7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
1/6
@ Perkins
1300 Edi Series-Electropack
1500/50 Hertz, can be wired 3 ways,(auto or manual, (load share) or stand alone, (isochronous)
1800/60Hertz, can be wired 3 ways(auto or manual, (load share) or stand alone, (isochronous)
1500/1800 Switchable, can be wired 2 ways1500 or 1800, Isochronous Only
12 Volt and 24 Volt ECMs available.If you are not sure of the voltage and the markings have been removed
check PIN 35 to ground 1.4K Ohms 12 volts / 2.8K Ohms 24 volts.
Notes:On start up for genset applications the ECM automatically determines which speed/loadsignal out of range (o.o.r.) fault management to use. This is dependant on the wiringconfiguration it observesStand alone (isochronous) operation APS & RPS inputs are both inactive.
Manual synchronised load sharing APS input is active, RPS input is inactive.
Automatic synchronised load sharing APS input is inactive, RPS input isactive.
2 way protection is achieved by selecting 3 way protection and normally open (plastictank) for the CLS type. No connection should then be made to the CLS input.
APS >>>>> PIN 8
7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
2/6
W1361/1
1
Attention
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
1
Clear wire
18 AWG
87
85
Chassis harness connector
Interface harness
(if used)
See note 5
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
18 AWG
5 AMP
5 AMP
18
AWG
16 AWG
18 AWG
10 AWG
18 AWG
16 AWG
16 AWG
25
21
2241
23
42
1
2
3732
1617
55
54
24
34
10 AMP
10 AMP
Red
lamp
Amber
lamp
See note 6
See note 3
18AWG
Terminal can be
marked 87 or G
See note 4
Main
power rly
See note 2
87a
86
30
30 AMP
10 AWG
On/off switch
16AWG
Diagnostic
connector
Black wire
ABEC
10
AWG
Emergency
stop device
Rating 30Amin
To starter and
charging circuits
Battery
+
-
Battery
+
-
12V or 24V
Power relay out
DC/DC Converter
(+) FeedHSO (+) Feed
HSO Ground feed
DPS O/Ps Ground feed
DC/DC Converter
Ground feed
PRE InputSCS Input (set coast)
ATA (+)ATA (-)
ENG Warn light output
Oil water lamp output
VIGN - IPR (+) Feed
STI Switch
(Data link J1708)
ECM
Diagnostic
switch
Notes
1)
2)
3)
4)
5)
6)
Wire sizing:10AWG (approx. 5mm ) Main feed and return to battery14AWG (approx. 2mm ) ECM pin Nos 21.22.41.23.42.1.216AWG (approx. 1mm ) Ignition and diagnostic socket supply18AWG (approx. 0.8mm ) All other circuits
Main Power Relay12V part no. 1688314C1
(12V alternative part nos. 2848A203)
24V part no. 2848A226
Where shown, cables must be twisted together (360 per 25 mm andscreened to minimise noise effects. Connect screen at one end only.
All fuses must comply with SAE J1284 and be located close to thebattery so as to protect the wiring.
All unused interface harness cables must be insulated.
Recommended rating for lamps is between 2 and 2.2 watts.
2
2
2
2
0
Stand alone (isochronous)
operation
APS (PIN 8) & RPS (PIN 30)
in uts are both inactive
7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
3/6
W1362/1
1Attention
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
Notes
1)
2)
3)
4)
5)
6)
7)
Wire sizing:10AWG (approx. 5mm ) Main feed and return to battery14AWG (approx. 2mm ) ECM pin Nos 21.22.41.23.42.1.216AWG (approx. 1mm ) Ignition and diagnostic socket supply18AWG (approx. 0.8mm ) All other circuits
Main Power Relay12V part no. 1688314C1(12V alternative part nos. 2848A203)
24V part no. 2848A226
Where shown, cables must be twisted together (360 per 25 mm andscreened to minimise noise effects. Connect screen at one end only.
All fuses must comply with SAE J1284 and be located close to thebattery so as to protect the wiring.
All unused interface harness cables must be insulated.
Recommended rating for lamps is between 2 and 2.2 watts.
Where shown, cables must be twisted together (360 per 25 mm a
2
2
2
2
0
0
1
Clear wire
18 AWG
87
85
Chassis harness connectorInterface harness (if used)
See note 5
18 AWG
18 AWG
18 AWG
18 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG14 AWG
14 AWG
18 AWG
5 AMP
18
AWG
16 AWG
10 AWG
18 AWG
16 AWG
16 AWG
25
21
22
41
23
42
1
2
16
17
55
54
24
10 AMP
10 AMP
Red lamp
Amber lampSee note 6
See note 3
Terminal can be
marked 87 or G
See note 4
Main
power rly
See note 2
87a
86
30
30 AMP
10 AWG
On/off switch
16AW
G
Diagnostic
connector
Black wire
ABEC
10
AWG
Emergency
stop device
Rating 30A
min
To starter and
charging circuits
Battery
+
-
Battery
+
-
12V
or
24V
Power relay out
DC/DC Converter
(+) Feed
HSO (+) Feed
HSO Ground feed
DPS O/Ps Ground feed
DC/DC Converter
Ground feed
ATA (+)
ATA (-)
ENG Warn light output
Oil water lamp output
VIGN - IPR (+) Feed
(Data link J1708)
ECM
18 AWG18 AWG34 STI Switch
Diagnostic
switch
3
8
11
VBREF (5V) Sensor supply
APS Input
VBREF GND Sensor supplySee note 7See
note 3
250
Ohms
2 K
Ohms
250Ohms
Manual speed
(demand) signal.
(working range
0.5 to 4.5 volts
into ECM pin 8).
All resistors ratedat 0.25 watts.
Manual synchronised load
sharing
APS input (PIN 8) is active
RPS input (PIN 30) is inactive
7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
4/6
W1363/1
1
Clear wire18 AWG
87
85
Chassis harness connectorInterface harness (if used)
See note 5
18 AWG
18 AWG
18 AWG
18 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG14 AWG
14 AWG
18 AWG
5 AMP
18
AWG
16 AWG
10 AWG
18 AWG
16 AWG
16 AWG
25
21
22
41
23
42
1
2
16
17
55
54
10 AMP
10 AMP
Red
lamp
Amber
lamp
See note 6
See note 3
Terminal can be
marked 87 or G
See note 4
Main
power rly
See note 2
87a
86
30
30 AMP
10 AWG
On/off switch
16AWG
Diagnostic
connector
Black wire
ABEC
10
AWG
Emergency
stop device
Rating 30Amin
To starter and
charging circuits
Battery
+
-
Battery
+
-
12V or 24V
Power relay out
DC/DC Converter
(+) Feed
HSO (+) Feed
HSO Ground feed
DPS O/Ps Ground feed
DC/DC Converter
Ground feed
ATA (+)
ATA (-)
ENG Warn light output
Oil water lamp output
VIGN - IPR (+) Feed
(Data link J1708)
ECM
18 AWG18 AWG34 STI Switch
Diagnostic
switch
3
11
VBREF (5V) Sensor supply
RPS Input
VBREF GND Sensor supply
See note 7
Auto speed
(demand)
signal
Working input
voltage into ECMpin 30 is 0.5 to 4.5
30
37
24
RPRE Input
5AMP
18 AWG
1Attention
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
Notes
1)
2)
3)
4)
5)
6)
7)
Wire sizing:10AWG (approx. 5mm ) Main feed and return to battery14AWG (approx. 2mm ) ECM pin Nos 21.22.41.23.42.1.216AWG (approx. 1mm ) Ignition and diagnostic socket supply18AWG (approx. 0.8mm ) All other circuits
Main Power Relay12V part no. 1688314C1(12V alternative part nos. 2848A203)
24V part no. 2848A226
Where shown, cables must be twisted together (360 per 25 mm andscreened to minimise noise effects. Connect screen at one end only.
All fuses must comply with SAE J1284 and be located close to thebattery so as to protect the wiring.
All unused interface harness cables must be insulated.
Recommended rating for lamps is between 2 and 2.2 watts.
Where shown, cables must be twisted together (360 per 25 mm a
2
2
2
2
0
0
Automatic synchronised load
sharingAPS input (PIN 8) is inactive
RPS input (PIN 30) is active
7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
5/6
W1364/1
1
Clear wire
18 AWG
87
85
Chassis harness connectorInterface harness (if used)
See note 5
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
14 AWG
18 AWG
5 AMP
5 AMP
18
AWG
16 AWG
18 AWG
10 AWG
18 AWG
16 AWG
16 AWG
25
21
2241
23
42
1
2
37
32
1617
55
54
24
34
10 AMP
10 AMP
Red
lamp
Amber
lamp
See note 6
See note 3
18AWG
Terminal can be
marked 87 or G
See note 4
Main
power rly
See note 2
87a
86
30
30 AMP
10 AWG
On/off switch
16AWG
Diagnostic
connector
Black wire
ABEC
10
AWG
Emergency
stop device
Rating 30Amin
To starter and
charging circuits
Battery
+
-
Battery
+
-
12V or 24V
Power relay out
DC/DC Converter
(+) FeedHSO (+) Feed
HSO Ground feed
DPS O/Ps Ground feed
DC/DC Converter
Ground feed
PRE Input
SCS Input (set coast)
ATA (+)ATA (-)
ENG Warn light output
Oil water lamp output
VIGN - IPR (+) Feed
STI Switch
(Data link J1708)
ECM
Diagnostic
switch
J1
18 AWGJ2
31 RAS Input (resume/accel)See note 7
1Attention
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
Notes
1)
2)
3)
4)
5)
6)
7)
Wire sizing:10AWG (approx. 5mm ) Main feed and return to battery14AWG (approx. 2mm ) ECM pin Nos 21.22.41.23.42.1.216AWG (approx. 1mm ) Ignition and diagnostic socket supply18AWG (approx. 0.8mm ) All other circuits
Main Power Relay12V part no. 1688314C1(12V alternative part nos. 2848A203)
24V part no. 2848A226
Where shown, cables must be twisted together (360 per 25 mm andscreened to minimise noise effects. Connect screen at one end only.
All fuses must comply with SAE J1284 and be located close to thebattery so as to protect the wiring.
All unused interface harness cables must be insulated.
Recommended rating for lamps is between 2 and 2.2 watts.
Genset speed settings.
For 1500 rpm connect link J1
For 1800 rpm connect link J2
2
2
2
2
0
7/25/2019 1300EDI WIRING DIAGRAMS for Genset Applications
6/6
W1365
10 AMP
87
85
Radiator
shutter
control relay
87a
86
30
See note 3
AB
Two pin
connector
Single pin
connector
11
9
Snooze (run enable)
Radiator shutter
Engine harness connector
Chassis harness connector
54 OWL Output (press/temp)
10 Coolant level switch
Snooze
10 AMP
See note 2
Coolant
level
switchRequest to
shutdown
See note 1
RedOn/off
Battery
+
-
Battery
+
-
Vbal
Emergency
stop
Standard operating mode circuit
Additional notes
1) Maximum total current from OWL (54) output = 1 Amp (including lamp and
request to shutdown signal).
2) Coolant level sensor operation depends on EPN option selected
normally closed (metal tank)
narmally open (plastic tank).
3) Customers must specify the relay, the wiring and appropriate fuses for
the radiator shutter control circuit.
Snooze (run enable) single pin connector:
Packard part # Description
12065171...............Mating connector
12065249...............Secondary lock
12048159...............Male terminal 18 - 16 AWG
PIN 10
PIN 54