OperationManual

30 kVA--160kVAUninterruptible Power

Supply

164200252 Rev. I

9315

Page 2: 160Kva UPS Operations Manual

ii Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

------------------------------------------------------------------------------------------------------------------------------------------------

----------------------------------

IMPORTANT SAFETY INSTRUCTIONS

Instructions Importantes Concernant La Sécurité

SAVE THESE INSTRUCTIONS

Conserver Ces Instructions

This manual contains important instructions for your Uninterruptible PowerSupply (UPS) system. You should follow these instructions during the

installation and maintenance of the UPS, options, accessories, and batteries.

Cette notice contient des instructions importantesconcernant la sécurité.

This equipment has been tested and found to comply with the limits for a Class Adigital device, pursuant to Part 15 of the FCC Rules. These limits are designed toprovide reasonable protection against harmful interference when the equipment isoperated in a commercial environment. This equipment generates, uses, and canradiate radio frequency energy and, if not installed and used in accordance withthe instruction manual, may cause harmful interference to radio communications.Operation of this equipment in a residential area is likely to cause harmfulinterference in which case the user will be required to correct the interference attheir own expense.

WARNING:This is a product for restricted sales distribution to informed partners. Installationrestrictions or additional measures may be needed to prevent disturbances.

Page 3: 160Kva UPS Operations Manual

iiiPowerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Table of Contents

1 Introduction 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using This Manual 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

For More Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Getting Help 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2 Getting Started 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Looking Inside the UPS 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UPS Standard Features 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Monitor Panel 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control Panel 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Communication Panel 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Computer Interface 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary Alarm Contacts 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Building Alarm Monitoring 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Input Filter 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Emergency Load Off 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Automatic Battery Charge Current Limit 5. . . . . . . . . . . . . . . . . . . . . .

Installation Features 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Options and Accessories 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

External Battery Disconnect 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power Distribution Module(available for North American voltages only) 6. . . . . . . . . . . . . . .

Upgrade Capability 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Monitor Panel 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Relay Interface Module 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Isolation Transformer 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Modem 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Customer Convenience Outlet 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety Considerations 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Symbols, Controls, and Indicators 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 Understanding UPS Operation 9. . . . . . . . . . . . . . . . . . . . . . . . . . .

Normal Mode 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Bypass Mode 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery Mode 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Monitoring and Controlling UPS Operation 13. . . . . . . . . . . . . . . . . . . . . .

Page 4: 160Kva UPS Operations Manual

iv Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

4 Starting and Stopping the UPS 15. . . . . . . . . . . . . . . . . . . . . . . . . .

Using the Control Panel 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .To Place the UPS in Normal Mode 16. . . . . . . . . . . . . . . . . . . . . . . . . . .

To Shut Down the UPS from Normal Mode 17. . . . . . . . . . . . . . . . . . .

To Start the UPS in Bypass Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . .

To Shut Down Power to the Critical LoadWhile in Bypass Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5 Using the Monitor Panel 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using the LCD Screen 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using the Pushbuttons 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Adjusting the Contrast 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using the Load Off Pushbutton 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Reading the Status Indicators 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Using the Menu Options 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6 Using Features and Options 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Building Alarm Monitoring 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary Alarm Contacts 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Monitor Panel 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery Cabinets 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

External Battery Disconnect 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Relay Interface Module 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Supervisory Contact Module 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7 Serial Communications 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Locating the Communications Panel 40. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connecting Equipment to a Serial Port 41. . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring the Serial Ports 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Mode 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rate 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Data/Stop 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Handshaking 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Disabled (No Handshaking) 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

XON/XOFF 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Save 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Default Settings 45. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Terminal Mode 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Printing Selected Information 46. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Entire Log (Ctrl + P) 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Meters Printout (Ctrl + M) 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Information Printout (Ctrl + A) 48. . . . . . . . . . . . . . . . . . . . . . .

Battery Test Printout (Ctrl + B) 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: 160Kva UPS Operations Manual

vPowerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

System Configuration 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .System Configuration Mode Main Menu 50. . . . . . . . . . . . . . . . . . . . . .

Program Building Alarms 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Enable/Disable Default Functions 51. . . . . . . . . . . . . . . . . . . . . . . . . . .

Customize Alarm Messages 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Program Unit Name 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Adjust Output Voltage 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Change Password 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery Test Setup 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Modify Low Battery Time 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Calibration Mode 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Computer Mode 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Monitor Mode 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 Remote Notification 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Notification Features 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Description of Operation 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Call Answer 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Call Out 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Housekeeping 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Hardware Requirements 61. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring the Modem 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Basic Modem Configuration 62. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Configuring the Modem to Call a Remote Computer 63. . . . . . . . . . .

Configuring the Modem to Call a Numeric Pager 64. . . . . . . . . . . . . .

Configuring the Modem to Answer Incoming Calls 65. . . . . . . . . . . . .

Final Modem Configuration 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

UPS Setup Configuration 67. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

User-Selected Events 68. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9 Maintaining the UPS System 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important Safety Instructions 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Performing Preventive Maintenance 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Maintenance Training 73. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10 Product Specifications 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Input 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Output 76. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Environmental Specifications 77. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Battery Specifications 77. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 6: 160Kva UPS Operations Manual

vi Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

11 Responding to System Events 79. . . . . . . . . . . . . . . . . . . . . . . . . . .

System Event Horns 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Event Lights 79. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Event Messages 80. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

12 Using the LOAD OFF Pushbutton 83. . . . . . . . . . . . . . . . . . . . . . . .

To use the LOAD OFF Pushbutton 83. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Resetting the UPS System after Load Off 83. . . . . . . . . . . . . . . . . . . . . . . .

Page 7: 160Kva UPS Operations Manual

viiPowerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

List of Figures

Figure 1. Typical Powerware Plus UPS System 3. . . . . . . . . . . . . . . . . . . . .

Figure 2. Main Elements of the UPS System 4. . . . . . . . . . . . . . . . . . . . . . .

Figure 3. Path of Current Through the UPS in Normal Mode 10. . . . . . . . .

Figure 4. Path of Current Through the UPS in Bypass Mode 11. . . . . . . . .

Figure 5. Path of Current Through the UPS in Battery Mode 12. . . . . . . . .

Figure 6. Location of the Monitor Panel and the Control Panel 13. . . . . . .

Figure 7. UPS Control Panel 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 8. UPS Monitor Panel 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 9. Parts of the LCD Screen(Typical for Powerware Plus 80 480/208V Unit) 20. . . . . . . . . . . .

Figure 10. System Meters Screen(Typical for Powerware Plus 80 480/208V Unit) 23. . . . . . . . . . . .

Figure 11. Load Amps Meters Screen 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 12. Event History Log Screen 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 13. Active System Events Screen 26. . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 14. Unit Statistics Screen 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 15. Mimic Screen 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 16. Time Setup Screen 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 17. Port Setup Screen 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 18. External Connections for Building Alarm Monitoring 31. . . . . . . .

Figure 19. Summary Alarm Contacts 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 20. Remote Monitor Panel 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 21. Relay Interface Module 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 22. Supervisory Contact Module 37. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 23. Location of Communications Ports on the UPS(Powerware Plus 80) 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 24. Port 1 Pin Assignments 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 25. Port 2 Pin Assignments 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 26. Setup Serial Port 1 Screen 43. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 27. Event History Log 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 28. System Meters 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Figure 29. Battery Test Log 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8: 160Kva UPS Operations Manual

viii Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 9: 160Kva UPS Operations Manual

1Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Introduction

Congratulations on your purchase of a Powerware 9315 UninterruptiblePower Supply! The Powerware 9315 online power protection can be utilized to

prevent loss of valuable electronic information, minimize equipment downtime,and/or minimize the adverse effect on equipment production due to unexpectedpower problems.

The Powerware 9315 Uninterruptible Power Supply (UPS) continually monitorsincoming electrical power and removes the surges, spikes, sags, and otherirregularities that are inherent in commercial utility power. Working with yourbuilding’s electrical system, the UPS supplies clean, consistent power that yoursensitive electronic equipment requires for reliable operation. And duringbrownouts, blackouts, and other power interruptions, one or more optional batterycabinets can provide emergency power to safeguard your operation.

Your UPS will function automatically and require very little attention during normaloperation. However, you should read and understand the procedures described inthis manual to ensure trouble-free operation. In particular, you should bethoroughly familiar with the Load Off procedure described in Chapter 12.

Using This Manual

This manual describes the Powerware 9315 UPS routine operation andmaintenance. It also describes optional features and accessories that are availableto enhance UPS operation and performance. The text uses these conventions:

� Bold type highlights important concepts in discussions, key terms inprocedures, and menu options.

� Italic type highlights notes and new terms where they are defined.

� Rectangular boxes containing bold type are warnings or cautions that pertain tothe UPS system or its electrical connections. This important information alertsyou to possible dangers pertaining to personnel safety, UPS or equipmentdamage, critical load protection, or operational concerns.

In this manual, the term UPS refers only to the UPS cabinet and its internalelements. The term UPS system refers to the entire power protection system—theUPS cabinet and any options or accessories you have installed. The rectifier andinverter are internal UPS components that are together referred to as the powerprocessing unit (PPU) of the UPS.

Page 10: 160Kva UPS Operations Manual

2 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

For More Information

This manual describes how your UPS system works. For more information aboutyour system, refer to the following:

164200253 Powerware 9315 30---80 kVA UPS Installation

164200292 Powerware 9315 100---160 kVA UPS Installation

Both manuals contain the following information:

� How to prepare your site and plan for installation

� Detailed step-by-step procedures for installing each component of your system

� How to join cabinets in a line-up-and-match system

� Detailed illustrations of cabinets and optional accessories, includingdimensions and connection points.

Contact Powerware Corporation Field Service for information on how to obtaincopies of these manuals.

Getting Help

If you have a question about any of the information in this manual, or if you have aquestion this manual does not answer, please call Powerware Corporation FieldService:

United States 1-800-843-9433

Canada 1-800-461-9166

Outside the U.S. Call your local representative

Page 11: 160Kva UPS Operations Manual

3Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Getting Started

Each component of the UPS system is housed in a free-standingcabinet designed for industrial or computer room applications. The

cabinets line up and match in style and color, and have safety shields behind thedoors for hazardous voltage protection. Figure 1 shows a typical Powerware 9315UPS system.

PDM CABINET(optional)

INPUT

CABINET

UPS CABINET BATTERY

(optional)TRANSFORMER

(optional)

CABINET

Figure 1. Typical Powerware 9315 UPS System

Each cabinet of the UPS system is shipped separately with hardware for joining toother cabinets during installation. As shown in Figure 1, you can combine a UPSwith any of the options described in this manual to meet your system needs. TheUPS and options are described in detail later in this manual. The followingdescriptions provide a brief overview of standard UPS features and availableenhancements.

NOTE: You should read this manual and have thorough knowledge of UPS operationbefore attempting to operate any of the switches or controls on the UPS oroptional components.

Page 12: 160Kva UPS Operations Manual

4 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Looking Inside the UPS

The Powerware 9315 is a continuous duty, solid-state UPS that supports thefollowing equipment: process control, data processing, telecommunications/PBX,research, and medical. The Powerware 9315 maintains power to the critical loadsduring commercial electrical power brownout, blackout, overvoltage, undervoltage,and out-of-tolerance frequency conditions.

In this manual, the power required by your equipment is called the critical load. TheUPS supplies the critical load with conditioned power that is synchronized with yourutility power. Figure 2 shows the main elements of the UPS.

BATTERY CABINET

OUTPUT

DIGITAL

BYPASS

AC INPUT TO

AC INPUT TO

AC OUTPUT

INPUT

RECTIFIER/ INVERTER

BATTERY

FILTER

CONTACTOR

CONTACTOR

METERING

CONTACTOR

RECTIFIER/

BYPASS

TO CRITICAL

CHARGER

STATICSWITCH

CHARGER

UPS CABINET

LOAD

TRANSFORMEROUTPUT

POWER PROCESSING UNIT

Figure 2. Main Elements of the UPS System

If utility power is interrupted or falls outside the parameters specified in Chapter 10,“Product Specifications,” the UPS uses a backup battery supply to sustain power tothe critical load for a specified period of time or until the utility power returns. Forextended power outages, the backup battery supply allows you to either transfer toan alternative power system (such as a generator) or shut down your critical load inan orderly manner.

The operation of the UPS system is described in greater detail in Chapter 3,“Understanding UPS Operation.” Chapter 10, “Product Specifications,” outlinesthe storage and operating specifications for the UPS and optional battery.

Page 13: 160Kva UPS Operations Manual

5Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

UPS Standard Features

The UPS has many standard features that provide cost-effective and consistentlyreliable power protection:

Monitor PanelThe Monitor Panel on the front of the UPS contains an LCD screen to display thecurrent status of the UPS. You can view a statistical history and log of UPS eventsand display a real-time graphic representation of power flowing through the UPScomponents. Backlit status indicators show the operating mode of the UPS andalert you to system events. The emergency LOAD OFF pushbutton is also locatedon the monitor panel and is described in Chapter 5, “Using the Monitor Panel.”

Control PanelThe Control Panel inside the right door of the UPS contains the operator controls tostart and stop the UPS, change the operating mode, and reset the LOAD OFFpushbutton. The Control Panel is described in “Using the Control Panel” section ofChapter 4.

Communication PanelComputer InterfaceTwo serial communications ports are standard on all units, and are electrically isolatedfrom the UPS. You can use these ports to link the UPS to the features described inChapter 7, “Serial Communications” and Chapter 8, “Remote Notification.”

Summary Alarm ContactsAlarm contacts are provided for connection to equipment at your facility, such as alight, an audible alarm, or a computer terminal. The equipment you connect to thesecontacts alerts you to a UPS alarm. This feature is described further in Chapter 6,“Using Features and Options.”

Building Alarm MonitoringYou can connect your facility’s alarm system contacts to six (6) inputs in the UPS. TheUPS uses these inputs to monitor your building alarms in addition to the UPS status.This feature is described further in Chapter 6, “Using Features and Options.”

Input FilterYour unit may be equipped with an input filter. An input filter yields power factorcorrection that allows you to save on your initial installation and operating costs.The filter also reduces input harmonic current distortion and minimizes upstreaminterference that can damage sensitive hardware components.

Emergency Load OffA LOAD OFF pushbutton is provided for situations where you must immediatelyremove all power to your critical load. The pushbutton is located on the front of theUPS for quick access and is covered with a clear plastic shield to preventinadvertent operation. The shield must be raised before pressing the pushbutton.The LOAD OFF pushbutton is described in detail in Chapter 12, “Using the LOADOFF Pushbutton.”

Automatic Battery Charge Current LimitA preset limit restricts battery charging current to protect batteries from damagedue to high current charging. Charging at high currents can overheat and damagebatteries.

Page 14: 160Kva UPS Operations Manual

6 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Installation FeaturesPower and control wiring can be routed through the top or bottom of each UPScabinet. Each cabinet has an internal wireway.

Options and Accessories

Contact your sales representative for information about any of these availableoptions:

BatteryYou can enhance the protection provided by your UPS with one or more backupbattery supplies equipped with sealed lead-acid, maintenance-free batteries in amatching cabinet. Each battery cabinet contains individual modular battery traysand a battery circuit breaker. Several battery capacities are available.

The UPS battery cabinets can be paralleled; you can increase your battery backuptime by adding battery cabinets to your UPS system. Your UPS system cansupport up to four (4) battery cabinets.

External Battery DisconnectAn optional DC circuit breaker, enclosed in a wall-mounted box adjacent to theUPS, provides a manual means of disconnecting a battery that is located remotelyfrom the UPS. This option is described further in Chapter 6, “Using Features andOptions.”

Power Distribution Module (available for North American voltages only)An optional output power distribution module (PDM) is available to distribute theoutput power of the UPS to your critical load. The PDM cabinet has two panels,each containing 40 poles for breaker switches you can assign with flexibility tomeet the needs of your facility. Each panel is controlled by one 225 amp feederbreaker. The PDM is enclosed in a separate cabinet that matches the UPS.

Upgrade CapabilityThe UPS is available in various output power ratings in both 50 and 60 Hz models.If your power requirements increase, you can upgrade your UPS system to providemore output power with a minimum impact on your facility.

Remote Monitor PanelAn optional Remote Monitor Panel (RMP) contains backlit status indicators and alocal horn, allowing you to monitor the operational status and alarm condition ofthe UPS from virtually any location within your facility. You can install multipleRMPs at remote locations to increase your monitoring capabilities. This option isdescribed further in Chapter 6, “Using Features and Options.”

Relay Interface ModuleAn optional Relay Interface Module (RIM) uses relay contact closures to indicatethe operating status and alarm condition of the UPS system. The module uses aserial interface line and may support up to eight critical loads. This option isdescribed further in Chapter 6, “Using Features and Options.”

Isolation TransformerAn optional voltage-stepping input isolation transformer provides an isolated inputto the rectifier for applications that require a DC link that is not ground referenced.The transformer is contained in a matching cabinet. The input isolation transformeroption is not available with a Powerware 9315 40 or Powerware 9315 50 UPScabinet.

Page 15: 160Kva UPS Operations Manual

7Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

ModemAn optional modem is available for use with the UPS Remote Notification featuredescribed in Chapter 8, “Remote Notification”. Refer to the manual supplied withthe modem for modem operating instructions.

Customer Convenience OutletAn uninterruptible 120VAC, 0.2 amp, fuse-protected convenience outlet is providedwith the optional modem. It is located adjacent to the Communications Panel.

Safety Considerations

The UPS enclosures are designed for industrial or computer room applications,and contain safety shields behind the doors. However, the UPS is a sophisticatedpower system and should be handled with appropriate care, following theseguidelines:

� Keep surroundings clean and free from excess moisture.

� Do not operate the UPS close to gas or electric heat sources.

� The system is not intended for outdoor use.

� The UPS operating environment should be maintained within theparameters stated in this manual.

� Keep the UPS doors closed to ensure proper cooling airflow and to protectpersonnel from dangerous voltages inside the unit.

� The UPS contains its own power source. Lethal voltages are present evenwhen the UPS is disconnected from utility power.

WARNING:Only AUTHORIZED SERVICE PERSONNEL should perform service ormaintenance on the UPS or battery.

If service or routine UPS maintenance is required:

� Ensure all power is disconnected before performing installation or service.

� Ensure the area around the UPS system is clean and uncluttered.

� Battery cabinet maintenance or battery replacement should be performedonly by authorized service personnel.

� Observe all DANGER, CAUTION, and WARNING notices affixed to theinside and outside of the equipment.

� Always conform to the more detailed safety precautions described in“Important Safety Instructions” section of Chapter 9.

Page 16: 160Kva UPS Operations Manual

8 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Symbols, Controls, and Indicators

These symbols may appear on your UPS system or on labels inside the UPS. Theyare accepted by most international safety agents. Everyone in your organizationwho works with your UPS should understand the meaning of these symbols:

ONThe principal power switch is in the “On” position.

OFFThe principal power switch is in the “Off” position.

PHASEThe word “phase.”

CAUTION: REFER TO MANUALStop and refer to the Operator’s Manual for moreinformation.

RISK OF ELECTRIC SHOCKThere is a risk of electric shock present, and you shouldobserve associated warnings. The UPS contains highvoltages.

Page 17: 160Kva UPS Operations Manual

9Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Understanding UPS Operation

Your UPS functions automatically to supply AC electrical power to yourcritical load. The UPS always operates in one of three modes:

� In Normal mode, the critical load is supplied by the inverter, which derives itspower from rectified utility AC power. In this mode, the rectifier also providescharging current for the battery.

� In Battery mode, the battery cabinet provides DC power, which maintainsinverter operation. The battery supports the critical load.

� In Bypass mode, the critical load is directly supported by the utility through anisolation transformer.

The UPS continually monitors itself and the incoming utility power, andautomatically switches between these modes as required, with no operatorintervention. The sophisticated detection and switching logic inside the UPSensures that operating mode changes are automatic and transparent to the criticalload. The UPS switches operating modes in response to these system events:

� A command is an intervention that is externally initiated by an operator or bysome site action. A command causes the UPS to switch operating modes; itusually does not require any further action by you.

� A notice is a minor system event that may or may not require your attention.

� An alarm is a system event that requires immediate operator intervention.

System events, alarm horns, and indicator lights are described in Chapter 11,“Responding to System Events.”

Page 18: 160Kva UPS Operations Manual

10 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Normal Mode

In Normal mode, utility AC power is supplied to the rectifier. The rectifier suppliesDC power to the inverter, which then supplies the critical load with AC power. Therectifier also provides charging power to the battery. The battery charge conditionis monitored by the UPS and reported by a status indicator on the Monitor Panel.The message “System Normal” appears in the status area of the LCD screen.

Figure 3 shows the path of electrical power through the UPS system when the UPSis operating in Normal mode.

Bypass

Rectifier

K4

Input

Input

K3CB1

K2

(closed)

BATTERY

Path of electrical power

RECTIFIER INVERTER

(closed)

Output

TRANSFORMER

BYPASS

Figure 3. Path of Current Through the UPS in Normal Mode

If the utility AC power is interrupted or is out of specification, the UPS automaticallyswitches to Battery mode to support the critical load with no interruption. Whenutility power returns, the UPS returns to Normal mode.

If the UPS system becomes overloaded, the UPS switches to Bypass mode. TheUPS automatically returns to Normal mode when the error condition is cleared andsystem operation is restored within specified limits.

If the UPS suffers an internal failure, it switches automatically to Bypass mode andremains in that mode until the failure is corrected and the UPS is back in service.

Page 19: 160Kva UPS Operations Manual

11Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Bypass Mode

The UPS automatically switches to Bypass mode if it detects an overload, loadfault, or internal failure. The bypass source supplies the commercial AC power tothe load through an internal switch and an internal transformer.

CAUTION:The critical load is not protected while the UPS is in Bypass mode.

Figure 4 shows the path of electrical power through the UPS system when the UPSis operating in Bypass mode.

Path of electrical power

Bypass

Rectifier

K4

Input

Input

K3CB1

K2

(open)

BATTERY

RECTIFIER INVERTER

(closed)

Output

TRANSFORMER

BYPASS

Figure 4. Path of Current Through the UPS in Bypass Mode

You can transfer the UPS from Normal mode to Bypass mode manually. However,the UPS switches automatically to Bypass mode whenever the inverter can nolonger supply the critical load. If the UPS transfers to Bypass mode from Normalmode due to any reason other than operator intervention, the UPS automaticallyattempts to transfer back to Normal mode (up to three times within a 10-minuteperiod).

Bypass mode is a normal operating mode, and not an alarm condition. However, ifthe UPS is unable to return to Normal mode following an automatic transfer toBypass mode, an alarm condition will be recorded.

Page 20: 160Kva UPS Operations Manual

12 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Battery Mode

The UPS transfers to Battery mode automatically if a utility power outage occurs, orif the utility power does not conform to specified parameters. In Battery mode, thebattery provides emergency DC power that the inverter converts to AC power.When the UPS switches to Battery mode, the alarm indications depend on thecause and condition of the battery charge. The length of time the system canoperate in Battery mode depends on loading and the battery supply capacity.

Figure 5 shows the path of electrical power through theUPSwhen operating in Batterymode.

Path of electrical power

Bypass

Rectifier

K4

Input

Input

K3CB1

K2

(closed)

BATTERY

RECTIFIER INVERTER

(closed)

Output

TRANSFORMER

BYPASS

Figure 5. Path of Current Through the UPS in Battery Mode

When the discharging battery voltage reaches the lower limit of UPS operationcapability, the critical load transfers to Bypass mode if it is available. If Bypass inputis not available, a “Shutdown Imminent” warning occurs. The warning time beforecritical load loss occurs is approximately 2 minutes, depending on battery capacityand the amount of loading.

If incoming power returns to within specified parameters, the UPS automaticallyreturns toNormalmode andalarm indications clear. However, theprocess of returningto Normal mode is not instantaneous. The rectifier gradually draws increasing powerfrom the incoming utility until Normal mode is achieved.

Page 21: 160Kva UPS Operations Manual

13Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Monitoring and Controlling UPS Operation

After you start the UPS, no operator intervention is necessary except for periodicchecks of the UPS status. Manual operation is required only during routinemaintenance or service. Use the Monitor Panel and the Control Panel to monitorand control the UPS. Figure 6 shows the location of these two panels on the frontof the UPS.

CONTROL PANEL

MONITORPANEL

Figure 6. Location of the Monitor Panel and the Control Panel

The Monitor Panel on the left front of the UPS continually indicates the presentmode of UPS operation. This panel contains an LCD screen, backlit statusindicators, and the LOAD OFF pushbutton. Use the LCD screen on the MonitorPanel to view performance meters or graphic representations of UPS operation.The Monitor Panel is described in detail in Chapter 5, “Using the Monitor Panel.” Aquick reference label describing how to use the Monitor Panel is located inside theUPS above the Control Panel.

Open the right front door of the UPS to view the Control Panel containing variouscontrols and switches. These control power to and from the UPS, and allow you tochange the UPS mode manually. The Control Panel is discussed in Chapter 4.

Page 22: 160Kva UPS Operations Manual

14 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 23: 160Kva UPS Operations Manual

15Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Starting and Stopping the UPS

This chapter describes how to use the Control Panel to start and stop theUPS.

NOTE: Before starting the UPS, ensure all installation tasks are complete and a preliminarystartup has been performed by authorized service personnel. The preliminarystartup verifies all electrical interconnections to ensure the installation wassuccessful and the UPS system operates properly.

Using the Control Panel

The Control Panel (see Figure 7) is inside the right door of the UPS cabinet.Although the Control Panel appears easy to use, you should read theseinstructions and thoroughly understand how the controls work before attempting touse them.

CAUTION:Incorrect use of the power controls on the Control Panel can cause a loss ofpower to your equipment.

OFF

MODE

BATTERY

PUSH

TO RESET

OFF

CB1

ON

NORMAL

BYPASS

NORMAL

START

Figure 7. UPS Control Panel

Page 24: 160Kva UPS Operations Manual

16 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

The following describes the switches on the Control Panel (see Figure 7):

� The MODE switch is a two-position rotary switch that controls the manualtransfer of the UPS to and from Bypass mode. The MODE switch is used to:

--- Place the critical load in Bypass mode when the UPS is operating in Normalmode and the bypass source is within acceptable limits. If the transfer doesnot occur within 2 seconds, an alarm sounds.

--- Prevent transfer to Normal mode when the UPS is in Bypass mode.

--- Shut down the power processing unit (inverter and rectifier) of the UPS.

� The BATTERY switch is a two-position rotary switch that allows you to manuallyenable or disable the battery contactor.

� The circuit breaker (CB1) switch controls the operation of the rectifier andinverter. If CB1 is on (closed), the rectifier turns on when the START switch isactivated and the proper voltage is at the input terminals.

� The PUSH TO RESET pushbutton is described in the “Resetting the UPSSystem after Load Off” section of Chapter 12.

� The START switch activates the power controls on the Control Panel. TheSTART switch is center-biased (the key will rest only in the upright position).Its operation is similar to that of an automobile ignition switch. After setting theoperator controls, you turn the START switch to the right momentarily toactivate the controls. When you release it, it returns to the upright position.

The following sections describe how to operate these controls to start, stop, or changethe operating mode of the UPS.

To Place the UPS in Normal Mode:

1. Move the CB1 switch to ON.

2. Turn the BATTERY switch to NORMAL.

3. Turn the MODE switch to NORMAL.

4. Be sure the Load Off PUSH TO RESET pushbutton is pressed in.

5. Turn the START switch to the right momentarily.

The rectifier turns on, then the inverter turns on. When the inverter reaches fullvoltage, it turns on and supplies power to the critical load. It takes less than 1 minutefor the UPS to achieve Normal mode.

If a bypass source is available when you turn the START switch on, the critical load isimmediately supplied by the bypass source in Bypass mode until the inverter turns onand the UPS transfers to Normal mode. The status indicators on the Monitor Panelindicate when the UPS is in Bypass mode and Normal mode.

Page 25: 160Kva UPS Operations Manual

17Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

To Shut Down the UPS from Normal Mode:

1. Turn the MODE switch to BYPASS.

The UPS switches to Bypass mode. If the bypass source is not available, the powerprocessor remains on and an alarm sounds.

2. When the transfer is complete (the LCD screen reads “On Bypass”), move theCB1 switch to OFF.

The bypass source supplies the critical load and the power processor de-energizes.The Bypass mode indicator illuminates on the Monitor Panel.

To Start the UPS in Bypass Mode:If the power processing unit (PPU) of the UPS is not available and you need toenergize your critical load right away, you can energize your critical load withoutthe benefit of backup. To turn the UPS on in Bypass mode:

1. Turn the MODE switch to BYPASS. (The remaining switches can be in anyposition.)

2. Turn the START switch to the right momentarily.

Power to the critical load is supplied by the bypass source. No backup is available.

To Shut Down Power to the Critical Load While in Bypass Mode:To perform maintenance or service on your critical load, you must shut it down first:

1. Turn off all equipment that is being powered through the UPS.

2. Press the LOAD OFF pushbutton on the Monitor Panel.

Page 26: 160Kva UPS Operations Manual

18 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 27: 160Kva UPS Operations Manual

19Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Using the Monitor Panel

This chapter describes the Monitor Panel and how to monitor and controlUPS operation. The Monitor Panel is a black rectangular area on the front of

the UPS (see Figure 8).

Figure 8. UPS Monitor Panel

The Monitor Panel contains a flat liquid crystal display (LCD) screen (1), a horizontalrow of pushbuttons (2), a vertical column of backlit status indicators (3), and the redLOAD OFF pushbutton (4). A quick reference label describing how to use the MonitorPanel is located inside the UPS above the Control Panel. The following sectionsdescribe the Monitor Panel in detail.

Page 28: 160Kva UPS Operations Manual

20 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Using the LCD Screen

The LCD screen at the top of the Monitor Panel provides an operator interface withthe UPS. Figure 9 identifies the display fields discussed in the following sections.

Uninterruptible Power System

System NormalAlarm: NoneNotice: None

Meters

System

Load Amps

Events Statistics Graphics Setup

Input Output

Bypass Battery

VAB480

VBC VCA

KW69

KVA73

IA IB IC

FREQ60.0

PF0.95

V540

I000

Meters

88

480 480

8888

VAB480

VBC VCA480 480

IA IB IC222 222222

IN000

VAB208

VBC VCA208 208

FREQ60.0

KVA80

KW64

PF0.80

Battery

04 MAY 1994 14:23:45

100%Percent

A

E

D

C

B

F

G

Figure 9. Parts of the LCD Screen (Typical for Powerware 9315 80 480/208V Unit)

A The UPS status area contains three lines that display the current state of the UPS. The firstline shows the present operational mode of the UPS. The second line shows the highest levelof the current active alarms, and the third line shows any notices the UPS has posted. (Formore information about alarms and notices, refer to Chapter 11, “Responding to SystemEvents.”)

B The battery charge box shows the percentage of battery capacity available.

C The menu box shows the currently selected menu and lists the options available on thatmenu. The title at the top of the menu box is also shown below on the menu bar (E). Pressthe and pushbuttons to scroll up and down through the options in the menu box.

D The currently selected option is highlighted in the menu box. Press the and pushbuttonsto move the highlight up or down. The data in the information area (G) changes accordingly.

E The menu bar lists the titles of the menus. The title of the menu currently displayed in themenu box is highlighted. When you press the and pushbuttons to move the highlightleft or right, the data in the menu box and the information area change accordingly.

F The timestamp shows the current date and time. This date and time are recorded in the EventLog when a notice or alarm is activated.

Page 29: 160Kva UPS Operations Manual

21Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

G The information area contains data about UPS status and operations. Select a menu option todisplay statistics or graphics.

You can use the LCD screen and the pushbuttons beneath it to:

� Monitor UPS operation

� Look at a log of UPS events (alarms, notices, and commands).

Using the Pushbuttons

The pushbuttons below the LCD screen are labeled with arrows indicating theirfunctions:

� Press the and pushbuttons to move through the options in a menu, or toscroll through the list of alarms and notices in the event log.

� Press the and pushbuttons to move through the menu titles on themenu bar. Press them simultaneously to silence the horn, or to test the lampsbehind the status indicators.

� Press the pushbutton to toggle the use of the and pushbuttonsbetween the menu box and the information area.

Adjusting the Contrast

� Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the

pushbutton, then press the pushbutton to increase the contrast or the

pushbutton to decrease the contrast.

Using the Load Off Pushbutton

The LOAD OFF pushbutton is red and covered by a clear plastic shield. In anemergency, you can press this pushbutton to cut off utility power to the powerprocessing unit of the UPS and to your critical load. For more information, refer toChapter 12, “Using the LOAD OFF Pushbutton.”

CAUTION: All power to the critical load is lost when you press the LOADOFF pushbutton. You should use the LOADOFF pushbuttononly whenyouwant to de-energize the critical load.

Page 30: 160Kva UPS Operations Manual

22 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Reading the Status Indicators

The six symbols on the left side of the monitor panel are status indicators. They arebacklit by colored light emitting diode (LED) lamps, and they work in conjunctionwith the alarm horn to let you know the operating status of the UPS.

Normal This green symbol is lit when the UPS is operating inNormal mode. The power processing unit (PPU) issupplying power to the critical load.

Battery This yellow symbol is lit when the UPS is operating inBattery mode. Because Battery mode is a normalcondition of the UPS, the Normal indicator also remains lit.

Bypass This yellow symbol is lit when the UPS is operating inBypass mode. The critical load is supported by thebypass source. The Normal indicator is not lit when thesystem is in Bypass mode.

Notice This yellow symbol is lit when the system needs attention.The LCD screen shows all active notices. Some noticesmay be accompanied by an audible horn. To silence the

horn, press the and pushbuttons simultaneously.The Notice indicator may be lit along with other indicators.

Alarm This red symbol is lit when a situation requires immediateattention. The LCD screen shows the highest priorityactive alarms. All alarms are accompanied by an audible

horn. To silence the horn, press the andpushbuttons simultaneously. The Alarm indicator may belit along with other indicators.

Standby This yellow symbol is lit when electricity is present in thePPU of the UPS and the Normal indicator is not lit. Duringnormal startup, this indicator illuminates until the the UPStransfers to Normal mode, at which point the Normalindicator is lit. During normal shutdown, the Standbyindicator is lit until all energy in the UPS is dissipated andshutdown is complete.

For more information about audible horns, refer to the “System Event Horns” sectionof Chapter 11.

To test the LED lamps behind the status indicators, press the andpushbuttons simultaneously for 3 seconds. All the indicators should light while youhold down these pushbuttons. If any indicator does not light, its LED may need tobe replaced. Contact Customer Service if you have a problem with the indicatorlamps.

Page 31: 160Kva UPS Operations Manual

23Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Using the Menu Options

The UPS menus allow you to display data in the information area to help youmonitor and control UPS operation. The following menus and options areavailable:

� Meters Displays UPS performance meters for the system or critical load.

� Events Displays the list of Active System Events and a historical log ofsystem events.

� Statistics Displays statistical information about UPS operations for thebattery, load, or line.

� Graphics Displays a real-time graphic representation of the flow of currentthrough the internal UPS components.

� Setup Allows you to configure the UPS communications port and setthe date and time for the timestamp.

Figure 10 shows the LCD screen as it appearswhen you first start theUPS. TheMetersmenu is displayed in the menu box, with the System option highlighted. In theinformation area, the system meters show their current readings.

Uninterruptible Power System

System NormalAlarm: NoneNotice: None

Meters

System

Load Amps

Events Statistics Graphics Setup

Input Output

Bypass Battery

VAB480

VBC VCA

KW69

KVA73

IA IB IC

FREQ60.0

PF0.95

V540

I000

Meters

88

480 480

8888

VAB480

VBC VCA480 480

IA IB IC222 222222

IN000

VAB208

VBC VCA208 208

FREQ60.0

KVA80

KW64

PF0.80

Battery

04 MAY 1994 14:23:45

100%Percent

Figure 10. System Meters Screen (Typical for Powerware 9315 80 480/208V Unit)

The Input area shows the phase-to-phase voltage, frequency, andphase current of theincomingutility, followedby theKVA, KW, andpower factormeasurements. Theoutputarea shows the same information for the power being output by the UPS.

TheBypass area shows the phase-to-phase voltage of the bypass source. TheBatteryarea displays the DC voltage (V) and the DC current (I).

Page 32: 160Kva UPS Operations Manual

24 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Select Load Amps from the Meters menu to see a real-time bar graph of the outputcurrent of the UPS. The graph shows the current for each phase.

Figure 11 shows the Load Amps Meters screen.

Uninterruptible Power System

System NormalAlarm: NoneNotice: None

Meters

System

Load Amps

Events Statistics Graphics SetupMeters

Output Current

125%

100%

75%

50%

25%

0%

Phase A Phase B Phase C

04 MAY 1994 14:23:45

Battery

100%Percent

Figure 11. Load Amps Meters Screen

Page 33: 160Kva UPS Operations Manual

25Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Select History from the Events menu to display the Event History Log. The EventHistory Log lists up to 400 system events in chronological order, with the mostrecent event listed last. The end of the log (the most recent events) appears whenyou display the screen, and you must scroll upward to view older event listings.

Figure 12 shows the Event History Log screen.

Statistics Graphics Setup

Events

History

Active

Uninterruptible Power System

System NormalAlarm: NoneNotice: None

EventsMeters

04 MAY 1994 14:23:45

Event History Log

Event Description

03

03

03

03

03

03

03

03

16:41:19.3

16:41:20.1

16:41:22.4

16:41:25.5

16:41:26.8

16:41:27.8

16:41:30.4

16:41:29.1

COMMAND: Keyswitch On

STATUS: Auto Mode

COMMAND: Rectifier Commanded On

STATUS: Inverter On

STATUS: Rectifier On

STATUS: Battery Contactor (K2) Closed

STATUS: Inverter Contactor (3) Closed

STATUS: Bypass Contactor (K4) Open03

16:41:36.6 STATUS: Inverter Normal

Battery

100%Percent

Date / TimeMay

Figure 12. Event History Log Screen

A small return arrow ( ) appears in the upper right corner of the information areaof the Event History Log screen. This arrow is a reminder that you can press the

pushbutton on the Monitor Panel to toggle the scroll bar between the menubox and the information area. When the scroll bar is in the information area, thereturn arrow is in the menu box. When the scroll bar is in the menu box, the returnarrow is in the information area.

When the scroll bar is in the information area, you can press the and pushbuttonsto scroll through the Event History log.

Page 34: 160Kva UPS Operations Manual

26 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Select Active from the Events menu to display a listing of all system events that arecurrently active. The most recent system event is listed first. As events clear, theyare removed from the Active System Events listing.

Figure 13 shows the Active System Events screen.

Uninterruptible Power System

Alarm: On Battery Shutdown ImminentNotice: None

Events Statistics Graphics SetupMeters

Events

Active

History

Active System Events

NOTICE: Input power unavailableNOTICE: Bypass Not AvailableALARM: Shutdown Imminent

04 MAY 1994 14:23:45

BatteryMinutes001.3

Figure 13. Active System Events Screen

Page 35: 160Kva UPS Operations Manual

27Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Select Unit from the Statistics menu to display a listing of statistics about UPSoperation.

Figure 14 shows the Unit Statistics screen.

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

04 MAY 1994 14:23:45

Events Statistics Graphics SetupMeters

Statistics

Unit

Start Date: 04 MAY 1994

Number of Incidents:

On Battery < 1 Min.

On Battery 1-4 Min.On Battery > 4 Min.Full Batt. DischargeBuilding Alarm 1Building Alarm 2Building Alarm 3Building Alarm 4Building Alarm 5Building Alarm 6

UPSBypassBatteryGeneratorLogic

AvailabilityUPSBypass

0100223233

00001198589

0.990.81

100%PercentBattery

Month Total DAYS HR MNTime On:

0035 20 590000 00 300000 00 020000 00 000035 21 30

Figure 14. Unit Statistics Screen

The left column shows the number of UPS incidents for the current month andsince the start date shown at the top of the screen. The top right column showsthe time that the UPS was on bypass, battery, or generator, and the amount of timethe UPS logic has been functioning since the start date. The lower right columnshows the percent of availability of the UPS and the bypass source.

Page 36: 160Kva UPS Operations Manual

28 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

SelectMimic from the Graphics menu to display a real-time graphical representationof the flow of current through the UPS.

Figure 15 shows the Mimic screen.

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

Events Statistics Graphics SetupMeters

Graphics

Mimic

04 MAY 1994 14:23:45

CB1 K3

K2

Rectifier Inverter

Bypass

Battery

100%PercentBattery

Figure 15. Mimic Screen

The Mimic screen shows the internal components of the UPS cabinet. The flow ofcurrent through the components is highlighted.

Page 37: 160Kva UPS Operations Manual

29Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Select Time from the Setup menu to display the Time Setup screen. The TimeSetup screen allows you to set the internal timestamp of the UPS. The timestampis used for logging events in the Event History Log. Figure 16 shows the TimeSetup screen.

Statistics Graphics Setup

Setup

Time

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

EventsMeters

Port 1

Set Time & Date

DAY DTMON 07

MONAPR

YR94

HR:MN15:06

SAVEYES

Port 2

04 MAY 1994 14:23:45

100%PercentBattery

Figure 16. Time Setup Screen

The small return arrow ( ) appears in the upper right corner of the Time Setupscreen. This arrow is a reminder that you can press the pushbutton on theMonitor Panel to toggle the pushbuttons between the menu box and theinformation area. When the scroll bar is in the information area, the return arrow isin the menu box. When the scroll bar is in the menu box, the return arrow is in theinformation area.

When the scroll bar appears in the information area, you can use the pushbuttonsto change the timestamp settings. To change a setting in the timestamp, press theand pushbuttons to highlight the setting you want to change. To increase the

setting (make it a higher value), press the pushbutton. To decrease the setting(make it a lower value), press the pushbutton. If you want to save the settingsupon exit from this screen, be sure the SAVE field is set to YES.

Page 38: 160Kva UPS Operations Manual

30 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Select Port 1 or Port 2 from the Setup menu to display one of the Port Setupscreens. The Port Setup screens allow you to specify settings for the two serialcommunication ports on the UPS. Figure 17 shows the Setup Serial Port 1 screen.

Statistics Graphics Setup

Setup

Port 1

Uninterruptible Power System

UPS System Normal

Alarm: NoneNotice: None

EventsMeters

Setup Serial Port 1

RATE9600

DATA/STOP8 1

HANDSHAKINGXON / XOFF

SAVENO

Time

MODETERMINAL

Port 2

04 MAY 1994 14:23:45

100%PercentBattery

Figure 17. Port Setup Screen

The small return arrow ( ) appears in the upper right corner of the Port Setupscreen. This arrow is a reminder that you can press the pushbutton on theMonitor Panel to toggle the pushbuttons between the menu box and theinformation area. When the scroll bar is in the information area, the return arrow isin the menu box. When the scroll bar is in the menu box, the return arrow is in theinformation area.

When the scroll bar appears in the information area, you can use the pushbuttonsto change the port configuration. To change a setting, press the and pushbuttonsto move the highlight to the setting you want to change. To scroll through theavailable options for that setting, press the or pushbutton. To save thesettings upon exit from this screen, be sure the SAVE field is set to YES.

The setup screens for Port 1 and Port 2 are identical. For detailed informationabout configuring the serial ports, refer to Chapter 7, “Serial Communications.”

Page 39: 160Kva UPS Operations Manual

31Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Using Features and Options

The many standard features of your UPS provide consistent, economical,and dependable power protection. In addition, you can add available options

and accessories to enhance the performance of your UPS system. This chapterprovides detailed descriptions of some of the features and options introducedearlier in this manual.

Building Alarm Monitoring

This standard feature lets you connect the UPS to your building alarms, such assmoke detectors or overtemperature alarms. The terminals for externalconnections are located inside the UPS on the customer interface panel(see Figure 18).

TB1

BLDG ALARM 1

BLDG ALARM 4

BLDG ALARM 5

NOTE:All building alarm inputs or remotefeatures require an isolated, normallyopen contact or switch (rated at 24 Vdc20 mA minimum) connected betweenthe alarm input terminal and commonterminal as shown. All control wiring,relay, and switch contacts are customerprovided.

1

2

3

4

5

6

7

8

9

15

10

11

14

13

12

TB2

BLDG ALARM 2

BLDG ALARM 3

BLDG ALARM 6

1

2

3

4

5

6

7

8

9

15

10

11

14

13

12

RS232

RS485

ON BYPASS

BATTERY CONTACTOR CLOSED

RELAY 2 NC

ON INV

RELAY 2 NO

RELAY 1 NC

RELAY 1 NO

BLDG ALARM 1 RTN

BLDG ALARM 4 RTN

BLDG ALARM 5 RTN

BLDG ALARM 2 RTN

BLDG ALARM 3 RTN

BLDG ALARM 6 RTN

REMOTE EPO

REMOTE EPO RTN

ON BYPASS RTN

BATTERY CONT RTN

ON INV RTN

ALARM RTN

NOTICE RTN

Figure 18. External Connections for Building Alarm Monitoring

Regardless of how you assign the building alarms, they display as Building Alarm 1,Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. Youshould use twisted pair wires for each alarm input and common.

Page 40: 160Kva UPS Operations Manual

32 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Summary Alarm Contacts

Two summary alarm contacts are provided as a standard feature on the UPS. Thealarm contacts (one notice and one alarm) are located inside the UPS on thecustomer interface panel (see Figure 19).

NOTICE NC

NOTICE NO

COMMON

ALARM NC

ALARM NO

COMMON

10

11

12

13

14

15

TB2

Figure 19. Summary Alarm Contacts

You can specify that each contact be either normally closed (NC) or normally open(NO). If the state of the contact changes from the state you specify as normal, an alarmis issued. You can connect these contacts to equipment at your facility (such as a lightor an alarm bell) to let you know when an alarm is active on the UPS. This feature isuseful if the UPS is located in a remote area where the UPS alarm horn may not beheard immediately.

CAUTION:Contacts should not be operated in excess of 30 VAC or 42.4V peak AC or DC@ 1A maximum.

Page 41: 160Kva UPS Operations Manual

33Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Remote Monitor Panel

As an option, you can install Remote Monitor Panels (RMPs) to monitor theoperation of the UPS system from virtually any location within your facility, up to500 feet from the UPS. Each RMP contains backlit status indicators and a localhorn. You can flush-mount or surface-mount an RMP on a desktop, wall, orwherever you have a serial interface line. A maximum of two monitoringaccessories (RMPs, Relay Interface Modules (RIMs), or Supervisory ContactModules (SCMs)) can be installed. See Table 1 for the number of accessoriespermitted. Figure 20 shows an RMP.

Figure 20. Remote Monitor Panel

Table 1. Optional Monitoring Accessories

Number and Type of Accessories Permitted

Remote Monitor Panel Relay Interface Module Supervisory Contact Module

2 — —

— 2 —

— — 2

1 1 —

1 — 1

— 1 1

Page 42: 160Kva UPS Operations Manual

34 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

The RMP contains a local horn and the following backlit status indicators:

SYSTEM NORMALThe UPS is energized (either with utility poweror battery backup) and is supplyingconditioned power to the critical load.

NO REDUNDANCYThis indicator applies only to parallel systemswhen one cabinet is not functioning. Thisfeature is not available on this system.

ON GENERATORThis alarm means that the UPS input andbypass are being supplied by the power fromthe generator, instead of from the utility power.

ON BYPASSThe bypass source is supplying the criticalload. Usually this means that the UPS is notenergized. The load is not protected in Bypassmode, and a horn sounds after 30 seconds.

UPS ALARMThe UPS system is issuing an alarm.Conditions that affect the current UPS modeare indicated by the alarm lamps and horn onthe UPS.

ON BATTERYThe UPS battery backup is supplying thecritical load. The utility power is eitherinterrupted or out of specification. TheSYSTEM NORMAL indicator is also lit.

BYPASS UNAVAILABLEThe UPS system is in Normal mode, buta bypass source is not within specification.A horn sounds after 30 seconds.

SHUTDOWN IMMINENTThe UPS is preparing to shut down becausethe UPS is in Battery mode and the DC voltageis approaching its low limit.This light is accompanied by an audible alarmhorn.

Page 43: 160Kva UPS Operations Manual

35Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Battery Cabinets

You can enhance the protection time provided by your UPS by adding one or morebattery cabinets. The battery cabinets provided by the UPS manufacturer areequipped with sealed lead-acid, maintenance-free batteries in a cabinet thatmatches the UPS. Each battery cabinet contains a battery circuit breaker. Severalbattery capacities are available.

The UPS battery cabinets can be paralleled. With this capability, you can increaseyour battery backup time by adding battery cabinets to your UPS system. MostUPS models can support up to four battery cabinets.

External Battery Disconnect

A breaker switch is located inside each battery cabinet supplied by the UPSmanufacturer. However, due to space limitations, your battery cabinets may not belocated in the same area as your UPS. An optional external DC circuit breakerprovides a manual means of disconnecting a battery that is located remotely fromthe UPS. The circuit breaker is enclosed in a wall-mounted box. You can install itanywhere between the remote DC supply and the UPS, according to national andlocal codes.

The breaker switch should be set to ON for normal UPS operation when DC poweris available at the UPS. When service personnel are performing maintenance onthe UPS or battery cabinet, the switch should be set to OFF.

Page 44: 160Kva UPS Operations Manual

36 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Relay Interface Module

An optional Relay Interface Module (RIM) uses relay contact closures to indicatethe operating status and alarm condition of the UPS system. A maximum of twomonitoring accessories (RMPs, RIMs, or SCMs) can be installed. See Table 1 forthe number of accessories permitted. Figure 21 shows the RIM with its four 15-pinconnectors labeled J1 through J4.

Figure 21. Relay Interface Module

The RIM can provide these signals:

� UPS AVAILABLE (pins 1 and 12) Contacts are closed when the UPS isoffline.

� UPS OFF LINE (pins 3 and 13) Contacts are closed when the UPS isoperating in Normal mode.

� UTILITY FAILURE (pins 6 and 15) Contacts are closed when Utility Failure isdetected.

� BATTERY WEAK (pins 5 and 14) Contacts are closed when approximately2 minutes of battery time is remaining, before the criticalload is lost.

Page 45: 160Kva UPS Operations Manual

37Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Supervisory Contact Module

An optional Supervisory Contact Module (SCM) establishes an interface betweenthe UPS manufacturer’s equipment and the customer’s monitor. This interfaceallows the customer to monitor operational status of the UPS equipment. Amaximum of two monitoring accessories (RMPs, RIMs, or SCMs) can be installed.See Table 1 for the number of accessories permitted. Figure 22 shows the SCM,input connections on TB1, and output connections on TB2.

TB2

Figure 22. Supervisory Contact Module

The SCM provides signals for the following indications:

� SYSTEM NORMAL TB2---1 through TB2---3

� NO REDUNDANCY TB2---4 through TB2---6

� ON GENERATOR TB2---7 through TB2---9

� BYPASS NOT AVAILABLE TB2---10 through TB2---12

� ON BATTERY TB2---13 through TB2---15

� UPS ALARM TB2---16 through TB2---18

� ON BYPASS TB2---19 through TB2---21

� SHUTDOWN IMMINENT TB2---22 through TB2---24

Refer to Powerware 9315 Installation manual, Chapter 12, for TB2 contactconfigurations.

Page 46: 160Kva UPS Operations Manual

38 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 47: 160Kva UPS Operations Manual

39Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Serial Communications

This chapter describes the serial communications feature of the Powerware

9315 UPS. Two serial communications ports on the UPS let you connectequipment to view system event information.

The following sections describe the serial communications feature, and provideinformation about connecting hardware, setting up the ports, changing settings,and changing modes.

Page 48: 160Kva UPS Operations Manual

40 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Locating the Communications Panel

The Communications Panel inside the UPS contains two serial communicationsports, one DE---9 and one DB---25. The ports provide a computer interface to aRemote Monitor Panel (RMP), Relay Interface Module (RIM), or remote terminaland/or printer. The Communications Panel also contains terminals (TB1 and TB2)for connecting your equipment to the UPS. Figure 23 shows the location of theseitems inside the UPS.

RS---232/485

RS---232

Connection

Connection

PORT 1 (DE---9F)

PORT 2 (DB---25F)

TB1 and TB2

COMMUNICATIONSPANEL

Figure 23. Location of Communications Ports on the UPS (Powerware 9315 80)

Page 49: 160Kva UPS Operations Manual

41Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Connecting Equipment to a Serial Port

You can connect a wide variety of terminals, printers, and computers to each port,and configure the UPS as the Data Communication Equipment (DCE). Set up theremote equipment using the appropriate parameters for the mode you select. Thefollowing section provides more information about configuration.

The cables you use for connection depend on the equipment you are connectingto the UPS. Cables should be no longer than 16m (50 ft). The connectors forPort 1 and Port 2 on the Communications Panel in the UPS are female, so thecables should be male. Figure 24 shows the pin assignments for Port 1, andTable 2 describes them. Figure 25 shows the pin assignments for Port 2, andTable 3 describes them.

3

2

1

5

4

7

6

9

8

+24V

RS232 TXD

RS232 RXD

NOT USED

RETURN

NOT USED

485 +

485 --

RETURN

PORT 1 (DE--9)

Figure 24. Port 1 Pin Assignments

Table 2. Pin Assignments for Port 1 (DE---9)

Pin # Symbol Description Comments

1 +24V + 24 volts DC

2 TXD Transmit Data Input to UPS

3 RXD Receive Data Output from UPS

5 RTN Return

7 485+ RS485 + Data

8 485--- RS485 --- Data

9 RTN Return

Page 50: 160Kva UPS Operations Manual

42 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

3

2

1

6

5

4

9

8

7

12

11

10

13

15

14

18

17

16

21

20

19

24

23

22

25

GND

RS232 TXD

RS232 RXD

RS232 RTS

RS232 CTS

RS232 DSR

RTN

+12V

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

RS232 DTR

NOT USED

--12V

NOT USED

NOT USED

NOT USED

PORT 2 (DB--25)

Figure 25. Port 2 Pin Assignments

Table 3. Pin Assignments for Port 2 (DB---25)

Pin # Symbol Description Comments

1 GND Chassis Ground

2 TXD Transmit Data Input to UPS

3 RXD Receive Data Output from UPS

4 RTS Request to Send Input to UPS

5 CTS Clear to Send Output from UPS

6 DSR Data Set Ready Output from UPS

7 RTN Return

8 +12V +12 volts Output from UPS --- always true

20 DTR Data Terminal Ready Input to UPS --- typically not used by UPS

22 ---12V --- 12 volts Output from UPS --- always true

NOTE: Pins 5 and 6 are tied together internally.

Page 51: 160Kva UPS Operations Manual

43Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Configuring the Serial Ports

You must configure the port for communications using the LCD screen andpushbuttons on the UPS Monitor Panel.

Select Port 1 or Port 2 from the Setup menu to display one of the Setup Portscreens. The screens for Port 1 and Port 2 are identical, and allow you to specifysettings for the two serial communication ports. Figure 26 shows the Setup SerialPort 1 screen.

Statistics Graphics Setup

Setup

Port 1

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

03 JAN 1994 14:23:45

EventsMeters

Setup Serial Port 1

Rate9600

Data/Stop8 1

HandshakingXON / XOFF

SaveNO

Time

ModeTERMINAL

Port 2

Battery

100%Percent

Figure 26. Setup Serial Port 1 Screen

A small return arrow ( ) appears in the upper right corner of the Setup Portscreen. This arrow is a reminder that you can press the pushbutton on theMonitor Panel to toggle the pushbuttons between the menu box and theinformation area.

If the scroll bar is in the menu box, press the pushbutton to toggle to theinformation area. The first setting (Mode) is highlighted. Press the orpushbutton to move the highlight to the setting you want to change. To scrollthrough the available options for that setting, press the or pushbutton.

To save the settings upon exit from this screen, be sure the Save field is set to YES.

Page 52: 160Kva UPS Operations Manual

44 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Table 4 shows which options are available for each port. The sections that followdescribe the configuration settings you can change.

Table 4. Options Available for Each Communication Port

Port 1 Port 2 Options

X X Terminal Mode

Calibration Mode

X X System Configuration

X Computer Mode

X Remote Monitor Mode

X X Baud rate of 300, 1200, 2400, 4800, 9600, or 19,200

X X Data size/stop bits of 8/1 or 8/2

X Data size/stop bits of 7/1 or 7/2

X X Disabled handshaking

X X XON/XOFF handshaking

Mode

The operational mode of the port. Each communications port operates in one ofthe following modes:

Terminal mode System events are logged immediately as they occur.

Calibration Used only by service personnel.

System Config. Allows you to set building alarms, battery tests, etc.(Check with your Sales or Service Representative for availability.)

Computer Provides a proprietary Binary Computer Mode (BCM) Interface.

Remote Monitor Sends all system event information to an RMP, RIM, orSupervisory Contact Module (SCM). Available for Port 1 only.

Port 1 and Port 2 cannot be in the same mode simultaneously; they must always beoperating in different modes. The modes are described later in this chapter.

Rate

The baud rate of the equipment connected to this port. The baud rate determinesthe speed of data transferred between the UPS and the connected equipment. ForRemote Monitor mode, the baud rate must be set to 300. All other modes shouldoperate at the highest baud rate available with the connected equipment. 300baud is not recommended for any mode except Remote Monitor.

You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200.

Page 53: 160Kva UPS Operations Manual

45Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Data/Stop

The data size and stop bits of the equipment connected to this port. Thesesettings determine the number of bits transmitted per ASCII character. The datasize and stop bits you specify depend on the configuration of your equipment.

For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 databits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.

NOTE: When connecting a computer running a terminal emulation program, youshould set your equipment to NO PARITY.

Handshaking

This setting controls handshaking. You can select XON/XOFF or Disabled for thissetting.

Disabled (No Handshaking)If handshaking is disabled, the UPS will transmit and receive data via the serialport, ignoring all inputs from handshaking lines.

XON/XOFFIf handshaking is enabled, the UPS uses special characters (XON and XOFF) tohandshake with the host terminal. The XON character is defined to be ASCII value11 hex, and the XOFF character is defined to be ASCII value 13 hex. Uponreception of an XOFF command, the UPS halts transmission until an XONcommand is received. In the same way, if the terminal receives an XOFFcommand, the UPS expects the terminal to halt transmission until the UPS sendsan XON command.

Save

Set to YES to save any changes to configuration settings upon exit from the Setupscreen. Set to NO if you do not want to save any changes.

Default Settings

The following are the default configuration settings for the serial communicationsports:

Port 1 Remote Monitor 300 baud 8/1 Handshaking Disabled

Port 2 Terminal 9600 baud 8/1 Handshaking Disabled

Each communications port on the UPS operates in one of five modes which youselect when configuring the port using the Setup Port screen.

Page 54: 160Kva UPS Operations Manual

46 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Terminal Mode

In this mode, system events are continually logged through the serial port to thedevice connected to the port. Port 2 operates by default in Terminal mode.

The printed log entries contain a time and date stamp and the alarm text message.Terminal mode uses this format for printing alarm entries:

MMM DD HH:MM:SS.hh KYWD MESSAGE :::: <CR> <LF>

Symbol DescriptionMMM Month (3 letters)DD Day (2 digits)HH Hour (2 digits)MM Minute (2 digits)SS Second (2 digits)hh Hundredths of Second (2 digits)KYWD Keyword (ALARM, NOTICE, COMMAND, or STATUS):::: System Diagnostic Information<CR> Carriage Return Character (ASCII 13)<LF> Line Feed (ASCII 10)

An alarmmessage is prefixed by the word “CLEAR” whenever an alarm is entered intothe Event History Log with a cleared status.

Printing Selected Information

If a port is operating in Terminal mode and is connected to a computer, you canuse key combinations at any time to print only selected information:

Ctrl+P Prints the entire log with a header

Ctrl+M Prints the current system meters with a header

Ctrl+A Prints all system information

Ctrl+B Prints Battery Test Log

To use a key combination, hold down the Control key and press the letter key.

Page 55: 160Kva UPS Operations Manual

47Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Entire Log (Ctrl + P)

This key sequence prints the entire Event History Log of the UPS at the time thedata is requested. The printout begins with the oldest alarm entry in the queue andends with the most recent. Any alarms that occur while the Event History Log isprinting are included in chronological order.

The Event History Log lists up to 400 system events in chronological order with themost recent event listed last. Figure 27 shows a sample Event History Log printout.

Event History Log

Event Description

MAY 1212121212121212

JUN 04

16:41:19.316:41:29.116:41:42.416:42:05.516:42:46.816:43:15.816:43:42.416:44:29.1

12:16:35.9

COMMAND: Keyswitch OnSTATUS: Auto ModeCOMMAND: Rectifier Commanded OnSTATUS: Inverter OnSTATUS: Rectifier OnSTATUS: Battery Contactor (K2) ClosedSTATUS: Inverter Contactor (3) ClosedSTATUS: Bypass Contactor (K4) Open

NOTICE: Room High Temperature

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

03 JAN 1994 14:22:49

12 16:44:36.6 STATUS: Inverter Normal

04211000

20302202

324001

Figure 27. Event History Log

Page 56: 160Kva UPS Operations Manual

48 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Meters Printout (Ctrl + M)

This key sequence prints the current readings of the UPS system meters. TheInput area shows the phase-to-phase voltage, frequency, and phase current of theincoming utility, followed by the kVA, kW, and power factor measurements. Theoutput area shows the same information for the power being output by the UPS.The Bypass area shows the phase-to-phase voltage of the bypass source. TheBattery area displays the DC voltage (V) and the DC current (I). Figure 28 showsa sample Meters printout.

Input Output

Bypass Battery

VAB480

VBC VCA

KW69

KVA73

IA IB IC

FREQ60.0

PF0.95

V540

I0

88

480 480

8888

VAB480

VBC VCA480 480

IA IB IC222 222222

IN0

VAB208

VBC VCA208 208

FREQ60.0

KVA80

KW64

PF0.80

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

03 JAN 1994 14:22:49

+

Figure 28. System Meters

System Information Printout (Ctrl + A)

This key sequence prints a listing of all available serial data. This printout containsthe information shown on the Event History Log and Meters screens of the UPS(both Figures 27 and 28).

Page 57: 160Kva UPS Operations Manual

49Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Battery Test Printout (Ctrl + B)

This key sequence prints the Battery Test Log. The log consists of a history of thelast 30 battery tests that were run and the results of those tests. The most recenttest will appear at the bottom of the log. Figure 29 shows a sample of the BatteryTest Log.

Uninterruptible Power System

UPS System NormalAlarm: NoneNotice: None

12 APR 95 15:39:31

UPS # 1

AUG 14 23:45 498.0 1.00 0000SEP 11 23:45 498.0 1.00 0000OCT 9 23:45 498.0 1.00 0000NOV 13 23:45 498.0 0.99 0000DEC 11 23:45 498.0 0.99 0000JAN 8 23:45 498.0 0.98 0000FEB 12 23:45 498.0 0.98 0000MAR 12 23:41 000.0 0.00 0003APR 9 23:45 496.2 0.98 0000

Battery Test LogDate/Time Volts Health Data

Figure 29. Battery Test Log

The Date/Time field is the date and time of the battery test.

The Volts field is a measured value of the battery voltage during the test. This fieldwill display 000.0 if the test did not run to completion.

The Health field is a relative measurement of your batteries condition. This numbercan be used to chart the condition of your batteries. If a sudden change of thisnumber occurs relative to the previous test results, it is an indication that yourbatteries may need attention. This display is 0.00 if the test does not run tocompletion.

The Data field is a value to be used by your field service engineer to gain moreinformation about the battery tests.

If the battery test does not complete, the Volts and Health field will read zero andthe UPS Event History Log will report either Battery Test Failed, Battery TestAborted (Load), or Battery Test Aborted (Utility). If the test ran to completion,Battery Passed Test will appear in the UPS Event History Log.

Page 58: 160Kva UPS Operations Manual

50 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

System Configuration

The System Configuration mode allows you to modify special functions in yourUPS. These functions include programming of building alarms, customizingbuilding alarm messages, adjusting the nominal output voltage, and schedulingbattery tests. The menus provided and their function are described in this section.

System Configuration Mode Main MenuWhen the System Configuration mode is selected with a terminal attached, you willbe prompted to enter the password for this mode:

Please Enter Password:

The default password is EXIDE1. You may modify this password using the changepassword function in the following menu. When the valid password is entered, themain menu will be displayed:

Program Mode Main Menu

1. Program Building Alarms

2. Program Unit Name

3. Adjust Output Voltage

4. Change Password

5. Battery Test Setup

6. Modify Low Battery Time

7. Exit Program Mode

Enter Selection:

Program Building Alarms

This menu provides access to all the functions available in the system configurationmode. If 1 is entered at the prompt, you can program the building alarm functions:

Program Building Alarms

1. Enable/Disable Default Functions

2. Customize Alarm Messages

3. Return to Main Menu

Enter Selection:

Page 59: 160Kva UPS Operations Manual

51Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Enable/Disable Default Functions

From this menu you may either enable the building alarms for general functions orspecial functions such as On Generator, Go To Bypass, and Go To UPS. You mayalso customize the alarm messages from this menu. When 1 is selected from thismenu, the following menu is displayed:

Enable/Disable Default Functions

1. Enable/Disable Go To Bypass

2. Enable/Disable Go To UPS

3. Enable/Disable On Generator

4. Enable/Disable Building Alarm

5. Return to Program Building Alarms Menu

Enter Selection:

If you select entry 1---3 from this menu, the following menu will be displayed:

Enable/Disable (Function)

Enabled Building Alarm Number(s)

1 4

Enter E# to Enable Building Alarm Number #

Enter D# to Disable Building Alarm Number #

Enter <CR> for No Change

Enter Selection:

Where (Function) indicates the function the building alarm is being programmed for.The line following the Enabled Building Alarm Number(s) label indicates whichbuilding alarms are currently enabled for the function. (In this example, BuildingAlarms 1 and 4 are enabled.) A building alarm can only be programmed for onespecial function at a time from these menus. Enabling a building alarm for aspecial function automatically enables the alarm. If you disable a special function,the building alarm is also disabled.

If you select entry 4 from this menu, the following menu will be displayed:

Enable/Disable Building Alarm

Enabled Building Alarm Number(s)

1 4

Enter E# to Enable Building Alarm Number #

Enter D# to Disable Building Alarm Number #

Enter <CR> for No Change

Enter Selection:

The line following the Enabled Building Alarm Number(s) label indicates whichbuilding alarms are currently enabled. (In this example, Building Alarms 1 and 4are enabled.)

Page 60: 160Kva UPS Operations Manual

52 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Customize Alarm MessagesIf Customize Alarm Messages is selected from the Program Building Alarm menu,you can select a custom message for a building alarm or disable a previouslyenabled building alarm custom message. When this entry is selected, the followingmenu is displayed:

Customize Alarm Messages

Enabled on Building Alarm Number(s)

2 3

Enter Building Alarm Number:

This example indicates that there are custom messages enabled for BuildingAlarms 2 and 3. When a building alarm number is entered, the message beingused by the software is displayed (either a custom message or the defaultmessage indicated by the list of enabled custom messages). If 1 was entered at theprompt, the following will be displayed:

Building Alarm Active Message: Building Alarm 1 (default message)

Enter New Message or <CR> for No Change:

At this level you can enter a custom message, 30 characters maximum, to displaywhen Building Alarm 1 is activated. If a custom message is entered to activate thebuilding alarm, a custom message should also be entered to deactivate. After themessage or a carriage return is entered, the following is displayed:

Building Alarm Clear Message: Clear Building Alarm 1 (default message)

Enter New Message or <CR> for No Change:

At this prompt, the user should enter the custom message for the building alarmdeactivation state. When a message or a carriage return is entered, the followingwill be displayed:

Enter E to Enable Custom Message

Enter D to Disable Custom Message

Enter <CR> for No Change

Enter Selection:

If an E is entered at the prompt, the custom messages will be used for the buildingalarm. If a D is entered, the default messages will be used for the building alarm.

Program Unit NameIf Program Unit Name is selected from the main menu, the following is displayed:

Program Unit Name

Unit Name:

Enter New Name or <CR> No Change:

NOTE: Unit Name is 45 characters maximum

The current unit name is displayed. This name will be displayed on the second lineof the display and in the headers of prints from Terminal mode. If a change isdesired, the new unit name should be entered at the prompt. The unit name is 45characters maximum and includes spaces and any punctuation. If the user wantsto center the text portion of the name, the appropriate number of leading spacesshould be included when entered.

Page 61: 160Kva UPS Operations Manual

53Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Adjust Output Voltage

If Adjust Output Voltage is selected from the main menu, the following menu isdisplayed:

Adjust Output Voltage

Output Voltage Setup: 208

Output Voltage Range: 197 --- 218

Enter Desired Output Voltage Setup:

The output voltage desired can then be entered or a carriage return for no change.Only values within the range will be accepted.

Change Password

If Change Password is selected from the main menu, the following menu isdisplayed:

Change Password

Enter New Password:

Verify New Password:

NOTE: Password must be six characters in length.

<CR> to return with no change.

The password will be changed if the user enters and verifies the password. Theentry must be six characters.

Page 62: 160Kva UPS Operations Manual

54 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Battery Test Setup

If Battery Test Setup is selected from the main menu, the following menu isdisplayed:

Battery Test Setup

1. Setup One-time Delayed Battery Test

2. Setup Monthly Battery Test

3. Setup Quarterly Battery Test

4. Cancel Pending Battery Test

5. Display Next Scheduled Battery Test

6. Return to Main Menu

Enter Selection:

This menu allows you to schedule, review schedule, or cancel pending batterytests. The following menu is displayed when 1---3 is selected:

Enter Starting Month (1---12):

Enter Day of Week, Sunday = 1, (1---7):

Enter Week of Month (1---5):

Enter Hour of Test (0---23):

Enter Minute of Test (0---59):

NOTE: Follow each entry with <CR>.

<CR> with no entry will return to Battery Test Setup Menu.

Enter the information at the prompt with a carriage return to schedule the batterytest.

If entry 4 is selected from the Battery Test Setup menu, you will be prompted toenter “Y” to cancel all pending tests. This selection will only cancel pending testsand will not stop a test currently in progress.

If entry 5 is selected from the Battery Test Setup menu, and if a Battery Test isscheduled, the following menu is displayed:

Next Battery Test Scheduled

WK DAY MON HR:MN

4 FRI MAR 15:34

NOTE: Enter <CR> to return to Battery Test Setup Menu.

If 5 is selected and there are no tests scheduled, the following will be displayed:

No Battery Test Scheduled

Enter <CR> to return to Battery Test Setup Menu

NOTE: The unit will only perform one battery test in any 24 hour period.

Page 63: 160Kva UPS Operations Manual

55Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Modify Low Battery Time

This menu allows you to modify the low battery time warning. When selected, thefollowing menu will be displayed:

Modify Low Battery Time

Low Battery Time (Minutes): 004

Enter New Low Battery Time:

NOTE: Low Battery Time should be no greater than 999. Enter <CR> to return withno change.

Enter the new time desired to change the warning level.

Calibration Mode

Calibration mode is used by factory and field service personnel to calibrate systemmeters. Factory test engineers calibrate the UPS meters prior to shipping so theUPS arrives at your site correctly calibrated. After use, field service personnel mayneed to use Calibration mode to recalibrate one or more meter settings.

NOTE: Calibration mode is for use by service personnel ONLY. To preventinadvertent modification, this mode can be accessed only by trainedpersonnel.

Computer Mode

This mode provides a computer interface which gives your system compatibilitywith system monitoring and network products. For a list of products available,contact your sales representative.

Remote Monitor Mode

This mode provides the interface for the RMP, RIM, or SCM described earlier.

Page 64: 160Kva UPS Operations Manual

56 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 65: 160Kva UPS Operations Manual

57Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Remote Notification

Remote Notification provides the user with the option of receivingalarms and notices at a remote location. Remote Notification also provides somebasic controls that can be performed remotely on the UPS. Remote Notificationoperates through a standard computer modem. Using the Terminal mode, the usercalls the UPS to perform basic monitoring and control. In the event of a UPS alarmor notice, the user is notified at the remote location. The UPS calls, through themodem, to the user’s computer or pager and leaves a message.

Remote Notification is an extension of the Terminal mode with the additionalsupport algorithms necessary to control an external modem (refer to Chapter 7,“Serial Communications”. Connection to the UPS is made when a user calls theUPS on the phone. The user has exactly the same capabilities as if using aterminal connected directly to the UPS RS---232 port. Remote Notification differsfrom the basic Terminal mode with the addition of Call Answer, Call Out, andHousekeeping functions. The Call Answer function allows the user to call into theUPS from a remote location and enter Terminal mode. The Call Out function allowsthe UPS to be configured to call either a remote computer or numeric pagingservice over the phone line. Call Out allows the UPS to call a remote computer andleave a one-line descriptive message of the alarm or notice condition. Numericpaging support allows the UPS to call a paging service and send numericmessages. The Housekeeping function maintains the link between the UPS andmodem.

Page 66: 160Kva UPS Operations Manual

58 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Remote Notification Features

Remote Notification provides the UPS with the capability to utilize a standardoff-the-shelf PC modem as a telephone interface. The features provided by thisoption are as follows:

� Call out to a remote terminal or pager based on programmable events andalarms.

� Two separate, programmable notification groups (phone numbers).

� Programmable number of redial attempts.

� Programmable time delay between call out attempts.

� Automatic answering (user configurable) for access to the Terminal mode ofthe UPS.

� Remote and local ability to clear Call Out alarms and events.

� Error detection and correction for misconfigured and disconnected modems.

� Uses standard modems and cables available at your local computer supplycenter.

Page 67: 160Kva UPS Operations Manual

59Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Description of Operation

The Remote Notification option performs three basic functions: Call Answer intoTerminal mode, Call Out to a remote terminal, and Housekeeping. RemoteNotification also allows access to any functions available in the Terminal mode froma remote computer or terminal.

Call Answer

To use the Call Answer function, the modem is configured to automatically answerby having the user program the S0 register of the modem to a non-zero number.When the modem receives a call, the UPS is alerted to wait for a connect signalfrom the modem. When the modem answers and finishes handshaking, the UPSacknowledges the modem connect signal and allows the caller into the Terminalmode (refer to Chapter 7, “Serial Communications”). In this mode, the user canrequest four items and perform one command:

NOTE: The brackets ([ ]) in the following steps indicate standard keyboardcharacters.

� Display all screens (^B, ^M, ^P). Press and hold [CTRL], then press [A].

� Display battery test results by pressing and holding [CTRL], then pressing [B].

� Display meters screen by pressing and holding [CTRL], then pressing [M].

� Display event history by pressing and holding [CTRL], then pressing [P].

� Reset Call Out Alarms by pressing and holding [CTRL], then pressing [R].

The Reset Call Out Alarms command causes the UPS to cease Call Out attemptson a currently active alarm and resets that alarm call. Refer to the “Call Out”section of this chapter for more information.

Call OutThe Call Out function contains programmable alarms and status events (refer toChapter 11, “Responding to System Events”). The notification groups tell the UPSto notify a remote computer or pager for each selected event. Refer to the“Configuring the Modem” section of this chapter for information on the modemconfiguration. Refer to the “User-Selected Events” section of this chapter to notewhich events are designated as group one or two. These events are selected whenthe UPS is purchased. The Call Out function activates as follows:

� A UPS alarm or notice occurs that is programmed to cause a Call Out.

� The UPS takes the modem off the hook and sends a command to the modemto call the notification groups (phone numbers) required. The command sent tothe modem for group one is “ATDTS0” and “ATDTS1” for group two. Thisallows the user to program the phone numbers into the modem.

Page 68: 160Kva UPS Operations Manual

60 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

� The UPS logs a successful notify to the event log when the remote computer ormodem answers and leaves an event message with the following format.

nnn<space>mmm<LF><CR> where:

nnn = The telephone number of the UPS (20 characters maximum)<space> = ASCII space character (0x20)mmm = Event message for notice or alarm (40 characters maximum)<LF> = ASCII line feed character (0x0A)<CR> = ASCII carriage return character (0x0D)

If calling a pager service and the service answers, the UPS delays momentarily andthen dials the pager number. Refer to the “Configuring the Modem to Call aNumeric Pager” section of this chapter for more information on configuring amodem to dial a pager.

NOTE: Because the pager service is not a modem, the UPS does not know if itsmessage got through; therefore, the UPS continues to call the pager servicefor a programmed number of times or until a call-in reset is performed.An unsuccessful notify event is logged into the UPS event log for eachattempted call out.

If the phone number that the UPS is calling does not answer, the UPS delays for atime period (programmable from 1 to 60 minutes) and then reattempts the call. Ifanswered, the UPS ceases further attempts to call. Each call group can beprogrammed for a separate number of attempts to call and delay between calls.Each unsuccessful attempt to call causes an unsuccessful notify event to belogged into the UPS event log.

If both call groups are active, the UPS alternates between calling the groups. TheCall Out process can be terminated at any time by calling into the UPS andsending the reset command (press and hold [CTRL] and press [R]) or by turningthe key switch on the front of the UPS.

HousekeepingWhen the modem is idle, the UPS “pings” (tests for connection) the modem bysending an “AT” to the modem at five-minute intervals. If the modem does notrespond correctly, by sending either “OK” or “0” to the UPS, the UPS attempts tore-initialize the modem. After a successful re-initialization, the UPS returns to theHousekeeping function. If the re-initialization is unsuccessful, two more attempts tore-initialize the modem are made before the UPS disables all Call Out attempts.Re-initialization is then attempted every ten minutes or until the communicationsmode is changed by the UPS front panel controls (or the modem re-initializes). Foreach unsuccessful attempt, the UPS logs a modem failure event into the event log.When the modem link is confirmed, the UPS communications resume normaloperation and Call Out is enabled.

Page 69: 160Kva UPS Operations Manual

61Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Hardware Requirements

The following hardware components are required to connect the RemoteNotification function.

� Modem: Basic external PC modem supporting the following AT commands.

E0 --- Do not echo characters in command state.M0 --- Turn speaker off.N0 --- Handshake only at speed specified by S37.Q0 --- Return result codes in both originate and answer mode.V0 --- Display result codes as numbers.X0 --- Provide basic result codes: CONNECT, NO CARRIER, and RING.&A0 --- Connect as answering modem when auto-answering.&D0 --- Ignore status of DTR signal.&K0 --- Disable local flow control.&Q5 --- Communicate in error control mode.

NOTE: Consult the modem manufacturer’s manual to confirm that the abovecommands are supported by your modem.

� Standard serial cable with a male DB25 connector on both ends.

� DB25 null modem adapter.

All the above items can be acquired at your local computer products supply store.

An alternative to purchasing a cable is to build your own serial cable using thefollowing pin out description:

Male DB25 Male DB25

pin 7 pin 7

pin 2 pin 2

pin 3 pin 2

Page 70: 160Kva UPS Operations Manual

62 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Configuring the Modem

The modem must be configured by the user before connecting to the UPS. Inaddition, the modem must be programmed with the Call Out telephone numbers inorder to operate the Remote Notification option.

To configure the modem, connect the serial port of a standard PC computer tothe modem through the serial cable. Run a terminal emulation program on thecomputer. Test the connection to the modem by typing [A], [T] and [ENTER].The modem should respond with either “OK” or “0” (zero). If the modem does notrespond, consult the modem manufacturer’s manual to confirm your setup. If themodem still does not respond, then seek technical assistance from your modemmanufacturer.

After connection, perform “Basic Modem Configuration” and the remainingsections of this chapter.

Basic Modem ConfigurationThe basic modem configuration consists of establishing the default operatingparameters for the modem and saving them to the modem memory. Thisprocedure sets up the modem for all operations. The configuration procedureis as follows:

1. Connect the modem to the PC through the serial port as described in the modemmanufacturer’s manual.

NOTE: The brackets ([ ]) in the following steps indicate characters that requirekeying in prior to pressing [ENTER].

2. Key in [A], [T], then press [ENTER].

3. Confirm that the modem responds with “OK” or “0” (zero).

4. Key in [A], [T], [&], [F], then press [ENTER].

5. Confirm that the modem responds with “OK” or “0” (zero).

6. Key in [A], [T], [Q], [0] (zero), [V], [0] (zero), [M], [0] (zero), [N], [0] (zero), [X],[0] (zero), [&], [A], [0] (zero), [&], [D], [0] (zero), [&], [K], [0] (zero), [&], [Q], [5].Verify that the display reads “ATQ0V0M0N0X0&A0&D0&K0&Q5”, then press[ENTER].

7. Confirm that the modem responds with “OK” or “0” (zero).

8. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

9. Confirm that the modem responds with “OK” or “0” (zero).

10. Key in [A], [T], [&], [Y], [0] (zero), then press [ENTER].

11. Confirm that the modem responds with “OK” or “0” (zero).

Page 71: 160Kva UPS Operations Manual

63Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Configuring the Modem to Call a Remote ComputerTo configure the modem to call a remote computer, perform the followingprocedure:

NOTE: Perform this procedure only after completing “Basic Modem Configuration”section of this chapter.

The brackets ([ ]) in the following steps indicate characters that requirekeying in prior to pressing [ENTER].

1. Connect the modem to the PC through the serial port as described in the modemmanufacturer’s manual .

2. Key in [A], [T], then press [ENTER].

3. Confirm that the modem responds with “OK” or “0” (zero).

NOTE: In steps 4 and 5, the “xxxxxxx” is the phone number of a remote computer.The phone number should include all local line and long distance accessnumbers needed to dial out. This number is limited to 32 characters.Placing a “T” at the beginning of the number informs the modem to use tonedialing. For example, use “9” if needed for an outside line, “1” for longdistance + (Area Code) + Number or whatever access codes are needed todial the call directly. Add a “,” in the number anywhere that a delay isneeded. This will cause a one-second delay. More than one delay may beadded to the number; for example, enter “AT&Z0=T,9,,1 (Area Code) (PhoneNumber)”.

4. To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [T], [,],[xxxxxxx], then press [ENTER].

5. To program a group two number, key in [A], [T], [&], [Z], [1], [=], [T], [,], [xxxxxxx],then press [ENTER].

6. Confirm that the modem responds with “OK” or “0” (zero).

7. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

8. Confirm that the modem responds with “OK” or “0” (zero).

9. Connect a telephone line to the modem and test the modem by keying in [A], [T],[D], [S], [0] (zero), then pressing [ENTER].

10. The modem dials the telephone number stored in step 4 or 5. (The number isdisplayed on the terminal screen as it is dialed.) Repeat steps 4 (or 5) through 9as necessary to modify the telephone number.

11. Confirm that the modem responds with “1” (one) when the connection is made.

NOTE: To set up a group one or group two pager number, refer to “Configuring theModem to Call a Numeric Pager” section of this chapter.

Page 72: 160Kva UPS Operations Manual

64 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Configuring the Modem to Call a Numeric PagerTo configure the modem to call a numeric pager system, perform the followingprocedure.

NOTE: Perform this procedure only after completing “Basic Modem Configuration”section of this chapter.

The brackets ([ ]) in the following steps indicate characters that requirekeying in prior to pressing [ENTER].

1. Connect the modem to the PC through the serial port as described in the modemmanufacturer’s manual .

2. Key in [A], [T], then press [ENTER].

3. Confirm that the modem responds with “OK” or “0” (zero).

NOTE: In steps 4 and 5 the “xxxxxxx” is the pager system number and “yyyyyyy” is thenumeric message (usually a phone number). The three“[,]” provide a delay whilethe pager system computer answers. The “xxxxxxx” entry should include all localline and long distance access numbers needed to dial out, as well as the pausenecessary between dialing the pager service and sending the pager the numericmessage. This number is limited to 32 characters. Placing a “T” at the beginningof the number informs the modem to use tone dialing. For example, use “9” ifneeded for an outside line, “1” for long distance + (Area Code) + Number orwhatever access codes are needed to dial the call directly. Add a “,” in the numberanywhere that a delay is needed. This causes a one-second delay. More than onedelay may be added to the number; for example, enter “AT&Z0=T,9,,1 (Area Code)(Phone Number) (Pauses) (Numeric Message)”. For areas with pulse dialing, the“T” should be inserted before the numeric message to switch to tone dialing. Thenumeric message can only be delivered using tone dialing. Keying in the “#”(pound) character at the end of the numeric message is very important. Itprevents the pager service from picking up on the modem hang-upcommands and sending additional characters.

4. To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [T], [,],[xxxxxxx], [,], [,], [,], [yyyyyyy], [#], then press [ENTER].

5. To program a group two number, key in [A], [T], [&], [Z], [1], [=], [T], [,], [xxxxxxx],[,], [,], [,], [yyyyyyy], [#], then press [ENTER].

6. Confirm that the modem responds with “OK” or “0” (zero).

7. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

8. Confirm that the modem responds with “OK” or “0” (zero).

9. Connect a telephone line to the modem and test the modem by keying in [A], [T],[D], [S], [0] (zero), then pressing [ENTER].

10. The modem dials the telephone number stored in step 4 or step 5. (The number isdisplayed on the terminal screen as it is dialed.) Confirm that the pager receivesthe message. Repeat steps 4 (or 5) through 9 as required to modify the telephonenumber and message.

NOTE: To set up a group one or group two number to call a computer, refer to“Configuring the Modem to Call a Remote Computer” section of this chapter.

Page 73: 160Kva UPS Operations Manual

65Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Configuring the Modem to Answer Incoming CallsTo configure the modem to answer incoming calls, perform the followingprocedure.

NOTE: Calling into the UPS does not present any type of security risk. There are nocommands that can be executed via the call-in feature except those availableto the Terminal mode.

1. Connect the modem to the PC through the serial port as described in the modemmanufacturer’s manual .

NOTE: The brackets ([ ]) in the following steps indicate characters that requirekeying in prior to pressing [ENTER].

2. Key in [A], [T], then press [ENTER].

3. Confirm that the modem responds with “OK” or “0” (zero).

4. Key in [A], [T], [S], [0] (zero), [=], [2], then press [ENTER].

5. Confirm that the modem responds with “OK” or “0” (zero).

6. Key in [A], [T], [S], [0] (zero), [?], then press [ENTER].

7. Confirm that the modem responds with “OK” or “0” (zero) and a value of “002”.

8. Connect a telephone line to the modem. Test the modem by using another PCequipped with a modem to dial the first modem.

9. Confirm that the UPS modem responds with “2” when the phone is ringing, and a“1” after the UPS modem has answered and the carrier has been detected.

10. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

11. Confirm that the modem responds with “OK” or “0” (zero).

Page 74: 160Kva UPS Operations Manual

66 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Final Modem ConfigurationThe final step in configuring the PCmodem for use with the UPS is to turn off the echofeature of the modem. Perform the following procedure.

NOTE: The brackets ([ ]) in the following steps indicate characters that requirekeying in prior to pressing [ENTER].

1. Connect the modem to the PC as described in the modem manufacturer’s manual.

2. Key in [A], [T], then press [ENTER].

3. Confirm that the modem responds with “OK” or “0” (zero).

4. Key in [A], [T], [E], [0] (zero), then press [ENTER].

5. Confirm that the modem responds with “OK” or “0” (zero).

6. Key in [A], [T], then press [ENTER].

7. Confirm that the modem responds with “OK” or “0” (zero) and that the “AT” is notechoed back to the terminal.

8. Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

9. Confirm that the modem responds with “OK” or “0” (zero).

Page 75: 160Kva UPS Operations Manual

67Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

UPS Setup Configuration

Connect the modem to the UPS by connecting one end of the serial cable to theUPS Port 2 DB---25F connector and the other to the modem (refer to Chapter 7,“Serial Communications”). If using a standard serial cable, a null modem adapteris required for the connection to the modem.

The Powerware 9315 UPS can only use serial Port 2, DB---25F, for the RemoteNotification option. This connection is located in the serial communications panelat the base of the UPS cabinet, behind the front door.

The modem operates at only one baud rate because there is no handshakingbetween the modem and the UPS. Select the lowest common baud rate (less thanor equal to 2400 baud) compatible with the capability of the UPS interfaceequipment. For example, if the computer only has a 2400 baud modem, then theUPS should be set for 2400 baud. Remember, the remote computer modem canalways slow down to the UPS baud rate, e.g., a 14400 baud modem can run at2400 baud, but a 2400 baud modem cannot run at 14400 baud.

Following the instructions in Chapter 5, “Using the Monitor Panel” and Chapter 7,“Serial Communications”, use the LCD screen and pushbuttons on the MonitorPanel to access the setup screen and configure Port 2 as follows.

NOTE: The modem should be connected to the UPS as described in the modemmanufacturer’s manual before configuring the UPS communications port.

<MODE> Remote Notify

<RATE> The baud rate at which the modem will communicateto other modems, 2400 baud maximum.

<DATA/STOP> 8 1 Standard 8 data bits, 1 stop bit, no parity.

<HANDSHAKING> Disabled

<SAVE> Yes. To save new configuration.

The handshaking feature listed is for UPS-to-terminal handshaking, notUPS-to-modem handshaking. Setting the handshaking to “modem” has no effect.If the remote terminal has buffering problems because of excessive data transferrate from the UPS, XON/XOFF handshaking can be selected to resolve this issue.The user must make sure that the modem (not the remote terminal) at the remoteterminal end of the connection is configured for either hardware handshaking ornone at all. This is required so that the modem does not attempt to trap theXON/XOFF characters and prevent them from being transmitted to the UPS.

Page 76: 160Kva UPS Operations Manual

68 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

User-Selected EventsInsert a check at each alarm or notice in the appropriate Group 1 or Group 2 blockto indicate the configuration of your UPS.

INVERTERMESSAGES --ALARMS

Group1

Group2

INVERTERMESSAGES --NOTICES

Group1

Group2

Inverter AC OverVoltage

Inv. Logic Power Failed

Inverter AC UnderVoltage

Bypass AC OverVoltage

Inverter CalibrationRequired

Bypass AC UnderVoltage

Inverter Contactor (K3)Failed

Bypass is Not Available

Inverter DC OverVoltage

Bypass Mode

Inverter Failure Bypass OverFrequency

Inverter OverFrequency

Bypass UnderFrequency

Inverter Phase Rotation Input Breaker (CB1)Open

Inverter SetupRequired

Battery Contactor (K2)Open

Inverter UnderFrequency

Battery DC UnderVoltage

100% OverloadShutdown

Battery Discharged

125% OverloadShutdown

Battery Not Charged

Over TemperatureShutdown

Battery Voltage Low

Shutdown Imminent Phase A Current Limit

Load Off Phase B Current Limit

Bypass Contactor (K4)Failed

Phase C Current Limit

Bypass Control Failed

Bypass Phase Rotation

Go To Bypass Active

Battery Contactor (K2)Failed

Battery Ground Fault

Page 77: 160Kva UPS Operations Manual

69Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

RECTIFIERMESSAGES --ALARMS

Group1

Group2

RECTIFIERMESSAGES --NOTICES

Group1

Group2

Input Phase Rotation Battery Test Failed

Over Temperature DC Voltage High

Over TemperatureWarning

DC Voltage Low

Rectifier CalibrationRequired

Equalizing Battery

Rectifier DC OverVoltage

Input AC Over Voltage

Rectifier DC UnderVoltage

Input AC Under Voltage

Rectifier Failure Input Over Frequency

Rectifier SetupRequired

Input Transient

Temperature SensorFailure

Input Under Frequency

Input/Battery CurrentLimit

Logic Power Failed

Power Supply OverVoltage

Power Supply UnderVoltage

Rectifier 1.12

Reduced Input CurrentLimit

Testing Battery

Page 78: 160Kva UPS Operations Manual

70 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

MONITORMESSAGES --ALARMS

Group1

Group2

MONITORMESSAGES --NOTICES

Group1

Group2

Battery Test Failed Battery Passed Test

Battery Test Failed Battery Test Aborted(load)

Fan Failure Battery Test Aborted(utility)

Load Over 100% Battery Test RequiresCalibration

Load Over 125% Battery Time Low

Monitor CalibrationRequired

Building Alarm 1 Active

Monitor SetupRequired

Building Alarm 2 Active

Overload Warning Building Alarm 3 Active

Power Supply Failure Building Alarm 4 Active

Building Alarm 5 Active

Building Alarm 6 Active

Inverter Network Down

Monitor Logic Pwr Fail

Monitor Network Down

No Active Events

Output AC OverVoltage

Output AC UnderVoltage

Output Over Frequency

Output UnderFrequency

Power Off Switch

Rectifier Network Down

Testing Battery

Three Wire AC OverVoltage

Three Wire AC UnderVoltage

Three Wire Over Freq.

Three Wire Under Freq.

Page 79: 160Kva UPS Operations Manual

71Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Maintaining the UPS System

The components inside the UPS cabinet are secured to a sturdy metalframe that is supported by the UPS magnetics. This design allows authorizedservice personnel to remove repairable components with very little disassembly.All repairable parts and assemblies are located in the front of the UPS, allowingall routine maintenance and servicing to be performed with front panel access.

You must schedule periodic performance checks of your UPS to keep it runningproperly. Regular routine checks of operation and system parameters will enableyour UPS system to function efficiently for many trouble-free years.

Important Safety Instructions

Remember that your UPS is designed to supply power EVEN WHENDISCONNECTED FROM THE UTILITY POWER. The UPS interior is unsafe until theDC power source is disconnected and the electrolytic capacitors are discharged.After disconnecting the utility power and the DC power, authorized servicepersonnel should wait at least 5 minutes before attempting internal access to theUPS system.

WARNING:LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinetdoors open or protective panels removed. Do not make any assumptions aboutthe electrical state of any cabinet in the UPS system.

WARNING:Battery cabinet maintenance or battery replacement should be performed byauthorized service personnel only. Keep unauthorized personnel away frombattery cabinets.

Since each battery cabinet is an energy source in itself, opening the Battery CircuitBreaker does not de-energize the voltage within the battery cabinet. DO NOTATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY CABINETYOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY CABINET.If you suspect that a battery cabinet needs service, you should contact your localfield service office.

If the cabinet requiring service was not provided by the UPS manufacturer, refer tothe battery cabinet manufacturer’s operating manual for instructions on batterycabinet installation and maintenance, or contact your local field service office.

Page 80: 160Kva UPS Operations Manual

72 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

Observe these precautions when working on or around battery cabinets:

� Remove watches, rings, or other metal objects.

� Use tools with insulated handles.

� Wear rubber gloves and boots.

� Do not lay tools or metal parts on top of batteries or battery cabinets.

� Disconnect the charging source prior to connecting or disconnecting terminals.

� Determine if the battery is inadvertently grounded. If it is, remove the source ofthe ground. Contact with any part of a grounded battery can result in electricalshock. The likelihood of such shock will be reduced if such grounds areremoved during installation and maintenance.

� When replacing batteries, use the same number of sealed, lead-acid batteries.

� Proper disposal of batteries is required. Refer to your local codes for disposalrequirements.

WARNING:HAZARDOUS WASTE. Do not incinerate or dispose of batteriesindiscriminately. Observe local and national codes.

WARNING:Do not dispose of battery or batteries in a fire. The battery may explode.

Do not open or mutilate the battery or batteries. Released electrolyte is harm-ful to the skin and eyes, and may be toxic.

A battery can cause electrical shock, burn from high short-circuit current, orfire. Observe proper precautions.

ATTENTION:Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’in-cendie. Suivre les précautions qui s’imposent.

� Pour le remplacement, utiliser le même nombre et modéle des batteries.

� L’élimination des batteries est règlementée. Consulter les codes locaux à ceteffet.

Page 81: 160Kva UPS Operations Manual

73Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Performing Preventive Maintenance

The UPS requires very little preventive maintenance. However, the UPS should beinspected periodically to verify that the unit is operating normally and that thebatteries are in good condition.

Perform the following checks DAILY:

� Check the area surrounding the UPS. Ensure the area is not cluttered, allowingfree access to the unit.

� Ensure the air intakes (vents on the front doors) and exhaust opening(on top of the UPS cabinet) are not blocked.

� Ensure there is at least six inches of clearance behind the unit for proper aircirculation.

� Ensure the operating environment is within the parameters specified inChapter 10, “Product Specifications.”

� Ensure the UPS is in Normal mode (Normal status indicator is lit). If an alarmlamp is lit or the Normal status indicator is not lit, contact Customer Support.

Perform the following checks MONTHLY:

� Ensure all status indicator lamps are operative. (Press the andpushbuttons simultaneously to test the lamps.)

� Monitor system parameters as described in Chapter 5, “Using the MonitorPanel.”

� Check the air filters (located behind the front doors) and replace them asnecessary. The filter size is 16 in. x 20 in. x 1 in.

� Record the results of your checks and any corrective actions in a suitable log.

ANNUAL maintenance:

Annual preventive maintenance should be performed only by authorized servicepersonnel familiar with maintenance and servicing of the UPS system. Contactyour nearest field service office for more information about service offerings.

BATTERY maintenance:

Contact your nearest field service office for battery maintenance. Batteryreplacement and maintenance should be performed only by authorized servicepersonnel.

Maintenance Training

A basic training course, available from Powerware Corporation, gives you acompetent working knowledge of UPS operation and teaches you how to performfirst level corrective maintenance. For more information about training and otherservices, contact the Powerware Training Coordinator in Raleigh, North Carolina, orcall Powerware Corporation field service at 1--800--843--9433.

Page 82: 160Kva UPS Operations Manual

74 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 83: 160Kva UPS Operations Manual

75Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Product Specifications

The UPS systems are housed in freestanding, double-front cabinetswith safety shields behind the doors. The UPS systems are available in

both 50 Hz and 60 Hz, with various output power ratings. Smaller models within asystem may be upgraded in the field to larger models:

System Models Notes

Powerware 9315 40 140 kVA & 30 kVA 50 Hz or 60 Hz (400V models only)Powerware 9315 50 150 kVA, 40 kVA & 30 kVA 60 Hz onlyPowerware 9315 65 165 kVA & 50 kVA 50 Hz or 60 Hz (400V models only)Powerware 9315 80 180 kVA, 65 kVA & 50 kVA 50 Hz or 60 Hz modelsPowerware 9315 125 100 kVA & 125 kVA 50 Hz or 60 Hz (400V models only)Powerware 9315 130 100 kVA & 130 kVA 50 Hz or 60 Hz (400V models only)Powerware 9315 150 100 kVA, 125 kVA & 150 kVA 50 Hz or 60 Hz modelsPowerware 9315 160 100 kVA, 130 kVA & 160 kVA 50 Hz or 60 Hz models

The following sections detail the input, output, environmental, and batteryspecifications for the UPS.

System Input

Operating InputVoltage

400 VAC for operation from 340 VAC to 440 VAC (50/60 Hz)

208 VAC for operation from 177 VAC to 229 VAC (60 Hz only)

220 VAC for operation from 187 VAC to 242 VAC (60 Hz only)

480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)

400 VAC for operation from 340 VAC to 440 VAC (60 Hz only)

600 VAC for operation from 510 VAC to 600 VAC (60 Hz only)

Operating InputFrequency Range

3 Hz of nominal (50 Hz or 60 Hz)

Operating InputCurrent

Battery Charge:125% of full load for overload + battery chargeActual load + 25% of full load for battery charge

Reduced for Generator:Adjustable, set to 102%

Input CurrentHarmonic Content

10% maximum over zero to full load based on 10% THD at fullload (with input filter option installed)

Power Walk-In Typically 15---20 second rectifier ramp-up to full utility load

Power Factor Minimum 0.9

Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

Page 84: 160Kva UPS Operations Manual

76 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

System Output

Rectifier/Charger Capacity 115% for 160 kVA models125% for 100---150 kVA models

DC Filtering Ripple voltage less than 0.5% peak to peak

UPS Output Capacity 100% current at 0.8 power factor

Output Voltage Regulation 1% (10% to 100% load)

Output Voltage Adjustment 400 VAC nominal, adjustable from 375 VACto 420 VAC (50/60 Hz)

208 VAC nominal, adjustable from 196 VACto 220 VAC (60 Hz only)

220 VAC nominal, adjustable from 208 VACto 232 VAC (60 Hz only)

480 VAC nominal, adjustable from 452 VACto 508 VAC (60 Hz only)

600 VAC nominal, adjustable from 570 VACto 630 VAC (60 Hz only)

400 VAC nominal, adjustable from 395 VACto 420 VAC (60 Hz only)

Output Voltage Harmonic Content 3% max THD, 2% max single (for linear load)

Output Voltage Balance 2% for 100% maximum load imbalance

Output Voltage PhaseDisplacement

2˚ for 100% maximum load imbalance

Output Transients 5% for 100% load step or removal

Frequency Regulation 0.005 Hz free running

Synchronous to Bypass Bypass within voltage limits of +5%, ---8% ofoutput setting; bypass within0.5 Hz

Frequency Slew Rate 1 Hz per second maximum

Overload Capability 1125% for 10 minutes1150% for 10 seconds1000% for 10 cycles with bypass

Maximum Output Capability 300% peak for 10 cycles without bypass

Page 85: 160Kva UPS Operations Manual

77Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Environmental Specifications

Operating Temperature 0 to 40˚C without derating. However, operatingat or near 40˚C will adversely affect battery life(refer to your battery specifications for moreinformation). The recommended operatingtemperature is 25˚C.

Operating Altitude Maximum 1500m (5000 ft) at 40_C withoutderating

Storage Temperature ---20 to +70˚C (prolonged storage above 40˚Cwill cause rapid battery self-discharge)

Relative Humidity (operating andstorage)

95% maximum noncondensing

Acoustical Noise 65 dBA at a 1m distance

EMI Supression Meets FCC Part 15, Subpart J, for class Adevices

Electrostatic Discharge (ESD)Immunity

Meets IEC 801---2 specifications. Withstands upto 25 kV without damage and with nodisturbance or adverse effect to the critical load.

System Efficiency at Full UnityPower Factor Load and NominalInput Voltage

400V, 600V Models: Note: The 208 systems use91% an input auto transformer

option that reduces systemefficiency by 1% to 2%. Theoptional input isolation

480V Models: transformer option reduces92% system efficiency by 3%.

Battery SpecificationsThese specifications are for batteries supplied by the UPS manufacturer inline-up-and-match cabinets:

Battery Type Sealed, maintenance-free, high rate discharge, lead-acidcells

Nominal Battery StringVoltage

480 VDC (240 cells) for Powerware 9315 50, 80, 150, 160420 VDC (210 cells) for Powerware 9315 40, 65, 125, 130

Float Charging 2.25 VDC per cell(540 VDC based on 240 cells)(420 VDC based on 210 cells)

Equalizing Charge 2.35 VDC per cell, set to 2.25 VDC at factory

Battery Charge CurrentLimit

Limited to 25% of full, regardless of actual load on inverter

Page 86: 160Kva UPS Operations Manual

78 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.

Page 87: 160Kva UPS Operations Manual

79Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Responding to System Events

When the UPS system is running in Normal mode, it continuallymonitors itself and the incoming utility power. In Battery or Bypass

modes, the UPS may issue alarms to let you know exactly what event caused thechange from Normal mode. System events can be indicated by horns, lights onthe UPS, or both.

Select Active from the Events menu on the LCD screen to look at the ActiveSystem Events screen. This screen shows any currently active alarms, notices, orcommands.

System Event Horns

The system event horn beeps according to the type of event it is signifying:

� When the UPS detects an alarm that requires your attention, the horn beeps at½-second intervals.

� When a notice occurs, the horn beeps at 2-second intervals.

� If the battery contactor is open and the Bypass mode is unavailable, the hornbeeps every 4 seconds.

System Event Lights

The status indicators on the UPS Monitor Panel work in conjunction with the eventhorn to let you know when the UPS is operating in any mode other than Normal.Only the Normal indicator is visible during normal UPS operation. The others lightto indicate alarms or events. When an alarm occurs, you should first check theseindicators to see what type of event has taken place. (For descriptions of thestatus indicators, refer to the “Reading the Status Indicators” section of Chapter 5.)

Page 88: 160Kva UPS Operations Manual

80 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

System Event Messages

When a system event occurs, a message is added to the Event History Log. Amessage may also appear on the Monitor Panel of the UPS. The Event History Logcontains all system event messages, whether or not they were displayed on theMonitor Panel.

INVERTER MESSAGES -- ALARMS INVERTER MESSAGES -- NOTICES

Inverter DC Over VoltageClear Inverter DC Over Voltage

Bypass AC Over VoltageClear Bypass AC Over Voltage

Inverter AC Over VoltageClear Inverter AC Over Voltage

Bypass AC Under VoltageClear Bypass AC Under Voltage

Inverter AC Under VoltageClear Inverter AC Under Voltage

Bypass Over FrequencyClear Bypass Over Frequency

Inverter Over FrequencyClear Inverter Over Frequency

Bypass Under FrequencyClear Bypass Under Frequency

Inverter Under FrequencyClear Inverter Under Frequency

Battery DC Under VoltageClear Battery DC Under Voltage

Over Temperature Shutdown Battery Not ChargedClear Battery Not Charged

100% Overload Shutdown Bypass is Not AvailableBypass is Available

125% Overload Shutdown Input Breaker Open

Battery Cont. (K2) Failure Inv. Logic Power FailureClear Inv. Logic Pwr Fail.

Bypass Cont. (K4) Failure Phase A Current LimitPhase B Current LimitPhase C Current Limit

Bypass Control Failure Load Transferred to Bypass

Inverter Cont. (K3) Failure

Inverter Failure

Load Off

Inverter Cont. (K3) Open

Bypass Cont. (K4) Failure

Page 89: 160Kva UPS Operations Manual

81Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

INVERTER MESSAGES --COMMANDS INVERTER STATUS MESSAGES

Bypass ModeNormal Mode

Inverter OnInverter Off

Keyswitch On Battery Contactor (K2) ClosedBattery Contactor (K2) Opened

Inverter Commanded OnInverter Commanded Off

Total Battery Discharge

Bypass Contactor (K4) ClosedBypass Contactor (K4) Opened

Input Breaker (CB1) ClosedInput Breaker (CB1) Opened

Inverter Contactor (K3) ClosedInverter Contactor (K3) Opened

Inverter Shutdown

Inverter Normal

Load Transferred to Bypass

Auto Mode

RECTIFIER MESSAGES -- ALARMS RECTIFIER MESSAGES -- NOTICES

Rectifier DC Over VoltageClear Rectifier DC Over Voltage

Input AC Over VoltageClear Input AC Over Voltage

Rectifier DC Under VoltageClear Rectifier DC Under Voltage

Input AC Under VoltageClear Input AC Under Voltage

Rectifier Over TemperatureClear Rectifier Over Temperature

Input AC Over FrequencyClear Input AC Over Frequency

Rct. Over Temperature WarningClear Rct. Over Temp. Warning

Input AC Under FrequencyClear Input AC Under Frequency

Rct. Temp. Sensor FailureClear Rct. Temp. Sensor Failure

Rct. Logic Pwr Supply OVClear Rct. Logic Pwr Sply OV

Rectifier Failure Rct. Logic Pwr Supply UVClear Rct. Logic Pwr Sply UV

Rectifier Alarm Rectifier DC Too Low

Input Voltage Transient

Rct. Logic Pwr Fail.Clear Rct. Logic Pwr Fail.

Battery Current LimitClear Battery Current Limit

DC Too High

Page 90: 160Kva UPS Operations Manual

82 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

RECTIFIER MESSAGES --COMMANDS RECTIFIER STATUS MESSAGES

Rectifier Commanded OnRectifier Commanded Off

Rectifier OnRectifier Off

Rectifier Shutdown

MONITOR PANEL ALARMS MONITOR PANEL NOTICES

Load Over 100%Clear Load Over 100%

Output AC Over VoltageClear Output AC Over Voltage

Overload 100%Clear Overload 100%

Output AC Under VoltageClear Output AC Under Voltage

Overload 125%Clear Overload 125%

Output Over Freq.Clear Output Over Freq.

Power Supply FailureClear Power Supply Fail.

Output Under FrequencyClear Output Under Frequency

Fan FailureClear Fan Failure

3W AC Over VoltageClear 3W AC Over Voltage

3W AC Under VoltageClear 3W AC Under Voltage

3W Over FrequencyClear 3W Over Frequency

3W Under FrequencyClear 3W Under Frequency

Power FailClear Power Fail

Power Off Switch

Building Alarm 1Clear Building Alarm 1

Building Alarm 2Clear Building Alarm 2

Building Alarm 3Clear Building Alarm 3

Building Alarm 4Clear Building Alarm 4

Building Alarm 5Clear Building Alarm 5

Building Alarm 6Clear Building Alarm 6

Rectifier Network DownRectifier Network Clear

Inverter Network DownInverter Network Clear

Monitor Network DownMonitor Network Clear

Page 91: 160Kva UPS Operations Manual

83Powerware 9315 30---160kVA UPS Operation164200252 Rev. I 023000

Using the LOAD OFF Pushbutton

Load Off is initiated by the covered, red LOAD OFFpushbutton on the Monitor Panel. This pushbutton is protected by

a clear plastic shield to prevent accidental activation. In an emergency, you canpress this pushbutton to instantaneously open the input breaker and interrupt UPSoutput. The UPS is cut off from utility power, and your critical load is de-energized.All power to the critical load is lost. The UPS (including Bypass) remains locked offuntil you reset the LOAD OFF pushbutton.

WARNING:All power to the critical load is lost when you press this pushbutton. You shoulduse this feature only in an emergency or when you want to de-energize the criticalload.

To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure“Resetting the UPS System after Load Off” of this chapter before starting the UPS.

NOTE: The Remote Emergency Load Off option functions the same way as theLOAD OFF pushbutton on the Monitor Panel.

To Use the LOAD OFF Pushbutton:

1. Raise the clear plastic shield covering the red LOAD OFF pushbutton on theMonitor Panel.

2. Press the LOAD OFF pushbutton.

The breaker and contactors open (you can hear them opening). The CB1 switchtrips, and the Load Off PUSH TO RESET pushbutton on the UPS Control Panel popsout. The UPS system shuts down.

Resetting the UPS System after Load Off

CAUTION:Do not attempt to restart the system after Load Off until the cause of theemergency has been identified and cleared.

The Load Off PUSH TO RESET pushbutton is a small white button on the UPSControl Panel. The PUSH TO RESET pushbutton pops out and the CB1 switchtrips when the LOAD OFF pushbutton on the Monitor Panel is activated.

To reset the UPS system:

1. Press the Load Off PUSH TO RESET pushbutton until it clicks in and remainsrecessed.

2. Move the CB1 switch from the center (tripped) position to OFF. The switchshould be difficult to move from the TRIPPED position.

3. The UPS system is now reset. To restart the UPS system, follow the procedurein Chapter 4, “Starting and Stopping the UPS.”

Page 92: 160Kva UPS Operations Manual

84 Powerware 9315 30---160kVA UPS Operation164200252, Rev. I 023000

This Page Intentionally Left Blank.