Why Different Standards? ANSI vs UL

Feature Switchboard Switchgear Environment Environment

History HistorySegment Residential/Commercial Utility/IndustrialConcerns Safety/Fire Protection Safety/Fire/ Protection

Personnel/Property Protection

Process Protection and Continuation

Certification Many small suppliers-Third Party (UL) required to assure requirements

Few, Large suppliers User-Specifier Standards (Self Certified) Industry Groups (ANSI/IEEE)

(Third Party Certification since 1982)

Design Verification

"Paper Design" or Test Verification

Test Verification Required

Maintenance Minimum or None Permitted (Often Necessary!)

Page 5: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

5Current Date

Standards

Document Path..ppt

Standards Comparison

Feature Switchboard Switchgear

Structure UL 891 ANSI C37.20.1(UL 1558)

Devices UL 489(MCCB)

ANSI C37.13(LVPB)(UL 1066)

UL 977(BOLT-LOC)

UL 98(Fused Switch)

Page 6: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

6Current Date

Standards

Document Path..ppt

Standards Comparison (cont.)

Feature Switchboard Switchgear

Qualification Analysis or Test Must Test

Device Mtg. Fixed or DO DO Only

Bus Sizing Design or Test Heat RiseTest

InternalBarriers

Optional-Mfg.Determines

BreakerCompt.-Defined(Others-Optional

Page 7: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

7Current Date

Standards

Document Path..ppt

Comparison (cont.)

Feature Switchboard Switchgear

Short TimeWithstandRating

Not Defined(Mfgr.Establishestest)

PreciselyDefined

ANSI Test:.5 sec closed15 sec open.5 sec closedNo trip unit(aux trip)

Switchgear has Defined Short Time Withstand Ratings!

Page 8: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

8Current Date

Standards

Document Path..ppt

“Practice” Comparison

Feature Switchboard SwitchgearMaintenance(Industry

Practice)

VariousPractices; non-maintainablebreakers and tripunits acceptable

Permitted to maintainequipment operatingparameters

Breaker can be rebuilt;contacts and trip unitsfield replaceable

Switchgear maintenance permitted (not required by standard).

Switchboard maintenance often not allowed.

Page 9: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

9Current Date

Standards

Document Path..ppt

Side View

Page 10: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

10Current Date

Standards

Document Path..ppt

Rear View

Page 11: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

11Current Date

Standards

Document Path..ppt

Insulated Case vs Molded Case

Insulated Case

Page 12: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

12Current Date

Standards

Document Path..ppt

Old Vs New

Insulated Case UL 1066 IRON FRAME ANSI

Page 13: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

13Current Date

Standards

Document Path..ppt

Insulated Case vs Molded Case

Molded Case

Page 14: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

14Current Date

Standards

Document Path..ppt

Advantages of Insulated Case Vs Iron Frame

Smaller footprintMore reliable (Modular Design with Fewer Parts)Higher interrupting ratings Higher withstand ratings (30 Cycles)Reduced maintenanceElectronic Trip Units

Field Installable Trip UnitsCommunicationsPower monitoring (2.5% Accuracy)

Page 15: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

15Current Date

Standards

Document Path..ppt

Mechanical Construction

• Breaker Frames– Small :

• 800A ANSI, • 1200A UL, • 1600A IEC

– Medium : – 800 to 3200A ANSI, – 800 to 3000A UL, – 800 to 4000A IEC

– Large : – 4000 to 5000A ANSI, – 4000 to 6000A UL,– 4000 to 6300A IEC

Page 16: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

16Current Date

Standards

Document Path..ppt

Organic Vs Iron Frame

• Very strong and lightweight• Provides good insulation, isolation,

and dielectric• Molded to support and hold internal

parts with no adjustments• Fewer parts reduces complexity of

assembly and maintenance

The thermoset material of the organic case has several advantages:

Page 17: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

17Current Date

Standards

Document Path..ppt

Organic Vs Iron Frame

Page 18: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

18Current Date

Standards

Document Path..ppt

A

LCD ammeter LED Bargraph

P

LCD All functions

Display type

H

LCD All functions

Page 19: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

19Current Date

Standards

Document Path..ppt

UL 891 Switchboards

Page 20: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

20Current Date

Standards

Document Path..ppt

Switchboards

Page 21: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

21Current Date

Standards

Document Path..ppt

Switchboards

• Typical Switchboard Ratings

•5000 A Mains and Bus•1200 A and smaller group mounted•Greater than 1200A Individally mounted Fixed or Drawout•Front Connected•UL 891 Gear•UL 489 Breakers

Page 22: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

22Current Date

Standards

Document Path..ppt

Page 23: 1 Current Date Standards Document Path..ppt SWITCHGEAR BIG GRAY BOXES SWITCHBOARD

23Current Date

Standards

Document Path..ppt

“Hybred UL 891 Switchboards”

• Mix Insulated Case and Molded Case• Individially mounted

– Front Connected– Rear Connected

• Individually mounted – Drawout– Fixed

• Group Mounted and Drawout• Fusible and Circuit Breaker• No requirement for isolation or

– Barriers