Upload
jmmankavil6230
View
3
Download
0
Embed Size (px)
DESCRIPTION
10 - Mitigate the Magnetic Field Exposure Near Power Transformer
Citation preview
MITIGATE THE MAGNETIC FIELD EXPOSURE NEAR
TRANSFORMER SUBSTATIONS
BLA VALI1,2
PETER GAJEK1
INSTITUTE OF NON-IONIZING RADIATION, POHORSKEGA BATALJONA 215, 1000 LJUBLJANA,
SLOVENIA
GENERA, PREVALE 10, 1236 TRZIN
Abstract
Transformer substations located close to the living areas could induce high long-term exposures to extremely
low frequency magnetic fields of nearby inhabitants. Some of the researches have shown increased risk to
childhood leukemia associated with the long term exposure to the elevated levels of magnetic fields. With the
increasing public interest, prudent avoidance and good practice it is becoming more and more important to
minimize the exposure of the nearby inhabitants. The most cost efficient way of achieving this goal is to include
the magnetic field mitigation in the early stage of the planning and construction/reconstruction process of each
transformer substation. Using numerical modeling we studied different variants of reconstruction of a typical
transformer substation located in the basement of a block of flats with a living room located right above the
transformer. To obtain a comprehensive snapshot of current situation before the reconstruction we performed
detailed spot and 24-hour measurements of magnetic flux densities. Based on the results of the numerical
modeling we proposed the optimum and cost effective reconstruction plan. After the reconstruction, numerical
results were evaluated by the comparison of the numerical results with the results of the measurements after the
reconstruction and numerically predicted 10-fold reduction factor of the highest values of the magnetic field was
confirmed.
Introduction
International Agency for Research on Cancer included extremely low frequency (ELF) magnetic field among the
possibly carcinogenic factors for humans [1]. This decision is based on the results of two studies [2, 3], which
showed that elevated 24 hours averaged values of ELF magnetic field (
BLA VALI, PETER GAJEK
Figure 1: Transformer located in the right room of the transformer substation.
Measurements
Magnetic field is linearly correlated to the actual current load, but this can vary during the day depending on the
present use. To obtain the detailed snapshot of the magnetic field in the apartment above the TS it is therefore
not enough to make only spot measurements, but also 24-hour measurements to evaluate the time variability of
the magnetic field and determine worst case condition.
For spot measurements we have used Wandel & Goltermann EM field analyzer EFA-3 with the B field probe.
For 24-hour measurements we have used automatic measurement station PMM 8055 which measures the
magnetic flux density continuously 24 hours per day. It consists of measurement probe for ELF magnetic flux
density HP-051, control unit with the GSM modem to send the measurements from the measurement station to
the server connected to the internet, housing with solar cells and accumulator. After the data are automatically
transferred to the server, they could be viewed by everyone through an internet application.
According to the Slovenian legislation and the international standards (IEC 61786) the magnetic flux density is
measured at the height of 1 or 1.5 m above the ground. But in the apartment, it is not uncommon that the
children have their beds on the floor or do they play on the floor and with measurements 1 m above the ground
the exposure would be greatly underestimated. Therefore all the measurements spot and continuous 24-hour were taken at the height of 0.2 m above the ground.
Numerical calculations
We used program package Narda EFC-400EP for numerical modeling of the magnetic flux density in the
vicinity of the TS. It is based on segmentation method where each conductor is presented with finite segments.
Corresponding material and electromagnetic characteristics are assigned to all the segments and the resulting
magnetic field is the sum of the contributions of all the segments.
Results
Results of spot measurements
Spot measurements were carried out on the 22 of October 2008 between the 10.30 and 11.30. Measurements
were taken on 15 locations inside the TS as well as on 17 locations in the apartment above the TS. Measurement
results in the apartment together with the locations are shown in Table 1. Based on the data from electric
distribution company the value of the current in the LV busbar during measurements was 100 A.
MAGNETIC FIELD OF TRANSFORMER SUBSTATIONS
Table 1: Measured values of magnetic flux density in apartment above TS
Measure distance [m] height [m] B [T]
1 0.2 0.2 0.57
2 0.2 0.2 0.62
3 0.2 0.2 2.54
4 0.2 0.2 3.50
5 0.2 0.2 2.17
6 0.2 0.2 0.98
7 0.5 0.2 7.10
8 1.0 0.2 11.40
9 1.5 0.2 6.95
10 2.0 0.2 4.72
11 3.0 0.2 2.43
12 1.0 0.2 7.53
13 1.0 0.2 7.75
14 1.0 0.2 4.54
15 see Figure on
right
0.2 0.46
16 0.2 0.46
17 0.2 0.26
Results of continuous 24-hour measurements
Continuous 24-hour measurements were carried out first time between the beginning of December 2007 and the
end of January 2008 and second time between the beginning of spot measurements (22 October 2008) and 6
December 2008. The highest measured magnetic flux density was 15.6 T with the highest 24-hour average of 9.4 T. Based on the results of continuous measurements we estimated the real worst case load of the TS. During spot
measurements the current in the LV busbar was 100 A. A nominal load with the current 909 A represents the worst case condition where such conditions in real situations are very unlikely. Based on the results of
continuous measurements we estimated that in real worst case condition the current in the LV busbar is 200 A.
Numerical modeling
To verify our numerical model of the TS we compared measured and calculated results under the same load
conditions at the same locations (Table 2) and it could be seen that both values agree well. Small differences are
possible due to different factors (simplification of the model, changes of the load of the TS). We made separate calculations for different parts of TS to evaluate which parts are the most critical and
identified LV busbar, which is fixed on the ceiling of the TS and therefore the distance between the LV busbar
and the floor of the above apartment is only 0.5 m. Other important sources are also switchgear and transformer.
Based on this findings we numerically analyzed the re-construction of the TS with following modifications:
removing LV busbar, new LV busbar located under the floor of the TS; change of the switchgear, since it is
already old, with a new, which should be as low as possible; proper design and realizations of all the busbars in
the TS (all cables close together and arranged in the triangle, as short busbars as possible, especially parts of
them which are higher than the floor of the TS). We propose transformer to remain, since it was replaced few
years ago.
Table 2: Comparison of measured and calculated magnetic flux density inside the apartment above the TS
Measure Bmeasured [T] Bcalculated [T] Measure Bmeasured [T] Bcalculated [T]
1 0.57 0.521 4 3.50 2.985
2 0.62 0.899 5 2.17 1.416
3 2.54 1.845 6 0.98 0.634
From the results in Table 3 and Figure 2 to 5 we can see that the reconstruction will lower the maximum value of
the magnetic flux density for about 10 times.
Kitchen and dining room
Passage in front of Bedrooms
17
1615
141312
11
10
9
8
7
653214
Living room Measurementstation
BLA VALI, PETER GAJEK
Table 3: Comparison of the maximum calculated values of the magnetic flux density before the reconstruction
and after it
Current in LV busbar [A] Bbefore [T] Bafter [T]
100 7.5 0.65
200 15 1.5
909 70 8
Figure 2: Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m
above the floor before (left) and after the reconstruction (right). The current in the LV busbar is 100 A.
Figure 3: Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m
above the floor before (left) and after the reconstruction (right). The current in the LV busbar is 909 A.
MAGNETIC FIELD OF TRANSFORMER SUBSTATIONS
Figure 4: Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar
before (left) and after the reconstruction (right). The current in the LV busbar is 100 A.
Figure 5: Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar
before (left) and after the reconstruction (right). The current in the LV busbar is 909 A.
Spot measurements after the reconstruction
To verify the findings of the numerical calculations measured the magnetic flux density after the reconstruction
on the same locations as before the reconstruction (Figure 2). During the measurements after the reconstruction,
the current load was slightly higher current: before it was about 100 A, after it was about 160 A. In Table 4
where the values of the magnetic flux density are given for the measurements before the reconstruction (second
column) and after it (third column). The ratio between both measurements showing the reduction of the magnetic
field in the apartment above TS, given in the fourth column, therefore slightly underestimate the effectiveness of
the reconstruction, as the current load was 1.6 times higher during the measurements after the reconstruction
Table 4: Measured magnetic flux density in the apartment above the TS
Measure Bbefore [T] Bafter [T] Bbefore/Bafter Measure Bbefore [T] Bafter [T] Bbefore/Bafter
1 0.57 0.21 2.7 10 4.72 0.36 13.1
2 0.62 0.29 2.1 11 2.43 0.21 11.6
3 2.54 0.37 6.9 12 7.53 0.35 21.5
4 3.50 0.45 7.8 13 7.75 0.47 16.5
5 2.17 0.60 3.6 14 4.54 0.62 7.3
6 0.98 0.57 1.7 15 0.46 0.12 3.8
7 7.10 0.48 14.8 16 0.46 0.15 3.1
8 11.40 0.40 28.5 17 0.26 0.062 4.2
9 6.95 0.44 15.8
BLA VALI, PETER GAJEK
Discussion and conclusions
We analyzed the magnetic field in the apartment above the TS before the reconstruction. With numerical
calculations the reconstruction was optimized in terms of cost effectiveness and the goal to reduce the levels of
the magnetic field in the apartment above the TS. In spite of the fact that the increase of the costs of the
reconstruction was minimal and the realization of the proposed solution was not problematic, it still reduced the
exposure of the people living in the apartment for a factor of 10.
To further lower the magnetic field in the apartment it will be necessary to either change the transformer with a
one with reduced magnetic field emissions or to use shielding materials for ELF magnetic field. Shielding
materials are either good conductors (aluminium or copper plates) or have high permeability. With shielding
materials it is possible to reduce the magnetic field for a factor of 5 or even more, but these solutions are
associated with much higher costs compared to the proposed one.
References
1. IARC. (2002) Non-ionizing radiation, Part 1: Static and extremely low-frequency (ELF) electric and magnetic fields. IARC Monogr Eval Carcinog Risks Hum 80:1395. Lyon, France
2. Ahlbom A, Day N, Feychting M et. al. (2000) A pooled analysis of magnetic fields and childhood leukaemia. Br J Cancer 83:692698
3. Greenland S, Sheppard AR, Kaune WT et. al. (2000) A pooled analysis of magnetic fields, wire codes, and childhood leukemia. Childhood Leukemia-EMF Study Group. Epidemiology 11: 624634
4. Kheifets L, Repacholi M, Saunders R et. al. (2005) The sensitivity of children to electromagnetic fields. Pediatrics 116:303313
5. Swanson J, Kheifets L (2006) Biophysical mechanisms and the weight of evidence for EMF. Radiat Res 165:470478
6. Schuz J (2007) Implications on protection guidelines from epidemiologic studies on magnetic fields and the risk of childhood leukemia. Health Phys 92:642-648
7. Ilonen K, Markkanen A, Mezei G et. al. (2008) Indoor Transformer Stations as Predictors of Residential ELF Magnetic Field Exposure. Bioelectromagnetics: 29: 213-218