Upload
denysenko1982
View
219
Download
0
Embed Size (px)
Citation preview
7/31/2019 07 SEP-602A_Fuse Failure
1/10
1
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
REL 670 Line DistanceProtection IED
Fuse failure
Substation Automation andProtection Training
2
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
FUSE FAILURE the problem
7/31/2019 07 SEP-602A_Fuse Failure
2/10
3
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FUSE FAILURE the idea
Fuse failure function detects the loss of signal from VTs.
This information is used to block distance protection function and any other voltagerelated function.
ZM01ZM02ZM03ZM04ZM05
To Block Voltagerelated functions
4
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
FSD the algorithms
Detection of Fuse Failure:
high value of zero sequence voltage (3Uo>)
absence of zero sequence current (3Io)absence of negative sequence current (3I2
7/31/2019 07 SEP-602A_Fuse Failure
3/10
5
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FSD the algorithms
INFORMATION FROM BUILT-INDEAD PHASE DETECTION
U> and I> check:
The line had normal operating conditions for at least 200 msbefore the fuse failure was activated
Dead phase detection prevents activation of fuse failure duringsingle pole A/R (when temporary unbalance in the primarysystem could cause unwanted activation of fuse failure signal)
6
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
Detection of Fuse (MCB) Failure:
Auxiliary contact from the MCB connected to a
binary input of the terminal
MCB trips generally three phase (3-phase fuse failure)
All the three voltages are missing atthe same time
It is impossible to detect
a negative sequence voltageor a zero sequence voltage.
FSD the algorithms
7/31/2019 07 SEP-602A_Fuse Failure
4/10
7
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FSD Presence of line Disconnector
7/31/2019 07 SEP-602A_Fuse Failure
5/10
9
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
In this situation FUSE should also operate:
Delta U and Delta I algorithm:
The delta current and delta voltagealgorithm, detects a fuse failure if asufficient negative change in voltageamplitude without a sufficient change incurrent amplitude is detected.
This algorithm only operates if the circuitbreaker is closed.
I/t
U/t
FSD Busbar switching (or 3-phase fuse failure)
10
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
FSD (RFUF) Settings
What happens in case of real fuse failure?3Io or 3I2 is more or less very small, so which algorithm will be choosen?
Actually it does not matter which one will be chosen because they bothwork well in case of real fuse failure. This algorithm has been done toincrease the security during network unbalances (single phase opening,faults etc.).
7/31/2019 07 SEP-602A_Fuse Failure
6/10
11
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FSD Settings
Settings for >> and
7/31/2019 07 SEP-602A_Fuse Failure
7/10
13
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FSD Settings
Settings for Dead Phase detection
14
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
FSD Settings
Settings for Locking (seal-in) FUSE FAILUREdetection in the non-volatile memoryand for its automatic reset at line energization(see next page for state diagram)
7/31/2019 07 SEP-602A_Fuse Failure
8/10
15
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
FSD (RFUF) - State diagram
Normal
Load
Condition
0,0,0
Block
U functions
0,1,0
Block
U, Z functions
0,1,1
Fusefailuredetected
AND
DEADPHASE
FuseFailuredetecte
dmore
than5s
ANDSEALIN=ON
FuseFailureDetected
FuseFa
ilure
moretha
n5s
AND
SEALIN=O
N
Block U, Z functions
1,1,1
Linede-energized
STORE
non-volatile memory
NoFuseFailure
detected
NoFuse
Failurede
tected
(Fuserep
aired)
Switch-on
andSwitch-off
theterminal
Lineenergized
FUSE
Lineen
ergized
ANDn
oFuse
Failure
Detect
ed
(fusere
paired
)
0,1,1
Block
U, Z functions
Internal Latch
x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ
16
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
Normal
Load
Condition
0,0,0
DISC(opendisconn
ector)
MCBTrip
Disconnector close
d
Block
U functions
by disconnector0,1,0
Block
U, Z functions
by MCB trip
0,1,1
MCBrepaired
FSD (RFUF) - State diagram
x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ
7/31/2019 07 SEP-602A_Fuse Failure
9/10
17
ABBAB,
2007
2007-10-03 Substation Automation and Protection Training
x,y,z = output status = FSD1-3PH, FSD1-BLKU, FSD1-BLKZ
Normal
Load
Condition
0,0,0
Block
U functions
0,1,0
Block
U, Z functions
0,1,1
FUSE+DEADPHASE FUSEmorethan5
s
FUSE
FUSE
more
than
5s
Block U, Z functions
1,1,1
Linede-energized
STORE
non-volatile memory
NoFUSE
NoFUSE
(Fuserep
aired)
Switch-on
andSwitch-off
theterminal
Lineenergized
FUSE
Lineenergiz
ed
noFUS
E(fuse
repaired)
0,1,1
Block
U, Z functions
InternalLatch
Block
U functions
by disconnector
0,1,0
Block
U, Z functions
by MCB trip
0,1,1
DISCo
pen
DISC
closed
MC
BTr i
p
MC B
r e
p a i r
e d
FSD (RFUF) - State diagram
18
ABB
AB,
2007
2007-10-03 Substation Automation and Protection Training
FSD (RFUF) Configuration
7/31/2019 07 SEP-602A_Fuse Failure
10/10