10
1 3 1 2 1 1 9 7 5 4 3 2 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long re are two “styles” of Ceiling tile, square and rectangular cross s New stairs here

131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Embed Size (px)

Citation preview

Page 1: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

131211975432

6’ tall Empty space below this metal sheet

66’

14’

4’

10’

Ceiling tiles = 24 Concrete blocks 14’ long

There are two “styles” of Ceiling tile, square and rectangular cross sections

New stairs here

Page 2: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

PSS

RadCon

DC powermagnets

Network andcommunications

bpmsI&C

High power rf

Gun HV power supply

LLRFcryo

Buncher solid state amp

vacuum

Old layout

Page 3: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

131211975432

6’ tall Empty space below this metal sheet

66’

4’

Ceiling tiles = 24 Concrete blocks 14’ longThere are two “styles” of Ceiling tile, square and rectangular cross sections

New stairs here

klystrons

Completely empty

One waveguide and LCW

Two waveguides

New electric here

HDIce

14’ 10’

New layout

Page 4: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

131211975432

6’ tall Empty space below this metal sheet4’

klystrons

Completely empty

One waveguide and LCW

Two waveguides

New electric here

HDIce

14’ 10’

PSSRadCon

DC powermagnets

Network andcommunications

bpms

I&C

Gun HV power supplyLLRF

cryo

Buncher solid state amp

vacuum

Page 5: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Dimensions will be checked, more dimensions added

Page 6: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,
Page 7: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Walkway:Backs of racks here

Metal plate, rad shielding

Electronics racks, side view

Front of rack hereFront of rack here

Grating-type floor

Page 8: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Walkway:Backs of racks here

Electronics racks, side view

Front of rack here68”

39” 39”?”

Should we install sides and backs?

Page 9: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Device Qty AC Power Each Total AC Power LCW Location

Gun High Voltage power supply 1 30A / 208 VAC 3

phase30A / 208 VAC 3 phase None Top of cave

ODH rack needs emergency power 1 20A/120 VAC single

phase20A/120 VAC single phase None

from an emergency power loop

Trim Rack 2 50A / 208 VAC 3 phase

100A/208 3Phase None Top of cave

Chicane power supply 1 30A / 208 VAC 3

phase 30A/208 3Phase None Top of cave

Chicane magnets 3 none 4 GPM Cave

LLRF/Master Oscillator 1 20A / 120VAC single

phase20A / 120VAC single phase None Top of cave

Water skids for chopper & buncher 2 20A / 208 VAC 3

phase 40A/208 3Phase 4 GPM Cave

Solid state RF amps for choppers 4 20 Amp / 208 VAC

single phase80 Amp / 208 VAC single - phase to phase

Top of cave 4 Amplifiers at 400 Watts each

Solid state amplifier for 750 MHz buncher 1 25A/480 VAC 3 phase 25A/480VAC

three phase Top of cave

Cathode Power Supply for klystrons 1 100A / 480VAC 3

phase100A / 480VAC 3 phase None Top of cave

also for High power RF 1 208 VAC three phase

and 120 VAC Top of cave

Klystrons 3 none 16.5 GPM Top of cave 5.5 GPM each

Circulators & loads 3 none 6 GPM Top of cave 2 GPM each

Cave Vacuum & Utility power

20A / 208 3Phase XX A / 240 VAC X circuits 20 A / 120 VAC

20A/208 3Phase 240 VAC Cave

Ion Pump power supplies 1 20A 120VAC single

phase20A 120VAC single phase none Top of cave

Control Racks including cryo 12 20A / 120VAC single

phase12 circuits@ 120 VAC@ 20 Amps Top of cave

Control Room 1 20A / 120VAC single phase

4 circuits@ 120 VAC@ 20 Amps Control Room

Inside the Cave 20A / 120VAC single phase

12 circuits@ 120 VAC@ 20 Amps

along perimeter of the cave

HDIce gets power from Big Bertha. Big Bertha will get power fed from a distribution panel in the annex. This distribution panel is attached to the generator. Ground isolated linesWalt thinks we might want two additional 480 VAC welding receptacles installed inside the cave too. These additional lines do not need to be attached to a generator.

Page 10: 131211975432 6’ tall Empty space below this metal sheet 66’ 14’ 4’ 10’ Ceiling tiles = 24 Concrete blocks 14’ long There are two “styles” of Ceiling tile,

Rf system for VTA750 MHz buncher rf systemFront width 32”, depth 39”, height 68”