3

Click here to load reader

11 General Technical Requirement of FOTE

Embed Size (px)

Citation preview

  • GETCO/E/GTR FOTE 4101A/ R0 Dt. 07-07-10

    Seal & sign of Bidder Page 1 of 3

    General Technical Requirement of FOTE (Fibre Optic Terminal Equipment)

    The Fibre Optic Terminal Equipment (FOTE) shall have following features.

    1. Substation Automation System (SAS) interface

    The Substation Automation System (SAS) will be as per the technical specification given separately. The offered FOTE shall include all the interface (hardware & software) required to connect & to integrate it with the SAS system.

    2. Speech communication

    6 Wire E&M, VF Interface for Speech communication - 4 W for speech & 2 for M & E wire.

    Voice Interface (VF interface) This module shall provide connections for voice channels with a bandwidth

    of 300 Hz - 3.4 kHz with analogue 4 wire for Speech (2 wires for TX & 2 wires for RX) and 2 wires for signaling channels (M => E, M => E) per voice channel.

    Each voice channel shall be configurable to operate with or without CAS (Channel Associated Signal, i.e. 16th bit of 2 Mbps Frame).

    The Input & Output levels shall be software adjustable within the following range:

    Input: +7.5 to -16dBr Output: +7.0 to -16dBr

    Modules of VF interface where each voice channel can be individually configured with 1+1 path protection shall also be available.

    3. Tele-protection

    A. Tele-protection commands

    Independent Tele-protection commands i.e. each command transmission / reception shall be independent and in case of simultaneous operation of commands, all shall be transmitted / received.

    B. Tele-protection command interface:

    The Tele-protection and communication system has to ensure the easy and secure function of the Tele-protection. Therefore following features shall be provided:

    At least an 8 bit command addressing for Tele-protection signal shall be provided to prevent tripping if the signal is inadvertently re-routed through the telecommunication network.

  • GETCO/E/GTR FOTE 4101A/ R0 Dt. 07-07-10

    Seal & sign of Bidder Page 2 of 3

    An automatic and periodic loop test (

  • GETCO/E/GTR FOTE 4101A/ R0 Dt. 07-07-10

    Seal & sign of Bidder Page 3 of 3

    5. The offered systems of FOTE must support expandability further for same number of E&M interface & Tele-protection commands interface.

    6. The offered FOTE shall be compatible to have connectivity in transit with conventional PLCC terminals installed at line opposite end Sub- station.

    7. The bidder shall have to ensure about the data connectivity onwards the opposite end Sub- station which is to be made available at ALDC Jetpur or / and SLDC, Gotri through Conventional PLCC.

    8. It shall be highly reliable and provide secure communications for real time signals such as voice, Tele-protection, data including IP/Ethernet and status, control signals & other information from SCADA system.

    9. The bidder shall have to submit the technical details of module of each above application along with the technical bid.

    _________________ __________________________

    SEAL OF THE FIRM SIGNATURE OF BIDDER