10 - Mitigate the Magnetic Field Exposure Near Power Transformer

Embed Size (px)

DESCRIPTION

10 - Mitigate the Magnetic Field Exposure Near Power Transformer

Citation preview

  • MITIGATE THE MAGNETIC FIELD EXPOSURE NEAR

    TRANSFORMER SUBSTATIONS

    BLA VALI1,2

    PETER GAJEK1

    INSTITUTE OF NON-IONIZING RADIATION, POHORSKEGA BATALJONA 215, 1000 LJUBLJANA,

    SLOVENIA

    GENERA, PREVALE 10, 1236 TRZIN

    Abstract

    Transformer substations located close to the living areas could induce high long-term exposures to extremely

    low frequency magnetic fields of nearby inhabitants. Some of the researches have shown increased risk to

    childhood leukemia associated with the long term exposure to the elevated levels of magnetic fields. With the

    increasing public interest, prudent avoidance and good practice it is becoming more and more important to

    minimize the exposure of the nearby inhabitants. The most cost efficient way of achieving this goal is to include

    the magnetic field mitigation in the early stage of the planning and construction/reconstruction process of each

    transformer substation. Using numerical modeling we studied different variants of reconstruction of a typical

    transformer substation located in the basement of a block of flats with a living room located right above the

    transformer. To obtain a comprehensive snapshot of current situation before the reconstruction we performed

    detailed spot and 24-hour measurements of magnetic flux densities. Based on the results of the numerical

    modeling we proposed the optimum and cost effective reconstruction plan. After the reconstruction, numerical

    results were evaluated by the comparison of the numerical results with the results of the measurements after the

    reconstruction and numerically predicted 10-fold reduction factor of the highest values of the magnetic field was

    confirmed.

    Introduction

    International Agency for Research on Cancer included extremely low frequency (ELF) magnetic field among the

    possibly carcinogenic factors for humans [1]. This decision is based on the results of two studies [2, 3], which

    showed that elevated 24 hours averaged values of ELF magnetic field (

  • BLA VALI, PETER GAJEK

    Figure 1: Transformer located in the right room of the transformer substation.

    Measurements

    Magnetic field is linearly correlated to the actual current load, but this can vary during the day depending on the

    present use. To obtain the detailed snapshot of the magnetic field in the apartment above the TS it is therefore

    not enough to make only spot measurements, but also 24-hour measurements to evaluate the time variability of

    the magnetic field and determine worst case condition.

    For spot measurements we have used Wandel & Goltermann EM field analyzer EFA-3 with the B field probe.

    For 24-hour measurements we have used automatic measurement station PMM 8055 which measures the

    magnetic flux density continuously 24 hours per day. It consists of measurement probe for ELF magnetic flux

    density HP-051, control unit with the GSM modem to send the measurements from the measurement station to

    the server connected to the internet, housing with solar cells and accumulator. After the data are automatically

    transferred to the server, they could be viewed by everyone through an internet application.

    According to the Slovenian legislation and the international standards (IEC 61786) the magnetic flux density is

    measured at the height of 1 or 1.5 m above the ground. But in the apartment, it is not uncommon that the

    children have their beds on the floor or do they play on the floor and with measurements 1 m above the ground

    the exposure would be greatly underestimated. Therefore all the measurements spot and continuous 24-hour were taken at the height of 0.2 m above the ground.

    Numerical calculations

    We used program package Narda EFC-400EP for numerical modeling of the magnetic flux density in the

    vicinity of the TS. It is based on segmentation method where each conductor is presented with finite segments.

    Corresponding material and electromagnetic characteristics are assigned to all the segments and the resulting

    magnetic field is the sum of the contributions of all the segments.

    Results

    Results of spot measurements

    Spot measurements were carried out on the 22 of October 2008 between the 10.30 and 11.30. Measurements

    were taken on 15 locations inside the TS as well as on 17 locations in the apartment above the TS. Measurement

    results in the apartment together with the locations are shown in Table 1. Based on the data from electric

    distribution company the value of the current in the LV busbar during measurements was 100 A.

  • MAGNETIC FIELD OF TRANSFORMER SUBSTATIONS

    Table 1: Measured values of magnetic flux density in apartment above TS

    Measure distance [m] height [m] B [T]

    1 0.2 0.2 0.57

    2 0.2 0.2 0.62

    3 0.2 0.2 2.54

    4 0.2 0.2 3.50

    5 0.2 0.2 2.17

    6 0.2 0.2 0.98

    7 0.5 0.2 7.10

    8 1.0 0.2 11.40

    9 1.5 0.2 6.95

    10 2.0 0.2 4.72

    11 3.0 0.2 2.43

    12 1.0 0.2 7.53

    13 1.0 0.2 7.75

    14 1.0 0.2 4.54

    15 see Figure on

    right

    0.2 0.46

    16 0.2 0.46

    17 0.2 0.26

    Results of continuous 24-hour measurements

    Continuous 24-hour measurements were carried out first time between the beginning of December 2007 and the

    end of January 2008 and second time between the beginning of spot measurements (22 October 2008) and 6

    December 2008. The highest measured magnetic flux density was 15.6 T with the highest 24-hour average of 9.4 T. Based on the results of continuous measurements we estimated the real worst case load of the TS. During spot

    measurements the current in the LV busbar was 100 A. A nominal load with the current 909 A represents the worst case condition where such conditions in real situations are very unlikely. Based on the results of

    continuous measurements we estimated that in real worst case condition the current in the LV busbar is 200 A.

    Numerical modeling

    To verify our numerical model of the TS we compared measured and calculated results under the same load

    conditions at the same locations (Table 2) and it could be seen that both values agree well. Small differences are

    possible due to different factors (simplification of the model, changes of the load of the TS). We made separate calculations for different parts of TS to evaluate which parts are the most critical and

    identified LV busbar, which is fixed on the ceiling of the TS and therefore the distance between the LV busbar

    and the floor of the above apartment is only 0.5 m. Other important sources are also switchgear and transformer.

    Based on this findings we numerically analyzed the re-construction of the TS with following modifications:

    removing LV busbar, new LV busbar located under the floor of the TS; change of the switchgear, since it is

    already old, with a new, which should be as low as possible; proper design and realizations of all the busbars in

    the TS (all cables close together and arranged in the triangle, as short busbars as possible, especially parts of

    them which are higher than the floor of the TS). We propose transformer to remain, since it was replaced few

    years ago.

    Table 2: Comparison of measured and calculated magnetic flux density inside the apartment above the TS

    Measure Bmeasured [T] Bcalculated [T] Measure Bmeasured [T] Bcalculated [T]

    1 0.57 0.521 4 3.50 2.985

    2 0.62 0.899 5 2.17 1.416

    3 2.54 1.845 6 0.98 0.634

    From the results in Table 3 and Figure 2 to 5 we can see that the reconstruction will lower the maximum value of

    the magnetic flux density for about 10 times.

    Kitchen and dining room

    Passage in front of Bedrooms

    17

    1615

    141312

    11

    10

    9

    8

    7

    653214

    Living room Measurementstation

  • BLA VALI, PETER GAJEK

    Table 3: Comparison of the maximum calculated values of the magnetic flux density before the reconstruction

    and after it

    Current in LV busbar [A] Bbefore [T] Bafter [T]

    100 7.5 0.65

    200 15 1.5

    909 70 8

    Figure 2: Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m

    above the floor before (left) and after the reconstruction (right). The current in the LV busbar is 100 A.

    Figure 3: Results of the numerical calculation of the magnetic flux density in the apartment at the height of 0.2 m

    above the floor before (left) and after the reconstruction (right). The current in the LV busbar is 909 A.

  • MAGNETIC FIELD OF TRANSFORMER SUBSTATIONS

    Figure 4: Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar

    before (left) and after the reconstruction (right). The current in the LV busbar is 100 A.

    Figure 5: Results of the numerical calculation of the magnetic flux density in vertical plane through LV busbar

    before (left) and after the reconstruction (right). The current in the LV busbar is 909 A.

    Spot measurements after the reconstruction

    To verify the findings of the numerical calculations measured the magnetic flux density after the reconstruction

    on the same locations as before the reconstruction (Figure 2). During the measurements after the reconstruction,

    the current load was slightly higher current: before it was about 100 A, after it was about 160 A. In Table 4

    where the values of the magnetic flux density are given for the measurements before the reconstruction (second

    column) and after it (third column). The ratio between both measurements showing the reduction of the magnetic

    field in the apartment above TS, given in the fourth column, therefore slightly underestimate the effectiveness of

    the reconstruction, as the current load was 1.6 times higher during the measurements after the reconstruction

    Table 4: Measured magnetic flux density in the apartment above the TS

    Measure Bbefore [T] Bafter [T] Bbefore/Bafter Measure Bbefore [T] Bafter [T] Bbefore/Bafter

    1 0.57 0.21 2.7 10 4.72 0.36 13.1

    2 0.62 0.29 2.1 11 2.43 0.21 11.6

    3 2.54 0.37 6.9 12 7.53 0.35 21.5

    4 3.50 0.45 7.8 13 7.75 0.47 16.5

    5 2.17 0.60 3.6 14 4.54 0.62 7.3

    6 0.98 0.57 1.7 15 0.46 0.12 3.8

    7 7.10 0.48 14.8 16 0.46 0.15 3.1

    8 11.40 0.40 28.5 17 0.26 0.062 4.2

    9 6.95 0.44 15.8

  • BLA VALI, PETER GAJEK

    Discussion and conclusions

    We analyzed the magnetic field in the apartment above the TS before the reconstruction. With numerical

    calculations the reconstruction was optimized in terms of cost effectiveness and the goal to reduce the levels of

    the magnetic field in the apartment above the TS. In spite of the fact that the increase of the costs of the

    reconstruction was minimal and the realization of the proposed solution was not problematic, it still reduced the

    exposure of the people living in the apartment for a factor of 10.

    To further lower the magnetic field in the apartment it will be necessary to either change the transformer with a

    one with reduced magnetic field emissions or to use shielding materials for ELF magnetic field. Shielding

    materials are either good conductors (aluminium or copper plates) or have high permeability. With shielding

    materials it is possible to reduce the magnetic field for a factor of 5 or even more, but these solutions are

    associated with much higher costs compared to the proposed one.

    References

    1. IARC. (2002) Non-ionizing radiation, Part 1: Static and extremely low-frequency (ELF) electric and magnetic fields. IARC Monogr Eval Carcinog Risks Hum 80:1395. Lyon, France

    2. Ahlbom A, Day N, Feychting M et. al. (2000) A pooled analysis of magnetic fields and childhood leukaemia. Br J Cancer 83:692698

    3. Greenland S, Sheppard AR, Kaune WT et. al. (2000) A pooled analysis of magnetic fields, wire codes, and childhood leukemia. Childhood Leukemia-EMF Study Group. Epidemiology 11: 624634

    4. Kheifets L, Repacholi M, Saunders R et. al. (2005) The sensitivity of children to electromagnetic fields. Pediatrics 116:303313

    5. Swanson J, Kheifets L (2006) Biophysical mechanisms and the weight of evidence for EMF. Radiat Res 165:470478

    6. Schuz J (2007) Implications on protection guidelines from epidemiologic studies on magnetic fields and the risk of childhood leukemia. Health Phys 92:642-648

    7. Ilonen K, Markkanen A, Mezei G et. al. (2008) Indoor Transformer Stations as Predictors of Residential ELF Magnetic Field Exposure. Bioelectromagnetics: 29: 213-218