HOOKING UP GAUGES ON SUCTION AND LIQUID LINES
USE LOW LOSS
ALL 4 VALVES CLOSED
WHITE
RECEIVER
RED
BLUE
5
WHEN THESE STEPS ARE COMPLETE … PURGE HOSES AND TURN ON RECOVERY UNIT
WHITE
RECEIVER
EXTRA HOSE
OPENOPEN OPEN
CLOSED
RECOVERY UNIT OFF
6
WHITE
RECEIVER
EXTRA HOSE
OPENOPEN OPEN
RECOVERY UNIT ON
SLOWLY OPEN THE FRONT ACCESS HANDLE … KEEP THE RECOVERY UNIT PRESSURE BELOW 50 PSIG AS IT RUNS…RUN UNTIL THE SYSTEM IS EMPTY
RECOVERY UNIT ON
7
WHEN THE SYSTEM IS EMPTY…… 1. CLOSE OFF ALL GAUGE HANDLES .. 2. TURN OFF REC UNIT 3. CLOSE OFF CYLINDER VALVE
WHITE
RECEIVER
EXTRA HOSE
CLOSECLOSE CLOSE
CLOSED
RECOVERY UNIT OFF0 PSI0 PSI
9
TRIPLE EVACUATE … TURN ON VACUUM PUMP … OPEN THE VACUUM PUMP ACCESS VALVE
WHITE
RECEIVER
CLOSECLOSE
CLOSED
0 PSI0 PSI
11
WHITE
RECEIVER
OPENOPEN
OPEN
30”
OPEN THE SIDE ACCESS GAUGE VALVES … LET RUN UNTIL COMPOUND GAUGE SHOWS DEEP VACUUM
12
WHITE
RECEIVER
CLOSECLOSE
OPEN
30”
CLOSE THE SIDE ACCESS GAUGE VALVES … SEE IF VACUUM HOLDS…IF NOT…GO LONGER
13
WHITE
RECEIVER
CLOSECLOSE
CLOSE
30”
WHEN IT HOLDS, (CLOSE THE ACCESS VALVE ON THE V-PUMP)..SET UP A CYLINDER TO BREAK THE VACUUM WITH
REFRIGERANT OR NITROGEN
PURGE HOSE
OPEN
14
WHITE
RECEIVER
CRACK UNTIL 0 PSI
CRACK UNTIL 0 PSI
0 PSIOPEN
OPEN
0 PSI
ONCE AT 0 PSI ON BOTH GAUGES … EVACUATE AGAIN
16
WHITE
RECEIVER
CLOSECLOSE
CLOSE
30”
WHEN IT HOLDS, (CLOSE THE ACCESS VALVE ON THE V-PUMP)..SET UP A CYLINDER AGAIN TO BREAK THE VACUUM
WITH REFRIGERANT OR NITROGEN
PURGE HOSE
17
WHITE
RECEIVER
CRACK UNTIL 0 PSI
CRACK UNTIL 0 PSI
0 PSIOPEN
OPEN
0 PSI
ONCE AT 0 PSI ON BOTH GAUGES … EVACUATE AGAIN
18
WHITE
RECEIVER
CLOSECLOSE
CLOSE
30”
GET SYSTEM BACK TO A 500 MICRON VACUUM...(CLOSE OFF ALL VALVES AND V-PUMP HANDLE BEFORE TURNING IT OFF)
19
WHITE
RECEIVER
30”
OPEN
CLOSED
CLOSEDCLOSED
PURGE HOSEUPSIDE DOWN
CYLINDER
SETTING UP FOR CHARGING THE SYSTEM
20
WHITE
RECEIVER
50 PSI
OPEN
OPEN
CRACK SLOWLYCLOSED
UPSIDE DOWN
CYLINDER
OPEN FRONT ACCESS VALVE ON GAUGES…SLOWLY CRACK THE HIGH SIDE HANDLE SO LIQUID CAN FLOW INTO THE
HIGH SIDE (JUST BREAK THE VACUUM)
50 PSI
21
WHITE
RECEIVER
50 PSI
OPEN
OPEN
CLOSED!!!CLOSED
UPSIDE DOWN
CYLINDER
WHEN READY TO TURN ON SYSTEM…BE SURE HIGH SIDE GAUGE HANDLE IS CLOSED … TURN ON SYSTEM
50 PSI
22
WHITE
RECEIVER
3 PSI
OPEN
OPEN
CLOSED!!!CLOSED
UPSIDE DOWN
CYLINDER
WHEN READY TO TURN ON SYSTEM…BE SURE HIGH SIDE GAUGE HANDLE IS CLOSED … TURN ON SYSTEM
75 PSI
RUNNING