1704-1R1611 Commercial Air Conditioners 2017 R410A 50Hz Rooftop Package iOS Version Android Version Midea CAC After-service Application iOS Version Midea CAC News Application Commercial Air Conditioner Division Midea Group Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China Postal code: 528311 Tel: +86-757-26338346 Fax: +86-757-22390205 cac.midea.com global.midea.com Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this document. ISO 9001 Q u a li t y A s s u r a n c e ISO 14001 E n v i r o n m e n t a l M a n a g e m e n t OHSAS 18001 O c c u p a t i o n a l H e a l t h a n d S a f e t y A s s e s s m e n t

1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

1704-1R1611

Commercial Air Conditioners 2017

R410A 50Hz

Rooftop Package

iOS Version Android Version

Midea CAC After-service Application

iOS Version

Midea CAC News Application

Commercial Air Conditioner DivisionMidea GroupAdd.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China

Postal code: 528311

Tel: +86-757-26338346 Fax: +86-757-22390205

cac.midea.com global.midea.com

Note: Product speci�cations change from time to time as product improvements and

developments are released and may vary from those in this document.

ISO9001

Quality Assurance

ISO14001

Envi

ro

nmental Management OHSAS

18001

Occup

atio

nal H

ealth and Safety Assessment

Page 2: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

There are three production bases: Shunde, Chongqing and Hefei.

MCAC Shunde: 38 product lines focusing on VRF, Split Products, Heat Pump Water Heaters, and AHU/FCU.

MCAC Chongqing: 14 product lines focusing on Water Cooled Centrifugal/Screw/Scroll Chillers, Air Cooled Screw/Scroll Chillers,

and AHU/FCU.

MCAC Hefei: 11 product lines focusing on VRF, Chillers, and Heat Pump Water Heaters.

Midea CACMidea CAC is a key division of the Midea Group, a leading producer of consumer appliances and provider of heating, ventilation

and air conditioning solutions. Midea CAC has continued with the tradition of innovation upon which it was founded, and

emerged as a global leader in the HVAC industry. A strong drive for advancement has created a groundbreaking R&D

department that has placed Midea CAC at the forefront of a competitive field. Through these independent efforts and joint

cooperation with other global enterprises, Midea has supplied thousands of innovative solutions to customers worldwide.

2015 JV with Carrier in China in chiller field, BOSCH in VRF production and Siix in smart control

2014 Launched the rooftop package ClimaCreator globally

2010 Built the 3rd manufacturing base in Hefei

2008 Launched the rooftop package ClimaMaster globally

2007 Won the first Midea centrifugal chiller project overseas

2006 Launched the first VSD centrifugal chiller

2004 Acquired MGRE entered the chiller industry

2001 Partnered with Copeland to develop the digital scroll VRF system

2000 Developed the first inverter VRF With Toshiba

1999 Entered the CAC field

Midea Company Introduction

Midea CAC Introduction

Page 3: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

03 04

Intr

oduc

tion

Introduction

Midea rooftop package air conditioners are designed and manufactured to off the all-in-one solutions for large halls, ware-

houses or other appliations.

Midea rooftop package air conditioner are totally two series: ClimaCreator series and ClimaMaster series.

380~415V 3Ph~ 50Hz

T1

T1

Tropical (T3)

380~415V 3Ph~ 50Hz

Heat pump

Heat pump

Cooling only

7.5RT~25RT

Tropical (T3) Cooling only 4RT~30RT

3RT~5RT

Heat pump 6.2RT~30RT

Cooling only+EHK 6.2RT~30RT

5RT~30RT

R410A

ClimaCreator series

R410A

ClimaMaster series

Power supply Application Function Cooling capactity rangeSeries

Notes: 1. Product’s cooling capacity as per specification.

Golden Dragen Mart1,320RTBarka, Oman

Traki Store560RTValencia, Venezuela

Contents

22 ClimaMaster Series

41 Controllers

10 ClimaCreator Series

05 General Features

10 Product lineups

11 Specifications16 Dimensions

22 Product lineups

23 Specifications

33 Dimensions

Page 4: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

05 06

General Features

Gen

eral

Fea

ture

s

Gen

eral

Fea

ture

s

Removable access door on the electric box. It is easy to

move the cover of the electric box.

Only connect the wires of power supply, and no need

to connect any signal wires.

Convenient for wires connection

Easy to installation

Reserved external drainage port, quickly and accurately

connect the rubber drainage pipe.

Easily connect the drainage pipe

Famous brand compressor: Copeland, Hitachi, Danfoss,

etc. More reliable.

No complex internal suction and discharge valves for

quieter operation and higher reliability.

Compact, light-weight design, and fewer moving parts

design.

Reliable scroll compressor

The rooftop package air conditioners with special anti-corrosion treatment are suitable for seaside areas or the areas

exposed to acidic substances.

Customized anti-corrosion treatment

Multi-measurement to ensure units operate normally

and reliably:

System current protection, High/low pressure switch

protection, Temperature sensor on/off protection, etc.

Three-phase protector can be customized.

Multi-protection design

Temperature sensorHP/LP switch

Special anti-corrosion treatment of heat exchanger

provides 5 to 6 times greater resistance against acid

rain and salt corrosion.

All PCB parts in the unit are coated with double-side

moisture proof paint. The outer side of electric box

metal cover is spray-painted.

All screws are anti-rust.

Casings of the unit and motors are anti-rust.

Convenient for unit selection

Wide cooling capacity range, from 36000Btu/h to 360000Btu/h.

Wide cooling capacity range

Compact design.

Flanges of air flow inlet and outlet as standard.

It is suitable for installation in rooftop and ground.

Design �exibility

Pre-painted exterior cabinet panels pass 1000 hours Salt Spray Test for durability.

Weather-resistant construction with capped steams and sloped top panels.

G90 galvanized heavy gauge plate conforming to ASTM-A-653.

Durable construction

Outstanding reliability

ClimaMaster series ClimaCreator series

Page 5: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

07 08

Multi-accessories

EHK (Electric Heater Kits) √

√ √

Filter

Three-phase protector

Network interface module

Anti-corrosion fin

Drainage pipe

Snap ring

Outlet drainage

Description

Standard accessories Optional accessories

ClimaCreator series ClimaMaster series

Standard accessories Optional accessories

The unit provides external pressure gauge ports for convenient and fast checking

system pressure without removing the panel.

External pressure gauge ports

Removable the access doors on the filter, fan motor, and electric box sections.

Provide convenient access to system components for mainenance and service.

Easy access doors design

Press the ‘Check’ button, the LED display in PCB board of the unit will dislay the normal checking code.

If the unit is in running with abnormal operation, the LED display will show the error code.

System self-diagnostic

Washable �lter

Easy to maintenance

Electric box

Access panel for electric box

Flexible choise of accessories

CCM30

Max.64

MD-NIM01 MD-NIM01 MD-NIM01 MD-NIM01

Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be

connected between rooftop package units and centralized controller.

Controllers

Wired controller as standard.

Besides standard wired controller, others can be chosen too.

KJR-12B/dP(T)-E

Other brand thermostat can be matched as optional solution.

Non-programmable thermostat

SW3: set to 1SW3

Gen

eral

Fea

ture

s

Gen

eral

Fea

ture

s

Page 6: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

09 10

Mechanical speci�cation

Product lineups

ClimaCreator Series

Through changing the working pitch diameter of the pulley

mounted on driver shaft, in turn the revolutions per minute of the

driven shaft will increase or decrease to change air volume.

Adjustable pulley

Three thickness filter: 0.5inch, 1inch and 2inch;

Two kinds of filter materials: Metal or Nylon + Metal frame.

EHK (Electric Heater Kits) and control box can be customized.

Air intake �lter & EHK as optional

T1

Applications

Tropical (T3)

Applications

Nominal ton* 4 5 6.2 7.5 8.5 10 12.5 17.515 20 25 30

Notes:

1. * Nominal ton only for reference.

2. means cooling type product; means heat pump type product.

3. Cooling or heating capacity as per specifications.

Gen

eral

Fea

ture

s

Clim

aCre

ator

Ser

ies

GeneralThe units are convertible airflow. All units are factory assembled, internally wired, fully charged refrigerant and 100% run tested to check cooling and heating operation, fan and blower rotation, and control sequence before leaving the factory. Wiring internal to the unit is colored and numbered for simplified identification. The unit is provided with an integral weather resistant control panel.

CasingUnit casing is constructed of Zinc coated, heavy gauge, galvanized steel. Exterior surfaces are cleaned, G90 galvanized heavy gauge plate conforming to ASTMA 653, followed by baked on electrostatic polyester dry powder coat paint on all external panels, completely weatherized for outdoor installation and propely reinforced and brazed. Salt Spray Test for steel sheet under 1000 hours, specially treated can be up to 2000 hours and even more. Cabinet contruction allows for all maintenance. Service panels are removed easily and reinstalled by removing bolts. All panels and top covers indoor side of the unit are insulated with 16mm, foam-faced, closed-cell insulation. The unit has provisions for forklift and crane lifting, with forklift capabilities on four sides of the unit.

CompressorsAll units have direct-drive, hermetic, scroll type compressors with centrifugal type oil pump. Motor is suction gas-cooled and has a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads are provided with the scroll compressors.Compressors used in Rooftop Package unit are hermetically sealed reciprocating type. They are equipped with a crankcase heater as standard.The compressors, incorporating a built-in muffler, are mounted on spring within a heavy gauge steel housing to give a low noise level.The unit contains the best compressor technology available to achieve the highest possible performance. Dual compressors are outstanding for humidity control, light load cooling conditions and system back-up applicaitons.

ControlsThe unit is completely factory-wired with necessary controls and terminal block for power wiring. The unit provides an external location for mounting a fused disconnect device.Microprocessor controls provide for all 24V control functions. The precision control makes all heating, cooling, or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures.The control maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized micro-processor provides a higher level of machine protection.

CoilsInternally finned, copper tubes mechanically bonded to a configured hydrophilic aluminum fin is standard. Coils are leak tested under 3100KPa (450 psig) at the factory to ensure the pressure integrity.

Electronic thermostatsGeneral information: A dedicated electronic thermostat is supplied with unit controls as standard. It controls one or two stage cooling applications. The thermostat normally displays room temperature and mode of operation. It also allows to select continuous fan operation, or has the fan on intermittent operation with the equipment. Finally, it displays the status of unit, thus providing maximum information for the user.

Page 7: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

11 12

T1 application, 380-415V 3Ph~ 50Hz

Speci�cations Speci�cations

6.2RT & 7.5RT 8.5RT & 10RT 12.5RT

T1 application, 380-415V 3Ph~ 50Hz

15RT 17.5RT & 20RT 25RT & 30RT

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Heating capacity test condition (2): Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 26.7°C DB / 19.4°C WB;

2. Units are suitable for operation to ±20% of nominal CFM;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Heating capacity test condition (2): Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 26.7°C DB / 19.4°C WB;

2. Units are suitable for operation to ±20% of nominal CFM;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Clim

aCre

ator

Ser

ies

Clim

aCre

ator

Ser

ies

Nominal ton*

Cooling

Heating

Model

Air flow Indoor side

External static pressure

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

Cooling

Heating

DimensionNet (W×H×D)

Weight

Ambienttemperature

Wired controller

Net / Gross

Packing (W×H×D)

CapacityBtu/h

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

mm

dB(A)

mm

kg

kW

kW

A

Input

EER

Capacity

Input

COP

Type / Quantity

Brand

75,000

22.0

6.6

11.4

89,000

26.0

7.5

11.9

2,800

Default: 80; 0 ~ 250

18.3

Scroll / 1

Copeland

Centrifugal / Direct

Axial / Direct

KJR-25B

8,600

MRC-062HWN1-R(C)

1,475×840×1,130

1,495×870×1,150

229/234

10°C ~ 46°C

6.2

89,000

26.0

7.9

11.3

103,000

30.0

8.9

11.6

2,830

Default: 80; 0 ~ 250

24.8

Scroll / 1

Danfoss

Axial / Direct

KJR-25B

Centrifugal / Direct

12,000

MRC-075HWN1-R(C)

1,475×840×1,130

1,495×870×1,150

325/335

10°C ~ 46°C

7.5

103,000

30.0

9.3

11.1

120,000

35.0

10.6

11.3

3,500

Default: 80; 0 ~ 200

26.5

Scroll / 2

Hitachi

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

13,600

MRC-085HWN1-R(C)

1,483×1,138×1,231

1,500×1,255×1,155

340/350

10°C ~ 46°C

8.5

120,000

35.0

10.7

11.2

137,000

40.0

11.9

11.5

4,100

Default: 90; 0 ~ 250

28.8

Scroll / 2

Hitachi

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

16,000

MRC-100HWN1-R(C)

1,483×1,138×1,231

1,500×1,255×1,155

343/354

10°C ~ 46°C

10

150,000

44.0

13.3

11.3

154,000

45.0

13.2

11.7

5,500

Default: 110; 0 ~ 275

38.2

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller (Optional)

Sound pressure level

No

71.0 72.1 71.5 71.5

No Yes Yes Yes

71.8

Centrifugal / Belt

19,700

MRC-125HWN1-R(C)

1,965×1,230×1,130

1,995×1,255×1,160

451/471

10°C ~ 46°C

-9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C

12.5

-9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C -9°C ~ 24°C

Nominal ton*

Cooling

Heating

Model

Air flow Indoor side

External static pressure

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Wired controller

Net / Gross

Packing (W×H×D)

CapacityBtu/h

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

mm

dB(A)

mm

kg

kW

kW

A

Input

EER

Capacity

Input

COP

Type / Quantity

Brand

180,000

53.0

16.7

10.8

191,000

56.0

17.2

11.1

7,000

Default: 110; 0 ~ 325

46.1

Scroll / 2

Copeland

Centrifugal / Belt

Axial / Direct

KJR-12B/dP(T)-E

25.0

MRC-150HWN1-R(C)

1,965×1,230×1,130

1,995×1,255×1,160

492/512

10°C ~ 46°C

15

208,000

61.0

19.1

10.9

218,000

64.0

19.5

11.2

7,600

Default: 110; 0 ~ 250

55.4

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

27.0

MRC-175HWN1-R(C)

1,670×1,247×2,192

1,695×1,284×2,212

615/645

10°C ~ 46°C

17.5

240,000

70.0

22.6

10.6

260,000

75.0

23.6

11.0

8,800

Default: 120; 0 ~ 375

63.2

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

32.5

MRC-200HWN1-R(C)

1,670×1,247×2,192

1,695×1,284×2,212

690/720

10°C ~ 46°C

20

300,000

88.0

28.9

10.4

330,000

97.0

30.3

10.9

10,000

Default: 130; 0 ~ 350

74.3

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Sound pressure level

Centrifugal / Belt

38.5

MRC-250HWN1-R(C)

2,320×1,245×2,220

2,330×1,275×2,230

940/970

10°C ~ 46°C

25

335,000

98.0

32.8

10.2

380,000

111.5

36.5

10.4

11,200

Default: 270; 25 ~ 400

81.7

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller (Optional) Yes Yes Yes Yes

76.9 76.0 75.3 76.8 77.9

Yes

Centrifugal / Belt

49.5

MRC-300HWN1-R(C)

2,320×1,245×2,220

2,330×1,275×2,230

955/985

10°C ~ 46°C

30

Ambienttemperature

Cooling

Heating

Page 8: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

13 14

Tropical (T3) application, 380-415V 3Ph~ 50Hz

Speci�cations

6.2RT & 7.5RT 8.5RT

Speci�cationsTropical (T3) application, 380-415V 3Ph~ 50Hz

8.5RT & 10RT 12.5RT

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Units are suitable for operation to ±20% of nominal CFM;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Units are suitable for operation to ±20% of nominal CFM;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Nominal ton*

Cooling

Model

Air flow Indoor side

External pressure level

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

48,000

12.4

Scroll / 1

Copeland

Centrifugal / Direct

Axial / Direct

KJR-12B/dP(T)-E

6.2

MRCT-48CWN1-R(C)

1,310×840×900

1,340×865×935

167/170

10°C ~ 52°C

4

58,000

15.5

Scroll / 1

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Direct

7.4

MRCT-60CWN1-R(C)

1,310×840×900

1,340×865×935

180/183

10°C ~ 52°C

5

75,000

22.0

6.6

11.4

61,400

18.0

7.8

7.9

2,800

Default: 80; 0 ~ 250

19.3

Scroll / 1

Copeland

Axial / Direct

KJR-25B

Centrifugal / Direct

9.0

MRCT-062CWN1-R(C)

1,475×840×1,130

1,495×870×1,150

223/228

10°C ~ 52°C

6.2

89,000

26.0

7.9

11.3

69,600

20.4

9.0

7.8

2,830

Default: 80; 0 ~ 250

14.1

4.1

11.7

39,000

11.4

4.8

8.1

1,750

Default: 75; 0 ~ 200

17.0

5.0

11.6

47,900

14.0

5.9

8.1

2,000

Default: 75; 0 ~ 200

27.2

Scroll / 1

Danfoss

Axial / Direct

KJR-25B

Centralized controller (Optional) Yes Yes No

Sound pressure level 64.4 66.3 71.0

No

71.5

Centrifugal / Direct

13.6

MRCT-075CWN1-R(C)

1,475×840×1,130

1,495×870×1,150

231/236

10°C ~ 52°C

7.5 Nominal ton*

Cooling

Model

Air flow Indoor side

External static pressure

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

102,000

30.0

9.2

11.1

80,700

23.7

10.3

7.9

3,500

Default: 80; 0 ~ 200

29.2

Scroll / 2

Hitachi

Centrifugal / Belt

Axial / Direct

KJR-12B/dP(T)-E

14.8

MRCT-085CWN1-R(C)

1,483×1,231×1,138

1,500×1,255×1,155

331/342

10°C ~ 52°C

8.5

102,000

30.0

9.2

11.1

80,700

23.7

10.3

7.9

3,500

Default: 80; 0 ~ 200

29.2

Scroll / 1

Copeland

Axial / Direct

KJR-23B

Centrifugal / Belt

14.8

MRCT-085WN1-R(D)

1,483×1,231×1,138

1,500×1,255×1,155

302/313

10°C ~ 52°C

8.5

120,000

35.0

10.7

11.2

100,200

29.4

12.6

8.0

4,100

Default: 90; 0 ~ 250

34.1

Scroll / 2

Hitachi

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

18.0

MRCT-100CWN1-R(C)

1,483×1,231×1,138

1,500×1,255×1,155

335/346

10°C ~ 52°C

10

120,000

35.0

10.7

11.2

100,200

29.4

12.6

8.0

4,100

Default: 90; 0 ~ 250

34.1

Scroll / 1

Copeland

Axial / Direct

KJR-23B

Centrifugal / Belt

18.0

MRCT-100CWN1-R(D)

1,483×1,231×1,138

1,500×1,255×1,155

323/335

10°C ~ 52°C

10

150,000

44.0

13.3

11.3

125,400

36.8

16.1

7.8

5,500

Default: 110; 0 ~ 275

41.2

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller (Optional) Yes No Yes No

Sound pressure level 70.3 71.7 72.6 72.4

Yes

71.8

Centrifugal / Belt

21.0

MRCT-125CWN1-R(C)

1,965×1,230×1,130

1,995×1,255×1,160

433/453

10°C ~ 52°C

12.5

4RT & 5RT

Clim

aCre

ator

Ser

ies

Clim

aCre

ator

Ser

ies

Page 9: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

15 16

DimensionsClimaCreator seriesTropical (T3) application: MRCT-48CWN1-R(C), MRCT-60CWN1-R(C)(Units: mm)

Speci�cationsTropical (T3) application, 380-415V 3Ph~ 50Hz

15RT 17.5RT & 20RT 25RT & 30RT

Maintain orifice for air supply motor

Hole for bottom installation8-15×25

8871,294

840

60273

5181,310

63

42169

647

900

736

776

211

238

478

211

855

900

3961,2651,310

518

60

100314

280

370

250

285

310

280327

280

180

Nominal ton*

Cooling

Model

Air flow Indoor side

External static pressure

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

180,000

53.0

16.7

10.8

146,000

42.8

18.7

7.8

7,000

Default: 110; 0 ~ 325

48.0

Scroll / 2

Copeland

Centrifugal / Belt

Axial / Direct

KJR-12B/dP(T)-E

25.0

MRCT-150CWN1-R(C)

1,965×1,230×1,130

1,995×1,255×1,160

470/490

10°C ~ 52°C

15

208,000

61.0

19.1

10.9

181,100

53.1

22.6

8.0

7,600

Default: 110; 0 ~ 250

55.0

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

26.5

MRCT-175CWN1-R(C)

1,670×1,247×2,192

1,695×1,284×2,212

590/620

10°C ~ 52°C

17.5

240,000

70.0

22.6

10.6

199,200

58.4

25.1

7.9

8,800

Default: 120; 0 ~ 375

66.9

Scroll / 2

Copeland

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

33.0

MRCT-200CWN1-R(C)

1,670×1,247×2,192

1,695×1,284×2,212

670/700

10°C ~ 52°C

20

300,000

87.0

28.0

10.7

251,700

73.8

32.0

7.9

10,000

Default: 110; 0 ~ 350

77.4

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centrifugal / Belt

40.5

MRCT-250CWN1-R(C)

2,320×1,245×2,220

2,330×1,275×2,230

895/925

10°C ~ 52°C

25

360,000

105.0

34.3

10.5

336,300

98.6

41.8

8.0

12,000

Default: 270; 0 ~ 400

94.1

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller Yes Yes Yes Yes

Sound pressure level 75.5 75.0 75.3 76.8

Yes

77.9

Centrifugal / Belt

49.5

MRCT-300CWN1-R(C)

2,320×1,245×2,220

2,330×1,275×2,230

910/940

10°C ~ 52°C

30

Clim

aCre

ator

Ser

ies

Clim

aCre

ator

Ser

ies

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Units are suitable for operation to ±20% of nominal CFM;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Page 10: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

17 18

ClimaCreator series T1 application: MRC-062HWN1-D(C), MRC-075HWN1-R(C)Tropical (T3) application: MRCT-062CWN1-R(C), MRCT-075CWN1-R(C)(Units: mm)

Condenser fan

Maintain orifice for air supply motor

Hole for bottom installation8-15×20

1,4591,115

840

6063

280

6681,475

42189

857

1,130

60

306

102

1,016

966

1,430

668 404

231

1,08

566

8

1,13

0

1,475

370327

328

294

310

285

370

327

310

328

294

285

ClimaCreator seriesT1 application: MRC-085HWN1-R(C), MRC-100HWN1-R(C)Tropical (T3) application: MRCT-085CWN1-R(C), MRCT-085CWN1-R(D), MRCT-100CWN1-R(C), MRCT-100CWN1-D(C)(Units: mm)

Condenser fan

Maintain orifice for air supply motor

1462

1117

1222

123

123388

700

105

105

284

560

392423

338 36

9

165

580 60

4

952

982

1,130

820

655

105

180

559

1,09

0

180

1,13

0

655

952982

581

369

339

423392

123265265 7001,4351,475

Hole for bottom installation10-15×20

Clim

aCre

ator

Ser

ies

Clim

aCre

ator

Ser

ies

Page 11: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

19 20

ClimaCreator seriesT1 application: MRC-125HWN1-R(C), MRC-150HWN1-R(C)Tropical (T3) application: MRCT-125CWN1-R(C), MRCT-150CWN1-R(C)(Units: mm)

Hole for bottom installation 12-15×20

74506 801 506

232

232

665

74

972

467

555

335

67 165

67165666

75

75508

800

508

Condenser fan

Maintain orifice for air supply motor

1,130

1,965

1,22

7

1,1151,953

ClimaCreator seriesT1 application: MRC-175HWN1-R(C), MRC-200HWN1-RTropical (T3) application: MRCT-175CWN1-R(C), MRCT-200CWN1-R(C)(Units: mm)

Condenser fan

Compressor panel

Hole for bottom installation

14-15×20

8×Φ4.2

14×Φ4.2

Horizontal supply opening

Horizontal return opening

Maintain orifice for air supply motor

2,1711,654

1,247

2,192125

125

800

125

695

800

1,670 125434

Control panel

2,192

569

804

569

125

1,670800 310 12520

2,014

512

438 394 394 394

404 315 403 578

102 512 512 512

32.5

641

2520

230

020

232

731

108

297

Clim

aCre

ator

Ser

ies

Clim

aCre

ator

Ser

ies

Page 12: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

21 22

ClimaCreator seriesT1 application: MRC-250HWN1-R(C), MRC-300HWN1-R(C)Tropical (T3) application: MRCT-250CWN1-R(C), MRCT-300CWN1-R(C)(Units: mm)

Hole for wires

Drain connection hole

Maintain orifice for air supply motor

Condenser fan

Horizontal supply opening

Horizontal return opening

Hole for bottom installation

16-15×20

2,220900

1,24

5

9002,320

130 130650 450900

130

130

500

500

900

490300

450 450 450

1,960

450

450

320

300

360

640

250

250

Product lineups

ClimaMaster Series

Notes:

1. * Nominal ton only for reference.

2. means cooling type product; means cooling type product with EHK; means heat pump type product.

3. Cooling or heating capacity as per specifications.

T3Applications

T1Applications

Nominal ton* 543 6.2 7.5 10 15 17.5 20 3012.58.5

Clim

aCre

ator

Ser

ies

Clim

aMas

ter S

erie

s

Page 13: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

23 24

Speci�cationsT1 application, heat pump, 380~415V 3Ph~ 50Hz

Model

External static pressure

Nominal ton*

Cooling

Heating

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Centralized controller

Net / Gross

Packing (W×H×D)

Side-discharge Side-discharge Side-discharge

36,000 48,000 58,000

10.55 14.07 17.29

3.05 4.79 5.64

11.8 10.0 10.3

37,500 51,500 62,500

10.99 15.09 18.32

3.00 4.56 5.21

12.5 11.3 12.0

1,500 1,858 2,045

50 50 50

4.25 6.05 7.05

6.4 8.8 10.9

Scroll / 1 Scroll / 1 Scroll / 1

Copeland Copeland Copeland

Centrifugal / Direct

Axial / Direct Axial / Direct Axial / Direct

- - -

Centrifugal / Direct Centrifugal / Direct

MRC-36HWN1-R MRC-48HWN1-R MRC-60HWN1-R

Type

Btu/h

kW

Btu/h.W

CFM

Pa

1,116×830×744

No No

Sound pressure level 64.9 67.7 68.8

No

1,116×830×744 1,116×830×744

1,152×855×765 1,152×855×765 1,152×855×765

139/142 146/149 159/162

21°C ~ 43°C 21°C ~ 43°C 21°C ~ 43°C

mm

dB(A)

mm

kg

kW

Btu/h

kW

Btu/h.W

kW

kW

A

Capacity

Input

EER

Capacity

Input

COP

Type / Quantity

Brand

3 4 5

Notes:

1. Cooling capacity test condition: Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Heating capacity test condition: Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Tropical (T3) application, cooling only, 380~415V 3Ph~ 50Hz

5RT 8.5RT6.2RT & 7.5RT

Model

External static pressure

Nominal ton*

Cooling

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 59,000

Two-way air out-in Side-discharge

89,000

Type

17.0 26.0

5.6 9.2

10.5 9.7

51,200 74,500

15.0 21.8

6.7 9.9

7.6 7.5

1,800 3,000

50 60

18.0 25.6

Scroll / 1 Scroll / 1

Copeland Danfoss

Centrifugal / Direct

Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centrifugal / Belt

8.1 12.0

MRBT-60CWN1-R MRBT-075CWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

1,920×840×1,068 1,630×1,068×1,065

1,955×870×1,085 1,700×1,110×1,155

230/234 315/335

18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

5

75,000

Side-discharge

22.0

7.7

9.7

62,700

18.4

8.6

7.3

2,600

60

20.1

Scroll / 1

Danfoss

Centrifugal / Direct

Axial / Direct

KJR-12B/dP(T)-E

10.4

MRBT-062CWN1-R

1,630×1,068×1,065

1,700×1,110×1,155

315/335

18°C ~ 52°C

6.2 7.5

Side-discharge

103,000

30.0

10.4

9.8

85,600

25.1

11.4

7.5

3,600

75

26.3

Scroll / 1

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller Yes YesYes

Sound pressure level 62.0 75.174.7

Yes

76.8

Centrifugal / Belt

13.6

MRBT-085CWN1-R

2,165×1,002×1,335

2,220×1,040×1,415

445/458

18°C ~ 52°C

8.5

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 14: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

25 26

Tropical (T3) application, cooling only, 380~415V 3Ph~ 50Hz

10RT 15RT12.5RT

Model

External static pressure

Nominal ton*

Cooling

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 120,000

Side-discharge Side-discharge

150,000

Type

35.0 43.0

11.8 15.3

10.2 9.8

100,000 125,600

29.3 34.2

13.1 16.8

7.6 7.5

3,800 5,600

75 90

30.0 41.6

Scroll / 1 Scroll / 2

Danfoss Copeland

Centrifugal / Direct

Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centrifugal / Belt

16.0 20.0

MRBT-100CWN1-R MRBT-125CWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

2,165×1,002×1,335 2,229×1,245×1,400

2,220×1,040×1,415 2,265×1,280×1,455

445/458 520/535

18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

10 12.5

Side-discharge

180,000

53.0

18.0

10.0

159,600

46.7

21.3

7.5

6,600

90

53.0

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller Yes Yes

Sound pressure level 77.2 77.1

Yes

77.4

Centrifugal / Belt

27.0

MRBT-150CWN1-R

2,229×1,245×1,825

2,236×1,280×1,855

710/730

18°C ~ 52°C

15

Tropical (T3) application, cooling only, 380~415V 3Ph~ 50Hz

17.5RT 30RT20RT

Model

External static pressure

Nominal ton*

Cooling

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 210,000

Side-discharge Side-discharge

240,000

Type

60.0 70.0

20.0 23.6

10.5 10.2

180,600 213,000

52.9 62.4

23.5 27.7

7.7 7.7

7,300 8,400

90 100

57.8 66.0

Scroll / 2 Scroll / 2

Danfoss Danfoss

Centrifugal / Direct

Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centrifugal / Belt

29.0 36.0

MRBT-175CWN1-R MRBT-200CWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

2,229×1,245×1,825 2,753×1,245×2,157

2,236×1,280×1,855 2,760×1,280×2,175

730/750 925/940

18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

17.5 20

Side-discharge

358,300

105.0

35.8

10.0

328,600

96.0

43.8

7.5

13,400

250

92.0

Scroll / 2

Danfoss

Axial / Direct

KJR-12B/dP(T)-E

Centralized controller Yes Yes Customized

Sound pressure level 80.7 83.2 84.4

Centrifugal / Belt

49.0

MRCT-300CWN1-R

2,753×1,674×2,157

2,755×1,690×2,180

1,110/1,130

18°C ~ 52°C

30

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Page 15: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

27 28

Tropical (T3) application, heat pump, 380~415V 3Ph~ 50Hz

Model

External static pressure

Nominal ton*

Heating

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Side-discharge Side-discharge Side-discharge

75,000 89,000 103,000

22.0 26.0 30.0

7.7 9.2 10.4

9.7 9.7 9.8

89,000 102,000 120,000

26.0 30.0 35.0

7.6 8.8 10.1

11.7 11.6 11.8

2,600 3,000 3,600

60 60 75

10.4 12.0 13.6

21.0 25.6 27.5

Scroll / 1 Scroll / 1 Scroll / 1

Danfoss Danfoss Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centralized controller Yes Yes

Sound pressure level 74.7 75.1

Yes

76.8

Centrifugal / Belt Centrifugal / Belt

MRBT-062HWN1-R MRBT-075HWN1-R MRBT-085HWN1-R

Type

Btu/h

kW

Btu/h.W

CFM

Pa

1,630×1,068×1,065 1,630×1,068×1,065 2,165×1,002×1,335

1,700×1,110×1,155 1,700×1,110×1,155 2,220×1,040×1,415

320/340 320/340 450/463

-5°C ~ 52°C -5°C ~ 52°C -5°C ~ 52°C

mm

dB(A)

mm

kg

kW

Btu/h

kW

Btu/h.W

kW

kW

A

Capacity (1)

Input (1)

EER (1)Cooling

62,700 74,500 85,600

18.4 21.8 25.1

8.6 9.9 11.4

7.3 7.5 7.5

Btu/h

kW

Btu/h.W

kW

Capacity (2)

Input (2)

EER (2)

Capacity

Input

COP

Type / Quantity

Brand

6.2 7.5 8.5

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Heating capacity test condition: Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Heating capacity test condition: Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

6.2RT & 7.5RT 8.5RT

Tropical (T3) application, heat pump, 380~415V 3Ph~ 50Hz

Model

External static pressure

Nominal ton*

Heating

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Side-discharge Side-discharge Side-discharge

120,000 150,000 180,000

35.0 43.0 53.0

11.8 15.3 18.6

10.2 9.8 9.7

126,000 167,000 191,000

37.0 49.0 56.0

10.9 14.2 17.5

11.6 11.8 10.9

3,800 5,600 6,600

75 90 90

16.0 21.0 27.0

31.0 41.8 54.7

Scroll / 1 Scroll / 2 Scroll / 2

Danfoss Copeland Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centralized controller Yes Yes Yes

Sound pressure level 77.2 77.1 77.4

Centrifugal / Belt Centrifugal / Belt

MRBT-100HWN1-R MRBT-125HWN1-R MRBT-150HWN1-R

Type

Btu/h

kW

Btu/h.W

CFM

Pa

2,165×1,002×1,335 2,230×1,245×1,400 2,229×1,245×1,825

2,220×1,040×1,415 2,265×1,280×1,455 2,236×1,280×1,855

450/463 550/565 730/750

-5°C ~ 52°C -5°C ~ 52°C -5°C ~ 52°C

mm

dB(A)

mm

kg

kW

Btu/h

kW

Btu/h.W

kW

kW

A

Capacity (1)

Input (1)

EER (1)Cooling

100,000 125,600 159,600

29.3 34.2 46.7

13.1 16.8 21.3

7.6 7.5 7.5

Btu/h

kW

Btu/h.W

kW

Capacity (2)

Input (2)

EER (2)

Capacity

Input

COP

Type / Quantity

Brand

10 12.5 15

10RT 15RT12.5RT

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 16: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

29 30

Tropical (T3) application, heat pump, 380~415V 3Ph~ 50Hz

Model

External static pressure

Nominal ton*

Heating

Air flow Indoor side

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Side-discharge Side-discharge Side-discharge

210,000 240,000 358,300

60.0 70.0 105.0

20.0 23.6 35.8

10.5 10.2 10.0

229,000 256,000 358,000

67.0 75.0 105.0

19.8 23.4 35.8

11.5 10.9 10.0

7,300 8,400 12,000

90 100 250

29.0 36.0 49.0

58.2 69.2 93.1

Scroll / 2 Scroll / 2 Scroll / 2

Danfoss Danfoss Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Contralized controller Yes Yes

Sound pressure level 80.7 83.2 84.4

Customized

Centrifugal / Belt Centrifugal / Belt

MRBT-175HWN1-R MRBT-200HWN1-R MRCT-300HWN1-R

Type

Btu/h

kW

Btu/h.W

CFM

Pa

2,229×1,245×1,825 2,753×1,245×2,157 2,753×1,674×2,157

2,236×1,280×1,855 2,760×1,280×2,175 2,755×1,690×2,180

750/770 940/955 1,130/1,150

-5°C ~ 52°C -5°C ~ 52°C -5°C ~ 52°C

mm

dB(A)

mm

kg

kW

Btu/h

kW

Btu/h.W

kW

kW

A

Capacity (1)

Input (1)

EER (1)Cooling

180,600 213,000 328,600

52.9 62.4 96.0

23.5 27.7 43.8

7.7 7.7 7.5

Btu/h

kW

Btu/h.W

kW

Capacity (2)

Input (2)

EER (2)

Capacity

Input

COP

Type / Quantity

Brand

17.5 20 30

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Heating capacity test condition: Outdoor ambient temperature: 7°C DB / 6°C WB, indoor temperature 20°C DB / 15°C WB;

3. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

4. Specifications are subject to change without prior notice for product improvement.

5. * Nominal ton only for reference.

6. Cooling or heating capacity as per specifications.

17.5RT 30RT20RT

Tropical (T3) application, cooling only + EHK, 380~415V 3Ph~ 50Hz

6.2RT & 7.5RT 8.5RT

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Model

Nominal ton*

Cooling

Air flow Indoor side

Max. power input (Cooling)

Max. current (Cooling)

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 75,000

Side-discharge Side-discharge Side-discharge

89,000 103,000

22.0 26.0 30.0

7.7 9.2 10.4

9.7 9.7 9.8

62,700 74,500 85,600

18.4 21.8 25.1

8.6 9.9 11.4

7.3 7.5

21

7.5

2,600 3,000

14 14

3,600

60 60 75

20.1 25.6 26.3

Scroll / 1 Scroll / 1 Scroll / 1

Danfoss Danfoss Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centralized controller Yes Yes

Sound pressure level 74.7 75.1

Yes

76.8

Centrifugal / Belt Centrifugal / Belt

10.4 12.0 13.6

MRCT-062EWN1-R MRCT-075EWN1-R MRCT-085EWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

1,630×1,068×1,065 1,630×1,068×1,065 2,165×1,002×1,335

1,700×1,110×1,155 1,700×1,110×1,155 2,220×1,040×1,415

323/343 323/343 455/468

18°C ~ 52°C 18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

Electric heater kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

6.2 7.5 8.5

External static pressure

Type

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 17: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

31 32

Tropical (T3) application, cooling only + EHK, 380~415V 3Ph~ 50Hz

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Model

Nominal ton*

Cooling

Air flow Indoor side

Input

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 120,000

Side-discharge Side-discharge Side-discharge

180,000 210,000

35.0 53.0 60.0

11.8 18.0 20.0

10.2 10.0 10.5

100,000 159,600 180,600

29.3 46.7 52.9

13.1 21.3 23.5

7.6 7.5

30

7.7

3,800 6,600

21 30

7,300

75 90 90

30.0 53.0 57.8

Scroll / 1 Scroll / 2 Scroll / 2

Danfoss Danfoss Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centralized controller Yes Yes

Sound pressure level 77.2 77.4

Yes

80.7

Centrifugal / Belt Centrifugal / Belt

16.0 27.0 29.0

MRCT-100EWN1-R MRCT-150EWN1-R MRCT-175EWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

2,165×1,002×1,335 2,229×1,245×1,825 2,229×1,245×1,825

2,220×1,040×1,415 2,236×1,280×1,855 2,236×1,280×1,855

455/468 720/740 750/760

18°C ~ 52°C 18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

Electric heater kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

10 15 17.5

External static pressure

Type

10RT 15RT & 17.5

Tropical (T3) application, cooling only + EHK, 380~415V 3Ph~ 50Hz

20RT 30RT

Notes:

1. Cooling capacity test condition (1): Outdoor ambient temperature: 35°C, indoor temperature 26.7°C DB / 19.4°C WB;

Cooling capacity test condition (2): Outdoor ambient temperature: 46.1°C, indoor temperature 26.7°C DB / 19.4°C WB;

2. Sound values are measured in a semi-anechoic room, at a positon 1 meter in front of the unit and (1 meter+Height of unit)/2 above the floor.

3. Specifications are subject to change without prior notice for product improvement.

4. * Nominal ton only for reference.

5. Cooling or heating capacity as per specifications.

Model

Nominal ton*

Cooling

Air flow Indoor side

Input

Max. power input

Max. current

Compressor

Indoor fan Type / Drive type

Outdoor fan Type / Drive type

DimensionNet (W×H×D)

Weight

Ambient temperature

Wired controller

Net / Gross

Packing (W×H×D)

Capacity (1)Btu/h 240,000

Side-discharge Side-discharge

358,300

70.0 105.0

23.6 35.8

10.2 10.0

213,000 328,600

62.4 96.0

27.7 43.8

7.7 7.5

8,400 13,400

39 39

100 250

66.0 92.0

Scroll / 2 Scroll / 2

Danfoss Danfoss

Centrifugal / Belt

Axial / Direct Axial / Direct

KJR-12B/dP(T)-E KJR-12B/dP(T)-E

Centralized controller Yes

Sound pressure level 83.2

Customized

84.4

Centrifugal / Belt

36.0 49.0

MRCT-200EWN1-R MRCT-300EWN1-R

kW

Btu/h.W

kW

Btu/h

kW

Btu/h.W

CFM

Pa

2,753×1,245×2,157 2,753×1,674×2,157

2,760×1,280×2,175 2,755×1,690×2,180

940/955 1,130/1,150

18°C ~ 52°C 18°C ~ 52°C

mm

dB(A)

mm

kg

kW

kW

Electric heater kW

A

Input (1)

EER (1)

Capacity (2)

Input (2)

EER (2)

Type / Quantity

Brand

20 30

External static pressure

Type

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 18: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

33 34

DimensionsClimaMaster, T1 application, 380~415V, 3Ph~, 50HzMRC-36HWN1-R, MRC-48HWN1-R, MRC-60HWN1-R(Units: mm)

121.

565

6

110

5040

43.8

Control box access panelHole for control wires

Hole for power wires

Hole for other purpose

299

293

830

89333

103195744

965

1,116

Retu

rn

Supply

Drain connection hole High prussure gauge portLow prussure gauge port

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-60CWN1-R(Units: mm)

High voltage Conn. 35mm Dia. knockout Low vlotage entrance 22mm Dia.High voltage Conn. 35mm Dia.

Electrical service accesscompapartment panel

Condensate drainconnection 3/4” NPTI(Trap required)

Recommended unit disconnect location

165Front

Left

840

60

97

7731,920(Overall)

110

102

8311

2

1,068(Overall)

Hi./Lo. pressure detected valve1/4’’ SAE

Drain pan service access compartment panel

Condenser coil

Bottom

Back

Do not drill or install screw in this area

Side return air opeing

Bottom power entry22mm and 50mm Dia.knockout

Bottom control entry 22mm Dia. knockout

Bottom condensate drain 3/4” NPTI

45

84

143

253

772

70

88

368

267

368

45

156

45

105

45

98

108

368

Side supply air opening

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 19: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

35 36

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-062CWN1-R, MRBT-062HWN1-R, MRCT-062EWN1-RMRBT-075CWN1-R, MRBT-075HWN1-Y, MRCT-075EWN1-R(Units: mm)

4-20×15

251,

015

1,06

5

1501,330

1,630

Hole for bottom installation

Control electric heaterbox access panel

Hole for electric heater power wires

Horizontal supply opening

Horizontal return opening

Fresh air 905

101

350

16193278

313

Condenser fan

Hole for power wires

Hole for control wires

Control and comperssor access panel

Filter access door

Drain connection hole

maintain orifice for air supply motor

1,058

1,620

1,068

1,0651,630

457.5

550 780

534

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-085CWN1-R, MRBT-085HWN1-R, MRCT-085EWN1-RMRBT-100CWN1-R, MRBT-100HWN1-R, MRCT-100EWN1-R(Units: mm)

Condenser fan

Hole for power wires

Hole for control wires

Hole for other purposeControl and comperssor access panel

Filter access doorDrain connection hole

maintain orifice for air supply motor 804

453

2,165

1,335

1,002

2,1491,323

17

863

594

1,27

530

1,33

5

1033508048052,165

8-19×14

Hole for bottom installation

822

290

485

628

Horizontal supply opening

Horizontal return opening

Fresh air

10360406

Control electric heater box access panel

Hole for electric heater power wires

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 20: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

37 38

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-125CWN1-R, MRBT-125HWN1-R(Units: mm)

2,214

1,245

1,388

131

126

115

135

400863

7742,229

8001,400

Filter access door

Drain connection hole

Maintain orifice for air supply motor

Control and comperssor access panelHole for control wires

Hole for power wires

Hole for other purpose

Hole for bottom installation14-15×25

131

1,40

0

30

125

1151,9802,1642,229

577313

36055

143

1,029500

Fresh air

Horizontal supply openingHorizontal return opening

Control electric heater box access panel

Hole for electric heater power wires

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-150CWN1-R, MRBT-150HWN1-R, MRCT-150EWN1-RMRBT-175CWN1-R, MRBT-175HWN1-R, MRCT-175EWN1-R(Units: mm)

Hole for bottom installation14-15×25

131

1,82

5

30

125

1151,9802,1642,229

1,8132,214

17

1245

131

1,825

126115

400863

2,229774 800

135

Filter access doorDrain connection hole

Maintain orifice for air supply motor

Control and comperssor access panelHole for control wires

Hole for power wiresHole for other purpose

Control electric heater box access panel

Hole for electric heater power wires

Horizontal supply opening

Horizontal return opening

577

313

360

55143

Fresh air

804

234

544

1,029

185

506

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 21: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

39 40

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRBT-200CWN1-R, MRBT-200HWN1-R, MRCT-200EWN1-R(Units: mm)

Filter access doorDrain connection hole

Maintain orifice for air supply motor

Control and comperssor access panelHole for control wires

Hole for other purposeHole for power wires

135

2,753783

1,2411,053135 142

467

870 2,157

142

1,245

2,748

17

2,138

Hole for bottom installation14-15×25

142

678

2,15

787

032

410

9

301171,259

2,6932,753

1,241

673

315599

1,031203

703880Control electric heater box access panel

Hole for electric heater power wires

Horizontal supply opening

Horizontal return opening

55143

Fresh air

294

644

ClimaMaster, Tropical (T3) application, 380~415V, 3Ph~, 50HzMRCT-300CWN1-R, MRCT-300HWN1-R, MRCT-300EWN1-R(Units: mm)

Hole for other purpose

Drain connection hole

Maintain orifice for air supply motor

Control and comperssor access panel

Hole for control wires

Hole for power wires

870

9972,157

142

9172,753

839

142

1,674

18

820142135

Filter access door

Horizontal return opening

1,512

120120

870

144

Fresh air

294

652

522

266

888Control electric heater box access panel

Hole for electric heater power wires

55

Horizontal supply opening

Hole for bottom installation 16-15×20

142

324

2,15

787

067

8

917 7302,6932,753

862 135

Clim

aMas

ter S

erie

s

Clim

aMas

ter S

erie

s

Page 22: 1704-1R1611...Centralized control function can be achieved through the centralized controller as optional. MD-NIM01 should be connected between rooftop package units and centralized

41 42

Controllers

Wired controllers

KJR-12B/dP(T)-E

Controller with Follow Me function, it helps making the

room environment comfortable.

Daily timer function.

ON/OFF indication4

5

6

7

31

2

Follow me function

Fan speed indication

Lock

Temperature display zone

Mode indication

Timer ON/OFF

It is easy and convenient to select cooling, heating

and fan operation mode.

Digital display, seting temperature in 1°C.

4-minute delay function. The restarted compressor can be delayed for 4 minutes by

this controller.

Filter-monitor function. When the run-time of operations reaches certain hours, the

Filter-change Indicatior of controller will flash to remind checking the filter of unit.

Easy to change °C and °F in site.

KJR-23B

KJR-25B

Centralized controllers

MD-NIM01CCM30

Centralized control function. It is a multifunctional device which is able to control up to 64 units.

It provides a superior way to manage the units. Users are able to make their own choice from locking wired controller,

running mode or the CCM30’s keyboard.

The control object can be either single or all, making the controlling operation convenient. It also easy to check all

units status.

It is able to bridge up to 64 units to the network monitoring system and the building managements system.

Two structures of centralized controller design, easy installation.

Structure A (Model No. CCM30/BKE-A) should be embedded into the wall and structure B (Model No. CCM30/BKE-B)

doesn’t need.

CCM30MAX.64

MD-NIM01

Structure A Structure B

MD-NIM01 MD-NIM01 MD-NIM01

Locking

Keyboard

Locking

Running

Mode

Locking

Wired

Controller

Structure B leading-out mode sketch

Rear side outlet

Under side outlet

Upper side outlet

Cont

rolle

rs

Cont

rolle

rs