73

08-Presentation Distance Protection

Embed Size (px)

Citation preview

Page 1: 08-Presentation Distance Protection
Page 2: 08-Presentation Distance Protection

> Distance Protection - January 2004

Distance Protection

J. Royle

Page 3: 08-Presentation Distance Protection

> Distance Protection - January 2004

Distance Protection

Popular, widely used on Sub-Transmission and Transmission Systems

Virtually independent of Fault Current Level (ZS/ZL ratios)

Fast Discriminative Protection:- Zone 1 or ‘Aided’ Distance Scheme

Time Delayed Remote Back-Up:- Incorporated at little extra cost

Page 4: 08-Presentation Distance Protection

> Distance Protection - January 2004

Advantages of Distance Protection

Measures Z, X or R correctly irrespective of System Conditions

Compare this with Instantaneous OvercurrentProtection:-

Page 5: 08-Presentation Distance Protection

> Distance Protection - January 2004

Advantages of Distance Protection

F1

115kV 50

IF1ZS = 10 Ω

ZS = 10 Ω

ZL = 4 Ω

IF1 = 115kV/√3(5+4) = 7380A

∴ Is > 7380A

Page 6: 08-Presentation Distance Protection

> Distance Protection - January 2004

Advantages of Distance Protection

Consider with one source out of service:-

IF2 = 115kV/√3 x 10 = 6640A

∴ Is <6640A

>7380A - IMPRACTICAL

F2

50

IF2

ZS = 10 Ω

Page 7: 08-Presentation Distance Protection

> Distance Protection - January 2004

Simplified Line Diagram

XL = jWL XC = -jWC

at FN (50Hz) XC = large :-

LR R R RLLLCCC

RL

Page 8: 08-Presentation Distance Protection

> Distance Protection - January 2004

Basic Principle of Distance Protection

ZLZS

Generation

DistanceRelay

IR

21 VR

Page 9: 08-Presentation Distance Protection

> Distance Protection - January 2004

Impedance Seen By Measuring Element

jX

ZL

R

Page 10: 08-Presentation Distance Protection

> Distance Protection - January 2004

Basic Principle of Distance Protection

LOADLRR

R Z Z V Zmeasured Impedance +=Ι

=

RelayPT.

Normal Load

IR ZLZS

VRVSZLOAD

Page 11: 08-Presentation Distance Protection

> Distance Protection - January 2004

Basic Principle of Distance Protection

Fault

IRZS

VRVSZLOAD

ZL

ZF

Impedance Measured ZR = VR/IR = ZF

Relay Operates if ZF < Z where Z = setting

Increasing VR has a Restraining Effect ∴VRcalled Restraining Voltage

Increasing IR has an Operating Effect

Page 12: 08-Presentation Distance Protection

> Distance Protection - January 2004

Plain Impedance Characteristic

jX ZL

R

TRIP STABLE

Impedance Seen At Measuring Location For Line Faults

Page 13: 08-Presentation Distance Protection

> Distance Protection - January 2004

Impedance Characteristic Generation

Operate

IF

VF

Restrain

Spring

Trip

zF

Ampere Turns : VF IZ

Trip Conditions : VF < IFZ

jIX

IZ V1V2V3

IR

TRIP STABLE

Voltage to Relay = VCurrent to Relay = IReplica Impedance = Z

Trip Condition : S2 < S1where : S1 = IZ ≈ Z

S2 = V ≈ ZF

Page 14: 08-Presentation Distance Protection

> Distance Protection - January 2004

Basic Principle of Distance Protection

IR

21 VR

I1/I2 ZP

V1V2

VFP

Relays are calibrated in secondary ohms :-

RATIOV.T.RATIO C.T. x Z Z

/VV/ x V

/ x /VVxV /V Z

PR

2121

FPFP

12FP12FP

RRR

=

ΙΙΙ

=ΙΙΙ

=Ι=

Page 15: 08-Presentation Distance Protection

> Distance Protection - January 2004

Example

ZP = 4Ω; V1/V2 = 115kV/115V; I1/I2 = 600/5A

ZR(5) = 4 x 600/5 x 115/115x103 = 0.48Ω -5A Relay

ZR(1) = 2.4 Ω - 1A Relay

C.T. RATIOZR = ZP x V.T. RATIO

Page 16: 08-Presentation Distance Protection

> Distance Protection - January 2004

Input Quantities for ∅-∅ Faults

FAULT VRESTRAINT IOPERATE

A - B VA - VB IA - IB

B - C VB - VC IB - IC

C - A VC - VA IC - IA

VRESTRAINT & IOPERATE are selected inside the relay

No setting adjustments are required apart from Z1 = Phase Replica Impedance

Page 17: 08-Presentation Distance Protection

> Distance Protection - January 2004

Input Quantities for Phase to Earth Faults

FAULT VRESTRAINT IOPERATE

A - E VA ? IA ?

B - E

C - E

Page 18: 08-Presentation Distance Protection

> Distance Protection - January 2004

Neutral Impedance Replica Vectorial Compensation

Replica impedance circuit :-

Z1IRA

IRN

∑IZNZ1

N

Z1

ZN

Z1 = Phase replica impedance

ZN = Neutral replica impedance

IRA passes through Z1

IRN passes through ZN

ZT = Z1 + ZN

Page 19: 08-Presentation Distance Protection

> Distance Protection - January 2004

Neutral Impedance Compensation

For a single phase to ground fault the total earth loop impedance is given by :- (Z1 + Z2 + Z0)/3 = ZT

ZT = (Z1 + Z2 + Z0)/3 = Z1 + ZN

ZN = (Z1 + Z2 + Z0)/3 - Z1

= (2Z1 + Z0)/3 - Z1

= - Z1 + Z0

= KN Z1

3 3

where KN = (Z0 - Z1) 3Z1

Page 20: 08-Presentation Distance Protection

> Distance Protection - January 2004

Neutral Impedance Vectorial Replica Compensation

Line CT’sA

ZPH

B

C

IAZPH

ZPH IBZPH

ZPH ICZPH

ZN INZN

Set Z PH = Z F1

Set Z N = (Z F0- Z F1)3

Usually ∠ ZN = ∠ ZPH for OHL’s

Page 21: 08-Presentation Distance Protection

> Distance Protection - January 2004

Neutral Impedance Replica Compensation

For cables ∠Z0 ≠ ∠Z1

∴ VECTORIAL COMPENSATION MUST BE USED

KN = Z0 - Z1 = KN ∠∅N

3Z1

Page 22: 08-Presentation Distance Protection

> Distance Protection - January 2004

Characteristics

Page 23: 08-Presentation Distance Protection

> Distance Protection - January 2004

Distance Characteristics

MHOR

Zn

jX

jX

R

Zs

Zn

CROSS-POLARISEDMHO

QUADRILATERAL

Zn

R

OFFSETMHO

jX

Zn′

ZnR

IMPEDANCE

jX

ZnR

LENTICULAR

jX

ZnR

POLYGON

Zn

R

Page 24: 08-Presentation Distance Protection

> Distance Protection - January 2004

Self Polarised Mho Relays

Very popular characteristic

Simple

Less sensitive to power swings

Inherently directional

Operates for F1, but not for F2

Mho = 1/OHM

Settings :-

Z = reach settingϕ = characteristic angle

jX

R

F2

F1

Z

ϕ

OPERATE

RESTRAIN

Page 25: 08-Presentation Distance Protection

> Distance Protection - January 2004

Neutral Impedance Replica Vectorial Compensation

Vectorial compensation allows for ∠ZN ≠ ∠ZPH which is especially important for cable distance protection where ∠ZN < ∠ZPH and ∠ZN is sometimes negative.

ZE = Earth-loop impedance for ∅ - earth fault on a cable

jX

R

ZE

ZPH ZN

Page 26: 08-Presentation Distance Protection

> Distance Protection - January 2004

Offset Mho Characteristic

Normally used as backup protection

Operates for zero faults (close up faults)

Generally time delayed (as not discriminative)

jX

R

Z

-Z’

Page 27: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mho Relays

Directional circular characteristic obtained by introducing VPOLARISING

VF → self polarisedVSOUND PHASE → fully cross-polarisedVF + xVS.F. → partially cross-polarisedVPRE-FAULT → ‘memory’ polarised

Purpose for this is to ensure operation for close up faults where measured fault voltage collapses

Page 28: 08-Presentation Distance Protection

> Distance Protection - January 2004

Quadrilateral Characteristic

Z

jX

ZR

RR

LoadL

1F

S

Page 29: 08-Presentation Distance Protection

> Distance Protection - January 2004

Lenticular Load Avoidance Characteristic

jIX

IR

ba

Lenticularcharacteristic created from two offset Mho comparators

Aspect ratio = a/b

Page 30: 08-Presentation Distance Protection

> Distance Protection - January 2004

Lenticular Characteristic

X

R

ab

Z3Aspect ratios a/b0.410.671.00

Load impedance area

Z3 reverse

Page 31: 08-Presentation Distance Protection

> Distance Protection - January 2004

Forward Offset Characteristic

Z3

Z2

Z1

Rf

X

R

Load area

Forward blinder

Enhanced resistive coverage for remote faults

Page 32: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zones of Protection

Page 33: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zones of Protection

Z2A Z2C

Z3A Z3C

Time

T3

T2

Z1CZ1A

Z1B DCA

Z2BT2

Z1A = 80% of ZABZ2A = 120% of ZABZ3A(FORWARD) = 120% of ZAB + ZCD

B

Page 34: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zones of Protection

RA

D

CB

Z1A

Z2A

Z3A

jX

Page 35: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1

FAST OPERATIONTrips circuit breaker without delay as soon asfault within Zone 1 reach is detected.

REACH SETTINGCannot be set to 100% of protected line or mayoverreach into next section.Overreach caused by possible errors in :-

CTsVTsZLINE informationRelay Measurement

Page 36: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1

PossibleOverreach

ZONE 1 = ZL

ZL

F

ZONE 1 = 0.8ZL

ZL

Possible incorrect tripping for fault at ‘F’

∴ Zone 1 set to ∼ 0.8ZL

Page 37: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1 Settings for Teed Feeders

Z1C = 0.8ZACA

C

Z1A = 0.8ZABZ1B = 0.8ZBA

B

Z1C

Z1AZ1B

Page 38: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1 Settings for Direct Intertrip Schemes

Z1AReceiveSend

Trip ‘B’

Z1BReceive Send

Z1B

Z1A

ZLA

B

Page 39: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1 Settings for Direct Intertrip Schemes

Effective Zone 1 reaches at A and B must overlap.Otherwise :- No trip for fault at ‘F’

∴ Effective Z1A and Z1B must be > 0.5ZL

Settings for Zone 1 > 0.8ZL are o.k.

Z1B

Z1A

F

A

B

Page 40: 08-Presentation Distance Protection

> Distance Protection - January 2004

Minimum Zone 1 Reach Setting

Dictated by :-

Minimum relay voltage for fault at Zone 1reach point to ensure accurate measurement.

Minimum voltage depends on relay design typically 1 → 3 volts.

Page 41: 08-Presentation Distance Protection

> Distance Protection - January 2004

System Impedance Ratio :- SIR

SIR = ZS/Zn

where :- ZS = Source impedance behind relayZn = Reach setting

VRPA = Minimum voltage for reach point accuracy

Can be expressed in terms of an equivalent value of SIRMAX

SIRMAX = ZS MAXZn MIN

∴ Zn MIN ≡ ZS MAXSIRMAX

Page 42: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 2

Covers last 20% of line not covered by Zone 1.Provides back-up protection for remote busbars.

To allow for errors :-Z2G > 1.2 ZGH

Zone 2 is time delayed to discriminate with Zone 1 on next section for faults in first 20% of next section.

Z1H

Z2G

TIMEZ1G

G H

F

Page 43: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 2

Overlap only occurs for faults in first 20% of following line.Faults at ‘F’ should result in operation of Z1H and tripping of circuit breaker ‘H’.

If ‘H’ fails to trip possible causes are :-Z1H operates but trip relays fail.

Z2H may operate but will not trip if followed by the same trip relays.Fault must be cleared at ‘G’ by Z2G.

Z1H and trip relays operate but circuit breaker fails to trip.

Zone 2 on adjacent line sections are not normally time graded with each other

Z1G Z1H

Z2G Z2H

‘H’‘G’F

Page 44: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 2

No advantage in time grading Z2G with Z2H

Unless Z2H + trip relays energise a 2nd circuit breaker trip coil.

Page 45: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 2Z1H fails to operate.

Results in race between breakers ‘G’ and ‘H’ if Z2H and Z2G have the same time setting.

Can only be overcome by time grading Z2G with Z2H.

Problem with this :-

Zone 2 time delays near source on systems with several line sections will be large.

End zone faults on lines nearest the infeed source point will be cleared very slowly.

Z1G Z1H

Z2G

Z2H

‘H’‘G’

Page 46: 08-Presentation Distance Protection

> Distance Protection - January 2004

Maximum Allowable Zone 2 Reach to Allow for Equal Zone 2 Time Settings

Z2A must not reach beyond Z1B

i.e. Z2A(EFF) MAX must not reach further than Z1B(EFF) MIN

Z1BSETTING = 0.8ZL2Z1B(EFF) MIN = 0.8 x 0.8ZL2 = 0.64ZL2

∴ Z2A(EFF) MAX < ZL1 + 0.64ZL2∴ 1.2 Z2ASETTING < ZL1 + 0.64ZL2

Z2ASETTING < 0.83ZL1 + 0.53ZL2

Z2A (EFF) MAX

Z1B (EFF) MIN

ZL2ZL1 BA

Page 47: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 2 Time Settings on Long Line Followed by Several Short Lines

Z3H

Z2G

Z3J

Z2HZ2J

Z1H Z1JZ1G

‘H’ ‘J’‘G’F

Z2G reaches into 3rd line section.

To limit remote back-up clearance for a fault at ‘F’, the time setting of Z2G must discriminate with Z3H.

Page 48: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 3

Provides back-up for next adjacent line.Provides back-up protection for busbars (reverse offset).Actual Zone 3 settings will be scheme specified, i.e. permissive or blocking schemes.Many modern relays have more than 3 Zones to allow the use of three forward and an independent reverse zone.

HG K

Z1G Z1HZ2G

Z3G REV Z3G FWD

Time

Typical settings : Z3FWD > 1.2 x (ZGH + ZHK)Z3REV 0.1 to 0.25 of Z1G

Page 49: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone Time Coordination - Ideal Situation

Zone 1 :- tZ1 = instantaneous (typically 15 - 35mS)

Zone 2 :- tZ2 = tZ1(down) + CB(down) + Z2(reset) + Margine.g. tZ2 = 35 + 100 + 40 + 100 = 275mS

Zone 3 :- tZ3 = tZ2(down) + CB(down) + Z3(reset) + Margine.g. tZ3 = 275 + 100 + 40 + 100 = 515mS

Note: Where upper and lower zones overlap, e.g. Zone 2 up sees beyond Zone 1 down, the upper and lower zone time delays will need to be coordinated, e.g. tZ2(up) to exceed tZ2(down).

Page 50: 08-Presentation Distance Protection

> Distance Protection - January 2004

Under / Overreach

Page 51: 08-Presentation Distance Protection

> Distance Protection - January 2004

Under-Reach

Impedance presented > apparent impedance

%age Underreach = ZR - ZF x 100%ZR

where ZR = Reach settingZF = Effective reach

Page 52: 08-Presentation Distance Protection

> Distance Protection - January 2004

IA IA+IB

Relay Location IB

ZA ZB

VR = IAZA + (IA + IB) ZB

IR = IA

ZR = ZA + ZB + IB . ZB

IA

Underreaching Due to Busbar Infeed between Relay and Fault

Page 53: 08-Presentation Distance Protection

> Distance Protection - January 2004

Underreaching Due to Busbar Infeed between Relay and Fault

∴ Relay with setting ZA + ZB will underreach withinfeed.

Relay with setting ZA + ZB + IB . ZB will measureIA

correctly with infeed present but if infeed is removed the relay will overreach.

Maximum allowable setting dictated by load impedance

Page 54: 08-Presentation Distance Protection

> Distance Protection - January 2004

Under-Reach

What relay reach setting is required to ensure fault at F is at boundary of operation ?

Impedance seen for fault at F= ZG + IG + IP . ZK

IGLimit of operation is when Impedance Seen = Reach Setting

∴ Reach setting required= ZG + IG + IP . ZK

IG

IP

ZK FIG+IP

ZG IG

RELAY

Page 55: 08-Presentation Distance Protection

> Distance Protection - January 2004

Over-Reach

Impedance seen < apparent impedance

%age Overreach = ZF - ZR x 100%ZR

where ZR = Reach settingZF = Effective reach

Page 56: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mutual Coupling

Page 57: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mutual Coupling

Mutual coupling causes distance relays to either underreach or overreach.

Positive and negative sequence has no impact.

Zero sequence mutual coupling can have a significant influence on the relay.

Only affects ground fault distance.

Page 58: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mutual Coupling Example Under Reach

Z2 ‘Boost’ G/F

Z2 PH

Zmo

Page 59: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mutual Coupling Example Over Reach

Z2 ‘reduced’ G/F

Z2 PH

Page 60: 08-Presentation Distance Protection

> Distance Protection - January 2004

Mutual Coupling Example Over Reach

Z1 G/F (optional)Z1 G/F (normal)

Zmo

Page 61: 08-Presentation Distance Protection

> Distance Protection - January 2004

Ancilliary Functions

Page 62: 08-Presentation Distance Protection

> Distance Protection - January 2004

Switch on to Fault (SOTF)

XXX

Fast tripping for faults on lineenergisation, even where line VTsprovide no prefault voltage memory

Page 63: 08-Presentation Distance Protection

> Distance Protection - January 2004

Voltage Transformer Supervision

A VT fault and subsequent operation of VT fuses or MCB’s results in misrepresentation of primary voltagesRelay will remain stable as the current phase selector will not pick upSubsequent system fault may cause unwanted / incorrect trippingVTS operating from presence of V0 with no I0 or V2 with no I2 is used to block relay if required

Page 64: 08-Presentation Distance Protection

> Distance Protection - January 2004

VT Supervision

Under load conditionsLoss of 1 or 2 phase voltagesLoss of all 3 phase voltages

Upon line energisationLoss of 1 or 2 phase voltagesLoss of all 3 phase voltages

Digital input to monitor MCB

Set to block voltage dependent functions

Page 65: 08-Presentation Distance Protection

> Distance Protection - January 2004

Zone 1 Mho Relay

Will not operate for load or stable power swingØ1, Ø2, Ø3, = Angles between system voltages at ‘K’ and ‘L’Ø increases as power swing approaches relay at G‘J’ is point where power swing enters relay characteristicAt ‘J’ the angle between voltages at ‘G’ & ‘H’ is 90°Normal limit of angle between voltages at ‘G’& ‘H’ for load is of the order of 30°

L

KZS

HH

Z1Ø3 J

G

ZS

G

Ø1

Power Swing Locus

Ø2 LOAD

Page 66: 08-Presentation Distance Protection

> Distance Protection - January 2004

Comparison between Stability of Mho and Quadrilateral Impedance Elements during a Power Swing

jX

Power Swing Locus

R

θ

Page 67: 08-Presentation Distance Protection

> Distance Protection - January 2004

Illustration of Basic Power Swing Blocking System

jX

Power Swing Locus

R

Z3

ZP

Page 68: 08-Presentation Distance Protection

> Distance Protection - January 2004

Power Swing Blocking

A power swing will result in continuous change of current

Continuous output from the relay superimposed current element can be used to block for a power swing

Using this method the relay is able to operate for faults occurring during a power swing

Page 69: 08-Presentation Distance Protection

> Distance Protection - January 2004

Directional Earth Fault Protection (DEF)

High resistance ground faults

Instantaneous or time delayed

IEC and IEEE curves

Single or shared signalling channel

Page 70: 08-Presentation Distance Protection

> Distance Protection - January 2004

Transformer Feeders

Page 71: 08-Presentation Distance Protection

> Distance Protection - January 2004

Transformer Feeders

Zone 1 = ZL + 0.5ZTT1 = Instantaneous

Zone 2 = 1.2 (ZL +ZT)T2 = Co-ordinate with downstream protection

Zone 3T3

- Back-up use as appropriate

ZL

ZT

21

Page 72: 08-Presentation Distance Protection

> Distance Protection - January 2004

Low Voltage VT, High Voltage CT

* 1 VT may be required to account for phase shift.Example 1

ZT = 10Ω , ZL = 1ΩSet relay Z1 = 0.8 x (ZT + ZL) = 8.8Ω∴ Z1 does not reach through transformer.Example 2

ZT = 10Ω , ZL = 1ΩZ1 = ZT + 0.8ZL = 10.8Ω

with 20% error = 12.96Ω - overreach problem

ZT

21

ZL

Page 73: 08-Presentation Distance Protection