SF6 Gas Density Monitoring
Very low temperature and liquefaction situation with
Trafag 87X6 SF6 gas
density monitor
SF6 Gas Density Monitoring
Very low temperature and liquefaction situation with
Trafag 87X6 SF6 gas
density monitor
05.02.07/ nip
The Reference Gas PrincipleThe Reference Gas Principle(Theory)(Theory)
SF6 filled switchgear
SF6 filled reference chamber
separating membrane
DM
The temperatures of the gas in the switchgear and the gas in the reference chamber of 87x6 density monitor are „the same“ (depends on the mounting situation)
Conclusion: „fully temperature compensation over the whole temperature range“
05.02.07/ nip
The Density Monitor with Reference The Density Monitor with Reference ChamberChamber
(Picture shows the “older” 87x0 density monitor generation)(Picture shows the “older” 87x0 density monitor generation)
Reference chamber filled with gasReference chamber filled with gas
Tappet moves whenTappet moves whenSFSF66 leaks from tank and leaks from tank and triggers alarm switchtriggers alarm switch
SFSF66 gas inlet gas inlet (connection to tank)(connection to tank)
...inside the monitor...inside the monitor
05.02.07/ nip
Behavior of bimetalic-Behavior of bimetalic-compensated Systemscompensated Systems
Isochoren von xyz No. 06397
3.000bar
3.500bar
4.000bar
4.500bar
5.000bar
5.500bar
6.000bar
6.500bar
7.000bar
7.500bar
8.000bar
-40.0°C -30.0°C -20.0°C -10.0°C 0.0°C 10.0°C 20.0°C 30.0°C 40.0°C 50.0°C 60.0°C
Schalter 1 sinkend
Schalter 2 sinkend
Isochore 5 bar
Isochore 6,4 bar
-8 kPa
+8 kPa
-8 kPa
+8 kPa
Contact 1, falling(bimetal comp, non-Trafag)
Contact 2, falling(bimetal comp, non-Trafag)
True isochor
Tolerance band of TrafagDM for calibration
True isochor
Tolerance band of TrafagDM for calibration
The accuracy of the alarm levels
05.02.07/ nip
Density Monitor at temperature Density Monitor at temperature below -55C below -55C •Due to the mechanical system the density monitor will still operate below -55°C•May be the specifications like accuracy and so on are out of the from Trafag specified values on the datasheets•The tolerances of the mechanical system may be are to high for a proper function
05.02.07/ nip
Liquefaction?Liquefaction?•The reference chamber of 87x6 density monitor is filled at previous alarm density level (1. stage)•In regular operation the density at switch breaker is higher (somewhere between filling pressure and previous alarm level) as previous alarm level in reference chamber of 87x6 density monitor•Therefore, the liquefaction in switch breaker starts at higher temperature (that means earlier) as in the reference chamber of 87x6 gas density monitorBenefits:• Small local liquefaction in the
switch breaker will not be detected by the 87x6 density monitor
• Serious liquefaction which can create a critical situation for the switch breaker get detected by the 87x6 density monitor