1 Pump Curves

Embed Size (px)

Citation preview

  • 8/17/2019 1 Pump Curves

    1/39

    Sulzer Pumps

    The Heart of Your Process

    Understanding Pump CurvesPresenter: Michael Stroh – Application & Project Engineer, Sulzer Pumps

    June 4th, 2015

    OWEA-S: Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    2/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 2

    Head 

    Flow

    Static Head

    The Static Head is the total vertical

    distance that the liquid must bepumped.

    The Static Head is measured from

    the starting water level surface to

    the discharge water level surface.

    The Static Head is normally

    expressed in “Feet” in thewastewater industry, meaning feet

    of water column.

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    3/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 3

    System Curve

    The Dynamic Head of a system is

    computed for multiple flow rates,

    and plotted along with the Static

    Head to produce a System Head

    Curve or simply System Curve.

    Dynamic Head

    The Dynamic Head is determined by

    analyzing the losses in the entirepiping system at various flow rates.

    The losses are based on the

    configuration of the piping system.

    All pipe and fittings through which

    the water flows must be taken into

    account.

    Head 

    Flow

    Static Head

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    4/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 4

    Head 

    Flow

    System Curve

    Static Head

    Dynamic Head

    DesignFlow

    The Design Flow is determined by

    the pumping requirements of thestation.

    Design

    Head

    The Design Head is determined

    from the System Curve. The

    intersection point of the Design

    Flow and the System Curve

    provides the Design Head.

    The whole purpose of the System

    Curve its to provide the Total Head

    for a particular system, at any flow

    rate.

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    5/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 5

    Head 

    Flow

    Static Head

    Dynamic Head

    DesignFlow

    Design

    Head

    The pump will always  runs at this

    intersection point. It is physically

    impossible for the pump to operate

    at any other point.

    System Curve

    The Pump Curve is then plotted on

    the same graph as the SystemCurve.

    Pump Curve

    The intersection point of the Pump

    Curve and the System Curve

    defines the Flow and Head at which

    the pump will operate in this

    particular system.

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    6/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 6

    Most pump stations actually have a

    System Curve that continuously

    changes during the pumping cycle.

    System Curves

    The full range of possible System

    Curves are normally represented bytwo curves, one at each extreme of

    the possible static head.

    This change results from changing

    static head while the pump is

    emptying the wet well.

    High WW Level Static Head

    Low WW Level Static Head

    Head 

    Flow

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    7/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 7

    Head 

    Flow

    System Curves

    High WW Level Static Head

    Low WW Level Static Head

    When the Pump Curve is added to

    the graph, the range of possibleoperating points during a pumping

    cycle can be seen.

    The pump will operate the higher

    flow, lower head point at the

    beginning of the pumping cycle.

    The pump will operate at the higherhead, lower flow point at the end of

    the pumping cycle.

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    8/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 8

    Head 

    FlowDesignFlow

    Design

    Head

    Most commonly however a single

    system curve is provided, and we

    select the pump with theunderstanding that it may run a little

    left or right of the given intersection

    point.

    Understanding Pump Curves

  • 8/17/2019 1 Pump Curves

    9/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 9

    An actual pump

    curve for a 12”pump with a

    450mm diameter

    impeller,

    showing Q-H,

    P2, and

    Hydraulic

    Efficiency.

    An Actual Pump Performance Curve (XFP 301M)

    81.6%

    P  E  1 0  4 0   /  6  

    Head

    Shaft power P2

    Hydraulic eff iciency

    H   / ft

    35

    40

    45

    50

    55

    60

    65

    70

    75

    80

    85

    90

    95

    100

    105

    110

    115

    120

    125

    130

    135

    140

    145

    150

    H   / psi

    16

    20

    24

    28

    32

    36

    40

    44

    48

    52

    56

    60

    64

    P₂  / hp

    75

    8085

    90

    95

    100

    105

    110

    115

    120

    125

    Q  / US g.p.m.0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600

    η  / %

    0

    10

    20

    30

    40

    50

    60

    70

  • 8/17/2019 1 Pump Curves

    10/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 10

    A duty point of

    4500 gpm at 80

    feet (40 feet

    static head) has

    been added.

    An Actual Pump Performance Curve (XFP 301M)

    80.1%

    P  E  1 0  4 0   /  6  

    Head

    Shaft power P2

    Hydraulic eff iciency

    H   / ft

    30

    35

    40

    45

    50

    55

    60

    65

    70

    75

    80

    85

    90

    95

    100

    105

    110

    115

    120

    125

    130

    135

    140

    145

    150

    H   / psi

    16

    20

    24

    28

    32

    36

    40

    44

    48

    52

    56

    60

    64

    P₂  / hp

    75

    8085

    90

    95

    100

    105

    110

    115

    120

    125

    Q  / US g.p.m.0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600

    η  / %

    0

    10

    20

    30

    40

    50

    60

    70

     A1

  • 8/17/2019 1 Pump Curves

    11/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 11

    Because the

    impeller isoversized for

    the duty point,

    the actual flow

    and head will be

    4712 gpm at

    83.7 feet… the

    intersection

    point betweenthe pump curve

    and system

    curve.

    An Actual Pump Performance Curve (XFP 301M)

    80.1%

    P  E  1 0  4 0   /  6  

    Head

    Shaft power P2

    Hydraulic eff iciency

    H   / ft

    30

    35

    40

    45

    50

    55

    60

    65

    70

    75

    80

    85

    90

    95

    100

    105

    110

    115

    120

    125

    130

    135

    140

    145

    150

    H   / psi

    16

    20

    24

    28

    32

    36

    40

    44

    48

    52

    56

    60

    64

    P₂  / hp

    75

    8085

    90

    95

    100

    105

    110

    115

    120

    125

    Q  / US g.p.m.0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600

    η  / %

    0

    10

    20

    30

    40

    50

    60

    70

     A1

    83.74 ft

    124.9 hp

    4712 US g.p.m.

    79.62 %

  • 8/17/2019 1 Pump Curves

    12/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 12

    Trimming the

    impeller to 440mm shifts the

    performance

    curve down so

    that it intersects

    the system

    curve at the duty

    point.

    An Actual Pump Performance Curve (XFP 301M)

    79.3%

    P  E  1 0  4 0   /  6  

    Head

    Shaft power P2

    Hydraulic eff iciency

    H   / ft

    30

    35

    40

    45

    50

    55

    60

    65

    70

    75

    80

    85

    90

    95

    100

    105

    110

    115

    120

    125

    130

    135

    140

    145H   / psi

    12

    16

    20

    24

    28

    32

    36

    40

    44

    48

    52

    56

    60

    P₂  / hp

    70

    7580

    85

    90

    95

    100

    105

    110

    115

    Q  / US g.p.m.0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600

    η  / %

    0

    10

    20

    30

    40

    50

    60

    70

     A1

    80.01 ft

    115.3 hp

    4499 US g.p.m.

    78.65 %

  • 8/17/2019 1 Pump Curves

    13/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 13

    For most

    wastewater

    pumps, the flow

    limits for

    smooth reliable

    operation is

    from 50% of

    BEP flow to

    125% of BEP

    flow.

    An Actual Pump Performance Curve (XFP 301M)

    79.3%

    P  E  1 0  4 0   /  6  

    Head

    Shaft power P2

    Hydraulic eff iciency

    H   / ft

    30

    35

    40

    45

    50

    55

    60

    65

    70

    75

    80

    85

    90

    95

    100

    105

    110

    115

    120

    125

    130

    135

    140

    145H   / psi

    12

    16

    20

    24

    28

    32

    36

    40

    44

    48

    52

    56

    60

    P₂  / hp

    70

    7580

    85

    90

    95

    100

    105

    110

    115

    Q  / US g.p.m.0 400 800 1200 1600 2000 2400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 6800 7200 7600

    η  / %

    0

    10

    20

    30

    40

    50

    60

    70

     A1

    80.01 ft

    115.3 hp

    4499 US g.p.m.

    78.65 %

  • 8/17/2019 1 Pump Curves

    14/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 14

    Summary

    The System Curve is a combination of static and dynamic head.

    It provides a means of selecting pumps by predicting the Total

    Head at any flow rate.

    The pump always operates at the head and flow corresponding to the

    intersection of the System Curve and the Pump Curve

    The static component is based on the vertical distance that the

    liquid must be pumped (change in elevation)

    The dynamic component is based on pipe and fitting size, quantity,

    and interior roughness of the material.

    When selecting wastewater pumps, the rule of thumb is stay in therange of 50%-125% of BEP flow. Going outside this range is possible,

    but more detailed analysis of the application is necessary.

  • 8/17/2019 1 Pump Curves

    15/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 15

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    16/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 16

    Primary Benefits of Variable Speed Pumping

    There are three primary reasons to use a VFD to control pump speeds:

    Control the output of the pump for process reasons (flow or pressure)

    Reduce energy consumption

    Manage starting current

    Secondary reasons to use a VFD can include:

    Manage water hammer

    Improve Power Factor Precision control of wet well levels

    Managing stations with wet wells that are too small

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    17/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 17

    Affinity Laws

    The Affinity Laws predict the

    performance of a centrifugal

    pump at differing speeds

    The change is flow is proportional to

    the change in speed

    The change is head is proportional

    to the square of the change in speed

    The change in power is proportional

    to the cube of the change in speed

    3

    2

    3

    1

    2

    1

    2

    2

    2

    1

    2

    1

    2

    1

    2

    1

    n

    n

     P 

     P n

    n

     H 

     H 

    n

    n

    Q

    Q

    Q = flow

    H = head pressure

    P = power

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    18/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 18

    Affinity Laws

    Since we don’t know the exact  speed the submersible

    pump is turning at any VFD output frequency, it’s common

    to substitute the frequency ratio for the speed ratio:

     Hz 

     Hz 

    rpm

    rpm

    50

    60

    1483

    1780

    n = rotational speed

    F = output frequency of the VFD

    2

    1

    2

    1

     F 

     F 

    n

    n

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    19/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 19

    Calculating Using the Affinity Laws

    Therefore, for a pump delivering 2000gpm at 100feet, with

    a BHP of 67hp, reducing the speed from 60 Hz to 50 Hz:

    Q = flow

    H = head pressure

    P = power

    hp

    hp

     Hz 

     Hz 

    8.38

    67

    50

    60

    3

    3

     ft 

     ft 

     Hz 

     Hz 

    4.69

    100

    50

    60

    2

    2

     gpm

     gpm

     Hz 

     Hz 

    1667

    2000

    50

    60

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    20/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 20

    Calculating Using the Affinity Laws

    Reducing the frequency (and rotational speed) from 60Hz

    to 50 Hz, or about 16.7% results in:

     A flow reduction of 16.7% to 1667 gpm

     A head reduction of 30.6% to 69.4 feet

     A power reduction of 42.1% to 38.8 hp

    Of course the pump will not necessarily run at this new flow andhead. The actual new operating point depends on where the system

    curve intersects with the reduced speed pump curve.

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    21/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 21

    Example pump, 8” discharge, 4

    pole, 115 HP, full speed curve 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    22/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 22

    Flow reduction is directly

    proportional to the speed

    reduction

    Head reduction is

    proportional to the square

    of the speed reduction

    Reduced speed curves are

    parallel to the full speed

    curve, and follow theaffinity laws

    Reduced speed curves

    shown in 5 Hz increments

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    23/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 23

    Lines of constant efficiency

    added to the curve 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    24/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 24

    Example system curve

    added 

    Full speed duty point is

    3600gpm at 95 feet, with

    a 30 foot static head 

    Pump performance at any

    speed can be determinedby the intersection point

    of the system curve and

    appropriate reduced

    speed pump curve 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    25/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 25

    The same pump with a

    slightly different systemcurve 

    Full speed duty point is

    still 3600gpm at 95 feet,

    but now with an 85 foot

    static head 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    26/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 26

    First Rule of Thumb

    First rule of thumb:

     Applications where the static head is greater than 50% of thetotal head are not usually good applications for VFDvariable speed pumping. This is because:

    Since the system curve is very flat, the pump efficiency at thereduced speed operating point falls off rapidly. The opportunity for

    energy savings at reduced speed is minimal.

    Since the system curve is very flat, there is very little useable

    speed reduction range.

    Pump rotational speed at reduced speed, lower flow conditions

    remains very high, resulting in high energy recirculation

    cavitation, which can damage the pump.

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    27/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 27

    10” pump selection with 25

    ft static head, 6 pole 115hp

    motor  

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    28/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 28

    10” pump selection with 25

    ft static head, 6 pole 115hp

    motor  

    Useable speed

    adjustment range down to

    below 30 Hz (about 800

    gpm) 

    Efficiency falls to 65% at800 gpm 

    Efficiency increases as the

    pump is slowed down, to a

    max of 80.4% at 2100 gpm,

    then begins to fall 

    Hydraulic efficiency at

    full speed duty point,

    75% 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    29/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 29

    10” pump selection with 60

    ft static head, 6 pole 115hpmotor  

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    30/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 30

    10” pump selection with 60

    ft static head, 6 pole 115hp

    motor  

    Useable speed

    adjustment range down to

    about 42 Hz (about 1100

    gpm) 

    Hydraulic efficiency at

    full speed duty point,

    75% 

    Efficiency falls to 60% at1100 gpm 

    Efficiency increases as the

    pump is slowed down, to a

    max of 80.4% at 2800 gpm,

    then begins to fall 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    31/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 31

    Second Rule of Thumb

    Second rule of thumb:

    For variable speed applications, select pumps with the fullspeed operating point to the right of BEP whenever

     possible.

    Selecting to the right of BEP improves efficiency at reducedspeed since the intersection point with the system curve moves

    toward BEP when slowing down.

    Variable speed applications often allow the use of smaller, less

    expensive pumps.

    Smaller pumps and selections right of BEP provide the best

    opportunity for energy savings at reduced speed (where the

    pumps run most of the time).

    Check NPSH margin for all selections, especially when selecting

    to the right of BEP!

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    32/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 32

    Establishing Minimum Speeds

    The minimum speed the pump can run in a VFD applicationis dependant on several factors:

    Fluid velocities through the pump and the piping systems. For

    normal wastewater you must maintain 2.5ft/sec in horizontal runs

    and 3ft/sec in vertical runs to keep solids suspended.

    Meet the pump manufacturer’s minimum flow requirements for

    the selected pump to avoid damaging recirculation cavitation.

    This can range from 20% of BEP flow to 50% of BEP flow,

    depending on the impeller design and operating speed.

    Maintaining high enough rotational speed to keep the motor’scooling system functioning. The min speed for proper cooling

    system operation depends on the type of cooling system

    provided.

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    33/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 33

    Clogging issues with pumps on VFDs

    Pumps running on VFDs are more prone to clogging thanconstant speed pumps. This is because:

     At reduced speed, fluid velocities through the impeller and in the

    piping can drop significantly allowing rag material to build up 

     At reduced speed, material moves more slowly through the impellerand volute and can build up, creating a clog.

    In the impeller, the natural scouring action which aids in rag handling

    can be greatly reduced

    Material can build up in the discharge piping, and eventually back up

    into the pump In dry pit, material can build up in the suction piping, and overwhelm

    the pump with solids when the speed is ramped up

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    34/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 34

    Other Important VFD setting and operational

    parameters

    Modern VFDs have many configuration options that must beset during startup. Setting these parameters properly canmake the difference between a good VFD pumpingsystem, and a poor one.

    Constant torque/variable torque: Centrifugal pumps are variabletorque machines, so this parameter should always be set to

    variable torque.

     Acceleration and deceleration ramp: Initial ramp setting should be

    10 sec for both accel and decel. This should be tuned to field

    conditions with the understanding that shorter ramp times are

    usually preferable (especially with systems that have a high

    percentage of static head). If water hammer is not an issue,

    coast to stop is preferred over controlled deceleration.

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    35/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 35

    Slip compensation: This parameter should be turned OFF unless

    the pump manufacturer specifically states that it should be on for

    the particular application. Slip compensation attempts to run the

    motor at full synchronous speed by increasing the max frequency

    above 60 Hz. This can cause overload and overheating of the

    motor.

    Minimum frequency: This must be set to an appropriate

    frequency to meet the minimum flow requirements of the system

    as previously discussed. Failure to set the minimum frequency to

    an acceptable level can cause the level controls or an

    unsuspecting operator to run the pump continuously at shutoffhead; damaging the pump.

    Maximum frequency: This should be set to the name plate

    frequency of the motor (60Hz in N. America) to prevent over

    speeding of the pump. Only set the max frequency above 60Hz if

    recommended and approved by the pump manufacturer.

    Other Important VFD setting and operational

    parameters

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    36/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 36

    Speed control settings: The control system should be set to ramp

    up the pump to full speed and allow it to stabilize before dropping

    it down to level control speed. This is normally accomplished

    through the PLC or controller rather than through the VFD

    settings. Systems that ramp up to control speed directly without a

    short run at full speed are more likely to clog.

    Parallel pumps on VFDs: When multiple identical pumps are run

    in parallel on VFDs, all pumps must be run at the same speed. If

    a VFD pump is to be run in parallel with a constant speed pump,

    the VFD pump must be run at full speed. Exceptions can be

    made to the above rule if a detailed analysis of the pump curvesand system curve has been performed, and it is found that the

    slower running pump will be running at an acceptable point on the

    curve.

    Other Important VFD setting and operational

    parameters

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    37/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 37

    Summary

    The general rules of thumb for selecting variable speedpumping systems are:

     Applications where the static head exceeds 50% of the

    duty head are not usually good applications for variablespeed pumping

    Select pumps so that the primary, full speed duty point is to

    the right of the pump’s BEP (but watch NPSH margin) 

    Understanding VFD Curves

  • 8/17/2019 1 Pump Curves

    38/39

    Sulzer Pumps

    Customer presentation | May 2012 Copyright © Sulzer Pumps | Slide 38

    Summary

    Some other guidelines:

     Allow about a 5-10 percent motor power reserve at full speed to account

    for extra heat generated in the motor

    Use motors that are acceptable for VFD service, and use appropriate

    filters for long cable runs to prevent damage to the motor

    Size and select VFD and Motor combinations with an emphasis on

    current, not horsepower, to be sure the VFD has adequate output

    capability for the application.

    Carefully consider operational parameters for VFD stations to minimize

    the possibility of clogging.

     Apply VFDs only where there is a real benefit in efficiency or process

    control. Don’t fall for the argument that VFDs always improve the

    efficiency and performance of pump systems, it’s simply not true. Some

    systems can benefit, but many cannot.

  • 8/17/2019 1 Pump Curves

    39/39

    Sulzer Pumps

    The Heart of Your Process

    The End