordinary Intermediate High Extra UltraHigh High

    Max Ceil Max Ceiling Max Ceil Max Ceil Max Ceil

    Temp Temp Temp Temp Temp100F 150F 225F 300F 465F(38C) (65C) (107C) (149C) (240C)

    Red Yellow Green Blue Mauve Black

    Standard Response Elements 5 mm bulb

  • 8/14/2019 Springkler System

    18/114

    155F 175F 200or212F 286F

    (68C) (79C) (93or100C) (141C)

    Ordinary Intermediate High

    Max Ceil Max Ceiling Max CeilTemp Temp Temp100F 150F 225F

    (38C) (65C) (107C)

    Red Yellow Green Blue

    Fast Response Elements 3 mm bulb

  • 8/14/2019 Springkler System

    19/114

    Control Mode Standard Response and Quick Response

    Standard Coverage

    Upright

    Pendent

    Sidewall

    Extended Coverage

    Upright

    Pendent

    Sidewall

    Control Mode Special Application

    Large Drop Sprinkler Suppression

    ESFR upright and Pendent Residential

    Type of Sprinkler Heads

  • 8/14/2019 Springkler System

    20/114

    Control Mode Sprinklers

    Control Mode Sprinklers are separated in the following

    Categories:Standard Coverage - Standard Response

    Standard Coverage - Quick Response

    Extended Coverage Standard Response

    Extended Coverage Quick Response

    Dry Barrel Standard Response/Quick Response

    Storage Standard/Quick Response

  • 8/14/2019 Springkler System

    21/114

  • 8/14/2019 Springkler System

    22/114

    QUICK RESPONSE & EXTENDED

  • 8/14/2019 Springkler System

    23/114

    QUICK RESPONSE & EXTENDED

    COVERAGE SPRINKLER

  • 8/14/2019 Springkler System

    24/114

  • 8/14/2019 Springkler System

    25/114

    FUSIBLE LINK SPRINKLER

  • 8/14/2019 Springkler System

    26/114

    STORAGE APPLICATION

  • 8/14/2019 Springkler System

    27/114

    STORAGE APPLICATION

    SPRINKLER

  • 8/14/2019 Springkler System

    28/114

  • 8/14/2019 Springkler System

    29/114

    DRY PIPE SPRINKLER

  • 8/14/2019 Springkler System

    30/114

    Basic Requirements

    The requirements for spacing, location, and position of

    sprinklers shall be based on the following principles :

    (1) Sprinklers shall be installed throughout the building.

    (2) Sprinklers shall be located not to exceed maximum protection

    area per sprinkler.(3) Sprinklers shall be positioned and located to provide satisfactory

    performance with respect to activation time and distribution.

    (4) Sprinklers shall be permitted to be omitted fromareas specifically allowed by this standard.

  • 8/14/2019 Springkler System

    31/114

    Basic Requirements

    The requirements for spacing, location, and position of

    sprinklers shall be based on the following principles :

    (5) When sprinklers are specifically tested and test results demonstrate

    that deviations from clearance requirements to structural members

    do not impair the ability of the sprinkler to control or suppress a fire,their positioning and locating in accordance with the test results shall

    be permitted.

    (6) Clearance between sprinklers and ceilings exceeding the maximumsspecified in this standard shall be permitted provided that tests or

    calculations demonstrate comparable sensitivity and performance of

    the sprinklers to those installed in conformance with these sections.

  • 8/14/2019 Springkler System

    32/114

    System Protection Area Limitations

    The maximum floor area on any one floor to be protected by sprinklers

    supplied by any one sprinkler system riser or combined system riser shall

    be as follows:

    (1) Light hazard = 52,000 ft2 (4831 m2)

    (2) Ordinary hazard = 52,000 ft2 (4831 m2)

    (3) Extra hazard

    (a) Pipe schedule = 25,000 ft2 (2323 m2)

    (b) Hydraulically calculated = 40,000 ft2 (3716 m2)

    (4) Storage High-piled storage = 40,000 ft2 (3716 m2)

    and storage covered

    by other NFPA standards

  • 8/14/2019 Springkler System

    33/114

  • 8/14/2019 Springkler System

    34/114

    Light Hazard Occupancies

  • 8/14/2019 Springkler System

    35/114

    Educational

    Hospitals Institutional

    Libraries, exceptlarge stack rooms

    Museums

    Nursing or convalescenthomes

    Offices, including dataprocessing

    Residential

    Restaurant seating areas

    Theaters andauditoriums, excluding

    stages and prosceniums

    Light Hazard Occupancies

    Educational

    Hospitals Institutional

    Libraries, exceptlarge stack rooms

    Museums

    Nursing or convalescenthomes

    Offices, including dataprocessing

    Residential

    Restaurant seating areas

    Theaters andauditoriums, excluding

    stages and prosceniums

    Educational

    Hospitals Institutional

    Libraries, exceptlarge stack rooms

    Museums

    Nursing or convalescenthomes

    Offices, including dataprocessing

    Residential

    Restaurant seating areas

    Theaters andauditoriums, excluding

    stages and prosceniums

  • 8/14/2019 Springkler System

    36/114

    1

    Ordinary Hazard Occupancies (Group 1)

  • 8/14/2019 Springkler System

    37/114

    Ordinary Hazard Occupancies (Group 1)

    Electronic plants

    Glass and glass

    products

    manufacturing

    Laundries

    Restaurant service

    areas

    Automobile parkingand showrooms

    Bakeries

    Beveragemanufacturing

    Canneries

    Dairy productsmanufacturing and

    processing

  • 8/14/2019 Springkler System

    38/114

    2

    Ordinary Hazard Occupancies (Group 2)

  • 8/14/2019 Springkler System

    39/114

    Ordinary Hazard Occupancies (Group 2)

    Confectionery products

    Distilleries

    Dry cleaners

    Feed mills

    Leather goods

    manufacturing

    Libraries - large stackroom areas

    Machine shops

    Mercantile

    Paper and pulp mills

    Paper process plants

    Post offices

    Printing andpublishing

    Repair garages Textile manufacturing

    Tire manufacturing

    Wood productassembly

    and etc.

  • 8/14/2019 Springkler System

    40/114

    1

    Extra Hazard Occupancies (Group 1)

  • 8/14/2019 Springkler System

    41/114

    Extra Hazard Occupancies (Group 1)

    Printing [using inkshaving flash points

    below 100F (38C)]

    Rubber reclaiming,

    compounding, drying,milling, vulcanizing

    Saw mills

    Aircraft hangars

    Combustible hydraulicfluid use areas

    Die casting

    Metal extruding

    Plywood and particleboard manufacturing

    Upholstering withplastic foams

  • 8/14/2019 Springkler System

    42/114

    2

    Extra Hazard Occupancies (Group 2)

  • 8/14/2019 Springkler System

    43/114

    Extra Hazard Occupancies (Group 2)

    Open oil quenching

    Plastics processing

    Solvent cleaning

    Varnish and paintdipping

    Asphalt saturating

    Flammable liquidsspraying

    Manufactured home ormodular building

    assemblies (wherefinished enclosure is

    present and has

    combustible interiors)

    Storage 3,7 Metres in Height and Less

  • 8/14/2019 Springkler System

    44/114

    g g

    (Miscellaneous Storage)

    Curve 1 Light Hazard Occupancy

    Curve 2 Ordinary Hazard Group 1

    Curve 3 Ordinary Hazard Group 2

    Curve 4 Extra Hazard Group 1

    Curve 5 Extra Hazard Group 2

    TREE SPRINKLER SYSTEM

  • 8/14/2019 Springkler System

    45/114

    TREE SPRINKLER SYSTEM

    LOOPED SPRINKLER SYSTEM

  • 8/14/2019 Springkler System

    46/114

    LOOPED SPRINKLER SYSTEM

    GRIDDED SPRINKLER SYSTEM

  • 8/14/2019 Springkler System

    47/114

    GRIDDED SPRINKLER SYSTEM

  • 8/14/2019 Springkler System

    48/114

    (Sprinkler System For Storage Warehouse)

    Initial Considerations

  • 8/14/2019 Springkler System

    49/114

    Initial Considerations

    Determining commodity classification

    Identifying storage arrangements

    Storage height & clearance

    Automatic Sprinklers for Storage Protection

    NFPA 13-2002, Chapter 12

    Some Storage Hazards not addressed

  • 8/14/2019 Springkler System

    50/114

    Some Storage Hazards not addressed

    by NFPA 13

    Sloped Ceilings

    Shelf Storage over 15 (4.57 m)

    Rack Storage of Exposed Expanded Plastics

    Rack Storage of Plastics with Control Mode Density/Area

    Sprinklers with Clearance greater than 10

    Open top five sided combustible containers

    Methods Of Storage

  • 8/14/2019 Springkler System

    51/114

    g

    Storage can be broken up in (4) categories:

    Idle Pallet Storage

    Storage 3,7 metres in height and less miscellaneous storage

    Storage greater than 3,7 metres in height high piled storage

    Special Storage Designs prescriptive designs for non-commodity

    based storage

    Warehouse Storage

  • 8/14/2019 Springkler System

    52/114

    1. Determine if miscellaneous storage or high piled storage

    Determine Occupancy hazard if miscellaneous or Classification of commodity if high piled

    storage.

    Apply the applicable standards of NFPA 13 requirements for this occupancy or commodity.

    Building height

    Storage height

    Will the commodity be stored on racks.After these questions are answered a sprinkler head can be selected to meet the required

    protection.

    Standard spray standard response sprinklers

    ELO Sprinkler heads, High Challenge Large Drop ,Early Suppression Fast

    Response (ESFR)

    NFPA 13 Chapter 12 covers storage protection by class of commodity, type of sprinkler,

    building height, storage height. The charts in chapter 12 provide water supply requirements for

    different storage occupancies.

    Storage 3,7 Metres in Height and Less

  • 8/14/2019 Springkler System

    53/114

    (Miscellaneous Storage)

    Storage limited in height to 3,7 metres generally is storage used for the production of

    goods or is considered miscellaneous storage. This would indicate that the facility is

    not primarily a storage warehouse. This storage is covered by the occupancy classes

    in NFPA 13.

    3,7 m or less

    Rack Storage Palletized Storage

    Warehouse Storage

  • 8/14/2019 Springkler System

    54/114

    1. Determine if miscellaneous storage or high piled storage

    2. Determine Occupancy hazard if miscellaneous Classification of commodity

    if high piled storage.

    Apply the applicable standards of NFPA 13 requirements for this occupancy or commodity.Building height

    Storage height

    Will the commodity be stored on racks.

    After these questions are answered a sprinkler head can be selected to meet the required

    protection.

    Standard spray standard response sprinklers

    ELO Sprinkler heads, High Challenge Large Drop ,Early Suppression Fast

    Response (ESFR)

    NFPA 13 Chapter 12 covers storage protection by class of commodity, type of sprinkler, building

    height, storage height. The charts in chapter 12 provide water supply requirements for different

    storage occupancies.

    Storage 3,7 Metres in Height and Less

    (Mi ll St )

  • 8/14/2019 Springkler System

    55/114

    (Miscellaneous Storage)

    Class l and ll Commodities - Curves 2 and 3

    Class lll Commodities Curve 3

    Class lV Commodities Curve 3 and 4

    Group A Plastics Curves 3, 4, and 5Miscellaneous Tire Storage Curves 3, 4, and 5

    Table 12.1.10.1.1

    from the 2002 Edition

    of NFPA 13. Storage

    heights and storage

    method dictate which

    curve to utilize

    Storage 3,7 Metres in Height and Less

  • 8/14/2019 Springkler System

    56/114

    (Miscellaneous Storage)

    Curve 1 Light Hazard Occupancy

    Curve 2 Ordinary Hazard Group 1

    Curve 3 Ordinary Hazard Group 2

    Curve 4 Extra Hazard Group 1

    Curve 5 Extra Hazard Group 2

    Warehouse Storage

  • 8/14/2019 Springkler System

    57/114

    1. Determine if miscellaneous storage or high piled storage

    2. Determine Occupancy hazard if miscellaneous

    3. Classification of commodity if high piled storage.

    Apply the applicable standards of NFPA 13 requirements for this

    occupancy or commodity.

    Building height

    Storage height

    Will the commodity be stored on racks.After these questions are answered a sprinkler head can be selected to meet the required protection.

    Standard spray standard response sprinklers

    ELO Sprinkler heads, High Challenge Large Drop ,Early Suppression Fast Response

    (ESFR)

    NFPA 13 Chapter 12 covers storage protection by class of commodity, type of sprinkler, building

    height, storage height. The charts in chapter 12 provide water supply requirements for different

    storage occupancies.

    Storage Greater than 3,7 Metres in Height

    (High Piled Storage)

  • 8/14/2019 Springkler System

    58/114

    (High Piled Storage)

    Protection approaches for High Piled Storage are based on a facility thats primary use is

    for storage. High Piled storage can be divided by its storage method as well as the

    product types being stored. Bulk or Palletized Storage, and Rack Storage are storage

    methods. Commodities Classes l through IV, Group A Plastics, Rubber Tires, and

    Rolled Paper Storage are Storage product types.

    Commodity Classification

  • 8/14/2019 Springkler System

    59/114

    Commodity Classification

    How will the product burn

    How will the burning product respond to the application

    of sprinkler discharge

    Plastic CupPaper Cup

    Styrofoam Cup

    CLASS I Commodity

  • 8/14/2019 Springkler System

    60/114

    Test Commodity

    Metal-lined cardboard cartons on wood pallets

    Examples:

    Alcoholic Beverages Cartoned or

    uncartoned

    Up to 20 percent alcohol in metal,

    glass, or ceramic containers

    Canned Foods In ordinary cartons

    Frozen Foods Non-waxed, non-plastic

    packaging

    Plastic Containers

    Noncombustible liquids or semi

    liquids in plastic containers less than

    5 gal (18.9 L) capacity

    CLASS II Commodity

  • 8/14/2019 Springkler System

    61/114

    Examples:

    Alcoholic Beverages

    Up to 20 percent alcohol in wood

    containers

    Frozen Foods Waxed-paper containers,

    cartoned

    Plastic Containers

    Noncombustible liquids or

    semiliquids (such as ketchup) in

    plastic containers with nominal wall

    thickness of 14 in. (6.4 mm) or less

    and larger than 5 gal (18.9 L)

    capacity

    Test Commodity

    Metal-lined double tri-wall corrugated

    carton on a wood pallet

    CLASS III Commodity

  • 8/14/2019 Springkler System

    62/114

    Test Commodity

    Paper cups in compartmented cardboard

    cartons on wood pallets

    Examples:

    Aerosols Cartoned or uncartoned - Level 1

    Frozen Foods - Plastic trays

    Paper Products

    Books, magazines, stationery, plastic-

    coated paper food containers,

    newspapers, cardboard games, cartoned

    tissue products

    PVC (polyvinyl chloride)

    Flexible (e.g., cable jackets, plasticized

    sheets)

    Rigid (e.g., pipe, pipe fittings)

    Bagged resins

    CLASS IV Commodity

  • 8/14/2019 Springkler System

    63/114

    Test Commodity

    A mixture of paper and plastic cups

    (5 - 15 % by weight & 5 - 25 % by volume) on

    wood pallets.

    Examples:

    Liquor -100 proof or less, 1 gal (3.8 L) or

    less, cartoned

    Glass (palletized)

    Plastic bottles

    Diapers

    Disposable with plastics and non-

    woven fabric (in cartons)

    Paints - Friction-top cans, cartoned

    Oil based

    Plastics

  • 8/14/2019 Springkler System

    64/114

    Plastic Types

    Group A - most severe hazard

    Group B - similar to Class IV commodities

    Group C - similar to Class III commodities

    Plastic materials

    Cartoned vs. Uncartoned (Exposed)

    Expanded vs. Unexpanded

    Unexpanded Group A Plastics

  • 8/14/2019 Springkler System

    65/114

    Test Commodity

    16-oz Polystyrene Plastic Jars in compartmented cardboard cartons

    Expanded Group A Plastics

  • 8/14/2019 Springkler System

    66/114

    Test Commodity

    Expanded Polystyrene Trays Exposed

    Storing Materials on Plastic Pallets

  • 8/14/2019 Springkler System

    67/114

    One class upgrade for un-reinforced

    plastic pallets

    Class II -> Class III

    Class IV -> Group A Plastics

    Two class upgrade for reinforced plastic

    pallets

    Class II -> Class IV

    Class IV -> Group A Plastics

    Plastic Pallet Types

  • 8/14/2019 Springkler System

    68/114

    Un-reinforced plastic pallets

    Melt fairly easily in a fire and are less of a fire challenge

    Material

    Polypropylene

    high-density polyethylene

    Reinforced plastic pallets

    Hold their structure and integrity longer allowing air gaps

    to remain longer within the pallet, which fuels the flames

    and creates a more intense fire

    Material

    Polypropylene

    high-density polyethylene

    Classification by Listing

    Encapsulation

    Plastic sheet completely enclosing

  • 8/14/2019 Springkler System

    69/114

    Plastic sheet completely enclosing

    the sides and top of a pallet load

    containing a combustible

    commodity

    Combustible commodities

    individually wrapped in plastic

    sheeting and stored exposed in a

    pallet load

    Where there are holes or voids inthe plastic on the top of the carton

    that exceed more than half of the

    area of the cover, the term

    encapsulateddoes not apply

    Mixed Commodities

  • 8/14/2019 Springkler System

    70/114

    Mixed commodity storage protected using highest

    classified commodity & storage arrangement.

    The protection requirements for the lower commodity

    may be used when:

    No more than 10 pallet loads of a higher hazard

    commodity in area > 40,000 ft2 (3716 m2) &

    Higher hazard commodity is randomly dispersed

    with no adjacent loads in any direction (including

    diagonally) &

    Where the ceiling protection is based on Class I -

    II commodities, the allowable number of pallet

    loads for Class IV or Group A plastics is reduced

    to five.

    Other Types of Commodities

  • 8/14/2019 Springkler System

    71/114

    Baled Cotton

    Rubber Tire

    Idle Pallet

    Rolled Paper

    Aisles

  • 8/14/2019 Springkler System

    72/114

    The clear space normally maintained between commodities

    stored in racks or on the floor for the transfer of commodities

    to or from the rack or storage pile.

    Flue Spaces The open spaces between rows of storage.

  • 8/14/2019 Springkler System

    73/114

    Rack Storage

    Longitudinal flue spaces are perpendicular to the direction of loading

    Transverse flue spaces are parallel to the direction of loading

    Solid-piled & palletized storage

    Vertical flue spaces may run in either direction

    Array

    Closed Array A storage

  • 8/14/2019 Springkler System

    74/114

    Closed Array. A storage

    arrangement where air movement

    through the pile is restricted

    because of 6-in. (152-mm) or less

    vertical flues.

    Open Array. A storage

    arrangement where air movement

    through the pile is enhanced

    because of vertical flues larger

    than 6 in. (152 mm).

    Pile Stability

  • 8/14/2019 Springkler System

    75/114

    Unstable Piles : Arrays wherecollapse, spillage of contents, or

    leaning of stacks across flue

    spaces occurs soon after initial fire

    development.

    Stable Piles : Arrays wherecollapse, spillage of content, or

    leaning of stacks across flue spaces

    is not likely to occur soon after

    initial fire development.

    Storage Arrangements

  • 8/14/2019 Springkler System

    76/114

    Miscellaneous Storage

    Idle Pallet Storage

    Solid Pile Storage

    Palletized Pile Storage

    Rack Storage

    Miscellaneous Storage

  • 8/14/2019 Springkler System

    77/114

    Storage must be incidental

    to another occupancy use

    group.

    Idle Pallet Storage

  • 8/14/2019 Springkler System

    78/114

    Wood Pallets Plastic Pallets

    Solid-Pile, Palletized, Bin Box & Shelf Storage

  • 8/14/2019 Springkler System

    79/114

    Palletized StorageSolid Pile Storage

    Solid-Pile, Palletized, Bin Box & Shelf Storage

  • 8/14/2019 Springkler System

    80/114

    Shelf Storage. Storage on

    structures less than 30 (76.2

    cm) deep with shelves usually 2

    (0.6 m) apart vertically and

    separated by approximately 30

    (76.2-cm) aisles.

    Shelf Storage

    Rack Storage - Single-Row Rack

  • 8/14/2019 Springkler System

    81/114

    Racks that have no

    longitudinal flue space and

    that have a width up to 6 ft(1.8 m) with aisles at least

    3.5 ft (1.1 m) from other

    storage.

    Rack Storage - Double-Row Rack

  • 8/14/2019 Springkler System

    82/114

    Two single-row racks placed back-to-back having a

    combined width up to 12 ft (3.7 m), with aisles at least

    3.5 ft (1.1 m) on each side.

    Rack Storage - Multiple-Row Rack

  • 8/14/2019 Springkler System

    83/114

    Racks greater than 12 ft (3.7 m) wide or single- or

    double-row racks separated by aisles less than 3.5 ft

    (1.1 m) wide having an overall width greater than 12

    ft (3.7 m).

    Movable Racks & Portable Racks

  • 8/14/2019 Springkler System

    84/114

    Movable Rack Portable Rack Portable Rack

    Solid Shelving Fixed in place, slatted, wire mesh or other type of shelves located within racks.

  • 8/14/2019 Springkler System

    85/114

    The area of a solid shelf is defined by perimeter aisle or flue space on all four sides.

    Solid shelves having an area equal to or less than 20 sq. ft. are open racks.

    Shelves of wire mesh, slates, or other materials more than 50 % open, where the flue

    spaces are maintained are open racks.

    Idle Pallet Storage

    Pallets not being used and are stored 2 metres high and either stored

  • 8/14/2019 Springkler System

    86/114

    on the floor or in racks are idle pallets. The most prevalent type of

    pallet is a standard wood pallet and a reinforced plastic pallet.

    Standard Wood Pallets Reinforced Plastic Pallets

    Idle Pallet Storage

  • 8/14/2019 Springkler System

    87/114

    It is encouraged to store idle pallets outdoors. If the pallets must be

    stored indoors, their storage is limited in height and pile size.

    Pallet piles should only be in groups of 4 pallets and the groups of

    pallets should not be stored closer than 1.4 metres to each other.

    Where idle pallets are stored near commodity storage, the idlepallets should not be stored closer than 7,6 metre to the

    commodity.

    Pallets are designed to burn, as there are small members that make up

    the pallet that ignite easily. The openings in the pallets allow great

    air movement and draw the fire up the pile.

    Storage 3,7 Metres in Height and Less

    (Miscellaneour Storage)

  • 8/14/2019 Springkler System

    88/114

    Storage limited in height to 3,7 metres generally is storage used for the

    production of goods or is considered miscellaneous storage. This would

    indicate that the facility is not primarily a storage warehouse. This storage

    is covered by the occupancy classes in NFPA 13.

    3,7 m or less

    Rack Storage Palletized Storage

    Storage 3,7 Metres in Height and Less

    (Mi ll St )

  • 8/14/2019 Springkler System

    89/114

    (Miscellaneous Storage)

    Class l and ll Commodities - Curves 2 and 3

    Class lll Commodities Curve 3

    Class lV Commodities Curve 3 and 4

    Group A Plastics Curves 3, 4, and 5

    Miscellaneous Tire Storage Curves 3, 4, and 5

    Table 12.1.10.1.1 from the

    2002 Edition of NFPA 13.

    Storage heights and storage

    method dictate whichcurve to utilize

    Storage 3,7 Metres in Height and Less

    (Mi ll St )

  • 8/14/2019 Springkler System

    90/114

    (Miscellaneous Storage)

    Curve 1 Light Hazard Occupancy

    Curve 2 Ordinary Hazard Group 1

    Curve 3 Ordinary Hazard Group 2

    Curve 4 Extra Hazard Group 1Curve 5 Extra Hazard Group 2

    Upright and pendent spray sprinklers shall be permitted in all occupancy hazard classifications and

    building construction types

    Classification of Occupancies

  • 8/14/2019 Springkler System

    91/114

    building construction types.

    5.1* Classification of Occupancies.

    5.1.1 Occupancy classifications for this standard shall relate to sprinkler design, installation, and water

    supply requirements only.5.1.2 Occupancy classifications shall not be intended to be a general classification of occupancy hazards.

    5.2* Light Hazard Occupancies.

    Light hazard occupancies shall be defined as occupancies or portions of other occupancies where the

    quantity and/or combustibility of contents is low and fires with relatively low rates of heat release are

    expected.

    Examples : Churches, Clubs, Hospitals, Museums, Offices, Restaurant Seating Areas

    5.3.1* Ordinary Hazard (Group 1).

    Ordinary hazard (Group 1) occupancies shall be defined as occupancies or portions of other occupancies

    where combustibility is low, quantity of combustibles is moderate, stockpiles of combustibles do not

    exceed 2.4 m, and fires with moderate rates of heat release are expected.Examples :Restaurant Service Areas, Bakeries, Automobile Parking and Showrooms, Laundrie

    5.3.2* Ordinary Hazard (Group 2). Ordinary hazard (Group 2) occupancies shall be defined as occupancies

    or portions of other occupancies where the quantity and combustibility of contents are moderate to high

    Classification of Occupancies - Continued

  • 8/14/2019 Springkler System

    92/114

    or portions of other occupancies where the quantity and combustibility of contents are moderate to high,stockpiles do not exceed 3.7 m, and fires with moderate to high rates of heat release are expected.

    Examples : Dry Cleaners, Horse Stables, Machine Shops, Library, Stack Rooms, Mercantile,

    Confectionary Products

    5.4.1* Extra Hazard (Group 1). Extra hazard (Group 1) occupancies shall be defined as occupancies or

    portions of other occupancies where the quantity and combustibility of contents are very high and dust,

    lint, or other materials are present, introducing the probability of rapidly developing fires with high rates

    of heat release but with little or no combustible or flammable liquids.

    Examples : Combustible Hydraulic Fluid Use Areas, Metal Extruding, Saw Mills, Upholstering

    with Plastic Foams, Rubber Reclaiming

    5.4.2* Extra Hazard (Group 2). Extra hazard (Group 2) occupancies shall be defined as occupancies orportions of other occupancies with moderate to substantial amounts of flammable or combustible liquids

    or occupancies where shielding of combustibles is extensive.

    Examples: Flammable Liquids Spraying, Open Oil Quenching, Plastics Processing, Solvent

    Cleaning, Varnish and Paint Dipping

    Storage Grater than 3,7 Metres in Height

    (High Piled Storage)

  • 8/14/2019 Springkler System

    93/114

    (High Piled Storage)

    Protection approaches for High Piled Storage are based on a facility thats primary

    use is for storage. High Piled storage can be divided by its storage method aswell as the product types being stored. Bulk or Palletized Storage, and Rack

    Storage are storage methods. Commodities Classes l through IV, Group A

    Plastics, Rubber Tires, and Rolled Paper Storage are Storage product types.

    Class I

    5 6 3 1* A Class I commodity shall be defined as a noncombustible product that meets one of

    Classification of Commodities

  • 8/14/2019 Springkler System

    94/114

    5.6.3.1 A Class I commodity shall be defined as a noncombustible product that meets one of

    the following criteria:

    (1) Placed directly on wooden pallets

    (2) Placed in single-layer corrugated cartons, with or without single-thickness cardboard

    dividers, with or without pallets

    (3) Shrink-wrapped or paper-wrapped as a unit load with or without pallets

    Examples :Bagged Cement, Metal File Cabinets, Wire, Appliances

    Class ll

    5.6.3.2* Class II. A Class II commodity shall be defined as a noncombustible product that is

    in slatted wooden crates, solid wood boxes, multiple-layered corrugated cartons, or

    equivalent combustible packaging material, with or without pallets.

    Examples : Boxes, Baled Leather Hides, Pharmaceauticals, Cartoned Light Fixtures(non-plastic)

    Classification of Commodities (Continued)

    Class lll

  • 8/14/2019 Springkler System

    95/114

    Class lll

    5.6.3.3.1 A Class III commodity shall be defined as a product fashioned from wood, paper,

    natural fibers, or Group C plastics with or without cartons, boxes, or crates and with or

    without pallets.

    5.6.3.3.2 A Class III commodity shall be permitted to contain a limited amount (5 percent by

    weight or volume or less) of Group A or Group B plastics.

    Examples : Wood Furniture, Natural Fiber Cloth, Diapers, Packaged Cartoned

    Dried Foods

    Classification of Commodities (Continued)

    Class IV

  • 8/14/2019 Springkler System

    96/114

    Class IV

    5.6.3.4.1 A Class IV commodity shall be defined as a product, with or without pallets, that meets one of the

    following criteria:

    (1) Constructed partially or totally of Group B plastics(2) Consists of free-flowing Group A plastic materials

    (3) Contains within itself or its packaging an appreciable amount (5 percent to 15 percent by weight or 5

    percent to 25 percent by volume) of Group A plastics

    5.6.3.4.2 The remaining materials shall be permitted to be metal, wood, paper, natural or synthetic fibers, or

    Group B or Group C plastics.

    EXAMPLES:Blocks of Natural Rubberin cartons, Vinyl Floor Covering, Nail Polish- 30 to 60 ml,

    Lightweight Rolled Paper in racks

    5.6.4* Classification of Plastics,

    Elastomers, and Rubber. Plastics, elastomers, and rubber shall be classified as Group A, Group B, or

    Group C.

    5.6.4.1* Group A. The following materials shall be classified as Group A:

    (1) ABS (acrylonitrile-butadiene-styrene copolymer)

    (2) Acetal (polyformaldehyde)

    Classification of Commodities (Continued) - Plastic

  • 8/14/2019 Springkler System

    97/114

    p y y

    (3) Acrylic (polymethyl methacrylate)

    (4) Butyl rubber

    (5) EPDM (ethylene-propylene rubber)

    (6) FRP (fiberglass-reinforced polyester)

    (7) Natural rubber (if expanded)

    (8) Nitrile-rubber (acrylonitrile-butadiene-rubber)

    (9) PET (thermoplastic polyester)

    (10) Polybutadiene

    (11) Polycarbonate

    (12) Polyester elastomer

    (13) Polyethylene

    (14) Polypropylene

    (15) Polystyrene

    (16) Polyurethane

    (17) PVC (polyvinyl chloride highly plasticized, with plasticizer content greater than 20 percent) (rarely found)

    (18) SAN (styrene acrylonitrile)

    (19) SBR (styrene-butadiene rubber)

    Classification of Commodities (Continued) - Plastic

    5.6.4.2 Group B. The following materials shall be classified as Group B:

    (1) Cellulosics (cellulose acetate, cellulose acetate butyrate, ethyl cellulose)

  • 8/14/2019 Springkler System

    98/114

    (2) Chloroprene rubber

    (3) Fluoroplastics (ECTFE ethylene-chlorotrifluoro-ethylene copolymer; ETFE ethylene-tetrafluoroethylene-

    copolymer; FEP fluorinated ethylene-propylene copolymer)

    (4) Natural rubber (not expanded)

    (5) Nylon (nylon 6, nylon 6/6)

    (6) Silicone rubber

    5.6.4.3 Group C. The following materials shall be classified as Group C:

    (1) Fluoroplastics (PCTFE polychlorotrifluoroethylene; PTFE polytetrafluoroethylene)

    (2) Melamine (melamine formaldehyde)

    (3) Phenolic

    (4) PVC (polyvinyl chloride flexible PVCs with plasticizer content up to 20 percent)

    (5) PVDC (polyvinylidene chloride)

    (6) PVDF (polyvinylidene fluoride)

    (7) PVF (polyvinyl fluoride)

    (8) Urea (urea formaldehyde)

    Classification of Commodities (Continued)

    5.6.5* Classification of Rolled Paper Storage. For the purposes of this standard, the classifications of paper

    d ib d i 5 6 5 1 th h 5 6 5 4 h ll l d h ll b d t d t i th i kl t d i

  • 8/14/2019 Springkler System

    99/114

    described in 5.6.5.1 through 5.6.5.4 shall apply and shall be used to determine the sprinkler system design

    criteria.

    5.6.5.1 Heavyweight Class. Heavyweight class shall be defined so as to include paperboard and paper stock

    having a basis weight per 92.9 m of 9.1 kg.

    5.6.5.2 Mediumweight Class. Mediumweight class shall be defined so as to include all the broad range of

    papers having a basis weight per 92.9 m of 4.5 kg to 9.1 kg.

    5.6.5.3 Lightweight Class. Lightweight class shall be defined so as to include all papers having a basis weight

    per 92.9 m of 4.5 kg.

    5.6.5.4 Tissue.

    5.6.5.4.1 Tissue shall be defined so as to include the broad range of papers of characteristic gauzy texture,which, in some cases, are fairly transparent.

    5.6.5.4.2 For the purposes of this standard, tissue shall be defined as the soft, absorbent type, regardless of

    basis weight specifically, crepe wadding and the sanitary class including facial tissue, paper napkins,

    bathroom tissue, and toweling.

  • 8/14/2019 Springkler System

    100/114

    In-Rack Sprinklers

    (also known as intermediate level sprinklers)

    In-Rack Sprinklers

    Generally, when storage exceeds 25-0 in racks and control mode

  • 8/14/2019 Springkler System

    101/114

    sprinklers are utilized, levels of in-rack sprinklers are within the rack

    structure.

    In-rack sprinklers require water shields to protect their operating

    elements from the ceiling sprinklers. Water shields are required to be

    a minimum of 3 in diameter.

    In-rack sprinklers are intermediate level sprinklers, as there is at

    least one level of sprinklers above them.

    In-Rack Sprinkler

  • 8/14/2019 Springkler System

    102/114

    In Rack Sprinkler

    With Water Shield

    Control Mode

    Sprinklers

    In-Rack Sprinklers

    In-rack sprinklers are typically have k factors of 5.6 and 8.0, but in

  • 8/14/2019 Springkler System

    103/114

    p yp y ,some cases are as large as 11.2.

    In-rack sprinklers are usually located in the longitudinal flue space

    of the rack, but can be located at the face of the rack loading

    entrance and can be located within the storage space within the rack.

    Rack structures with solid barriers require levels of in-rack

    sprinklers above the storage where the solid barriers exist.

    Storage Suppression Sprinkler

    (Early Suppression Fast Response (ESFR))

  • 8/14/2019 Springkler System

    104/114

    ESFR Sprinklers

    ESFR Sprinklers were developed by Factory Mutual in the early 1980s.

    ESFR i kl i i kl i th t f i kl

  • 8/14/2019 Springkler System

    105/114

    ESFR sprinklers are suppression sprinklers meaning these type of sprinklers

    are designed not to control a fire, but to suppress the fire.

    ESFR sprinklers in standard commodity storage, such as Class l, Class ll,

    Class lll, Class lV, commodities and plastic commodities, can eliminate in-rack

    sprinklers. ESFR sprinklers are limited to wet type sprinkler systems andmust be installed in buildings that have flat ceilings or roofs. Flat ceilings are

    defined as roof pitches no greater than 2 inches in 12 inches.

    In-Rack Sprinkler

  • 8/14/2019 Springkler System

    106/114

    pWith Water Shield

    Control Mode

    Sprinklers

  • 8/14/2019 Springkler System

    107/114

    ESFR SprinklersEliminate In-Rack

    Sprinklers in most

    Cases

    Control Mode Specific Application

    Sprinkler (Large Drop Sprinkler)

  • 8/14/2019 Springkler System

    108/114

    Sprinkler (Large Drop Sprinkler)

    Control Mode specific application sprinklers are also known asLarge Drop Sprinklers. Large Drop sprinklers were the first

    special storage sprinklers. Large Drop sprinkler design is notarea/density, but rather a prescriptive design of a number of

    sprinklers designed to operate at a minimum water pressure.

  • 8/14/2019 Springkler System

    109/114

  • 8/14/2019 Springkler System

    110/114

  • 8/14/2019 Springkler System

    111/114

  • 8/14/2019 Springkler System

    112/114

  • 8/14/2019 Springkler System

    113/114

  • 8/14/2019 Springkler System

    114/114