1. What is the Low temperature Tank?

Page 2: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 2/64

1.CONTAINMENT TYPE PER BS 7777 Part 1 Section 3 - Definitions

Type of Tank Single Containment Double Containment Full Containment

Definitions Only the inner tank is requiredto meet the low temperatureductility requirements forstorage of the product. 

The carbon steel outer tank isprimarily for the retention andprotection of insulation and toconstrain the vapor purge gas

pressure, but is not designed tocontain refrigerated liquid in theevent of leakage from the innertank.

Both the inner tank and outertank are capable ofindependently containing LNG. To minimize the pool of escapingliquid, the PC outer wall is locatedat a distance not exceeding 6meters from the carbon steel outertank.

The inner tank contains therefrigerated liquid under normaloperating conditions. The outertank or wall is intended tocontain the refrigerated liquidproduct leakage from the innertank, but it is not intended tocontain any vapor resultingfrom product leakage from theinner tank.

A double tank designed and

constructed so that both theinner tank and outer tank arecapable of independentlycontaining refrigerated liquidstored. The outer tank or wallshould be 1 meter to metersdistant from the inner tank.

The inner tank contains therefrigerated liquid under normaloperating conditions. The outertank is intended to be capableboth of containing LNG andcontrolled venting of the vaporresulting from product leakageafter a credible event.

Refer to the Fig. shown in the next sheet.

Page 3: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 3/64

1.CONTAINMENT TYPE PER BS 7777 Part 1 Section 3 - Definitions

Type of Tank Single Containment Double Containment Full Containment

In the Event ofLeakage fromthe Inner Tank

Normal

OperatingCondition

REFRIGERATED LIQUID

VAPOR

REFRIGERATED LIQUID

VAPOR

REFRIGERATED LIQUID 

VAPOR VAPOR 

BUND WALL

LEAKAGE

REFRIGERATED LIQUID

VAPOR VAPOR 

LEAKAGE

REFRIGERATED LIQUID

VAPOR

LEAKAGE

REFRIGERATED LIQUID

VAPORWEATHER COVER

Page 4: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 4/64

1.PROGRESSION OF BUND WALL & CONTAINMENT TYPE

Single Containment - 3 

BUND WALL

Single Containment - 1

BUND WALL

Single Containment - 2 

BUND WALL

Providing the taller bund wall to reduce area required.

Providing the tallest

bund wall at closest

point to the tank.

Double Containment

RC WALL & EARTH

EMBANKMENT

WEATHER COVER

WEATHER COVER

PC WALL

METAL BUND WALL(ABLE TO CONTAIN LIQUID)

WEATHER COVER

Full Containment

RC ROOFPC OUTER WALL

RC WALL & EARTH

EMBANKMENT

Providing the bund

wall integrated

with the tank

METAL OUTER TANK

(ABLE TO CONTAIN LIQUID)

Page 5: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 5/64

1.EXAMPLES - SINGLE CONTAINMENT TANKS PER BS 7777

 Application toLNG Storage Not appropriate.

The BOG rate will be extremelyhigh.

 Appropriate. Appropriate.

See Fig.-1.1 & 1.2 for Typical Configurationof LNG Storage Tank.

Figure

: METALLIC PARTS

: THERMAL INSULATION

: CONCRETE

BUND WALL

ELEVATED SLAB FOUNDATION OR

RAFT FOUNDATION WITH BOTTOM HEATER

BASE INSULATION

EXTERNAL INSULATION

EXTERNAL WEATHER BARRIER

ROOF

BUND WALL

ELEVATED SLAB FOUNDATION OR

RAFT FOUNDATION WITH BOTTOM HEATER

INNER TANK

BASE INSULATION

LOOSE FILL INSULATION

OUTER TANK

BUND WALL

ELEVATED SLAB FOUNDATION OR

RAFT FOUNDATION WITH BOTTOM HEATER

INNER TANK

INNER TANK

LOOSE FILL INSULATION

SUSPENDED DECK w/INSULATION

BASE INSULATION

OUTER TANK

INNER TANK

Page 6: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 6/64

1.EXAMPLES - DOUBLE CONTAINMENT TANKS PER BS 7777

Figure

 Application toLNG Storage Not appropriate.

The BOG rate will be extremelyhigh.

 Appropriate. Appropriate.See Fig.-2.1 for Typical Configuration ofLNG Storage Tank.

See Fig.-2.2 for Typical Configuration forLNG Storage Tank.

: METALLIC PARTS

: THERMAL INSULATION

: CONCRETE

BASE INSULATION

EXTERNAL INSULATION

EXTERNAL WEATHER BARRIER

ROOF

RAFT FOUNDATIONWITH BOTTOM HEATER

INNER TANK

WEATHER

COVER

METAL OUTER TANK SHELL

LOOSE FILL INSULATION

SUSPENDED DECK w/INSULATION

BASE INSULATION

OUTER TANK

INNER TANK

RAFT FOUNDATIONWITH BOTTOM HEATER

PC OUTER TANK WALL

WEATHERCOVER

LOOSE FILL INSULATION

SUSPENDED DECK w/INSULATION

BASE INSULATION

OUTER TANK

INNER TANK

RAFT FOUNDATIONWITH BOTTOM HEATER

RC OUTER TANK WALLWITH EARTH EMBANKMENT

WEATHERCOVER

Page 7: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 7/64

1.EXAMPLES - FULL CONTAINMENT TANKS PER BS 7777

Figure

 Application toLNG Storage  Appropriate.  Appropriate. Appropriate.See Fig.-3.1, 3.2 & 3.3 for Typical Configurationof LNG Storage Tank.

SUSPENDED DECK w/INSULATION

BASE INSULATION

INNER TANK

RAFT FOUNDATIONWITH BOTTOM HEATER

SUSPENDED DECK w/INSULATION

BASE INSULATION

INNER TANK

RAFT FOUNDATIONWITH BOTTOM HEATER

LOOSE FILL INSULATION OR EMPTY

SUSPENDED DECK w/INSULATION

BASE INSULATION

METAL OUTER TANK (ABLE TO CONTAIN LIQUID)

INNER TANK

RAFT FOUNDATIONWITH BOTTOM HEATER

INSULATION ON INSIDE OF OUTER TANK

LOOSE FILL INSULATION OR EMPTY

PC OUTER WALL (ABLE TO CONTAIN LIQUID)

INSULATION ON INSIDE OF OUTER WALL

LOOSE FILL INSULATION OR EMPTY

RC OUTER WALL w/EMBANKMENT

(ABLE TO CONTAIN LIQUID)

INSULATION ON INSIDE OF OUTER WALL

Instead of this wall insulation, secondary

bottom and corner protection made of 9% Ni

steel are provided in the latest design.

: METALLIC PARTS

: THERMAL INSULATION

: CONCRETE

Page 8: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 8/64

1.EXAMPLES - TYPE NOT DEFINED IN BS 7777

 Application toLNG Storage

 Appropriate. Appropriate. Appropriate.

Figure

SUSPENDED DECK w/INSULATION

SS MEMBRANE

ELEVATED OR RAFTFOUNDATION WITH BOTTOMHEATER

PC WALL

INSULATION

BASE INSULATION

RAFT FOUNDATIONWITH BOTTOM HEATER

INSULATION ON INSIDE OF OUTER WALL (PUF)

See Fig.- 4.1 & 4.2 for Typical Configurationof LNG Storage Tank.

Note:The outer tank metal dome is not intended to to becapable of controlled venting of the vapor resulting

from product leakage after a credible event.

METAL OR PC OUTER ROOF

INSULATION

FOUNDATION WITH BOTTOMHEATER

METAL DOME ROOF

INNER TANK

LOOSE FILL INSULATION

PC OUTER WALL (ABLE TO CONTAIN LIQUID)

DOME ROOF OR

SUSPENDED DECK w/INSULATION

SS MEMBRANE

PC WALL w/HEATING SYSTEMMETAL ROOF

 ABOVE GROUND

- MEMBRANE TANK

IN GROUND

- MEMBRANE TANK

PC OUTER WALL TANK

: METALLIC PARTS: THERMAL INSULATION

: CONCRETE

Page 9: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 9/64

1.FIG. OF EACH CONTAINMENT TYPE

INNER TANK

INNER TANK

Single Containment Double Containment Full Containment Others

Single Metal Tank

Double Metal Tank

Dome Roof Inner Tank

Double Metal Tank

w/Suspended Deck

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Page 10: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 10/64

1.FIG. OF EACH CONTAINMENT TYPE

Single Containment

Double Metal Tank

w/Suspended Deck

Single Metal Tank

INNER TANK

Double Metal Tank

Dome Roof Inner Tank

Double Containment Full Containment Others

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Single Containment

Page 11: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 11/64

ESCAPE LADDER

RESILIENT BLANKET

RC SLAB FOUNDATION

9% Ni INNER TANK WALL

 ANNULAR SPACE INSULATION

CS ROOF & STRUCTURE

SUSPENDED DECK

DECK INSULATION

ROOF WALKWAY

PRESSURE & VACUUM RELIEF VALVES

PERIFERAL ROOF WALKWAY

DECK VENT

BOTTOM HEATING SYSTEM9% Ni INNER TANK BOTTOM

INNER LADDER

STAIRCASE

MAIN PLATFORM

CRANE / HOIST FOR IN TANK PUMP

PUMP COLUMN HEAD

PUMP COLUMN

IN TANK PUMP & FOOT VALVE

INNER TANK FOUNDATION RING

COOL DOWN PIPING

BOTTOM INSULATION

Fig. - 1 : SINGLE CONTAINMENT - DOUBLE METAL TANK - TYPICAL

DRYING & PURGING LINE

VENT FOR DOME SPACE

RISER PIPES & SUPPORTS

CS OUTER WALL

BUND WALL

Page 12: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 12/64

CONCRETE SLAB FOUNDATIONFig. - 1.2 : SINGLE CONTAINMENT - DOUBLE METAL TANK - BOTTOM CORNER - TYPICAL

9% Ni INNER TANK WALL

RESILIENT BLANKET

CS OUTER TANK WALL

INNER TANK FOUNDATION RINGCS OUTER TANK BOTTOM

BOTTOM HEATING SYSTEM

9% Ni INNER TANK BOTTOM

FIBERGLASS BLANKET

 ANNULAR SPACE

INSULATION

(PERLITE)

RC SLAB FOUNDATION

SAND OR CONCRETE LEVELING LAYER

CELLULAR GLASS

 ANCHOR STRAP

Page 13: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 13/64

1.FIG. OF EACH CONTAINMENT TYPE

Single Containment

Double Metal Tank

w/Suspended Deck

Single Metal Tank

INNER TANK

Double Metal Tank

Dome Roof Inner Tank

Double Containment Full Containment Others

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Double Containment

Page 14: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 14/64

ESCAPE LADDER

RESILIENT BLANKET

RC SLAB FOUNDATION

9% Ni INNER TANK WALL

 ANNULAR SPACE INSULATION

CS ROOF & STRUCTURE

SUSPENDED DECK

DECK INSULATION

ROOF WALKWAY

PRESSURE & VACUUM RELIEF VALVES

PERIFERAL ROOF WALKWAY

DECK VENT

BOTTOM HEATING SYSTEM9% Ni INNER TANK BOTTOM

INNER LADDER

STAIRCASE

MAIN PLATFORM

CRANE / HOIST FOR IN TANK PUMP

PUMP COLUMN HEAD

PUMP COLUMN

IN TANK PUMP & FOOT VALVE

INNER TANK FOUNDATION RING

COOL DOWN PIPING

BOTTOM INSULATION

Fig. - 2.1 : DOUBLE CONTAINMENT - PC OUTER WALL - TYPICAL

DRYING & PURGING LINE

VENT FOR DOME SPACE

RISER PIPES & SUPPORTS

CS OUTER WALL

CS WEATHER COVER

PC OUTER WALL

Page 15: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 15/64

1.FIG. OF EACH CONTAINMENT TYPE

Single Containment

Double Metal Tank

w/Suspended Deck

Single Metal Tank

INNER TANK

Double Metal Tank

Dome Roof Inner Tank

Double Containment Full Containment Others

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Double Containment

Page 16: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 16/64

RESILIENT BLANKET

RC SLAB FOUNDATION

9% Ni INNER TANK WALL

 ANNULAR SPACE INSULATION

CS ROOF & STRUCTURE

SUSPENDED DECK

DECK INSULATION

ROOF WALKWAY

PRESSURE & VACUUM RELIEF VALVES

PERIFERAL ROOF WALKWAY

DECK VENT

BOTTOM HEATING SYSTEM9% Ni INNER TANK BOTTOM

INNER LADDER

MAIN PLATFORM

CRANE / HOIST FOR IN TANK PUMP

PUMP COLUMN HEAD

PUMP COLUMN

IN TANK PUMP & FOOT VALVE

INNER TANK FOUNDATION RING

COOL DOWN PIPING

BOTTOM INSULATION

Fig. - 2.2 : DOUBLE CONTAINMENT - RC OUTER WALL + EARTH EMBANKMENT - TYPICAL

DRYING & PURGING LINE

VENT FOR DOME SPACE

CS OUTER WALL

CS WEATHER COVER

RC WALL

EARTH EMBANKMENT

PIPE BRIDGE

Page 17: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 17/64

1.FIG. OF EACH CONTAINMENT TYPE

Single Containment

Double Metal Tank

w/Suspended Deck

Single Metal Tank

INNER TANK

Double Metal Tank

Dome Roof Inner Tank

Double Containment Full Containment Others

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Full Containment

Page 18: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 18/64

ESCAPE LADDER

RESILIENT BLANKET

RC SLAB FOUNDATION

9% Ni INNER TANK WALL

 ANNULAR SPACE INSULATION

RC ROOF

CS ROOF LINER & STRUCTURE

SUSPENDED DECK

DECK INSULATION

ROOF WALKWAY

PRESSURE & VACUUM RELIEF VALVES

PERIFERAL ROOF WALKWAY

DECK VENT

BOTTOM HEATING SYSTEM9% Ni INNER TANK BOTTOM

INNER LADDER

STAIRCASE

MAIN PLATFORM

CRANE / HOIST FOR IN TANK PUMP

PUMP COLUMN HEAD

PUMP COLUMN

IN TANK PUMP & FOOT VALVE

9% Ni SECONDARY BOTTOM

9% Ni CORNER PROTECTION

CS WALL VAPOR BARRIER

INNER TANK FOUNDATION RING

CS BOTTOM VAPOR BARRIER

COOL DOWN PIPING

BOTTOM INSULATION

Fig. - 3.1 : FULL CONTAINMENT - PC OUTER WALL TYPICAL

DRYING & PURGING LINE

VENT FOR DOME SPACE

RISER PIPES & SUPPORTS

PC OUTER WALL

Page 19: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 19/64

CELLULAR GLASS

CONCRETE SLAB FOUNDATIONFig. - 3.2 : FULL CONTAINMENT - PC OUTER WALL - BOTTOM CORNER - TYPICAL

PC OUTER WALL

9% Ni CORNER PROTECTION

9% Ni INNER TANK WALL

RESILIENT BLANKET

 ANNULAR SPACE

INSULATION

(PERLITE)

CS WALL VAPOR BARRIER

RC SLAB FOUNDATION

INNER TANK FOUNDATION RING9% Ni SECONDARY BOTTOM

BOTTOM HEATING SYSTEM

SAND OR CONCRETE LEVELING LAYERCELLULAR GLASS

9% Ni INNER TANK BOTTOM

FIBERGLASS BLANKET

FIBERGLASS BLANKET

PC DUCT & TENDON

HORIZONTAL

PC DUCT & TENDON

VERTICAL

Page 20: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 20/64

CS WALL VAPOR BARRIER

CONCRETE SLAB FOUNDATIONFig. - 3.3 : FULL CONTAINMENT - PC OUTER WALL - ROOF CORNER - TYPICAL

RC DOME ROOF

CS ROOF LINER

GLASS CLOTH

PERLITE RETAINING WALL

SUSPENDED DECK

INSULATION

(PERLITE OR FIBERGLASS BLANKET)

 ANNULAR SPACE

INSULATION

(PERLITE)

PC OUTER WALL

PERLITE FILL NOZZLE

SUSPENDED DECK

 ANNULAR SPACE

INSULATION

(PERLITE)

RESILIENT BLANKET

9% NI INNER TANK WALL

CS ROOF STRUCTURE

FIBERGLASS BLANKET

PC DUCT & TENDON

VERTICAL

PC DUCT & TENDON

HORIZONTAL

Page 21: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 21/64

1. FIG. OF EACH CONTAINMENT TYPE

Single Containment

Double Metal Tank

w/Suspended Deck

Single Metal Tank

INNER TANK

Double Metal Tank

Dome Roof Inner Tank

Double Containment Full Containment Others

Metal Outer Wall

PC Outer Wall

RC Outer Wall

+ Earth Embankment

Double Metal Tank

PC Outer Wall Tank

RC Outer Wall

+ Earth Embankment

 Above Ground

- Membrane Tank

In Ground

- Membrane Tank

PC Outer wall Tank

in Japan

Others

Page 22: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 22/64

ESCAPE LADDER

RC SLAB FOUNDATION

WALL INSULATION

RC ROOF

CS ROOF LINER & STRUCTURE

SUSPENDED DECK

DECK INSULATION

ROOF WALKWAY

PRESSURE & VACUUM RELIEF VALVES

PERIFERAL ROOF WALKWAY

DECK VENT

BOTTOM HEATING SYSTEM

INNER LADDER

STAIRCASE

MAIN PLATFORM

CRANE / HOIST FOR IN TANK PUMP

PUMP COLUMN HEAD

PUMP COLUMN

IN TANK PUMP & FOOT VALVE STAINLESS BOTTOM MEMBRANE

WALL MOISTURE BARRIER

BOTTOM MOISTURE BARRIER

COOL DOWN PIPING

BOTTOM INSULATION

Fig. - 4.1 : MEMBRANE TANK : ABOVE GROUND - TYPICAL

DRYING & PURGING LINE

VENT FOR DOME SPACE

RISER PIPES & SUPPORTS

PC OUTER WALL

STAINLESS WALL BEMBRANE

Page 23: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 23/64

Fig. - 4.2 : MEMBRANE TANK - CONTAINMENT SYSTEM BOTTOM / WALL - TYPICAL

 ANGLE PIECE (MEMBRANE)

CORNER PLATE (MEMBRANE)

WALL MEMBRANE

BOTTOM MEMBRANE

PLYWOOD

INSULATION PANEL

CONCRETE TANK WALL

MOISTURE BARRIER

BONDIND MASTIC

CONCRETE SLAB FOUNDATION

MEMBRANE ANCHOR

Page 24: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 24/64

1.COMPARISON OF EACH CONTAINMENT TYPE (1/2)DEFINITION OF CONTAINMENT TYPE PER BS 7777

Type of Tank Single Containment Double Containment Full Containment

1. Cost (*1)

2. Erection Schedule(*1,*2)

3. Resistance Against Abnormal Condition

(1) Thermal Radiation of Fire

(2) Blast Wave

(3) Flying Projectiles

4. Site Area Required

5. Inner Tank Geo. Capacity Range (m3)

100% *3

100% (Min. 25 months)

Good

Limited

Limited

Large

8,000~ 170,000

 Approx. 160 Tanks

Indonesia : 127,000m3 x 1 Tanks

 Abu Dhabi : 150,000m3 x 2 Tanks

-

150%

125% (Approx. 32 months)

Excellent

Good : WallRoof : Limited

Good : Wall

Roof : Limited

Small

85,000

 Appreox. 10 Tanks

-

-

180%

140% (Approx. 35 months)

Excellent

Excellent

Excellent

Small

55,000~176,000

 Approx. 50 Tanks

Oman : 146,000m3 x 2 Tanks

Qatar : 94,000m3 x 4 Tanks

Qatar : 152,000m3 x 2 Tanks

Sakhalin : 120,000m3 x 2 Tanks

Note :*1 : International Contractor base and for the tank having geometric capacity 100,000m 3 and over.*2 : Excluding connection of the pipe, purge and cooldown.

*3 : Excluding cost of bund wall.

6. Number of Tanks Ever Built

in the World as of July 2003.

7. Tanks Ever Built by CHIYODAas of July 2003.

8.Tanks Under Construction /

Engineering by CHIYODA

as of July 2003.

Page 25: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 25/64

1. COMPARISON OF EACH CONTAINMENT TYPE (2/2)CONTAINMENT TYPE NOT DEFINED IN BS 7777

Type of Tank Membrane - Above & In-ground PC Outer Wall LNG Tank in Japan

1. Cost

2. Erection Schedule)

3. Resistance Against Abnormal Condition

(1) Thermal Radiation of Fire

(2) Blast Wave

(3) Flying Projectiles

4. Site Area Required

5. Inner Tank Geo. Capacity Range (m3)

-

 Approx. 5 to 6 Years

Good

Good : WallRoof Limited

Good : Wall

Roof : Limited

Small

35,000~ 203,000

 Approx. 70 Tanks

-

-

-

 Approx. 4 Years

Excellent

Good : WallRoof : Limited

Good : Wall

Roof : Limited

Small

36,000 ~ 189,000

5 Tanks

-

1 Tank for MZL Project

6. Number of Tanks Ever Built

in the World as of July 2003.

7. Tanks Ever Built by CHIYODA

as of July 2003.

8.Tanks Under Construction /

Engineering by CHIYODA

as of July 2003.

Page 26: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 26/64

5. MATERIAL SELECTION FOR THE LNG CONTAINER

The material for the LNG container for the large capacity of LNG storage is 9% Ni steel in consideration of thedesign of -161 ~ -168 oC of the design temperature of LNG as shown in the following sheet “TEMPERATURE RANGE FOR MATERIAL OF CRYOGENIC STORAGE TANKS”. 

In principle, stainless steel type 304 is used for the tank having small capacity and in case that the use of9% Ni steel is not economical.

The stainless steel type 304 is also used for the membrane of in-ground and above ground tank.

Page 27: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 27/64

6. TANK SIZING (1/6)

4. TOP DEADWOOD

    1 .

    G    E    O

    M    E    T    R    I    C    C    A    P    A    C    I    T    Y

    2 .

    N    E    T

    W    O    R    K    I    N    G    C    A    P    A    C    I    T    Y

5. BOTTOM DEAD WOOD

    3 .

    S    T    O    R    A    G    E    C    A    P    A    C    I    T    Y

DEFINITION OF CAPACITY OF CYLINDRICAL TANK DESIGNED AT AMBIENT TEMPERATURE

1. GEOMETRIC CAPACITY :

(Inside Diameter)2 x π / 4 x Height 

2. NET WORKING CAPACITY“Geometric Capacity” - “Top Deadwood” - “Bottom Deadwood” 

3. STORAGE CAPACITY

Total Volume of Liquid Stored

“Geometric Capacity” - “Top Deadwood”

4. TOP DEADWOOD

Top space for safety to avoid over-fill and spillage due to sloshing

wave by earthquake.5. BOTTOM DEAD WOOD

Volume not possible to withdraw due to nozzle height, pump

NPSHR, etc

Page 28: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 28/64

6. TANK SIZING (2/6)

SPECIAL CONSIDERATION TO BE TAKEN FOR THE CAPACITY OF CYLINDRICAL TANK AT CRYOGENIC TEMPERATURE

The reducing of the tank size due to the contraction at design temperature as show in the following Fig.

shall be considered to maintain net working capacity required at design temperature.

 At Ambient Temperature 

Typical calculation for the net working capacity of LNG storage tank is shown in the following pages.

 At Design Temperature 

Page 29: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 29/64

6. TANK SIZING (3/6)

TYPICAL CALCULATION OF TANK CAPACITY OF LNG STORAGE TANK AT MINIMUM DESIGN TEMPERATURE

Basic Design Parameters

Item UNIT Value

Tank Material - 9% Ni Steel

 Ambient Temperature [oC] 38 Maximum Design Temperature

Design Temperature [oC] -167 Minimum Design Temperature

Temp. Diff. [oC] 205

Thermal Expantion Coeff. [/oC] 9.4E-06 For 9% Ni Steel

Inner Tank Capacity Check

 AT AMBIENT AT MINIMUM DESIGN

Item Unit TEMPERATURE TEMPERATURE Remarks

(CONSTRUCTION PHASE) (UNDER OPERATION

Inside Diameter [m] 63.300 63.178

Height [m] 30.000 29.942

Height of Top Deadwood [m] 0.500 0.500 Height to be kept at Min. Design Temp.

Height of Bottom Dead Wood [m] 2.300 2.300 Height to be kept at Min. Design Temp.

Contraction at Minimum Design Temperature

  Inside Diameter [mm] - -122.0

  Height [mm] - -57.8

Capacity

  Net Working Capacity Required [m3] 85,000 85,000

  Geometric Capacity [m3] 94,410 93,865 See Note 1.

  Net Working Capacity [m3] 85,599 85,088 See Note 2

  Top Deadwood [m3] 1,574 1,567

  Bottom Dead Wood [m3] 7,238 7,210

Note:

1. Normally the geometric capacity at ambient temp. is used to specify the geometric capacity of the tank.

2. The calculated net working capacity at minimum design temp. shall not be less than the net working capacity required.

  The calculated net working shall include margin for the displacement of internal accessories.

Remarks

Page 30: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 30/64

6. TANK SIZING (4/6)

NPSHR (@Rated Capacity) of

Submerged Pumps

Margin

Pumpable Minimum LNG

Level at Minimum Flow Rate

Top of Inner Tank Shell at Minimum Design Temperature

Maximum Design LNG Level (HLL)

Minimum Design LNG Level (LLL)

Net Working Capacity

Top Deadwood:

1,000 mm or Sloshing Height + 1 ft Liquid Run-

up whichever Larger.

Top of Inner Tank She ll at Ambient Temperature (Construction Phase)

Bottom

Deadwood

Minimum 150 mm at operation position ofthe foot valve.

Top of Inner Tank Bottom

Pump Well

Foot Valve

Submerged Pump

Inner Tank Inside Diameter at Design Temperature

Inner Tank Inside Diameter at Ambient Temperature (Construction Phase)

    I   n   n   e   r    T

   a   n

    k    H   e

    i   g    h    t   a

    t    D   e   s

    i   g   n

    T   e   m   p   e   r   a

    t   u   r   e

    I   n   n   e   r    T

   a   n

    k    H   e

    i   g    h    t   a

    t    A   m

    b    i   e   n

    t    T   e   m   p   e   r   a

    t   u   r   e

     (    C   o   n   s

    t   r   u   c

    t    i   o   n

    P    h   a   s   e

    )

TYPICAL CALCULATION OF TANK CAPACITY OF LNG STORAGE TANK AT MINIMUM DESIGN TEMPERATURE

Page 31: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 31/64

6. TANK SIZING (5/6)

OTHER RESTRICTIONS & LIMITATIONS TO BE CONSIDERED FOR THE INNER TANK SIZING (1/2)

1. Ratio of HLL/D (High Liquid Level / Tank Inside Diameter)The ratio of HLL/D shall be thoroughly decided in consideration of stability of the inner tank at seismic

condition to determine the necessity of the anchorage on the inner tank that are preferably to be eliminated

to avoid penetrations into the tank foundation slab.

2. Limit of the Inner Tank Height

(1) Soil Conditions

Survey of the inner tank height limit due to soil conditions shall be thoroughly performed based on thesoil investigation report and preliminary tank foundation design including implementation of the soil

improvement and/or piling shall also be performed simultaneously.

(2) Insulation Material Strength

Limitation of the inner tank height due to the allowable strength of bottom insulation material including

safety factor and seismic load on the inner tank bottom. The inner tank height may be increased up

to 40 m in consideration of design safety factor and allowable compressive load for the insulationmaterial (cellular glass) and bottom pressure due to earthquake.

Page 32: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 32/64

6. TANK SIZING (6/6)

OTHER RESTRICTIONS & LIMITATIONS TO BE CONSIDERED FOR THE INNER TANK SIZING (2/2)

3. Limit of the 9% Ni. Steel Shell ThicknessThe maximum inner tank sizes subject to the maximum shall plate thickness permitted are as follows:

BS 7777 : 40 mm (Type V improved 9% Ni steel)*

 API 620 /ASTM A553 : 50.8 (2 in.) per ASTM A 553**

* : When material thickness are required in excess of the value,, additional requirements to maintain the

same level of safety are to be agreed between purchaser and manufacturer.

**: The maximum thickness of plates is limited only by the capacity of the material to meet the specified

mechanical property requirements; however, current mill practice normally limits this material to 2 in. max.

Page 33: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 33/64

Rev.

LNG STORAGE TANK DATA SHEET

Owner  : A COMPANY

Project Title : X PROJECT

Location : -

CHIYODA Job No. : XXXXXX

Consortium Doc. No. :

CHIYODA Doc. No. :

 Abbreviation :

  Tank No. : T-0001, & T-0002 TBD = To be determined/verified by Subcontractor 

  Service : LNG Required Nos. : 2 tanks

1. Design Code  API STD 620 9TH ED ADDENDUM 3 , APPENDIX Q for Inner Tank Design

2. BS 7777 Part 3 as guidance for Outer Tank Design

3. Design Condition INNER TANK OUTER TANK

4. Type of Foundation --- Stone Column

5. Type of Roof Suspended Deck Dome

6. Type of Bottom Flat ---

7. Min. Working Capacity 140,000 m3 See Note 1. ---

8. Tank Diameter (I.D) 76,000 mm TBD 78,000 mm TBD

9. Tank Height 35,300 mm TBD 39,000 mm TBD

10. Design Pressure --- +290 mbarg / -5 mbarg

11. Max .Design Liquid Level 34,700 mm TBD ---

12. Hydrotest Water Level 21,000 mm TBD ---

13. Operating Pressure --- From +80 mbarg to +240 mbarg

14. Design Temperature -1650

C 38.50

C15. Operating T emperature (Later) 0C --- 0C

16. Design Amb. Temp.(Max./Min.) --- 38.5 0C / 6 0C

17. Design Spec. Gravity 483 kg/m3 ---

18. Corrosion Allowance 0 mm 0 mm

19. Filling Rate 11,500 m3/h ---

20. Emptying Rate 1,707 m3/h ---

21. Design Wind Velocity --- See sheet 2 of 4.

22. Snow Load None None

23. Seismic Load See sheet 2 of 4. See sheet 2 of 4.

24.

25. TANK MATERIAL

26. Wall 9 % Ni Steel Prestressed Concrete (PC)

27. Bottom 9 % Ni Steel Reinforced Concrete (RC)

28.  Annular Bottom 9 % Ni Steel ---

29. Roof Plate/Structure --- C.S + Reinforced Concrete (RC)

30. Suspended Deck Aluminum Alloy or equivalent. ---

31. Wall Vapor Barrier --- C.S

32. Bottom Vapor Barrier --- C.S

33. Secondary Bottom --- 9 % Ni Steel34. Corner Protection --- 9 % Ni Steel

35. Nozzle Neck/Internal Piping 304 SS See Note 2. CS

36. Nozzle Flange 304 SS CS

37. Flange/Bolting 304 SS CS

38. PAINTING

39. Temporary Rust Prevention Yes. See Specification.

40. Permanent

41.  E xternal See Specification.

42. Wall --- Bituminous coats See Note 5.

43. Roof --- ---

44. Underside of Bottom --- ---

45.  Appurtenances --- Yes See Note 3 & 4.

46.  Internal --- ---

47. Notes :

48. 1. At design temperature. See Appendix-3.

49. 2. Alternatively 9% Ni Steel for Pump Columns.

50. 3. Stainless steel bolt and nut such as type 304 and 316 except those of type 316L shall be coated.

51. 4. Including metallic surface for materials of stainless steel, carbon steel, galvanized steel except insulated surface.

52. 5. Side face of buried bottom slab only.

Sheet 1 of 4

 ALL RIGHTS RESERVED. THIS DOCUMENT AND ANY DATA AND INFORMATION CONTAINEDTHEREIN ARE CONFIDENTIAL AND THE PROPERTY OF CHIYODA CORPORATION (CHIYODA) AND

THE COPYRIGHT THEREIN IS VESTED IN CHIYODA. NO PART OF THIS DOCUMENT, DATA, OR

INFORMATION SHALL BE DISCLOSED TO OTHERS OR REPRODUCED IN ANY MANNER OR USED

  , .

7. DESIGN PARAMETERS & REQUIREMENTS (1/5)

Requirements Apply to the Inner Tank

Requirements Apply to the Outer Tank

Design Code Requirements

Basic Design Data

- Minimum Working

Capacity

- Tank Size- Hydrotest Water Level

- Internal Pressure, etc.

Material Requirements

Painting & Coating

Requirements

Page 34: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 34/64

7. DESIGN PARAMETERS & REQUIREMENTS (2/5)

Seismic Design Condition

Wind Velocity & Pressure

Design Against Flying Object

Design of Spill Protection

Design Against Heat Radiation

Design Against Blast Wave

OBE : Operating Basis Earthquake

SSE : Safety Shutdown Earthquake

See next sheet for detail per NFPA 59A.

Page 35: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 35/64

7. DESIGN PARAMETERS & REQUIREMENTS (3/5)

OBE ( Operating Basis Earthquake ) and SSE (Safety Shutdown Earthquake) per NFPA 59A

OBE (Operating Basis Earthquake):

The LNG container shall be designed to remain operable during and after an OBE.

SSE (Safety Shutdown Earthquake):

Similarly, the design shall be such that during and after an SSE there shall be no loss of containment

capability, and it shall be possible to isolate and maintain the LNG container.

 After the SSE event, the container shall be emptied and inspected prior to resumption of container-

filling operation

Page 36: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 36/64

7. DESIGN PARAMETERS & REQUIREMENTS (4/5)

Pump Column Design Data

BOG Requirements

BOG Performance Test

Requirements

Rev.

LNG STORAGE TANK DATA SHEET

Owner  : A COMPANY

Project Title : X PROJECT

Location : -

CTCI Job No.

CHIYODA Job No. : XXXXXX

Consortium Doc. No. :

CHIYODA Doc. No. :

 Abbreviation :

  Tank No. : T-0001, & T-0002 TBD = To be determined/verified by Subcontractor 

  Service : LNG Required Nos. : 2 tanks

1. PUMP COLUMN DESIGN DATA (See Note 1.)

2. - Quantity Nor mal opera tion : 2 sets, Spare : 1 set for one tan k

3. - Column Diameter 34"

4. - Design Flow Rate 569 m3/hr pump

5. - Design Pressure 15.0 barg

6. - F oot Valve Required (Supplied by Contractor)

7. - Filter Box Required.

8. - Weight of Pump 2,500 kg / one pump (maximum load to be lifted by hoist /crane)

9. - Weight of Foot Valve 1,300 kg / one foot valve

10. BOG RATE

11. - Ma xi mu m BO G R at e 0 .0 75 vo l. % p er da y

12. - Design Condition LNG latent heat of : 122 kcal/kg

13.  pure methane

14. Normal Internal pressure : 240 mbarg15. LNG temperature : -165℃

16.  Ambient temperature : 38.5 ℃

17. Solar radiation : Roof : 48 ℃ / Shell : 43 ℃

18.  equilibrium temperature (Minimum)

19. Liquid density of : 423 kg/m3

20.  pure methane

21. L iq ui d l ev el : Ma xi mu m a ll ow ab le li qu id le ve l ( Se e A pp en di x- 3.)

22. Wind speed : None

23. Relative Humidity : 93% average

24. Tank Condition : Stable

25.

26. BOG PERFORMANCE GUARANTEE TEST

27. - Test Required for each tank.

28. - Guarantee BOG Rate BOG rate (0.075 vol.% per day) shall be guaranteed under the following conditions:

29. - An ambient temperature of 30.0 ℃

30. - High liquid level

31. - Stable condition

32. - LNG tank normal operating pressure

33. - Constant barometric pressure

34. - No ship loading35. - No cold circulation

36. - No gas send-out

37. - Test Method BOG rate guarantee test shal l be done after heat stable condit ion is attained

38. under the constant pressure with no unloading, no cold circulation, and no

39. LNG send-out conditions. After confirmation of the tank conditions mentioned

40. in the "Guarantee BOG Rate", BOG rate measurement shall be carried out.

41. BOG rate shall be measured by the flow instrument with temperature and pressure

42. compensation which will be installed on BOG line from LNG tank.

44. The flow instrument will be provided by Contractor.

45. Storage tank concrete surface temperatures and bottom temperatures shall be measured

46. during the performance test.

47. The test result shall be corrected in consideration of the following factors:

48. - Barometric pressure change

49. - The difference between estimated heat ingress, which will be derived from

50.   the tank surface temperatures, bottom temperatures and other measured

51.   values during performance test and design heat ingress at the guarantee

52.  c onditions specified above.

53.

Sheet 3 of 4

 ALL RIGHTS RESERVED. THIS DOCUMENT AND ANY DATA AND INFORMATION CONTAINED

THEREIN ARE CONFIDENTIAL AND THE PROPERTY OF CHIYODA CORPORATION (CHIYODA) AND

  . , ,

, .

Page 37: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 37/64

7. DESIGN PARAMETERS & REQUIREMENTS (5/5)

Tank Appurtenances

Rev.

LNG STORAGE TANK DATA SHEET

ACCESSORY LIST OF REFRIGERATED STORAGE TANKOwner  : A COMPANY

Project Title : X PROJECT

Location : -

CTCI Job No.

CHIYODA Job No. : XXXXXXConsortium Doc. No. :

CHIYODA Doc. No. :

 Abbreviation :

  Tank No. : T-0001, & T-0002 TBD = To be determined/verified by Subcontractor 

  Service : LNG Required Nos. : 2 tanks

1.

2. Item Q'ty-Size Remarks Item Q'ty-Size Remarks

3.  Skin Temp Detector per P&ID For shell plate Roof Circumferential All around

4.   f or cooldown per P&ID For bottom plate Walkway

5. Stairway

6.  Inner Ladder along pump 1 Top Platform

7.   column with cage & PSV Platform

8.   i ntermediate landings VRV Platform

9.  Platform/ladder below roof 2 Emergency ladder w/cage Opposite side of  

10.   manway & platform stairway

11.  Deck Walkway 1 Lift

12.  Annular Space Monorail (TBD) External Monorail for  

13.  Wall Maintenance

14.  Deck Manhole 2

15.  Deck Vent Yes (TBD) PRV

16. VRV

17.  Deck Support Yes (TBD) Nozzle and Manholes Per Appendix-2.

18. Monorail/Hoist or Crane For intank pump.

19.  Pipe Supports Yes Pipe Support

20.  Internal Piping Yes

21. Pressure Gage

22.  Anchor Strap (TBD) Pressure Transmitter  

23.  Earth lugs Yes Tank Gage with Transmitter Capacitance type

24.  Grounding Yes To be connected to Tank Gage with Transmitter Radar type

25.  the outer tank Temperature Element Multi element

26. Instruments for Piping

27.  Leak Detection System

28.   Annular Space Horizontal 32 Incl. 16 spares Lighting

29.   Annular Space Vertical 2 Lightning Protection

30. Grounding

31. Junction Box Including

32.   Support & Foundation

33. Cable Tray/Support

34. Settlement Measur't System

35.  Bottom Heating Sys tem Yes See Data Sheet. Process Piping

36.   and Temperature Sensor Utility piping

37. Valves for Piping

38.   Settlement Measurem't Clip 12 Periphery Pressure Rel ief Valve

39.  Settlement Measurem't Yes Inclinometer for for Piping

40.   S ys tem f or Fo un d' n S la b c on st ru ct io n u se o nl y S pe ct ac le B li nd s

41.   for Piping

42. Fire Protection System See Note 1.

43. Spill Protection

44. Cathodic Protection

45. Pump Column Head See Note 4.

46.   Plate Stand

47. Temporary Pot for Intank See Note 4.

48.   Pump

49. Note :

50. 1. The following fire protection shall be provided per Appendix-8.

51. -1. Water spray system

52. -2. Fire extinguishing system for PRV tail pipe.

53. -3. Gas detectors for flange connections of LNG lines larger than 2" on roof main platform

54. -4. To be located on the top platform.

55.

Yes

Yes

1

1

1

Yes (TBD)

Yes

Yes

No

2

1

Yes

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

TANK FOUNDATION

Yes

Yes

Yes

Yes

Yes

Yes

Yes

INNER TANK OUTER TANK

Yes

Yes

Yes

No

1

1

1

Sheet 4 of 4

 ALL RIGHTS RESERVED. THIS DOCUMENT AND ANY DATA AND INFORMATION CONTAINEDTHEREIN ARE CONFIDENTIAL AND THE PROPERTY OF CHIYODA CORPORATION (CHIYODA) AND

THE COPYRIGHT THEREIN IS VESTED IN CHIYODA. NO PART OF THIS DOCUMENT, DATA, OR

INFORMATION SHALL BE DISCLOSED TO OTHERS OR REPRODUCED IN ANY MANNER OR USED

  , .

8 FILING AND WITHDRAWAL OF LNG (1/2)

Page 38: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 38/64

8. FILING AND WITHDRAWAL OF LNG (1/2)

Recently in-tank (submerged) pumps and pump columns are provided with not only full containment tanks but also singlecontainment tanks instead of wall and bottom connections and penetrations as shown below, since the leakage of LNG to theatmosphere can be minimized by avoiding all connections and penetrations on the tank below the maximum LNG level

Conventional Design with Penetrations below the LNG Level

Since all stored LNG above the wall penetration will be flown out to the atmosphere when the leakage of LNG occurs from the

potential leak sources shown in the above, BS 7777 requires to provide emergency remote control and/or automatic fail safe

shut-off valves as shown in the above.

Emergency remote control

and/or automatic fail safe

shut off valve

LNG

Relatively vulnerable points (Potential leak source).

LNG

Relatively vulnerable points (Potential leak source).

Emergency remote control

and/or automatic fail safe

shut off valve

LNG

Relatively vulnerable points (Potential leak source).

8 FILLING & WITHDRAWAL OF LNG (2/2)

Page 39: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 39/64

8. FILLING & WITHDRAWAL OF LNG (2/2)USING OF SUBMERGED PUMPS & PUMP WELL (OVER-THE -TOP FILLING & WITHDRAWAL)

FROM

LIQUEFICATION

PLANT AND/OR

LOADING FACILITIES

FILLING LINE WITH INTERNAL

PIPING DOWN TO BOTTOM

FILLING LINE WITH

BAFFLE PLATE

POWER SUPPLY TO SUBMERGED PUMP

PUMP COLUMN

SUBMERGED PUMP & FOOT VALVE

TO VAPORIZATION,

SEND-OUT PLANT

 AND/OR

LOADING FACILITIES

9 MAJOR SAFETY DEVICES FOR LNG TANK

Page 40: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 40/64

9. MAJOR SAFETY DEVICES FOR LNG TANK

Rollover Protection

Overfill Protection

VACUUM RELIEF VALVE (VRV) Protection against excessive vacuum

Protection against excessive pressure

Tail pipe fire protection

(Dry Chemical CO2, N2 Injection, etc.)

SPILL PROTECTION

TANK GAUGE SYSTEMWITH DENSITY MEASUREMENT

LNG spill correction & protection of roof

SLAB HEATING SYSTEM

GAS DETECTOR

FIRE DETECTOR

HIGH LIQUID LEVEL ALARM

PRESSURE RELIEF VALVE (PRV)

FIRE EXTINGUISHER FOR PRV

TAIL PIPE

WATER SPRAY SYSTEM

TEMPERATURE SENSOR

Protection against the frost of soil

Protection against adjacent fire

LNG leak & fire detection

LNG leak detection

Page 41: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 41/64

10. DESIGN OF DOUBLE METAL TANK

The typical basic concepts for design of double metal refrigerated tank is shown in the following pages.

(1) Double Metal Wall Tank Design - Suspended Deck - Typical

(2) Double Metal Wall Tank Design - Double Dome Roof - Typical

(1) DOUBLE METAL WALL TANK DESIGN SUSUPENDED DECK TYPICAL

Page 42: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 42/64

(1) DOUBLE METAL WALL TANK DESIGN - SUSUPENDED DECK - TYPICAL

Earthquake

Wind

Blast Wave

Heat Radiation from

Adjacent Fire

Heat Radiation from PRV

Tail Pipe Fire

Outer Tank Roof, Live

Load, Roof Accessories

& Suspended

Deck/Insulation

Insulation & Live Load

Pressure due to Earthquake

Product

Load exerted by Perlite

Load exerted by Perlite

Product*

Internal Pressure

Internal Vacuum

Internal Vacuum

Inner Tank Shell, Insulation (Resilient Blanket) and Accessories.Load due to moment caused by Earthquake.

Flying Object

Outer Tank Roof, Suspended Deck, Shell, Insulation (PUF) and Accessories.Load due to moment caused by Wind or Earthquake.

Hydrotest Water

Inner Tank Anchor

Outer Tank Anchor

Base Share Due to Earthquake

Overturning Moment Due to

Earthquake or Wind

Hydrotest Water*

Internal Pressure

Hydrotest Water*

Product* & Annular Space

Insulation

*: If outer tank to be designed to store productand to be hydrostatic tested.

Up Lift due to Earthquake

Overturning Moment.

Up Lift due to Internal

Pressure, Wind/Earthquake

Overturning Moment.

Factor such as solar radiation, ambient

temp. and subsoil temp. etc. for BOG &

insulation design are not shown.

(2) DOUBLE METAL WALL TANK DESIGN DOUBLE DOME ROOF TYPICAL

Page 43: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 43/64

(2) DOUBLE METAL WALL TANK DESIGN - DOUBLE DOME ROOF - TYPICAL

Earthquake

Wind

Blast Wave

Heat Radiation from

Adjacent Fire

Heat Radiation from PRV

Tail Pipe Fire

Outer Tank Roof,

Live Load, Roof

Accessories

Pressure due to Earthquake

Product

Load exerted by Perlite

Load exerted by Perlite

Product*

Internal Pressure

Internal Vacuum

Internal Vacuum

Inner Tank Shell, Insulation (Resilient Blanket) and Accessories.Load due to moment caused by Earthquake.

Flying Object

Outer Tank Roof, Suspended Deck, Shell, Insulation (PUF) and Accessories.Load due to moment caused by Wind or Earthquake.

Hydrotest Water

Inner Tank Anchor

Outer Tank Anchor

Base Share Due to Earthquake

Overturning Moment Due to

Earthquake or Wind

Hydrotest Water*

Internal Pressure

Hydrotest Water*

Product* & Annular Space

Insulation

Up Lift due to Internal

Pressure, Earthquake

Overturning Moment.

Up Lift due to Internal

Pressure, Wind/Earthquake

Overturning Moment.

Internal Pressure

Factor such as solar radiation, ambient

temp. and subsoil temp. etc. for BOG &

insulation design are not shown.

Internal Vacuum,

Insulation, Live

Load

*: If outer tank to be designed to store productand to be hydrostatic tested.

11 ROLLOVER PROTECTION (1/4)

Page 44: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 44/64

11. ROLLOVER PROTECTION (1/4)

1. What is Rollover?

Since the LNG stored in the refrigerated tank is naturally mixed by the convection at top surface due to the boiling off

of LNG as shown in the following fig., the rollover will not occur unless receiving LNG having different density into

same tank especially receiving heavier density of LNG into bottom level of the tank or leaving the stored LNG long time.

LNG

LNG VAPORVAPORIZING LIGHT PARTS

OF LNG

NORMAL CONDITION IN THE LNG OF EVEN DENSITY

HEAVIER LNG WILL GO DOWN

TO THE BOTTOM (CONVECTION)

LNG VAPOR

NATURAL MIXING

BY CONVECTION

11 ROLLOVER PROTECTION (2/4)

Page 45: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 45/64

11. ROLLOVER PROTECTION (2/4)

In consequence of the operation that receiving different density LNG into same tank especially receiving heavier

density of LNG into bottom level of the tank or leaving stored LNG long time without mixing and/or circulation;

(1) Light parts of LNG at upper layer will boil off due to heat transfer from the lower layer to upper layer of LNG(2) Density of upper layer will be heavier gradually due to the vaporization of light parts of LNG

(1) (2)

LNG VAPOR

HEAT TRANSFER

BOILING OFF OF LNG

LNG VAPOR

HEAT TRANSFER

BOILING OFF OF LNG

11 ROLLOVER PROTECTION (3/4)

Page 46: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 46/64

11. ROLLOVER PROTECTION (3/4)

(3) In case that the density of upper LNG layer become equal to or more that that of lower layer, the boiling off

of LNG stored at lower layer will occur due to the rollover suddenly

(4) The excessive boil-off gas caused by the rollover energy will be danger of damage the storage tank

LNG VAPOR

(3) (4)

EXCESSIVE LNG VAPOR

ROLL OVER OF LNG

BOILING OFF OF LNG

11 ROLLOVER PROTECTION (4/4)

Page 47: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 47/64

11. ROLLOVER PROTECTION (4/4)

2. How to Protect Rollover

(1) Measurement of Density of LNG Stored at Every Level

To detect the phenomena of stratiform of LNG having different density, the LNG tank shall be equipped with the level

gauging systems that are able to measure the density of LNG stored at any level of LNG.(2) To avoid the stratiform of LNG, the following counter measure(operation) shall be taken.

- Restriction of the receiving of LNG having different density into same tank

- *Mixing of LNG stored using of jet nozzle

- *Receiving of heavier LNG from top part of the tank and lighter LNG from bottom part of the tank

- *Circulation of LNG stored to mix lower layer and top layer

*: See Fig. below.

FROM

LIQUEFACTION

PLANT AND/OR

LOADING FACILITIES

Receiving of heavier LNG from

top part of the tank

PUMP COLUMN

SUBMERGED PUMP

TO VAPORIZATION,SEND-OUT PLANT

 AND/OR

LOADING FACILITIES

Mixing of LNG stored using jet nozzle

Receiving of lighter LNG from

bottom part of the tank

Circulation of LNG stored to mix

lower layer and top layer

12 BASIC DESIGN CONCEPT OF PC (PRE-STRESSED CONCRETE) (1/2)

Page 48: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 48/64

12. BASIC DESIGN CONCEPT OF PC (PRE-STRESSED CONCRETE) (1/2)

1. General

The concept of LNG storage tank for Full Containment Type is that the outer tank is intended to be capable both of

containing LNG and controlled venting of the vapor resulting from product leakage after a credible event. The pre-stressed

concrete outer tank wall instead of the RC (Reinforced Concrete) outer tank wall with the earth embankment is introduced

in 1990th to minimize tank area and construction cost.

The Pre-Stressing Concrete is common design technology and generally used for construction of superstructures such asbridges, etc.

2. Concept of Pre-stressing

The outer tank wall (reinforced concrete) is reinforced by by the Pre-stress Tendon against internal pressure as shown

in the following model.

DUCT

 ANCHOR

PRE-STRESSING

TENDON

PRE-STRESSING ON

TENDONREINFORCED

CONCRETE OUTER

WALL

BUTTRESS

HORIZONTAL

PRE-STRESSING

ON OUTER WALL

VERTICAL

PRE-STRESSING ON

TENDON

DUCT

PRE-STRESSING

ON OUTER WALL

PRE-STRESSING

ON OUTER WALL

TOP OF

PC WALL

PRE-STRESSING

TENDON

12 BASIC DESIGN CONCEPT OF PC (PRE-STRESSED CONCRETE) (2/2)

Page 49: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 49/64

12. BASIC DESIGN CONCEPT OF PC (PRE-STRESSED CONCRETE) (2/2)

3. Design Concept of Pre-stressed Concrete Outer Tank Wall

(1) Permeation of LNG Vapor

For the above corner protection, the carbon steel liner is used to provide and impervious barrier against permeation by

LNG vapor at the normal operation condition. Since the carbon steel liner is not intended to contain LNG leakage from

the inner tank, in principle, the PC outer wall shall be designed considering that the width of a crack on PC wall shall

not be more than 0.2 mm in case of LNG leakage.

Because of ice formation in pores the permeability is reduced at minimum design temperature of LNG as compared

to normal temperature and it is planned to utilize this self-blocking effect.

(2) Residual Compressive Stress

In addition to the aforesaid allowable crack width on the PC outer wall, the residual compressive stress zone shall be

15% of wall thickness, but not less than 80mm in case of LNG leakage as shown in the following fig.

The value of the minimum residual compression stress to be with discussed and agreed by the client for the project.

    O    U    T    S    I    D    E

LNG LEAK LEVEL

“T”: THICKNESS OF PC OUTER WALL 

RESIDUAL COMPRESSION STRESS ZONE

“T” X 0.15 OR 80 mm WHICHEVER LARGER 

PC OUTER WALL

    I    N    S    I    D    E

Page 50: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 50/64

2.Basic Design Data of Low Temperature

Page 51: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 51/64

3.1 Applicable Code

3 1 APPLICABLE DESIGN CODES & STANDARDS (1/9)

Page 52: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 52/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (1/9)

DOMESTIC (IN JAPAN) 

高圧ガス保安法 (High Press. Gas Control Low)

LNG地 式貯槽指針 

高圧ガス保安法(High Press. Gas Control Low)

LNG地 式貯槽指針

 

消防法

 

プラント 

安全規準

 

その他関連 

法規・規準

 

BS 7777 

OVERSEAS 

EEMUA 147 

EN 1473 

API Std 620 

Europe  USA 

NFPA 59A NFPA 15 

3 1 APPLICABLE DESIGN CODES & STANDARDS (2/9)

Page 53: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 53/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (2/9)

BS 7777 

OVERSEAS 

EEMUA 147 

EN 1473 

API Std 620 

Europe  USA 

NFPA 59A NFPA 15 

BS 7777 

3 1 APPLICABLE DESIGN CODES & STANDARDS (3/9)

Page 54: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 54/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (3/9)

Design Codes &

StandardsDescription Notes

BS 7777  British Standard 7777 

Flat-bottomed, vertical, cylindrical storage tanks for low temperatureservice

Consists of:

Part -1:

Guide to the general provisions applying for design, construction,

installation and operation

Part-2:

Specification for the design and construction of single, double and full

containment metal tanks for storage of liquefied gas at temperature

down to -165 oC

Part 3:

Recommendations for the design and construction of prestressedand reinforced concrete tanks and tank foundations, and the design

andb installation of tank insulation, tank liners and tank coatings

Part-4:

Specification for the design and construction of single containment

tanks for the storage of liquid oxygen, liquid nitrogen or liquid argon

Including definition of single, double

and full containment & prestressedouter tank design requirements inpart 3.

3 1 APPLICABLE DESIGN CODES & STANDARDS (4/9)

Page 55: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 55/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (4/9)

BS 7777 

OVERSEAS 

EEMUA 147 

EN 1473 

API Std 620 

Europe  USA 

NFPA 59A NFPA 15 

EEMUA 147 

EN 1473 

API Std 620 

3 1 APPLICABLE DESIGN CODES & STANDARDS (5/9)

Page 56: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 56/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (5/9)

Design Codes &

StandardsDescription Notes

EEMUA 147  The Engineering Equipment and Materials Users Association

Publication No. 147 

Recommendations for the Design and Construction of Refrigerated

Liquefied Gas Storage Tanks

Including definition of single, double

and full containment that are same asdefined in BS 7777.

EN 1473  Including definition of single, doubleand full containment that are same as

defined in BS 7777.

 Adopted European Standard

Installation and Equipment for Liquefied Natural Gas - design od

Onshore Installation

API Std 620  American Petroleum Institute

 API Standard 620 

Design and Construction of large, Welded, Low - Pressure Storage

Tanks

Definitions of single, double and fullcontainment that are not included.

 Applicable to the cylindrical inner tankof each containment type defined inBS 7777, and double metal single

and full containment tank.

3 1 APPLICABLE DESIGN CODES & STANDARDS (6/9)

Page 57: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 57/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (6/9)

BS 7777 

OVERSEAS 

EEMUA 147 

EN 1473 

API Std 620 

Europe  USA 

NFPA 59A  NFPA 15 

NFPA 59A  NFPA 15 

3 1 APPLICABLE DESIGN CODES & STANDARDS (7/9)

Page 58: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 58/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (7/9)

Design Codes &

StandardsDescription Notes

NFPA 59A 

NFPA 15 

National Fire Protection Association

NFPA 59 A 

Production, Storage, and Handling of Liquefied natural Gas (LNG)

 Applicable to the spacing, bund wall

design, fire protection, safety andsecurity.

National Fire Protection Association

NFPA 15 

Standard for Water Spray Fixed System for Fire Protection

 Applicable to the water spray system.

3 1 APPLICABLE DESIGN CODES & STANDARDS (8/9)

Page 59: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 59/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (8/9)

DOMESTIC (IN JAPAN) 

高圧ガス保安法 

LNG地 式貯槽指針 

高圧ガス保安法 

LNG地 式貯槽指針

 

消防法 プラント 

安全規準

 

その他関連 

法規・規準

 

高圧ガス保安法

 High Press. Gas Control LowLNG地 式貯槽指針

 LNG Aboveground Tank 

高圧ガス保安法

 High Press. Gas Control LowLNG地 式貯槽指針

 LNG Underground Tank 

3 1 APPLICABLE DESIGN CODES & STANDARDS (9/9)

Page 60: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 60/64

3.1. APPLICABLE DESIGN CODES & STANDARDS (9/9)

Design Codes &

StandardsDescription Notes

高圧ガス保

安法

 LNG地 式

貯槽指針 

経済産業省 

社団法人 日本ガス協会 

 Applicable to the above ground LNG

storage tank in Japan

高圧ガス保

安法

 

LNG地 式

貯槽指針 

 Applicable to the under ground and/orin-ground LNG storage tank in Japan

経済産業省 

社団法人 日本ガス協会 

Page 61: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 61/64

3.2 Seismic Load

3.2 Seismic Load

Page 62: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 62/64

3.2 Seismic Load

①OBE : 10% probability of exceedance within a 50-year period(=500years)

LNG Tanks shall be designed for two levels of seismic ground motion

②SSE : 1% probability of exceedance within a 50-year period(=500years)

OBE

SSE

Operating basis earthquake

Safe shutdown earthquake

( NFPA 59A, Para.4.1.3.2)

Page 63: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 63/64

3.3 Liquid Temperature

3.3. TEMPERATURE RANGE FOR MATERIAL OF CRYOGENIC STORAGE TANKS

Page 64: 122280432 Single Double Full Lng Tanks Ppt

7/24/2019 122280432 Single Double Full Lng Tanks Ppt

http://slidepdf.com/reader/full/122280432-single-double-full-lng-tanks-ppt 64/64

200

- 190

- 180

- 170

- 160

- 150- 140

- 130

- 120

- 110

- 100

- 90

- 80

- 70

- 60

- 50

- 40

- 30

- 20

- 10

0

10

20

30

oF oC

30

330

4050607080

2010

0- 10- 20- 30- 40- 50- 60- 70- 80- 90

- 110- 120- 130- 140- 150- 160- 170- 180- 190

- 210- 220- 230- 240- 250- 260- 270- 280- 290

- 320- 310

- 100

- 200

- 300

Boiling Temperature ofLiquefied Gases

Classificationof

Low temperature Service Steel

Ammonia : - 33.4oC ( - 28.1oF)

Propane : - 42.1oC ( - 43.8oF)Propylene : - 47.7oC ( - 53.9oF)

Hydrogen Sulfide : - 61.0oC ( - 77.8oF)

Radon : - 65.0oC ( - 85.0oF)

Carbon Dioxide : - 78.5oC ( -109.3oF)Acetylene : - 84.0oC ( -119.2oF)

- 46.0oC( - 50.8oF)

Ethylene : -103.5oC ( -154.3oF)

Xenon : -108.0oC ( -162.4oF)

Krypton : -151.7oC ( -241.1oF)

Oxygen : -183.0oC ( -297.4oF)

Argon : -185.5oC ( -301.9oF)

Nitrogen : -195.8oC ( -320.4oF)

Low-Carbon Steel

0.20~0.35% C

0.15~0.30% Si

<0.90% Mn

Low-Alloy Steel (2.5% Ni Steel)

2.20~2.60% Ni

Low-Alloy Steel (3.5% Ni Steel or

Cr-Ni-Cu-Al Steel)3.25~3.70% Ni or

0.75% Cr, 0.75% Ni

0.55% Cu, 0.15% Al

- 60.0oC( - 76.0oF)

-101.0oC( -149.8oF)

-196.0oC( -320 8oF)

9% Ni Steel

8.50~

9.50% Ni

Ethane : - 88.6oC ( -127.5oF)

Methane : -161.5oC ( -258.7oF)

Liquefied Natural Gas (LNG)