07 SEP-602A_Fuse Failure

Embed Size (px)

Citation preview

  • 7/31/2019 07 SEP-602A_Fuse Failure

    1/10

    1

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    REL 670 Line DistanceProtection IED

    Fuse failure

    Substation Automation andProtection Training

    2

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FUSE FAILURE the problem

  • 7/31/2019 07 SEP-602A_Fuse Failure

    2/10

    3

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FUSE FAILURE the idea

    Fuse failure function detects the loss of signal from VTs.

    This information is used to block distance protection function and any other voltagerelated function.

    ZM01ZM02ZM03ZM04ZM05

    To Block Voltagerelated functions

    4

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD the algorithms

    Detection of Fuse Failure:

    high value of zero sequence voltage (3Uo>)

    absence of zero sequence current (3Io)absence of negative sequence current (3I2

  • 7/31/2019 07 SEP-602A_Fuse Failure

    3/10

    5

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD the algorithms

    INFORMATION FROM BUILT-INDEAD PHASE DETECTION

    U> and I> check:

    The line had normal operating conditions for at least 200 msbefore the fuse failure was activated

    Dead phase detection prevents activation of fuse failure duringsingle pole A/R (when temporary unbalance in the primarysystem could cause unwanted activation of fuse failure signal)

    6

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    Detection of Fuse (MCB) Failure:

    Auxiliary contact from the MCB connected to a

    binary input of the terminal

    MCB trips generally three phase (3-phase fuse failure)

    All the three voltages are missing atthe same time

    It is impossible to detect

    a negative sequence voltageor a zero sequence voltage.

    FSD the algorithms

  • 7/31/2019 07 SEP-602A_Fuse Failure

    4/10

    7

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD Presence of line Disconnector

  • 7/31/2019 07 SEP-602A_Fuse Failure

    5/10

    9

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    In this situation FUSE should also operate:

    Delta U and Delta I algorithm:

    The delta current and delta voltagealgorithm, detects a fuse failure if asufficient negative change in voltageamplitude without a sufficient change incurrent amplitude is detected.

    This algorithm only operates if the circuitbreaker is closed.

    I/t

    U/t

    FSD Busbar switching (or 3-phase fuse failure)

    10

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD (RFUF) Settings

    What happens in case of real fuse failure?3Io or 3I2 is more or less very small, so which algorithm will be choosen?

    Actually it does not matter which one will be chosen because they bothwork well in case of real fuse failure. This algorithm has been done toincrease the security during network unbalances (single phase opening,faults etc.).

  • 7/31/2019 07 SEP-602A_Fuse Failure

    6/10

    11

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD Settings

    Settings for >> and

  • 7/31/2019 07 SEP-602A_Fuse Failure

    7/10

    13

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD Settings

    Settings for Dead Phase detection

    14

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD Settings

    Settings for Locking (seal-in) FUSE FAILUREdetection in the non-volatile memoryand for its automatic reset at line energization(see next page for state diagram)

  • 7/31/2019 07 SEP-602A_Fuse Failure

    8/10

    15

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD (RFUF) - State diagram

    Normal

    Load

    Condition

    0,0,0

    Block

    U functions

    0,1,0

    Block

    U, Z functions

    0,1,1

    Fusefailuredetected

    AND

    DEADPHASE

    FuseFailuredetecte

    dmore

    than5s

    ANDSEALIN=ON

    FuseFailureDetected

    FuseFa

    ilure

    moretha

    n5s

    AND

    SEALIN=O

    N

    Block U, Z functions

    1,1,1

    Linede-energized

    STORE

    non-volatile memory

    NoFuseFailure

    detected

    NoFuse

    Failurede

    tected

    (Fuserep

    aired)

    Switch-on

    andSwitch-off

    theterminal

    Lineenergized

    FUSE

    Lineen

    ergized

    ANDn

    oFuse

    Failure

    Detect

    ed

    (fusere

    paired

    )

    0,1,1

    Block

    U, Z functions

    Internal Latch

    x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ

    16

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    Normal

    Load

    Condition

    0,0,0

    DISC(opendisconn

    ector)

    MCBTrip

    Disconnector close

    d

    Block

    U functions

    by disconnector0,1,0

    Block

    U, Z functions

    by MCB trip

    0,1,1

    MCBrepaired

    FSD (RFUF) - State diagram

    x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ

  • 7/31/2019 07 SEP-602A_Fuse Failure

    9/10

    17

    ABBAB,

    2007

    2007-10-03 Substation Automation and Protection Training

    x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ

    Normal

    Load

    Condition

    0,0,0

    Block

    U functions

    0,1,0

    Block

    U, Z functions

    0,1,1

    FUSE+DEADPHASE FUSEmorethan5

    s

    FUSE

    FUSE

    more

    than

    5s

    Block U, Z functions

    1,1,1

    Linede-energized

    STORE

    non-volatile memory

    NoFUSE

    NoFUSE

    (Fuserep

    aired)

    Switch-on

    andSwitch-off

    theterminal

    Lineenergized

    FUSE

    Lineenergiz

    ed

    noFUS

    E(fuse

    repaired)

    0,1,1

    Block

    U, Z functions

    InternalLatch

    Block

    U functions

    by disconnector

    0,1,0

    Block

    U, Z functions

    by MCB trip

    0,1,1

    DISCo

    pen

    DISC

    closed

    MC

    BTr i

    p

    MC B

    r e

    p a i r

    e d

    FSD (RFUF) - State diagram

    18

    ABB

    AB,

    2007

    2007-10-03 Substation Automation and Protection Training

    FSD (RFUF) Configuration

  • 7/31/2019 07 SEP-602A_Fuse Failure

    10/10