Upload
mariajoaobotelho
View
24
Download
1
Embed Size (px)
Citation preview
Low temperature
corrosion in cement
plants
Christian Suchak, Volker Hoenig;
VDZ, Duesseldorf, Germany
Introduction
Corrosion describes a wide topic and
summarizes all the miscellaneous
corrosion types within one term. The
speed and severity of corrosion depend
on a number of factors, which in the
end define the actual corrosion
mechanism. Looking at the corrosion
problem in a cement plant, two basic
types of corrosion can be
distinguished. Corrosion at
temperatures above 400 °C is described
as high temperature corrosion and
beneath 400 °C as low temperature
corrosion. In case of low temperature
corrosion it is always implied that an
aqueous electrolyte takes part in the
electrochemical reaction, so that a
cathodic and anodic reaction takes
place. This rough classification allows
allocating the different components of
a cement plant to these corrosion types.
Basically all aggregates downstream of
the preheater, the bypass filter as well
as the clinker cooler filter are subject to
low temperature corrosion. Major
equipment parts such as dedusting
units or chimneys have often high
maintenance requirements related to
corrosion damages which cause
additional costs for the operating
companies.
Figure 1 & 2: Corroded sidewalls of a bag house
Possible corrosion mechanisms
The gas way of cement plants are
subjected to corrosion damage. In the
process gas are gaseous and solid
chloridic and sulphatic compounds
present which have corrosive
properties. The oxygen and water
vapour in the gas atmosphere provide
for oxidizing conditions. Carbon
dioxide, originating from the
decarbonisation reaction of calcium
carbonate and fuel combustion, has
both oxidizing and carburizing
characteristics. As soon as water and in
particular different kinds of acids are
condensing, the metal parts are subject
to corrosion. In table 1 hypothetical
acids present in the waste gases of
cement plants are summarized.
Table 1: Acids with corrosive potential
occurring in the waste gas path of cement
plants during running operation
Acid Gas Agent Relevance
Nitrous acid
HNO2
NO &
NO2
Low
Nitric acid
HNO3
NO2 Low
Hydrochloric acid
HCl
Cl2 Medium
Sulphurous acid
H2SO3
SO2 Low
Sulphuric acid
H2SO4
SO3 High
For the formation of nitrous, nitric and
sulphurous acid condensed water is
required. The gas agents are physically
dissolved in water and form the various
acids and could oppose a corrosive
threat to the metal.
Figure 3: SO3-Measurement in a low dust gas
environment
Corrosion during kiln operation
Inspections of different precipitators
during major maintenance stops
showed in general signs of both
extensive and uniform damages as well
as sign of pitting. Both these types of
corrosion damages can be caused by
acids (cf. Figure 1&2). A possible
explanation for this corrosion
occurrence could be the condensation
of sulphuric acid during the running
clinker production. If a considerable
concentration of SO3 is present in these
flue gases, it reacts with the water
vapour beneath 500 °C to H2SO4. Then
the acid can condensate on all open
metal surfaces by reaching the
sulphuric acid dew point. Until today,
the widely observed phenomenon of
corrosion and the hypothesis of the
existence of sulphuric acid corrosion in
cement plants have not been
investigated systematically yet.
Therefore, hardly any scientific studies
have been conducted in this matter so
far, also no systematically verified
measurements of SO3 in high dust
atmospheres at a cement plant have
been reported. Additionally, the
existing measuring techniques for
determining SO3 and H2SO4
respectively in flue gases are
exclusively designed for power plant
environments (cf. Figure 3). Such
measurements are regularly carried out
in the power industry at dust loads of
max 1 g/Nm³.
In comparison, the flue gases of
cement plants can have - depending on
the point of process - a dust load of 30
– 500 g/Nm³. The regular measuring
equipment is not usable for such
conditions. A new measuring technique
was therefore necessary to be able
firstly to measure and secondly assess
the possibility of the existence of
SO3/H2SO4 and furthermore to
determine whether the prevailing
concentrations are harmful or can be
neglected.
The determination of acidic components in high dust flue gases
All conventional measuring techniques
used to determine gas components in
flue gases consist of probes which are
equipped with ceramic and sintered
metal filters respectively. Over time a
considerable amount of dust builds up
on the filter surface and in filter pores
and a closed dust layer is formed. The
measured gas has to pass this dust layer
and is subject to the risk of chemical
reactions. This problem was confirmed
by several measurements done with a
conventional probe and a continuously
working SO2-analyzer. After five
minutes the dust layer starts to absorb
the major amount of SO2 (cf. Figure 5).
It is therefore not possible to rule out a
false measurement of highly reactive
gas components such as SO3/H2SO4.
Therefore, an electrostatic precipitator
was developed to avoid this problem.
With this equipment several
measurements in different cement
plants were successfully executed (cf.
Figure 4).
Figure 4: SO3-Measurement in a high dust gas environment
The measurements done with the
newly developed measuring probe
showed considerable amounts of SO3
(measured as H2SO4). In some cases
Figure 5: Continuous SO2-measurement with a
conventional gas probe
concentrations up to 90 mg/Nm³ were
found. Therefore qualitative and
quantitative proof of H2SO4 existence
in flue gases has been verified. This
underlines the possibility that H2SO4
can occur even in environments with
nearly pure carbonate particles,
particularly considering the common
dust loads of 30 - 500 g/m³. With
regard to the confirmation of the
H2SO4 existence in the clinker burning
process, it is suggested that this
compound is generated in the top
cyclone stages of the preheater. Then,
at temperatures of 400 – 600 °C the
geogenic sulphides are oxidizing to
SO2. Furthermore high amounts of
catalytic effective oxides like Al2O3,
SiO2 and Fe2O3 [1], as part of the kiln
feed, are suspended in the atmosphere
of the cyclones.
Figure 6: H2SO4 isothermal dew point curves for a cement plant important partial pressure ranges
and plant measurements
Through the heterogenic catalytic
chemical reaction SO2 is been oxidized
to SO3. During the cooling in the
conditioning tower or in the raw mill,
the SO3 reacts at temperatures beneath
500 °C with water in the gas
atmosphere to H2SO4 [2].
The calculations of the sulphuric acid
dew points of the performed SO3
measurements have been executed with
the following empirical determined
equation [3]:
422lg7.18lg6.274.122
SOHOHpp
With ϑ as the acid dew point in °C,
pH2O as the partial pressure of water
and pH2SO4 as the partial pressure of
sulphuric acid, both in mmHg. The
results of the plant measurements are
shown in figure 6. The graph displays a
selection of measurements in
comparison with the theoretical acid
dew point at different temperatures.
Several measurements are well below
the acid isothermal curve of 130 °C.
Since in many cement plants the
exhaust temperature is below 130 °C,
especially in mill on operation,
precipitation of acid takes place.
Correspondingly under these
conditions the sulphuric acid is present
as a condensate and can cause active
corrosion. This supports the earlier
mentioned hypothesis that the observed
corrosion could be partially caused by
sulphuric acid.
Measures against low temperature corrosion in cement plants
Considering the measured amount of
sulphuric acid and compared to the
observed extend of corrosion it is to
consider that also other factors could
cause these partially heavy damages.
Cement plants without considerable
amounts of H2SO4 in the flue gases
show in some cases also severe
damages. This leads to the assumption
that the observed corrosion is not
solely caused by the presence of
sulphuric acid. During periods of time
of short or long down-times the
temperatures of the flue gases are
dropping considerably and water
condensates freely. In all likelihood
other corrosive compounds and
corrosive agents in the flue gases are
also taking part in the active metal
corrosion. But these corrosion
mechanisms are not discussed any
further, because it goes beyond the
scope of this paper.
In general three possibilities to avoid
low temperature corrosion caused by
H2SO4 condensation can be defined as
following measures:
electrochemical protection
influencing the properties of the
reactants and/or changing the
reaction conditions respectively
separation of the metal from the
corrosive environment
However not all mentioned possible
actions are economically feasible.
Especially the first measure is much
too costly and practically not
achievable. In regard of the second
point not much can be done effectively
too. It is not feasible to lower the SO3-
generation by using different sources
of raw materials, merely if alternative
materials contribute significantly to
low volatile sulphur input.
Figure 7: Protective coating in a bag house [5]
Also the conditions in the waste gas
path are somewhat fixed and cannot be
varied much. It´s only in cases when
SO2 abatement is applied, that this
could be adapted to SO3 minimization
by means of Ca(OH)2 injections
directly after the preheater. The
neutralisation reaction of SO3 works
chemically as of SO2. So by applying
effective SO2-reduction systems
immediately after the preheater, the
absolute amount of acids in the flue gas
can be reduced and therefore the
corrosive potential.
Special attention could be given to the
temperature level of the exhaust gas.
As long the temperature is well above
the correspondent acid dew point, no
acid will condensate and cause
corrosion. In some cases the increase
of the waste gas temperature of 10 °C
would be sufficient to avoid any
condensations. It´s also important to
make sure that a proper insulation of
all affected aggregates is maintained.
Therefore it is crucial to avoid any
false air leakages so that no low gas
temperatures can occur locally, which
could lead to major water and acid
condensations.
With the application of a protective
coating of the affected areas by organic
coatings an effective corrosion
protection can be achieved (cf.
figure 7) [4]. But this measure is also
cost-intensive and requires a high
Figure 8: Spalling of an organic coating because of too high mechanical stress [5]
amount of preparation before
implementation. The different
coefficients of thermal expansion of
the coating and metal have to be
considered too. So the surfaces of all
areas which are to be coated have to be
especially prepared to avoid localized
mechanical stress and spalling of the
coating (cf. figure 8).
The application of high alloyed acid
resistant steels is a last possible
measure to avoid high material losses.
But it also implicates high material and
erection costs which are in most cases
not expedient.
References
[1] Wickert K.: Chemische
Umsetzungen im Feuerraum der
Schmelzkammerkessel; BWK 9
(1957); pp. 105-118
[2] Rolker J.: Zur elektrischen
Messung des Säuretaupunktes von
SO3-haltigen Rauchgasen;
Dissertation; Universität Stuttgart;
1973
[3] Haase R., Borgmann H.-W.:
Präzisionsmessungen zur Ermittlung
von Säuretaupunkten; Mitteilungen der
VGB 76 (1962) 2; S. 16-19
[4] Mazeika L., Sherin B., Cardwell B.:
Repairing a corroded baghouse filter at
the Durkee cement plant by coating the
surface; Cement International 5 (2004)
2; pp. 100-103
[5] Personal information: Solnhofer
Portland-Zementwerke GmbH & Co.
KG, Germany