    Satisfactory Boiler start up

    Start up of individual oil system AB/CD/EF

    Operation of fuel firing subject to certain conditionsA/B/C/D/F

    Protection and interlock of oil /Coal System

  • 7/31/2019 02 FSSS Logic System

    3/51

    24 May 2012 PMI Revision 00 3

    Typical Graphic Display of fuelfiring

    244 subscriptions (requests)

    for data from the DPU.

    75 maxSCRIPTS

    30 Buttons

    29 List Controls

    3 Bar Charts

    14 Text State controls

    45 objects have dynamicborders

    200K of various static bitmaps

  • 7/31/2019 02 FSSS Logic System

    4/51

    24 May 2012 PMI Revision 00 4

    The boiler can be placed in service, initially orafter a Master Fuel Trip, in the following

    sequence through FSSS.

    Furnace Purge

    Before any fuel firing can takes place, initially or

    following a boiler trip, a satisfactory PurgeCyclemust be completed.

  • 7/31/2019 02 FSSS Logic System

    5/51

    24 May 2012 PMI Revision 00 5

    Initially, the Heavy Oil must be recirculated andheated to obtain the proper temperature and

    viscosity for efficient combustion. After this is

    accomplished, the Heavy Oil Trip Valve (HOTV)

    can be closed and then the furnace purge

    cycle can be started.

  • 7/31/2019 02 FSSS Logic System

    6/51

    24 May 2012 PMI Revision 00 6

    After the furnace purge cycle is completed, the heavy oil

    elevation (AB, CD, EF, & GH) can be taken into service. Anoil elevation is said to be InService, when at least three

    out of four heavy oil nozzle valves are open and the flame

    is sensed by the scanners.

    After the heavy oil elevation is in service, either of the

    adjacent coal elevation can be taken into service because

    IgnitionPermit is now available for starting the pulverizer.

  • 7/31/2019 02 FSSS Logic System

    7/51

    24 May 2012 PMI Revision 00 7

    A Coal elevation is said to be In Service after

    the Pulverizer is ON, its Hot Air Gate (HAG) is

    open and the associated Feeder is proven (i.e.,

    feeder ON for more than 50 seconds). A fireballsignal is established when the associated fireball

    flame scanner senses flame and ELEVATION

    FLAME indicator is illuminated on the FSSSconsole in control room.

  • 7/31/2019 02 FSSS Logic System

    8/51

    24 May 2012 PMI Revision 00 8

    Boiler purge operation

    Start up of oil firing(AB,CD,FH & GH)

    Adequate Ignition permit

    Firing of coal elevation(A,B,C,D,E,F,G & H)

    Flame sensing by scanners.

  • 7/31/2019 02 FSSS Logic System

    9/51

    24 May 2012 PMI Revision 00 9

    FSSS LOGIC

    FSSS logics can be broadly divided

    into 3 sections.

    Unit Logic.

    Oil Elevation Logic.

    Coal Elevation Logic

  • 7/31/2019 02 FSSS Logic System

    10/51

    24 May 2012 PMI Revision 00 10

    Boiler purge logic

    Master fuel trip logic

    Oil trip valve operation logic

    PA Fans logic

    Scanner air Fans logic

    Seal air Fan logic

  • 7/31/2019 02 FSSS Logic System

    11/51

    24 May 2012 PMI Revision 00 11

    FURNACE PURGE

    Purpose::Complete Removal of unburnt fuel from entire furnace

    Procedure: Ensure that all fuel to furnace is cut off and all flame is out Provide adequate air flow through furnace (30 to 40%) Initiate a MANDATORY purge time cycle (9 min)

    Consequence: Master Fuel Trip Relays are reset Firing of fuel into the furnace is allowed

  • 7/31/2019 02 FSSS Logic System

    12/51

    24 May 2012 PMI Revision 00 12

    Boiler purge logic, which ensures a

    fiveminutes purge cycle is completed

    before any fuel firing can take place.

    A PurgeReady signal at control room

    will be available when all the following

    conditions are satisfied:

  • 7/31/2019 02 FSSS Logic System

    13/51

    24 May 2012 PMI Revision 00 13

    All HFO nozzle valves are closed

    All Pulverizers are off

    No MFT condition present

    All feeders are off All scanners sensing no flame.

    All auxiliary air dampers modulating

    Both PA fans off

    All HAGs closed Air flow more than 30% and less than 50%

    HFO trip valve is closed

    Wind box to furnace DP is adequate.

  • 7/31/2019 02 FSSS Logic System

    14/51

    24 May 2012 PMI Revision 00 14

    TOFSSS

    All HFO nozzle valves closed

    All pulverisers OFF

    All feeders OFF

    No MFT condition present

    All scanners senses no flame

    All Auxiliary Air dampers modulating

    Both PA fans OFF

    All Mill HAGs closed

    Air flow more than 30% and less than 50%

    HFO trip valve is closed

    Wind box to furnace DP is adequate

  • 7/31/2019 02 FSSS Logic System

    15/51

    24 May 2012 PMI Revision 00 15

    MASTER FUEL TRIP (MFT) MFT or Boiler Trip means:

    Complete isolation of all fuel to furnace under certainconditions

    Automatic Procedure:

    All oil valves are given closing command

    All mills and feeders are given trip command

    All Primary Air (PA) Fans are given trip command

    All Hot Air Gates (to mills) are given closing command

    Further Consequences: Turbine protection is initiated (to trip turbine) All SH and RH spray valves are given closing command

    All elevation SADC are given full open command

    Furnace pressure & Air flow controls are set to manual

  • 7/31/2019 02 FSSS Logic System

    16/51

    24 May 2012 PMI Revision 00 16

    This ensures a safe shut down of the boiler in case

    of any abnormal conditions in boiler/ furnace. Ifsome abnormal condition occurs, Master Fuel TripRelay acts and ensures the closure of Heavy OilTrip valve (HOTV) and all Oil Nozzle Valves (ONV),

    thus cutting off total oil supply. It also ensures thestopping of all pulverizer systems and Primary Air(PA) fans, cutting off total coal supply to boiler. Thevarious abnormal operating conditions under which

    Master Fuel Trip occurs are as follows:-

  • 7/31/2019 02 FSSS Logic System

    17/51

    24 May 2012 PMI Revision 00 17

    Both FD fans OFF

    Both ID fans OFF. Inadequate water wall circulation for more than 5 seconds.

    Loss of Reheat Protection for greater than 10 seconds. All BFPs tripped. Drum level very high for more than 10 seconds (2/3 logic) Drum level very low for more than 10 seconds (2/3 logic)

    Furnace pressure very high (2/3 logic) Furnace pressure very low (2/3 logic) Loss of all fuel. All feeders OFF and loss of AC Supply to the elevation in service.

    Unit flame failure.

    Loss of Unit Critical Power for more than 2 seconds Both Secondary APHs OFF.

    Loss of 220 V DC Supply for more than 2 seconds. Air flow less than 30% and boiler load not greater than 30%. Manual Emergency trip.

    B h FD f OFF

  • 7/31/2019 02 FSSS Logic System

    18/51

    24 May 2012 PMI Revision 00 18

    Both FD fans OFFBoth ID fans OFF

    MFTRELAY

    Air flow less than 30% and boiler load not greater than 30%

    Loss of 220 V DC Supply for more than 2 seconds

    Manual Emergency PB trip

    Both Secondary APHs OFF

    Loss of Unit Critical Power for more than 2 seconds

    Unit flame failure

    All feeders OFF and loss of AC Supply to the elevation in service

    Loss of all fuel

    Furnace pressure very low (2/3 logic)

    Furnace pressure very high (2/3 logic)

    Drum level very low for more than 10 seconds (2/3 logic)

    Drum level very high for more than 10 seconds (2/3 logic)

    All BFPs tripped

    Loss of Reheat Protection for greater than 10 seconds

    Inadequate water wall circulation for more than 5 seconds

  • 7/31/2019 02 FSSS Logic System

    19/51

    24 May 2012 PMI Revision 00 19

    Trips all mills

    Trips all feeders

    Trips PA fans

    Closes HFO trip valve

    Closes all elevation nozzle valves

    Close all HAGs

  • 7/31/2019 02 FSSS Logic System

    20/51

    24 May 2012 PMI Revision 00 20

  • 7/31/2019 02 FSSS Logic System

    21/51

    24 May 2012 PMI Revision 00 21

    This logic ensures that oil trip valve can be opened

    after the purge cycle is completed and no MFTcondition is present, if the following conditions are

    also satisfied.

    All nozzle valves are closed.

    HFO supply pressure is satisfactory.

    HFO header temperature is satisfactory. Similarly, this logic ensures the closure of oil trip

    valve in case of MFT.

  • 7/31/2019 02 FSSS Logic System

    22/51

    24 May 2012 PMI Revision 00 22

    It monitors the scanner air duct to furnace DP

    and ensures starting of scanner air fan - A or incase it fails to start, scanner air fan - B. Thislogic gives an open command to scanner fanoutlet damper after starting the fan.

    Also, in case of both FD fans not running, itensures the scanner air emergency damper is

    open.

  • 7/31/2019 02 FSSS Logic System

    23/51

    24 May 2012 PMI Revision 00 23

    Monitors seal air header to cold air duct DP

    and ensures the starting of seal air fan - A or

    B ( in case A does not start), provided at least

    one PA fan is running.

    Gives an open command to seal air fandischarge damper once fan starts.

  • 7/31/2019 02 FSSS Logic System

    24/51

    24 May 2012 PMI Revision 00 24

    Oil Elevation Logic

    AB/CD/EF/HJ*

  • 7/31/2019 02 FSSS Logic System

    25/51

    24 May 2012 PMI Revision 00 25

  • 7/31/2019 02 FSSS Logic System

    26/51

    24 May 2012 PMI Revision 00 26

  • 7/31/2019 02 FSSS Logic System

    27/51

    24 May 2012 PMI Revision 00 27

    Start of oil elevations AB,CD,EF and GH

    Sequential operation with start command

    Corner1,corner3,corner2 and corner4

    Gun advance,igniter advance

    Spark,atomizing valve open,oil valve open

    Sensing of discriminatory flame

    Retract of igniter

  • 7/31/2019 02 FSSS Logic System

    28/51

    24 May 2012 PMI Revision 00 28

    Stop of oil elevation

    Closure of oil valve,opening of scavenge valve

    Igniter advance and sparking

    Closure of atomizing valve and scavenge valve

    Retract of igniter and gun

  • 7/31/2019 02 FSSS Logic System

    29/51

    24 May 2012 PMI Revision 00 29

    OIL ELEVATION LOGIC

    There are four heavy oil elevations AB, CD, EF & GH. Forall these elevations, logics are same. Oil elevation can be

    placed in service auto/manual. For a particular elevation,

    only one command is given for all the four corners together.

    (e.g. One common start command for elevation AB-1, 2, 3and 4 guns). But start command goes to corners 1 to 4

    sequentially. First command goes to corner 1; after 15

    seconds start commend goes to corner 3; again after a

    lapse of 15 seconds start commend goes to corner 2; and

    again after a gap of 15 seconds start command goes to

    corner 4.

  • 7/31/2019 02 FSSS Logic System

    30/51

  • 7/31/2019 02 FSSS Logic System

    31/51

    24 May 2012 PMI Revision 00 31

    The sequence of operation taking place for a particular oil gun once thecommand is given is as follows:-

    First the oil gun is advanced. Once gun advanced feedback is available the HEA igniter is advanced. Then atomizing steam valve is opened for the particular corner. Then HFO nozzle valve gets open command.

    Spark command is given to igniter transformer, thus producing a spark at

    the spark tip. Then for this particular corner HFO flow satisfactory feedback comes

    from the flow switch in the oil line. The corner oil gun proves when the DISCR FLAME SCANNER senses

    FLAME.

    When 25 seconds elapses after oil valve open, igniter spark signal is

    removed and spark rod is retracted. If the corner oil gun did not prove FLAME by this time, Oil nozzle valve

    and atomizing steam valve closes. Gun and igniter are retracted.

  • 7/31/2019 02 FSSS Logic System

    32/51

    24 May 2012 PMI Revision 00 32

    OIL FIRING PERMISSIVE-

    1-PURGE COMPLETE/MFT RESET AND NO FIRST

    UP FAULT.2- HFO PR. OK >25 KSC.3- HFO TEMP OK >95C4- IGNITOR AIR PR. >200 MMWG.5- IGNITOR OIL PR. >10 KSC.

    6- NO LIGHT UP IN PROGRESS.7- NO BURNER START INHIBIT.8-PERMISSIVE TO FIRE OIL.

  • 7/31/2019 02 FSSS Logic System

    33/51

    24 May 2012 PMI Revision 00 33

    OIL BURNER START LOGIC

    *OIL BURNER START PUSH BUTTON (NO

    OTHER OIL BURNER START IN PROGRESS).

    OIL BURNER START SEQUENCE-

    1-OIL BURNER SEC. AIR DAMPER OPENED.2-OPEN IGNITER OIL MASTER TRIP VALVE.3-NO FLAME SENSED IN LAST 5 SEC.4-ENERGISE IGNITOR TRANSFORMER.

    5- OPEN IGNITOR OIL SOLENOID V/V.6- DETECT IGNITION OIL FLAME.7- 4 WAY V/V TO FIRING POSITION.8- OIL FLAME DETECTED.

    9-CLOSE IOTV/SOL. V/V.

  • 7/31/2019 02 FSSS Logic System

    34/51

    24 May 2012 PMI Revision 00 34

    Coal Elevation Logic

    A/B/C/D/F

  • 7/31/2019 02 FSSS Logic System

    35/51

    24 May 2012 PMI Revision 00 35

  • 7/31/2019 02 FSSS Logic System

    36/51

    24 May 2012 PMI Revision 00 36

  • 7/31/2019 02 FSSS Logic System

    37/51

    24 May 2012 PMI Revision 00 37

    Pulverizer start logic

    Availability of PA permit

    Availability of ignition permit

    Seal air /bowl differential pressure

    No MFT

    Lube oil pressure adequate

    Pulverizer stop logic

  • 7/31/2019 02 FSSS Logic System

    38/51

    24 May 2012 PMI Revision 00 38

    Feeder start logic

    Pulverizer on

    Outlet temperature adequate

    Speed demand minimum

    No MFT

    Feeder stop logic

    Had/cad logic

  • 7/31/2019 02 FSSS Logic System

    39/51

    24 May 2012 PMI Revision 00 39

    COAL ELEVATION LOGIC

    PULVERISER LOGIC

    This logic takes the count of total no. of pulverisers in

    service at any point of time, the no. of FD Fans andPA fans in service. With PA Fan ON and PA HeaderPressure adequate (>560 mmwcl), it gives PApermit to start the Pulverizer. In case of PA Header

    Pressure going low-low or PA/ FD fans trips, itensures the shut down of Pulverizers from topelevation to bottom elevation in a timed sequence.

  • 7/31/2019 02 FSSS Logic System

    40/51

    24 May 2012 PMI Revision 00 40

    Each mill can be taken in to service manually or

    automatically. Auto manual selection push button

    is available on FSSS console for each mill.

    Initially, Pulverizer Ignition Permit signal mustbe established for the mill to start. Other condition

    required to be established for starting the mill are

    as follows:-

  • 7/31/2019 02 FSSS Logic System

    41/51

    24 May 2012 41

    INTERMEDIATE OIL BURNERELEVATION FIRING

    OR

    30% BOILER LOAD

    ADJACENT MILL FIRING

    PA FAN IN SERVICE

    AND

    AND

  • 7/31/2019 02 FSSS Logic System

    42/51

    24 May 2012 PMI Revision 00 42

    Mill lub oil pressure adequate.

    Start permit from FSSS.

    Mill Discharge valve open.

    Mill outlet temp. > 93OC.(200OF)

    Cold Air Gate (CAG) open.

    Tramp iron vale (Top Reject Gate) open.

    Feeder inlet gate open.

    Seal air DP adequate (200 mmwcl).

    Feeder local switch in remote.

    Once the mill is ON, associated HAG can be opened

    and feeder can be placed in service.

  • 7/31/2019 02 FSSS Logic System

    43/51

    24 May 2012 PMI Revision 00 43

    OIL BURNER FIRING ON MILL BEING BROUGHT

    INTO SERVICE-

    FOR ANY MILLS(A,B,C,D,E,F,G,H)1-AT LEAST THREE OIL BURNER S FIRING IN SELECTED

    ELEVATION.

    2- (A) BOILER LOAD > 30% BCMR

    AND(B) UPPER OR LOWER ADJACENT COAL BURNER IN

    OPERATION

    EXAMPLE: FOR MILL A START PERMISSIVE:1- ELEVATION AB 3/4 OIL BURNER FIRING.

    OR2- MILL B FIRING

    ANDBOILER LOAD >30% BCMR.

    O

  • 7/31/2019 02 FSSS Logic System

    44/51

    24 May 2012 PMI Revision 00 44

    FOR B,D,F MILLA) AT LEAST 3 OIL BURNERS FIRING IN THE BURNER

    GROUP ABOVE

    AND(B) ADJACENT COAL BURNER ABOVE IN OPERATIONAND

    (C) THIS ELEVATION IS HIGHEST IN THE BURNER GROUP

    EXAMPLE- FOR MILL B START PERMISSIVE-

    (1) ELEVATION AB 3 / 4 OIL BURNER ARE I/ S .

    OR(2) MILL A FIRING OR MILL C FIRING

    AND

    BOILER LOAD > 30% OF BCMR.OR

    (3) MILL C FIRING

    ANDELEVATION CD 3 / 4 OIL BURNER ARE I/S.

    * NOTE THAT B ELEVATION IS HIGHEST IN THE BURNER GROUP AB.

  • 7/31/2019 02 FSSS Logic System

    45/51

    24 May 2012 PMI Revision 00 45

    FOR MILL C,E,GA) AT LEAST 3 OIL BURNER FIRING IN THE BURNER GROUP BELOW.

    AND

    (B) ADJACENT COAL BURNER BELOW IN OPERATION.AND

    (C) THIS ELEVATION IS LOWEST IN THE BURNER GROUP.

    EXAMPLE- FOR MILL C START PERMISSIVE (1) ELEVATION CD 3 / 4 OIL BURNER I/S.

    OR(2) MILL B FIRING OR MILL D FIRING

    ANDLOAD > 30% OF BCMR.

    OR(3) MILL B FIRING

    ANDELEVATION AB 3 / 4 OIL BURNER ARE I/S.

    * NOTE THAT C ELEVATION IS LOWEST IN THE BURNER GROUP CD

  • 7/31/2019 02 FSSS Logic System

    46/51

    24 May 2012 46

    30% BOILER LOAD

    ADJACENT MILL FIRING

    PA FAN IN SERVICE

    INTERMEDIATE OIL BURNERELEVATION FIRING

    ANDOR

    AND

  • 7/31/2019 02 FSSS Logic System

    47/51

    24 May 2012 47

    IT WILL NEVER OCCUR FOR THE FOLLOWING

    CONDITION-(1) IF THREE OR MORE MILLS FIRING THEN PARTIAL FLAME

    FAILURE WILL NEVER EXISTS.

    (2) IF LESS THAN THREE MILLS ARE FIRING THEN PARTIALFLAME FAILURE DOES NOT EXISTS IF MILL WHICH ISFIRING HAVE THE MILL PERMISSIVE FOR FIRING.

    IT WILL OCCUR WHEN THIS LOGIC SATISFY-

  • 7/31/2019 02 FSSS Logic System

    48/51

    24 May 2012 PMI Revision 00 48

    VOTING OF ELEVATION

    VOTING IN AB ELEVATION WILL BE AVAILABLE

    (1) MILL A FEEDER OR MILL B FEEDER I/S.

    ANDELEVATION AB 2 / 4 FLAMES IN.

    INTRLOCKED WITH ( ALL BURNER IN AB ELEVATION

    SATISFACTORY S/D OR 3 / 4 OIL BURNER IN THAT ELEVATION

    ARE I/S.)

    (2) VOTING IN BC ELEVATION WILL BE AVAILABLE-

    MILL B FEEDER OR MILL C FEEDER I/S.AND

    ELEVATION B 2 / 4 FLAMES IN.

    VOTING WIL NOT BE AVAILABLE (1) BOTH FEEDERS ON BURNER ELEVATION ARE NOT I/S.

    OR

    (2) 2/4 FLAME ARE NOT SENSED INTERLOCKED WITH 3 / 4 OILBURNER ARE NOT FIRING.

    OR

    (3) OIL GUN IN THAT ELEVATION NOT SATISFACTORLY

    SHUTDOWN INTROLOCKED WITH 3 / 4 OIL BURNER IN THAT

    ELEVATION NOT FIRING.

    Feeder start Logic

  • 7/31/2019 02 FSSS Logic System

    49/51

    24 May 2012 PMI Revision 00 49

    Feeder start Logic

    Feeder start command is given from FSSSElevation Logic only. This command is

    continuously required to keep the feeder in

    service. Feeder speed demand minimum,Pulverizer ON, pulverizer outlet temp > 130OF,

    HAG open and no MFT are the important

    conditions required to give the feeder start

    command from FSSS.

  • 7/31/2019 02 FSSS Logic System

    50/51

    24 May 2012 PMI Revision 00 50

    In case of pulveriser power high, bowl DP High or

    feeder OFF command, feeder speed demand is

    driven to minimum.

    Release feeder to Auto Signal is also coming from

    FSSS. All of the above conditions are present and

    feeder is not ON for more than 50 seconds, release

    signal for auto is available.