ISSUED DATE DETAIL NUMBER 5" HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM STANDARD ASSEMBLY - SPRAY APPLIED 2110 - SA - A1 [HG 3310] PROTECTIVE FLEECE [HG 3710] EXTENSIVE FILTER FLEECE [HG 4110] EXTENSIVE GROWTH MEDIA [HG 6100] SEDUM CUTTINGS [HG 3610] DRAINAGE BOARD [HG 3490] EROSION / WIND NETTING (as required) [HG 3195] INTENSIVE GEOFOAM INSULATION CONDUCTIVE MEDIUM / PRIMER AND SURFACE CONDITIONER (as required) COVER BOARD, ADHERED NOTES: 1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate. 2. Additional combinations of vegetated roof components are possible to meet specific project requirements. 3. Contact Hanging Gardens for variations to the standard assembly. 4. Saturated weight and stormwater retention based on 4" of growth media. 5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary. STORMWATER RETENTION: ·· 1.60 gallons / ft 2 ·· 2.57 in 3 / in 2 ROOF PITCH: ·· 0 - 5 o ·· 0 - 9% STANDARD ASSEMBLY - SPRAY APPLIED SCALE: 1 1/2" = 1'-0" 1 STRUCTURAL CONCRETE DECK [HG 3220] ROOT BARRIER [HG 3150] SPRAY APPLIED RUBBER WATERPROOFING · THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF) · INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF) SATURATED WEIGHT: ·· 28.93 lbs / ft 2 ·· 141.24 kg / m 2 01/01/19

1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

5"

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

STANDARD ASSEMBLY - SPRAY APPLIED 2110 - SA - A1

[HG 3310] PROTECTIVE FLEECE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Additional combinations of vegetated roof components are possible to meet specific project requirements.3. Contact Hanging Gardens for variations to the standard assembly.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

STANDARD ASSEMBLY - SPRAY APPLIEDSCALE: 1 1/2" = 1'-0"1

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 2: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBERHG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

[HG 3920] SLOTTED ALUMINUM EDGE

GREEN ROOF TO BALLAST STONE 2110 - SA - B1

5"

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO BALLAST STONESCALE: 1 1/2" = 1'-0"1

[HG 3310] PROTECTIVE FLEECE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING

· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

DECORATIVE BALLAST STONE, 1-112" MIN. DIAMETER

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 3: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO POURED IN PLACE CONCRETE 2110 - SA - C1

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO POURED IN PLACE CONCRETESCALE: 1 1/2" = 1'-0"1

POURED IN PLACE CONCRETE

[HG 3530] PEDESTRIAN PAVING DRAIN

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMER

AND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)

· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

4"

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up poured in place concrete.3. Root Barrier shall extend 1' past vegetated area.

4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

01/01/19

Page 4: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBERHG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO ROOF DRAIN - BALLAST STONE 2110 - SA - D1

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.

4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

5"

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO ROOF DRAIN - BALLAST STONESCALE: 1 1/2" = 1'-0"1

[HG 3920] SLOTTED ALUMINUM EDGE

DECORATIVE BALLAST STONE, 1-112" MIN.

TROWEL FLASHINGMIN 60 MILS (APPROX .5 LBS/SF)

ROOF DRAIN WITH ADJUSTABLE EXTENSION

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF) 3" MIN

SPECIFIED SEALANT UNDER MEMBRANE AT CLAMPING RING

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 5: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.

3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO DRAIN ACCESS BOX - BALLAST STONE 2110 - SA - D2

1' MIN

[HG 3920] SLOTTED ALUMINUM EDGE

DECORATIVE BALLAST STONE, 1-112" MIN. DIAMETER

5"

SPECIFIED SEALANT UNDER MEMBRANE AT CLAMPING RING

[HG 3550] DRAIN ACCESS BOX

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO DRAIN ACCESS BOX - BALLAST STONESCALE: 1 1/2" = 1'-0"1

ROOF DRAIN WITH ADJUSTABLE EXTENSION

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM/PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF) 3" MINTROWEL FLASHINGMIN 60 MILS (APPROX .5 LBS/SF)

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 6: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3550] DRAIN ACCESS BOX

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Drain Access Box.

3. Saturated weight and stormwater retention based on 4" of growth media.4. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO DRAIN ACCESS BOX 2110 - SA - D3

5"

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO DRAIN ACCESS BOXSCALE: 1 1/2" = 1'-0"1

ROOF DRAIN WITH ADJUSTABLE EXTENSION

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMER

AND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE

MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF) 3" MINTROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF)

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 7: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 5100] PAVER PEDESTALS

[HG 5310] CONCRETE PAVERS

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO CONCRETE PAVERS OVER DRAIN 2110 - SA - D4

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.

4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

5"

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

ROOF DRAIN WITH ADJUSTABLE EXTENSION

GREEN ROOF TO CONCRETE PAVERS OVER DRAINSCALE: 1 1/2" = 1'-0"1

[HG 3920] SLOTTED ALUMINUM EDGE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF) 3" MINTROWEL FLASHINGMIN 60 MILS (APPROX .5 LBS/SF)

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 8: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO CONCRETE PAVERS 2110 - SA - P1

5"

[HG 3920] SLOTTED ALUMINUM EDGE

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO CONCRETE PAVERSSCALE: 1 1/2" = 1'-0"1

[HG 3310] PROTECTIVE FLEECE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

[HG 5100] PAVER PEDESTALS

[HG 5310] CONCRETE PAVERS

[HG 3320] SEMI-INTENSIVE PROTECTIVE FLEECE

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 9: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO WOOD DECK TILES 2110 - SA - P2

5"

[HG 3920] SLOTTED ALUMINUM EDGE

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO WOOD DECK TILESSCALE: 1 1/2" = 1'-0"1

[HG 3310] PROTECTIVE FLEECE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMER

AND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

[HG 5100] PAVER PEDESTALS

[HG 5350] WOOD DECK TILES

[HG 3320] SEMI-INTENSIVE PROTECTIVE FLEECE

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 10: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PORCELAIN PAVERS 2110 - SA - P3

5"

[HG 3920] SLOTTED ALUMINUM EDGE

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PORCELAIN PAVERSSCALE: 1 1/2" = 1'-0"1

[HG 3310] PROTECTIVE FLEECE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMER

AND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE

MIN 80 MILS (APPROX 1LB/SF)

[HG 5100] PAVER PEDESTALS

[HG 5360] PORCELAIN PAVERS

[HG 3320] SEMI-INTENSIVE PROTECTIVE FLEECE

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 11: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBERHG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO ARTIFICIAL TURF - AGGREGATE 2110 - SA - T1

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO ARTIFICIAL TURF - AGGREGATESCALE: 1 1/2" = 1'-0"1

5"

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3920] SLOTTED ALUMINUM EDGE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 5410] SKYE TURF

[HG 3530] PEDESTRIAN PAVING DRAIN

[HG 5423] VERSATILE DRAINAGE MAT

[OTHERS] TREATED WOOD / COMPOSITE NAILER BOARD

- SET 1" BELOW FINISHED FLOOR ELEVATION

[OTHERS] 1" STAINLESS STEEL NAIL - SPACED EVERY 1"

WASHED SILICA SAND / [HG 5431] ENVIROFILL - GREEN(APPROX 3 LBS/SF)

[HG 3610] DRAINAGE BOARD

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE

MIN 80 MILS (APPROX 1LB/SF)

[HG 4620] DRAINAGE AGGREGATE

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Artificial turf must be installed and seamed with adjacent pieces running in the same direction.6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

01/01/19

Page 12: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBERHG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO ARTIFICIAL TURF - INSULATION 2110 - SA - T2

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO ARTIFICIAL TURF - INSULATIONSCALE: 1 1/2" = 1'-0"1

5"

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3920] SLOTTED ALUMINUM EDGE

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 3193] GEOFOAM INSULATION

[HG 3530] PEDESTRIAN PAVING DRAIN

[HG 5423] VERSATILE DRAINAGE MAT

[OTHERS] TREATED WOOD / COMPOSITE NAILER BOARD

- SET 1" BELOW FINISHED FLOOR ELEVATION

[OTHERS] 1" STAINLESS STEEL NAIL - SPACED EVERY 1"

[HG 3610] DRAINAGE BOARD

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

STRUCTURAL CONCRETE DECK

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· THERMAL PROTECTION COATING MIN 20 MILS (APPROX .16 LBS/SF)· INSTANT SETTING RUBBER MEMBRANE

MIN 80 MILS (APPROX 1LB/SF)

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Saturated weight and stormwater retention based on 4" of growth media.5. Artificial turf must be installed and seamed with adjacent pieces running in the same direction.6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

[HG 5410] SKYE TURF

WASHED SILICA SAND / [HG 5431] ENVIROFILL - GREEN(APPROX 3 LBS/SF)

01/01/19

Page 13: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3920] SLOTTED ALUMINUM EDGE

DECORATIVE BALLAST STONE, 1-112" MIN.

1' MIN

ROOF PENETRATION

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Waterproofing shall extend up roof penetration at least to the height of the top of the surfacing.

5. Some pipe materials (PVC, Copper, Brass) may require roughening/sanding, in addition to priming with surface conditioner, for proper adhesion of membrane.6. Saturated weight and stormwater retention based on 4" of growth media.7. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO ROOF PENETRATION - BALLAST STONE 2110 - SA - V1

5"

CLAMP TOP OF FLASHING SHEET WITH A STAINLESS STEELCLAMPING RING & SEALANT

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO ROOF PENETRATION - BALLAST STONESCALE: 1 1/2" = 1'-0"1

TROWEL FLASHING MIN 60 MILS (APPROX .5 LBS/SF)

6"

MIN

6" MIN

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMER

AND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE

MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF)

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 14: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

8" MIN

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO ROOF PENETRATION 2110 - SA - V2

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up roof penetration.3. Waterproofing shall extend up roof penetration a minimum of 8" above highest water line.4. Some pipe materials (PVC, Copper, Brass) may require roughening/sanding, in addition to priming with surface conditioner, for proper adhesion of membrane.5. Saturated weight and stormwater retention based on 4" of growth media.6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

5"

CLAMP TOP OF FLASHING SHEET WITH A STAINLESS STEELCLAMPING RING & SEALANT

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO ROOF PENETRATIONSCALE: 1 1/2" = 1'-0"1

ROOF PENETRATION

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING

· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF)

TROWEL FLASHINGMIN 60 MILS (APPROX .5 LBS/SF)

6"

MIN

6" MIN

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 15: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

1' MIN

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. All flashing shall extend a minimum of 8" above highest water line.5. Saturated weight and stormwater retention based on 4" of growth media.6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL - BALLAST STONE 2110 - SA - W1

6"

MIN

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALL - BALLAST STONESCALE: 1 1/2" = 1'-0"1

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF)

[HG 3920] SLOTTED ALUMINUM EDGE

DECORATIVE BALLAST STONE. 1-112" MIN. DIAMETER

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 16: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3920] SLOTTED ALUMINUM EDGE

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Waterproofing shall extend a minimum of 8" above highest water line.5. Saturated weight and stormwater retention based on 4" of growth media.

6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL - CONCRETE PAVERS 2110 - SA - W2

6"

MIN

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALL - CONCRETE PAVERS ON PEDESTALSSCALE: 1 1/2" = 1'-0"1

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF)

[HG 5100] PAVER PEDESTALS

[HG 5310] CONCRETE PAVERS

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 17: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3920] SLOTTED ALUMINUM EDGE

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Waterproofing shall extend a minimum of 8" above highest water line.5. Saturated weight and stormwater retention based on 4" of growth media.

6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL - WOOD DECK TILES 2110 - SA - W3

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALL - WOOD DECK TILES ON PEDESTALSSCALE: 1 1/2" = 1'-0"1

6"

MIN

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF)

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

[HG 5100] PAVER PEDESTALS

[HG 5350] WOOD DECK TILES

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 18: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

[HG 3920] SLOTTED ALUMINUM EDGE

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Waterproofing shall extend a minimum of 8" above highest water line.5. Saturated weight and stormwater retention based on 4" of growth media.

6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL - PORCELAIN PAVERS 2110 - SA - W4

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALL - PORCELAIN PAVERS ON PEDESTALSSCALE: 1 1/2" = 1'-0"1

6"

MIN

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATING

MIN 20 MILS (APPROX .16 LBS/SF)

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

[HG 5100] PAVER PEDESTALS

[HG 5360] PORCELAIN PAVERS

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 19: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up parapet wall.3. Waterproofing shall extend a minimum of 8" above highest water line.4. Saturated weight and stormwater retention based on 4" of growth media.

5. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL 2110 - SA - W5

6"

MIN

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALLSCALE: 1 1/2" = 1'-0"1

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF)

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19

Page 20: 1 ISSUED DATEDETAIL NUMBER HG 2110 - EXTENSIVE SEDUM ...€¦ · [hg 3150] spray applied rubber waterproofing ·instant setting rubber membrane min 80 mils (approx 1lb/sf) structural

ISSUED DATE DETAIL NUMBER

NOTES:1. Scatter sedum cuttings over growth media per layout plan & water-in. See specifications for application rate.2. Filter Fleece shall wrap up Aluminum Edge.3. Root Barrier shall extend 1' past vegetated area.4. Waterproofing shall extend a minimum of 8" above highest water line.5. Saturated weight and stormwater retention based on 4" of growth media.

6. Calculations performed using ASTM Standard E2397-11. Actual system weight and stormwater retention may vary.

HG 2110 - EXTENSIVE SEDUM CUTTINGS SYSTEM

GREEN ROOF TO PARAPET WALL - CONCRETE PAVERS 2110 - SA - W6

6"

MIN

STORMWATER RETENTION:·· 1.60 gallons / ft2

·· 2.57 in3 / in2

ROOF PITCH:·· 0 - 5o

·· 0 - 9%

GREEN ROOF TO PARAPET WALL - CONCRETE PAVERSSCALE: 1 1/2" = 1'-0"1

[HG 3710] EXTENSIVE FILTER FLEECE

[HG 4110] EXTENSIVE GROWTH MEDIA

[HG 6100] SEDUM CUTTINGS

[HG 3610] DRAINAGE BOARD

[HG 3490] EROSION / WIND NETTING (as required)

[HG 3310] PROTECTIVE FLEECE

[HG 3195] INTENSIVE GEOFOAM INSULATION

CONDUCTIVE MEDIUM / PRIMERAND SURFACE CONDITIONER (as required)

COVER BOARD, ADHERED

[HG 3220] ROOT BARRIER

[HG 3150] SPRAY APPLIED RUBBER WATERPROOFING· INSTANT SETTING RUBBER MEMBRANE MIN 80 MILS (APPROX 1LB/SF)

STRUCTURAL CONCRETE DECK

THERMAL PROTECTION COATINGMIN 20 MILS (APPROX .16 LBS/SF)

POLYFAB REINFORCEMENT

TROWEL FLASHING

MIN 60 MILS (APPROX .5 LBS/SF) 6" MIN

[HG 5310] CONCRETE PAVERS

[HG 3530] PEDESTRIAN PAVING DRAIN

[HG 3920] SLOTTED ALUMINUM EDGE

SATURATED WEIGHT:·· 28.93 lbs / ft2

·· 141.24 kg / m2

01/01/19