Danfoss Heating Solutions VIUHQ602 © Danfoss 03/20112
Instruction CF-RD Room Thermostat with Display
3© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display
Index
1. Functional Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3. Temperature Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4. Transmission Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5. Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6. Uninstallation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7. Change-over function for 3- and 4-pipe heating/cooling systems . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
8. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9. Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figures and illustrations . . . . . . . . . . . . . . . . . . . . . . . . . A1-A2
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/20114
1.FunctionalOverview
Front(fig.1) Up/down selector Push button Red LED (behind the cover) LEDmodesPermanent light . . . . . . ONNo light . . . . . . . . . . . . . . OFFSlow flashing . . . . . . . . . Flashes Fast flashing. . . . . . . . . . Flickers
Back(fig.2) Back plate Back plate lock/unlock (turn 90°) Screw hole for wall mounting Battery placement Screw and wall plug
Note: To activate batteries please remove enclosed strips from batteries.
Instruction CF-RD Room Thermostat with Display
5© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
2.Installation
Note: Assignment of room thermostats to Master Con-troller should be within a distance of 1.5 m.
ActivateInstallmodeonMasterController(fig.1)• Use the menu selection button to select the Install
mode. Install LED flashes.• Activate Install mode by pressing OK. Install LED
goes ON.
ActivateInstallmodeonroomthermostat• Press the push button . LED and flicker during
communication.
SelectoutputonMasterController• All available output LEDs on Master Controller light
up, and the first one flashes.• Press output selection button to select desired
output (flashes). Accept with OK .• All output LEDs go OFF. Selected output stays ON
shortly.
Roomthermostatinstallationstatus• Satisfactory: LED goes OFF.• Not satisfactory: LED flashes 5 times.
Note: A room thermostat can be assigned to several out-puts if needed by repeating the installation process.
Instruction CF-RD Room Thermostat with Display
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/20116
3.TemperatureSettings
DigitalDisplay(fig.1)
SET Set value adjustment
MIN Minimum temperature limitation
MAX Maximum temperature limitation
Transmission link icon
Low battery indicator
Alarm icon
Settings only available from CF-RC Remote controller:
Lock icon
Timer icon
Cooling icon *
AUTO Automatic change-over icon *
Heating icon *
* Icon only visible if the thermostat is defined as Master Thermostat for sequential control of heating and cooling (see chapter 7). Settingoftemperatures(fig.1)• The actual room temperature is shown in the display
as default.• Press the up/down selector to set the desired room
temperature value, SET is shown in the display.• When releasing the up/down selector the display
returns to actual room temperature.
Instruction CF-RD Room Thermostat with Display
7© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display
Roomtemperaturelimitation• Press and hold the push button until SETMAX is
shown in the display.• Press the up/down selector to set the maximum
room temperature limitation.• Press the push button shortly, SETMIN is shown in
the display.
4.TransmissionTest
Initiatetransmissiontestonroomthermostat(fig.1)• Press the push button .• LED goes ON.
Linktestissatisfactory• LED goes OFF.
Linktestisunsatisfactory • LED flashes 5 times.
NoLinkconnectiontoroomthermostat• Try to relocate room thermostat in the room.• Or install Repeater Unit (CF-RU) and locate between
Master Controller and room thermostat.
Note: When connected to a room thermostat, the Master Controller output LED(s) flash(es) during Link test.
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/20118
Instruction CF-RD Room Thermostat with Display
5.Mounting
Placingtheroomthermostat(fig.3) Wherever possible, the room thermostat should be installed at a place where the effect of sunlight, draught, other heaters (eg. TV’s), etc. is avoided.
Mountingwithscrews(fig.2) Back plate. Screw hole for wall mounting. Screw and wall plug.
6.Uninstallation
ActivateUninstallmodeonMasterController(fig.1)• Use the Menu selection button to choose the Unin-
stall menu. Uninstall LED flashes.• Activate Uninstall mode by pressing OK . Uninstall
LED goes ON.
DeselectoutputonMasterController• Select output to be removed by output selection
button .• Remove flashing output with OK .
9© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display
7.Change-overfunctionfor3-and4-pipe heating/coolingsystems
One of the standard CF-RD thermostats can be defined as a master thermostat for sequential control of heating and cooling stages, according to the room temperature. This function is only available via CF-RC Remote Controller (see instruction for CF-RC).
8.Specifications
Temperature setting range 5-35°C
Transmission frequency 868.42 MHz
Transmission range in normal buildings (up to)
30 m
Transmission power < 1 mW
Battery Alkaline 2xAA, 1.5 V
Battery lifetime (up to) 2-3 years
Ambient temperature 0-50°C
IP class 21
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/201110
Instruction CF-RD Room Thermostat with Display
9.Troubleshooting
ErrorIndication PossibleCause
The LED, and flashes every 5th minute
Low battery
The LED, and flashes every 30 sec.
Critical low battery
The LED, , and flashes
Critical low battery- transmission has stopped
The LED, and flashes 5 times
Installation/Link Test is unsatisfactory
E03 and Actuator error on output (CF-MC)
E05 and Room temperature below 5°C
11© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/201112
Instruction CF-RD Room Thermostat with Display
Fig.1A1
13© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display
Fig.2
Fig.3
1,5 m.
A2
Danfoss Heating Solutions VIUHQ602 © Danfoss 03/201114
Instruction CF-RD Room Thermostat with Display
15© Danfoss 03/2011 VIUHQ602 Danfoss Heating Solutions
Instruction CF-RD Room Thermostat with Display