185885-001 Water Heater

Embed Size (px)

Citation preview

  • 8/9/2019 185885-001 Water Heater

    1/36

    Ii M

    Keep thIs Manual In the pocKet on heater for future reference

    whenever MaIntenance adjustMent or servIce Is requIred.

    power dIrect vented Gas Models

    NOT FOR USE IN MANUFACTURED (MOBILE) HOMES

    all technIcal and warrantY questIons: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS

    PURCHASED. IF YOU ARE UNSUCCESSFUL, PLEASE WRITE TO THE COMPANY LISTED ON THE RATING PLATE ON THE WATER HEATER

    resIdentIal Gas water heaters

    f Y sy AN ODORANT IS ADDED TO THE GAS USED

    BY THIS WATER HEATER.

    GAMA certification applies

    to all residential gas water

    heaters with capacities of 20

    to 100 gallons with input rating

    of 75,000 BTU/Hr. or less.

    PRINTED 1007 185885-00

  • 8/9/2019 185885-001 Water Heater

    2/36

    2

    safe InstallatIon, use, and servIceY y y i xmy im i ii, , iig i .

    My y- mg ii b i i i m y y

    i z. r by y mg ii g i m. I i y im

    mig y mg i by y i, , i i .

    a y mg i gy y b y z, i y y mg

    i ik iy.

    t cii s dikig w txi em a i G cii bi i b

    k s cii , bi , i m, i bi

    i x b.

    ti i mi k s cii , bi , i m. ti

    i x m b i, iig my, b mxi .

    IMportant defInItIons

    Qualied Installer: Aqualiedinstallermusthaveabilityequivalenttoalicensedtradesmanintheeldsofplumbing,airsupply,venting,andgassupply,includingathoroughunderstandingoftherequirementsoftheNationalFuelGasCodeasit

    relatestotheinstallationofgasredwaterheaters.Thequaliedinstallermustalsobefamiliarwiththedesignfeaturesanduseofammablevaporignitionresistantwaterheaters,andhaveathoroughunderstandingofthisinstructionmanual.

    si agy: Aserviceagencyalsomusthaveabilityequivalenttoalicensedtradesmanintheeldsofplumbing,airsupply,venting,andgassupply,includingathoroughunderstandingoftherequirementsoftheNationalFuelGasCodeasitrelatestotheinstallationofgasredwaterheaters.Theserviceagencymustalsohaveathoroughunderstandingofthisinstructionmanual,andbeabletoperformrepairsstrictlyinaccordancewiththeserviceguidelines

    providedbythemanufacturer.

    Gas Supplier: TheNaturalGasorPropaneUtilityorservicewhosuppliesgasforutilizationbythegasburningapplianceswithinthisapplication.ThegassuppliertypicallyhasresponsibilityfortheinspectionandcodeapprovalofgaspipinguptoandincludingtheNaturalGasmeterorPropanestoragetankofabuilding.Manygassuppliersalso

    offerserviceandinspectionofapplianceswithinthebuilding.

  • 8/9/2019 185885-001 Water Heater

    3/36

    3

    General safetY

  • 8/9/2019 185885-001 Water Heater

    4/36

    4

    tk Yforpurchasingthiswaterheater.Properlyinstalledand

    maintained,itshouldgiveyouyearsoftroublefreeservice.

    AbbreviationsFoundInThisInstructionManual:

    CSA-CanadianStandardsAssociation

    ANSI-AmericanNationalStandardsInstitute

    NFPA-NationalFireProtectionAssociation

    ASME-AmericanSocietyofMechanicalEngineers

    GAMA-GasApplianceManufacturersAssociation

    Thisgas-redwaterheaterisdesigncertiedbyCSAInternational

    underAmerican National Standard/CSA Standard for Gas Water

    HeatersANSIZ21.10.1CSA4.1(currentedition).

    preparInG for the InstallatIon

    1. ReadtheGeneralSafetysection,page3ofthismanualrstand

    thentheentiremanualcarefully.Ifyoudontfollowthesafetyrules,

    thewaterheaterwillnotoperateproperly.ItcouldcauseDEATH,

    SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.

    Thismanualcontainsinstructionsfortheinstallation,operation,

    andmaintenanceofthegas-redwaterheater.Italsocontains

    warningsthroughoutthemanualthatyoumustreadandbeaware

    of. All warnings and all instructions are essential to the proper

    operationofthewaterheaterandyoursafety. read the entIre

    Manual Before atteMptInG to Install or operate

    the water heater.

    2.Theinstallationmustconformwiththeseinstructionsandthelocalcodeauthorityhavingjurisdiction.Intheabsenceoflocalcodes,installationsshallcomplywiththeNationalFuelGasCodeANSI

    Z223.1/NFPA 54 and the National Electrical Code, NFPA 70.ThesepublicationsareavailablefromTheNationalFireProtectionAssociation,1BatterymarchPark,Quincy,MA02269.

    3. Thewaterheaterwheninstalledmustbegroundedinaccordancewiththelocalcodes,orintheabsenceoflocalcodes:TheNationalElectrical Code. ANSI/NFPA 70.

    4.Ifafterreadingthismanualyouhaveanyquestionsordonotunderstandanyportionoftheinstructions,callthelocalgasutilityorthemanufacturerwhosenameappearsontheratingplate.

    5.Carefully planyour placement of the waterheater. Correctcombustion, ventaction, andvent pipeinstallation are veryimportant in preventingdeath frompossiblecarbon monoxidepoisoningandres,seeFigures1and2.

    ExaminethelocationtoensurethewaterheatercomplieswiththeLocatingtheNewWaterHeatersectioninthismanual.

    6.For Californiainstallation thiswater heater mustbe braced,anchored, orstrapped toavoidfalling ormovingduring anearthquake.Seeinstructionsforcorrectinstallationprocedures.InstructionsmaybeobtainedfromCaliforniaOfceoftheStateArchitect,400PStreet,Sacramento,CA95814.

    7.MassachusettsCoderequiresthiswaterheatertobeinstalledinaccordancewithMassachusetts248-CMR2.00:StatePlumbingCodeand248-CMR5.00.Formoreinformationseenextpage.

    8.ComplieswithSCAQMDrule#1121anddistrictshavingequivalentNOxrequirements.

    IntroductIon

    taBle of contents

    SAFE INSTALLATION, USE AND SERVICE....................... ........... 2

    GENERAL SAFETY................. .............. ............... .............. ............ 3

    TABLE OF CONTENTS ............. ............... .............. ............... ......... 4

    INTRODUCTION ............................................................................ 4

    Preparing for the New Installation.............. .............. ............... .... 4

    INSTALLATIONREQUIREMENTSFORTHE

    COMMONWEALTH OF MASSACHUSETTS ............... .............. .... 5

    TYPICAL INSTALLATION ............................................................... 6

    MIXING VALVE USAGE ............... .............. ............... .............. ....... 7

    LOCATING THE NEW WATER HEATER .............. .............. ...... 8-11

    FactstoConsiderAboutLocation............................................ 8-9

    CombustionAirandExhaustTerminationClearances........... 9-10

    Wire Fence .............. .............. ............... .............. ............... ....... 10

    AirforVentilationforAppliancesLocatedinConnedSpaces .... 10

    InsulationBlankets............... .............. ............... .............. ..... 10-11

    INSTALLING THE NEW WATER HEATER ..................... ........ 12-22

    Water Piping .............. ............... .............. ............... .............. 12-13

    Temperature-PressureReliefValve.......................................... 13

    Gas Piping .............. ............... .............. ............... .............. ........ 14

    SedimentTraps......................................................................... 15

    Filling the Water Heater .............. ............... .............. ............... .. 15

    BlowerAssemblyInstallation .................................................... 15

    VentConnectionstoBlowerAssembly ..................................... 16

    Venting and Installation........................................................ 16-17

    Venting Through an Outside Wall .............. ............... ........... 17-18

    VentingSystemExampleInstallationforAllModels................. 18

    Vent Pipe Separation ............. ............... .............. ............... ....... 18

    Cutting Openings Through an Outside

    Wall and Collar Installation .................................................. 18-19

    Installation Showing Use of PVC, ABS or CPVC Pipe

    for Inlet and Outlet Vent Piping ................................................. 19

    Connecting Vent to Blower ....................................................... 19

    InstallationShowingUseof(optional)

    DeluxeHorizontalVentKit ................................................... 19-20

    Venting Through a Roof ............. .............. ............... .............. .... 20Vent Pipe Preparation ..........................................................20-22

    LIGHTING & OPERATING LABEL .............. ............... .............. .... 23

    TEMPERATURE REGULATION ............. .............. ............... ........ 24

    FOR YOUR INFORMATION ............... .............. ............... ............. 25

    Start Up Conditions............... .............. ............... .............. ......... 25

    Operational Conditions .............. .............. ............... .............. .... 25

    PERIODIC MAINTENANCE .................................................... 26-28

    VentingSystemInspection ....................................................... 26

    Burner Operation and Inspection .............................................. 26

    Burner Cleaning ........................................................................ 26

    Housekeeping........................................................................... 26

    Anode Rod ............. ............... .............. ............... .............. ......... 27

    Temperature-PressureReliefValveOperation ......................... 27

    Draining ...............................................................................27-28 DrainValveWasherReplacement............................................ 28

    Service...................................................................................... 28

    LEAKAGECHECKPOINTS.......................................................... 29

    REPAIR PARTS LIST ............... .............. ............... .............. ......... 30

    TROUBLESHOOTING GUIDELINES......................................31-33

    WARRANTY ............................................................................34-35

  • 8/9/2019 185885-001 Water Heater

    5/36

    5

    Forallsidewallterminated,horizontallyventedpowervent,directvent,andpowerdirectventgasfueledwaterheatersinstalled

    ineverydwelling,buildingorstructureusedinwholeorinpartforresidentialpurposes,includingthoseownedoroperatedby

    theCommonwealthandwherethesidewallexhaustventterminationislessthanseven(7)feetabovenishedgradeinthe

    areaoftheventing,includingbutnotlimitedtodecksandporches,thefollowingrequirementsshallbesatised:

    InstallatIon of carBon MonoXIde detectorsAt thetimeof installationofthesidewallhorizontalventedgas

    fueledequipment,theinstallingplumberorgasttershallobservethatahardwiredcarbonmonoxidedetectorwithanalarm

    andbatteryback-upisinstalledontheoorlevelwherethegasequipmentistobeinstalled.Inaddition,theinstallingplumber

    orgasttershallobservethatabatteryoperatedorhardwiredcarbonmonoxidedetectorwithanalarmisinstalledoneach

    additionallevelofthedwelling,buildingorstructureservedbythesidewallhorizontalventedgasfueledequipment.Itshall

    betheresponsibilityofthepropertyownertosecuretheservicesofqualiedlicensedprofessionalsfortheinstallationofhard

    wiredcarbonmonoxidedetectors.

    Intheeventthatthesidewallhorizontallyventedgasfueledequipmentisinstalledinacrawlspaceoranattic,thehardwired

    carbonmonoxidedetectorwithalarmandbatteryback-upmaybeinstalledonthenextadjacentoorlevel.

    Intheeventthattherequirementsofthissubdivisioncannotbemetatthetimeofcompletionofinstallation,theownershall

    haveaperiodofthirty(30)daystocomplywiththeaboverequirementsprovidedthatduringsaidthirty(30)dayperiod,abat-

    teryoperatedcarbonmonoxidedetectorwithanalarmshallbeinstalled.

    approved carBon MonoXIde detectorsEachcarbonmonoxidedetectorasrequiredinaccordancewiththeabove

    provisionsshallcomplywithNFPA720andbeANSI/UL2034listedandCSAcertied.

    sIGnaGe Ametalorplasticidenticationplateshallbepermanentlymountedtotheexteriorofthebuildingataminimumheight

    ofeight(8)feetabovegradedirectlyinlinewiththeexhaustventterminalforthehorizontallyventedgasfueledheatingappli-

    anceorequipment.Thesignshallread,inprintsizenolessthanone-half(1/2)inchinsize,Gas vent dIrectlY Below.

    Keep clear of all oBstructIons.

    InspectIon Thestateorlocalgasinspectorofthesidewallhorizontallyventedgasfueledequipmentshallnotapprovethe

    installationunless,uponinspection,theinspectorobservescarbonmonoxidedetectorsandsignageinstalledinaccordance

    withtheprovisionsof248CMR5.08(2)(a)1through4.

    eXeMptIons:Thefollowingequipmentisexemptfrom248CMR5.08(2)(a)1through4:

    1.TheequipmentlistedinChapter10entitledEquipmentNotRequiredToBeVentedinthemostcurrenteditionofNFPA54

    asadoptedbytheBoard;and

    2.ProductApprovedsidewallhorizontallyventedgasfueledequipmentinstalledina roomorstructureseparatefromthe

    dwelling,building,orstructureusedinwholeorinpartforresidentialpurposes.

    Manufacturer requIreMents - Gas equIpMent ventInG sYsteM provIdedWhenthemanufacturerofProduct

    Approvedsidewallhorizontallyventedgasequipmentprovidesaventingsystemdesignorventingsystemcomponentswith

    theequipment,theinstructionsprovidedbythemanufacturerforinstallationoftheequipmentandtheventingsystemshall

    include:

    1.Detailedinstructionsfortheinstallationoftheventingsystemdesignortheventingsystemcomponents;and

    2.Acompletepartslistfortheventingsystemdesignorventingsystem.

    Manufacturer requIreMents - Gas equIpMent ventInG sYsteM not provIdedWhenthemanufacturerofaProductApprovedsidewallhorizontallyventedgasfueledequipmentdoesnotprovidethepartsforventingtheuegases,

    butidentiesspecialventingsystems,thefollowingrequirementsshallbesatisedbythemanufacturer:

    1.The referencedspecialventing systeminstructionsshall be includedwith theappliance or equipmentinstallation

    instructions;and

    2.ThespecialventingsystemsshallbeProductApprovedbytheBoard,andtheinstructionsforthatsystemshallincludea

    parts list and detailed installation instructions.

    AcopyofallinstallationinstructionsforallProductApprovedsidewallhorizontallyventedgasfueledequipment,allventing

    instructions,allpartslists forventinginstructions,and/orallventing designinstructionsshallremainwiththe applianceor

    equipmentatthecompletionoftheinstallation.

    InstallatIon requIreMents for the coMMonwealth of Massachusetts

  • 8/9/2019 185885-001 Water Heater

    6/36

    6

    tYpIcal InstallatIonGet to Know Your water heater - Gas Models

    a v piex

    B v tmiex

    c Ik cmbi ai pi

    d Ik cmbi ai tmi

    e v a

    f B ambyG c w I

    h I w s- v

    I ui

    fIGure 1.

    j I di tb

    K a**

    l h w o

    M o r (115 vac)

    n tm-p ri v

    o fP Flue Bafe Assembly**

    q Ii

    r rig p

    s G sy

    t M G s- v

    u G ji ui

    v di lg (sim t)

    w di v

    X G c v

    Y di pZ I d

    aa o d

    BB hsI B amby***

    cc fv s amby

    *cautIon: 115 vac

    control harness

    InsIde outer jacKet

    * all pIpInG MaterIals to Be supplIed BY custoMers.

    ** located under the Blower asseMBlY.

    *** not pIctured

    tYpIcal hot surface IGnIter & MaIn Burner

    hot

    surface

    IGnIter

    flaMe

    sensor

    teMperature IndIcators

    teMperature adjustMent Buttons

  • 8/9/2019 185885-001 Water Heater

    7/36

    7

    MIXInG valve usaGe

    fIGure 2.

    ThisappliancehasbeendesigncertiedascomplyingwithAmericanNational Standard/CSA Standard for water heaters and is consideredsuitablefor:

    w (pb) hig s hig:All modelsareconsideredsuitableforwater(potable)heatingandspaceheating.

    HOTTERWATERCANSCALD:

    Water heaters are intended to produce hot water. Water heated to a

    temperaturewhichwillsatisfyspaceheating,clotheswashing,dish

    washing,andothersanitizingneedscanscaldandpermanentlyinjure

    youuponcontact.Somepeoplearemorelikelytobepermanently

    injuredbyhotwaterthanothers.Theseincludetheelderly,children,

    theinrm,orphysically/mentallydisabled.Ifanyoneusinghotwate

    inyourhometsintooneofthesegroupsorifthereisalocalcodeor

    statelawrequiringacertaintemperaturewateratthehotwatertap

    thenyoumusttakespecialprecautions.Inadditiontousingthelowes

    possibletemperaturesettingthatsatisesyourhotwaterneeds,a

    meanssuchasa*MixingValve,shouldbeusedatthehotwater

    tapsusedbythesepeopleoratthewaterheater.Mixingvalvesare

    availableatplumbingsupplyorhardwarestores.ConsultaQualied

    Installer or ServiceAgency. Followmixing valve manufacturers

    instructionsforinstallationofthevalves.Beforechangingthefactory

    settingonthethermostat,readtheTemperatureRegulationsection

    inthismanual,seeFigure31.

    suGGested pIpInG arranGeMent for top connectIons

  • 8/9/2019 185885-001 Water Heater

    8/36

    8

    facts to consIder aBout the locatIon

    Carefullychooseanindoorlocationforthenewwaterheater,because

    theplacementisaveryimportantconsiderationforthesafetyofthe

    occupantsinthebuildingandforthemosteconomicaluseofthe

    appliance. ti i i m

    (mbi) m ii.

    Whether replacing an old water heater or putting the water heater in

    anewlocation,thefollowingcriticalpointsmustbeobserved:

    1. Selectalocationindoorsascloseaspracticaltotheventterminalor

    locationtowhichthewaterheaterventpipingisgoingtobeconnected,

    andascentralizedwiththewaterpipingsystemaspossible.

    2.Selectedlocationmustprovideadequateclearancesforservicing

    and proper operation of the water heater.

    Installationof the waterheatermust be accomplished in sucha

    mannerthatifthetankoranyconnectionsshouldleak,theowwillnot

    causedamagetothestructure.Forthisreason,itisnotadvisableto

    installthewaterheaterinanatticorupperoor.Whensuchlocations

    cannotbeavoided,asuitabledrainpanshouldbeinstalledunderthe

    waterheater.Drainpansareavailableatyourlocalhardwarestore.

    Suchadrainpanmusthaveaminimumlengthandwidthofatleast

    2(5.1cm)greaterthatthewaterheaterdimensionsandmustbe

    pipedtoanadequatedrain.Drainpandepthmustallowforaccesstotheouterdoorsforservicingtheignitorandburner.

    Waterheaterlifedependsuponwaterquality,waterpressureandthe

    environmentinwhichthewaterheaterisinstalled.Waterheatersare

    sometimesinstalledinlocationswhereleakagemayresultinproperty

    damage,evenwiththeuseofadrainpanpipedtoadrain.However,

    unanticipateddamagecanbereducedorpreventedbyaleakdetector

    orwatershut-offdeviceusedinconjunctionwithapipeddrainpan.

    Thesedevicesareavailablefromsomeplumbingsupplywholesalers

    andretailers,anddetectandreacttoleakageinvariousways:

    Sensorsmountedinthedrainpanthattriggeranalarmorturnoffthe

    incomingwatertothewaterheaterwhenleakageisdetected.

    Sensorsmountedinthedrainpanthatturnoffthewatersupplytotheentirehomewhenwaterisdetectedinthedrainpan.

    Water supply shut-offdevicesthat activatebased onthe water

    pressuredifferentialbetweenthecoldwaterandhotwaterpipes

    connected to the water heater.

    Devicesthatwillturnoffthegassupplytoagaswaterheaterwhile

    atthesametimeshuttingoffitswatersupply.

    INSTALLATIONSIN AREASWHERE FLAMMABLELIQUIDS

    (VAPORS)ARELIKELYTOBEPRESENTORSTORED(GARAGES,

    STORAGEANDUTILITYAREAS,ETC.):Flammableliquids(suchas

    gasoline,solvents,propane(LPorbutane,etc.)andothersubstances

    (suchasadhesives,etc.)emitammablevaporswhichcanbeignited

    locatInG the new water heaterbyagaswaterheatershotsurfaceigniterormainburner.Theresulting

    ashbackandrecancausedeathorseriousburnstoanyoneinthearea

    andpropertydamage.ThiswaterheaterisequippedwithaFVsensor

    fordetectingthepresenceofammablevapors,seeFigure3.Whenthe

    sensordetects thosevapors,theunitwillshutdownandnotoperate.

    Shouldthishappen,pleaserefertotroubleshootingguideinthismanual.

    Eventhoughthiswaterheaterisaammablevaporsignitionresistant

    waterheaterandisdesignedtoreducethechancesofammablevapors

    beingignited,gasolineandotherammablesubstancesshouldneverbestoredorusedinthesamevicinityorareacontainingagaswater

    heaterorotheropenameorsparkproducingappliance.

    fIGure 3.

    Also,thewaterheatermustbelocatedand/orprotectedsoitisnot

    subjecttophysicaldamagebyamovingvehicle.

    This water heatermust notbe installed directlyon carpeting.

    Carpetingmustbeprotectedbymetalorwoodpanelbeneaththe

    applianceextendingbeyondthefullwidthanddepthoftheappliance

    byatleast3(7.6cm)inanydirection,oriftheapplianceisinstalled

    inanalcoveorcloset,theentireoormustbecoveredbythepanel.

    Failuretoheedthiswarningmayresultinarehazard.

  • 8/9/2019 185885-001 Water Heater

    9/36

    9

    Minimum clearancesbetween the waterheater andcombustible

    constructionare0inchatthesidesandrear,6(15.2cm)fromthe

    frontofthejacket,and12(30.5cm)fromthetop(standardclearance).

    Ifclearancesstatedontheheaterdifferfromstandardclearances,

    install water heater according to clearances stated on the heater.

    Adequateclearanceforservicingthisapplianceshouldbeconsidered

    beforeinstallation,suchaschangingtheanodes,etc.

    Aminimumclearanceof5(12.7cm)fromthefrontofthejacketmust

    beallowedforaccesstoreplaceablepartssuchasthethermostats,

    drainvalveandreliefvalve.Provide24(61cm)frontclearancefor

    servicingandadequateclearancebetweenthejackettopandceiling

    forservicingtheuearea.

    Wheninstallingtheheater,considerationmustbegiventoproper

    location. Locationselectedshouldbe asclose tothe wall as

    practicable andas centralized withthe water pipingsystem as

    possible.

    fIGure 4.

    Donotinstallinaconnedareasuchasacloset,unlessyouprovide

    ventilationairasshowninthe"LocatingTheNewWaterHeater"

    sectionandFigure5.Neverobstructtheowofventilationair.Ifyou

    haveanydoubtsorquestionsatall,callyourgascompany.Failureto

    provideventilationaircanresultinareorexplosionandcancause

    DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.

    fIGure 5.

    Ifthiswaterheaterwillbe used inbeauty shops,barbershops

    cleaningestablishments,orself-servicelaundrieswithdrycleaning

    equipment,itisimperativethatthewaterheaterorwaterheater

    beinstalledsothatcombustionandventilationairbetakenfrom

    outside these areas.

    Propellantsofaerosolspraysandvolatilecompounds,(cleaners

    chlorine basedchemicals,refrigerants,etc.) in addition to being

    highlyammableinmanycases,willalsoreacttoformcorrosive

    hydrochloricacid when exposedto thecombustionproducts o

    thewaterheater.Theresultscanbehazardous,andalsocause

    product failure.

    coMBustIon aIr and eXhaust terMInatIon

    clearances

    vig tg oi w - c, fig 7.

    0"clearancefor3"PVC,ABS,orCPVCSchedule40pipingfrom

    combustiblesurfaces.

    Thelocationselectionmustprovideclearancesforservicingand

    proper operation of the water heater, see Figure 8.

    fIGure 6.

    Theventingsystemmustbeinstalledinamannerwhichallows

    inspectionoftheinstallationoftheventingpipesandjointsa

    wellasperiodicinspectionafterinstallationas requiredbythe

    National Fuel Gas Code ANSI Z223.1.

  • 8/9/2019 185885-001 Water Heater

    10/36

    10

    fIGure 7.

    vent terMInatIon clearances

    wIre fence

    Whenthewaterheateroutletterminalislowenoughtobetouched

    accidentally,orisaccessibletosmallchildren,awiremeshchain

    linkfence(asshowninFigure8)maybeused.Careshouldbe

    takentomaintainadequateventilationaroundtheoutletterminal.

    Ifachainlinkfenceisinstalled,itmustnotbeusedasastorage

    areaforitemsthatmayblockproperventilation.

    fIGure 8.

    vig tg r - c

    0"clearancefor3"PVC,ABS,orCPVCSchedule40pipingfrom

    combustibleandnoncombustiblesurfaces.

    Theventexhaustoutletandairinletterminalsshallterminateat

    least18"(45.7cm)abovetheroofsurface,seeFigure9.

    fIGure 9.

    aIr for ventIlatIon for applIances located In

    confIned spaces

    Airforventilationshouldbeprovidedifinstalledinaconnedspace.

    Refer to the National Fuel Gas Code, ANSI Z223.1.

    InsulatIon BlanKets

    Insulationblanketsareavailabletothegeneralpublicforexternal

    useongaswaterheatersbutarenotnecessarywiththeseproducts.

    Thepurposeofaninsulationblanketistoreducethestandbyheat

    lossencountered with storagetankheaters.Your water heater

    meetsorexceedstheNationalApplianceEnergyConversationAct

    standardswithrespecttoinsulationandstandbylossrequirements,

    makinganinsulationblanketunnecessary.

  • 8/9/2019 185885-001 Water Heater

    11/36

    11

    Shouldyouchoosetoapplyaninsulationblankettothisheater,you

    shouldfollow theseinstructions (Foridentication of components

    mentionedbelow,seeFigure1).Failuretofollowtheseinstructions

    canrestricttheairowrequiredforpropercombustion,potentially

    resultinginre,asphyxiation,seriouspersonalinjury,ordeath.

    Do notapplyinsulationtothetopofthewaterheater,asthiswi

    interfere with safe operation of the water heater.

    Do notcovertheouterdoor,thermostat,temperature&pressur

    reliefvalveorFVSensor.

    Do not let insulation around the gas water heater get within 8 inches

    oftheoor(accessforservicingtheburner).

    Do not covertheinstructionmanual. Keepit ontheside ofthe

    waterheaterornearbyforfuturereference.

    Doobtainnewwarningandinstructionlabelsfromthemanufacturer

    forplacementontheblanketdirectlyovertheexistinglabels.

    Doinspecttheinsulationblanketfrequentlytomakecertainit

    doesnotsag,therebyobstructingaccesstoburner.

  • 8/9/2019 185885-001 Water Heater

    12/36

    12

    therMal eXpansIon

    Aswaterisheated,itexpands(thermalexpansion).Inaclosed

    systemthevolumeofwaterwillgrowwhenitisheated.Asthe

    volumeofwatergrowstherewillbeacorrespondingincreasein

    waterpressureduetothermalexpansion.Thermalexpansioncan

    causeprematuretankfailure(leakage).Thistypeoffailureisnot

    coveredunderthelimitedwarranty.Thermalexpansioncanalso

    cause intermittent temperature-pressure relief valve operation:waterdischargedfromthevalveduetoexcessivepressurebuild

    up.Thisconditionisnotcoveredunderthelimitedwarranty.The

    temperature-pressurereliefvalveisnotintendedfortheconstant

    reliefofthermalexpansion.

    Aproperly sized thermalexpansion tankshouldbe installed

    onall closed systemsto controlthe harmfuleffects ofthermal

    expansion.Contactalocalplumbingserviceagencytohavea

    thermalexpansiontankinstalled.

    note:t gi imy i

    water ttings, it is strongly recommended that dielectric unions

    ig b i i

    i.

    Allgaspipingmustcomplywithlocalcodesandordinancesorwiththe

    NationalFuelGasCode(ANSIZ223.1/NFPA-54)whicheverapplies.

    Copperandbrasstubingandttings(excepttinlinedcoppertubing)

    shallnotbeused.

    fIGure 10.

    Figure10showsthetypicalattachmentofthewaterpipingtothewater heater. The water heater is equipped with 3/4 inch NPT waterconnections.

    water pIpInG

    HOTTERWATERCANSCALD:

    Water heaters are intended to produce hot water. Water heated to

    a temperaturewhich will satisfy space heating,clothes washing,

    dish washing, cleaning and othersanitizing needscan scald and

    permanentlyinjureyouuponcontact.Somepeoplearemorelikelytobepermanentlyinjuredbyhotwaterthanothers.Theseincludethe

    elderly,children,theinrm,orphysically/mentallydisabled.Ifanyone

    usinghotwaterinyourhometsintooneofthesegroupsorifthere

    isalocalcodeorstatelawrequiringacertaintemperaturewaterat

    thehotwatertap,thenyoumusttakespecialprecautions.Inaddition

    tousingthelowestpossibletemperaturesettingthatsatisesyour

    hotwaterneeds,ameanssuchasamixingvalveshouldbeusedat

    thehotwatertapsusedbythesepeopleoratthewaterheater,see

    Figure2.Valvesforreducingpointofusetemperaturebymixingcold

    andhotwaterarealsoavailable.

    ConsultaQualiedInstallerorServiceAgency.Followmanufacturers

    instructionsforinstallationofthevalves.Beforechangingthefactory

    settingonthethermostat,readtheTemperatureRegulationsection

    inthismanual.

    Thiswaterheatershallnotbeconnectedtoanyheatingsystemsor

    component(s)usedwithanon-potablewaterheatingappliance.

    All pipingcomponentsconnectedto this unit forspace heating

    applicationsshallbesuitableforusewithpotablewater.

    Toxicchemicals,suchasthoseusedforboilertreatmentshallnotbe

    introducedintothissystem.

    Whenthesystemrequireswaterforspaceheatingattemperatures

    higherthanrequiredfordomesticwaterpurposes,atemperingvalve

    must beinstalled. Pleasereferto Figure2 forsuggested piping

    arrangement.

    Watersupplysystemsmay,becauseofcoderequirementsorsuch

    conditionsas high line pressure, among others,have installed

    devicessuchaspressurereducingvalves,checkvalves,andback

    owpreventers.Devicessuchasthesecausethewatersystemto

    beaclosedsystem.

    InstallInG the new water heater

  • 8/9/2019 185885-001 Water Heater

    13/36

    13

    note:I ig big, big b

    ig i i. d

    y i iy i.

    I i m i b mg k.

    t & p v pi Ii (i i)

    RemoveinsulationforT&Pvalveandpipeconnectionsfromcarton.

    fIGure 11.

    Fitpipeinsulationovertheincomingcoldwaterlineandthehotwater

    line.Makesurethattheinsulationisagainstthetopcoveroftheheater.

    FitT&Pvalveinsulationovervalve.Makesurethattheinsulation

    doesnotinterferewiththeleveroftheT&Pvalve.

    Secure all insulation using tape.

    teMperature-pressure relIef valve

    Thisheateris provided witha properlycertifiedcombinationtemperature-pressurereliefvalvebythemanufacturer.

    Thevalveiscertiedbyanationallyrecognizedtestinglaboratory

    thatmaintainsperiodicinspectionofproductionoflistedequipmentof

    materialsasmeetingtherequirementsforReliefValvesforHotWater

    SupplySystems,ANSIZ21.22CSA4.4,andthecoderequirements

    of ASME.

    Ifreplaced,thevalvemustmeettherequirementsoflocalcodes,but

    notlessthanacombinationtemperatureandpressurereliefvalve

    certiedasindicatedintheaboveparagraph.

    Thevalvemustbemarkedwithamaximumsetpressurenotto

    exceedthemarkedhydrostaticworkingpressureofthewaterheater

    (150psi=1,035kPa)andadischargecapacitynotlessthanthewate

    heaterinputrateasshownonthemodelratingplate.

    Forsafeoperationofthewaterheater,thereliefvalvemustnotb

    removedfromitsdesignatedopeningnorplugged.

    Thetemperature-pressurereliefvalvemustbeinstalleddirectlyinto

    thettingofthewaterheaterdesignedforthereliefvalve.Positionthe

    valvedownwardandprovidetubingsothatanydischargewillexitonly

    within6inches(15.2cm)aboveanadequatedrainoroutsideofthe

    buildingorstructure.Becertainthatnocontactismadewithanylive

    electricalpart.Thedischargeopeningmustnotbeblockedorreducedinsizeunderanycircumstances.Excessivelength,over30feet(9.14

    m),oruseofmorethanfourelbowscancauserestrictionandreduce

    thedischargecapacityofthevalve,seeFigures10or14.

    Novalveorotherobstructionistobeplacedbetweenthereliefvalv

    andthetank.Donotconnecttubingdirectlytodischargedrainunless

    a6(15.2cm)airgapisprovided.Topreventbodilyinjury,hazardt

    life,orpropertydamage,thereliefvalvemustbeallowedtodischarge

    waterinquantitiesshouldcircumstancesdemand.Ifthedischarg

    pipeisnotconnectedtoadrainorothersuitablemeans,thewate

    owmaycausepropertydamage.

    TheDischargePipe:

    Shallnotbesmallerinsizethantheoutletpipesizeofthevalve,or

    haveanyreducingcouplingsorotherrestrictions.

    Shallnotbepluggedorblocked.

    Shallbeofmateriallistedforhotwaterdistribution.

    Shallbeinstalledsoastoallowcompletedrainageofboththe

    temperature-pressurereliefvalve,andthedischargepipe.

    Shallterminateatanadequatedrain.Shallnothaveanyvalvebetweenthereliefvalveandtank.

    Thetemperature-pressurereliefvalvemustbemanuallyoperateda

    leastonceayear.Cautionshouldbetakentoensurethat(1)noone

    isinfrontofor aroundtheoutletofthetemperature-pressurerelie

    valvedischargeline,and(2)thewatermanuallydischargedwillnot

    causeanybodilyinjuryorpropertydamagebecausethewatermay

    beextremelyhot.

    Ifaftermanuallyoperatingthevalve,itfailstocompletelyresetand

    continuesto release water, immediatelyclose the coldwater inle

    to the water heater, follow the draining instructions, and replace the

    temperature-pressurereliefvalvewithanewone.

  • 8/9/2019 185885-001 Water Heater

    14/36

    14

    Gas pIpInG

    Makesurethegassuppliedisthesametypelistedonthemodelratingplate.Theinletgaspressuremustnotexceed10.5inchwatercolumn(2.6kPa)fornaturaland13inchwatercolumn(3.2kPa)forpropanegas(L.P.).Theminimuminletgaspressureshownontheratingplateisthatwhichwillpermitringatratedinput.

    Allgaspipingmustcomplywithlocalcodesandordinancesorwith

    theNationalFuelGasCode(ANSIZ223.1/NFPA-54)whicheverapplies.Copperandbrasstubingandttings(excepttinlinedcoppertubing)shallnotbeused.

    Ifthegascontrolvalveissubjectedtopressuresexceeding1/2psi(14inchesofwatercolumnor3.5kPa),thedamagetothegascontrolvalvecouldresultinareorexplosionfromleakinggas.

    IfthemaingaslineShut-offservingallgasappliancesisused,alsoturnoffthegasateachappliance.Leaveallgasappliancesshutoffuntilthewaterheaterinstallationiscomplete.

    Agaslineofsufcientsizemustberuntothewaterheater.Consultthe current edition of National Fuel Gas Code ANSI Z223.1/NFPA54andyourgassupplierconcerningpipesize.

    Theremustbe: Areadilyaccessiblemanualshutoffvalveinthegassupplyline

    servingthewaterheater,and Adripleg(sedimenttrap)aheadofthegascontrolvalvetohelp

    preventdirtandforeignmaterialsfromenteringthegascontrolvalve.

    Aexiblegasconnectororagroundjointunionbetweentheshutoffvalveandthegascontrolvalvetopermitservicingoftheunit.

    Besuretocheckallthegaspipingforleaksbeforelightingthewaterheater.Useasoapywatersolution,notamatchoropename.Rinseoffsoapysolutionandwipedry.

    Wheninstalledatelevationsabove7,700feet(2,347meters),input

    ratingshouldbereducedattherateof4percentforeach1,000feet(305meters)abovesealevelwhichrequiresreplacementofthe

    burneroriceinaccordancewithTheNationalFuelGasCode

    ANSIZ223.1/NFPA54.Contactyourlocalgassupplierforfurther

    information.

    Failuretoreplacethestandardoricewithahighaltitudeoricewheninstalled couldresult in improper andinefcientoperationof the

    appliance,producingcarbonmonoxidegasinexcessofsafelimits,

    whichcouldresultinseriousinjuryordeath.Contactyourgassupplierforanyspecicchangeswhichmayberequiredinyourarea.

    UsepipejointcompoundorTeontapemarkedasbeingresistant

    totheactionofpetroleum[Propane(L.P.)]gases.

    Theapplianceanditsgasconnectionmustbeleaktestedbefore

    placing the appliance in operation.

    TheapplianceanditsindividualShut-offvalveshallbedisconnected

    fromthegassupplypipingsystemduringanypressuretestingof

    that systemat test pressuresin excessof 1/2 psi (14 inchesof

    watercolumnor3.5kPa).Itshallbeisolatedfromthegassupply

    pipingsystembyclosingitsindividualmanualShut-offvalveduring

    anypressuretestingofthegassupplypipingsystemattestpressures

    equal to or less than 1/2psi(14inchesofwatercolumnor3.5kPa) .

    Connectingthegas piping tothegas controlvalve ofthe waterheatercanbeaccomplishedbyeitherofthetwomethodsshownin

    Figures 12 and 13.

    fIGure 12. Gas pIpInG wIth

    fleXIBle connector.

    fIGure 13. Gas pIpInG wIth all

    BlacK Iron pIpe to Gas control.

  • 8/9/2019 185885-001 Water Heater

    15/36

    15

    sedIMent traps

    Asedimenttrapshallbeinstalledasclosetotheinletofthewater

    heater aspractical atthe timeof water heaterinstallation. The

    sedimenttrapshallbeeitherateettingwithacappednippleinthe

    bottomoutletorotherdevicerecognizedasaneffectivesediment

    trap.Ifateettingisused,itshallbeinstalledinconformancewith

    oneofthemethodsofinstallationshowninFigures12and13.

    Contaminantsinthegaslinesmaycauseimproperoperationofthegas

    controlvalvethatmayresultinreorexplosion.Beforeattachingthe

    gaslinebesurethatallgaspipeiscleanontheinside.Totrapanydirtorforeignmaterialinthegassupplyline,adripleg(sometimescalled

    asedimenttrap)mustbeincorporatedinthepiping.Thedriplegmust

    bereadilyaccessible.InstallinaccordancewiththeGasPiping

    section. Refer to the current edition of the National Fuel Gas Code,

    ANSI Z223.1/NFPA 54.

    fIGure 14.

    fIllInG the water heater

    Neverusethiswaterheaterunlessitiscompletelyfullofwater.Topreven

    damagetothetank,thetankmustbelledwithwater.Watermustow

    fromthehotwaterfaucetbeforeturningONgastothewaterheater.

    Tollthewaterheaterwithwater:

    1. Closethewaterheaterdrainvalveby turningthehandletothe righ

    (clockwise).Thedrainvalveisonthelowerfrontofthewaterheater.

    2.Openthecoldwatersupplyvalvetothewaterheater.

    note: t y m b

    i i .

    3. Toinsurecompletellingofthetank,allowairtoexitbyopeningthe

    nearesthotwaterfaucet.Allowwatertorununtilaconstantowiobtained.Thiswillletairoutofthewaterheaterandthepiping.

    4. Check allwaterpiping andconnections forleaks.Repair as

    needed.

    Blower asseMBlY InstallatIon

    sequence of InstallatIon

    1. This powerdirectventwater heater comeswiththebloweassemblyinstalled.

    2 Aftertheunitissetinplace,makesuretheblowerassemblyisstimountedsecurely,andmakesurethereisnodamagetotheblower

    3. Makesurethereisnopackingmaterialinthedischargeoftheblowerortheintake,seeFigure15.

    4. Makesurethattherubbertubingisstill attachedfrom the aipressureswitchtotheportontheblowerhousing.Makesuretherubbertubingisnotfoldedanywherebetweenthepressureswitchandtheblowerhousing.

    5. MakesuretheON/OFFswitchisinthe OFFpositionandthathewiringharnessisconnectedfromtheblowercontrolboxtotheconnectoronthebottomsideofthegascontrolvalve.

    6. Ifthewiringharnessisnotfactoryinstalled,makesuretheONOFF switch is in the OFF position and then connect the wiringharness from the blowercontrolboxto the connectoron thebottomsideofthegascontrolvalve.

    7. Thiswaterheateris apolaritysensitiveapplianceandwillnooperateifthepowersupplypolarityisreversed.Thepowersupploroutlet providing powerto this water heatermustbe wired

    properly(correctpolarity).

    8. DonotpluginpowercorduntilventsystemiscompletelyinstalledThispowerdirectventheateroperateson110-120Vac,thereforeagroundedoutletmustbewithinreachofthesix(6)foot(1.8m

    exiblepowercordsuppliedwiththeunit,seeFigure2.Ensurethepolarityattheoutletiscorrect.Thepowercordsuppliedmaybeusedonlywherelocalcodespermit.Iflocalcodesdonotpermtheuseofaexiblepowersupplycord:

    a.)Makesuretheunitisunpluggedfromwalloutlet.Removescrewsandremovecontrolbox.

    b.)Cuttheexiblepowercord,leavingenoughtobeabletomakeconnections,theremovethestrainreliefttingfrombox.

    c.)Installsuitableconduitttinginsideofenclosureandthenfollow(d.)and(e.)below.

    d.)Spliceeldwiringintoexisting wiringusingcode authorizedmethod(wirenuts,etc.).

    e.)Becertainthatneutralandliveconnectionsarenotreversedwhenmakingtheseconnections.

    f.) Replacecontrolbox,makesurethatcontrolboxissecuredshut

  • 8/9/2019 185885-001 Water Heater

    16/36

    16

    vent connectIons to Blower asseMBlY

    Figure15showsthetypicalventconnections.

    fIGure 15.

    ventInG and InstallatIon

    Planthelayoutoftheventsystemfromtheventterminationtothewater

    heaterconsideringallofthe90and45elbowsplusthenumberoffeet

    ofpipethatwouldbeneededtoinstallthetotalventsystem.Thewater

    heatermustbeventedtotheoutdoorsasdescribedintheseinstructions.

    DONOTconnectthiswaterheatertoanexistingventorchimney.Itmustbeventedseparatelyfromallotherappliances.Thettings,other

    thanthesuppliedVentTerminationshouldbeequivalenttothefollowing:

    PVC(Schedule40,DWV,ASTMD-2665),CPVC(Schedule40,DWV,

    ASTMF-438),ABS(Schedule40DWV,ASTMD-2661).

    Thecementusedshould beas recommendedby the vent

    pipe manufacturer. Seethe instructionsin theVENTPIPE

    PREPARATIONsectionofthismanualforthepropermethodof

    cuttingandcementingthePVCpipeandttings.

    Allventgasesmustbecompletelyventedtotheoutdoorsofthe

    structure(dwelling).Whendeterminingtheinstallationlocationfor

    apowerdirectventwaterheater,snowaccumulationanddrifting

    shouldbeconsideredinareaswhereapplicable.

  • 8/9/2019 185885-001 Water Heater

    17/36

    17

    fIGure 16.

    Horizontalrunsmust besecurelysupportedat 31/2 foot (1m)

    intervalsandverticalrunssupportedat5foot(1.5m)intervals.

    fIGure 17.

    ventInG throuGh an outsIde wall

    a. a 75 G M

    Inthecartonissupplied:

    1.Two3inletandoutletPVCSchedule40-45ventcaps.

    2. One3CPVCSchedule80-90elbow;usedtoconnectthe

    ventpipetothewaterheaterwhentheventpipeistobe

    turnedhorizontallydirectlyofftheblower.

    3. One5(1.5m)sectionof3CPVCSchedule40ventpipe

    (Moremayberequiredandmustbepurchasedlocally.)

    fIGure 18.

    1. Thewaterheaterrequiresitsown(separate)ventingsystem.

    2. oy3CPVCSchedule40pipingandttingsareacceptablematerialsontherstvefeetoftheventsystem.

    3. 3PVC,ABS,orCPVCSchedule40 piping and ttingsareacceptablematerialsfortheiventsystemandfortheventsystemaftertherstvefeet.

    4. Theunitcannotbeconnectedtoexistingventpipingorchimney

    5. Whenventingthroughanoutsidewall,theventsmustterminatehorizontallytotheoutdoors.

    B. a 50 G 65,000 Btu/hr MInthecartonissupplied:

    1. Two3i and PVCSchedule40-45ventcaps.

    2. One3ABSSchedule40-90streetelbow;usedtoconnecttheventpipetothewaterheaterwhentheventpipeitobeturnedhorizontallydirectlyofftheblower.

    3. One5(1.5m)sectionof3ABSSchedule40ventpipe

    (Moremayberequiredandmustbepurchasedlocally.)

    fIGure 19.

    1. Thewaterheaterrequiresitsown(separate)ventingsystem.

    2. oy3CPVCorABSSchedule40pipingandttingsareacceptablematerialsontherstvefeetofthe ventsystem.

    3. 3PVC,ABS,orCPVCSchedule40 piping and ttingsareacceptablematerialsfortheiventsystemandfortheventsystemaftertherstvefeet.

    4. Theunitcannotbeconnectedtoexistingventpipingorchimney

    5. Whenventingthroughanoutsidewall,theventsmustterminatehorizontallytotheoutdoors.

  • 8/9/2019 185885-001 Water Heater

    18/36

    18

    c. a 40 50 G 40,000 Btu/hr MInthecartonissupplied:

    1. Two3inletandoutletPVCSchedule40-45ventcaps.Allotherpipingmustbesuppliedbythesupplier.

    fIGure 20.

    * Ifmakinganimmediatehorizontalrunofventofftheblower,two

    3PVCorABSschedule40streetelbowsarerequired.

    ventInG sYsteM eXaMple InstallatIons for

    all Models

    Theventpipingcannotunderanycircumstancesberundownhill.

    fIGure 21.

    c ii iig:

    1. Horizontalrunsrequireaminimum1/8(3.2mm)risepervefeet

    of length.

    fIGure 22.

    2. The totalvertical and horizontal ventrunscannot exceed the

    maximumlengthwiththenumberof90elbowsasspeciedinthetablebelow.Ifmoreelbowsarerequired,theventingdistancemustbereduced5feet(1.5m)forevery90elbow:

    Thenumberof90elbowsshowninthetableisforboththeintake

    airandventpipes.IE:Theventpipecancontainthree90elbows,

    theintakeairpipecanalsocontainthree90elbows.

    3" dIa. vents MaX.

    lenGth (ft.)

    nuMBer of 90

    elBows*

    45 1

    40 2

    35 3

    *NOTE:Two45elbowsareequivalenttoone90elbow.One90

    elbowequals5feet(1.5m)ofequivalentventlength.

    fIGure 23.

    3. Minimumventlengthforallmodelsis18inches(46cm).

    vent pIpe separatIon

    Theinletandoutletventpipesmustbeseparatedbyaminimum

    distance of6 1/2 inches(16.5 cm)upto 24inches (61 cm)maximum.

    fIGure 24.

    cuttInG openInGs throuGh an outsIde wall

    and collar InstallatIon

    Afterreadingthe manualanddeterminingthe location forthe

    openingin the wall,cut one 31/2(9 cm) diameterholeforthe

    inletventpipingandone31/2(9cm)diameterholefortheoutlet

    ventpipingthroughanexteriorwall,seeFigure25.

    n: w miig i ig i

    outside wall, allow for the 1/8 (3.2 mm) rise per ve feet (1.5

    m) g i i iz .

  • 8/9/2019 185885-001 Water Heater

    19/36

    19

    fIGure 25.

    The3 PVC,ABS,or CPVC Schedule 40ventpipecan berun

    fromthewaterheaterthroughthewallorfromthewalltothewater

    heater,whicheverismostconvenient.Theventpipemustextenda

    minimumof11/2(4cm)throughtheexteriorwall.Extendingthe

    vent cap asfaras possiblefromthesurfaceofthe exteriorwall

    willhelpminimizediscolorationofthewall.Notethattheinsideue

    mounting adaptors mustbe slippedoverthe vent pipingbefore

    locating the pipe through the wall. Before securing the inside and

    outsidecollarstothewall,useasiliconesealerbetweenpipeand

    opening to insure a water and air tight seal.

    InstallatIon showInG use of pvc, aBs or

    cpvc pIpe for Inlet and outlet vent pIpInG

    Inletpipingthroughanytypewall.

    fIGure 26.

    connectInG vent to Blower

    1. Ifmakinganimmediatehorizontalrunofventofftheblower,one

    3PVCinletandone3 PVC (CPVCfor75gallonmodelsand

    ABSfor50gallon65,000Btu/Hrmodels)outletSchedule40street

    elbowsarerequired.Placetheelbowintherequireddirectionon

    theblowerandattachtheelbowwith3sheetmetalscrews.

    fIGure 27.

    2. Ifthereistobeaverticalrunofventfromtheblower,the3PVC

    inletandthe3PVC(CPVCfor75gallonmodelsandABSfo

    50gallon65,000Btu/Hrmodels)outletpipesmustbeattachedtotheblowerandventinghoodusing6sheetmetalscrews.

    fIGure 28.

    InstallatIon showInG use of (optIonal

    deluXe horIZontal vent KIt

    Typicalinstallation.

    fIGure 29a.

    oi 3 pvc hiz v Ki:

    fIGure 29B.

  • 8/9/2019 185885-001 Water Heater

    20/36

    20

    Ifthisconcentrictermination,throughthewalltypeofventingsystemispreferred,theconcentricventkitcanbeorderedfromtheServicePartsDepartmentunderkit#9002749.Installationinstructionsareprovidedwiththekit.

    ventInG throuGh a roof

    Two3inletandoutletPVCSchedule40-45ventcapsaresupplied.

    A5 (1.5m) sectionof 3CPVC Schedule40outletventpipe issuppliedwith75gallonmodelsanda5(1.5m)sectionof3ABSSchedule40outletventpipeissuppliedwith50gallon65,000Btu/Hrmodels.Moremayberequiredandmustbepurchasedlocally.

    1. Thewaterheaterrequiresitsown(separate)ventingsystem.2. Only3"ABS Schedule 40pipingand ttingsare acceptable

    materialsontherstvefeetoftheoutletventsystemonthe50gallon65,000BTU/HRmodelsand3"CPVCSchedule40pipingandSchedule80ttingsareacceptablematerialsontherstvefeetoftheoutletventsystemon75gallonmodels.

    3. 3PVC,ABS,orCPVCSchedule40 piping and ttings areacceptablematerialsfortheinletventsystemandfortheoutletventsystemaftertherstvefeet(1.5m).

    4. Theunitcannotbeconnectedtoexistingventpipingorchimney.5. Ventingmustterminateverticallytotheoutdoors.6. The total verticalandhorizontalventruns cannotexceedthe

    maximumlengthwithamaximumnumberof90elbowsas

    speciedinthetablebelow.Ifmoreelbowsarerequired,theventingdistancemustbereduced5feetforevery90elbow.

    Thenumberof90elbowsshowninthetableisforboththeintakeairandventpipes.IE:Theventpipecancontainthree90elbows,theintakeairpipecanalsocontainthree90elbows.

    3" dIa. vents MaX.

    lenGth (ft.)

    nuMBer of 90

    elBows*

    45 1

    40 2

    35 3

    *NOTE:Two45elbowsareequivalenttoone90elbow.One90

    elbowequals5feet(1.5m)ofequivalentventlength.

    fIGure 30.

    vent pIpe preparatIon

    1. InItIal preparatIon

    A. Makesurethesolventcementyouareplanningtouseis

    designedforthespecicapplicationyouareattempting.

    B. K no w the p hysi ca l a nd ch emical ch ar acte ri st ics a nd

    limitationsofthePVC,ABSandCPVCpipingmaterialsthatyouareabouttouse.

    C. Knowthereputationofyourmanufacturerandtheirproducts.

    D. Knowyourownqualicationsorthoseofyourcontractor.The

    solventweldingtechniqueofjoiningPVC,ABSandCPVCpipe

    isaspecializedskilljustasanyotherpipettingtechnique.

    E. Closelysupervisetheinstallationandinspectthenished

    jobbeforestart-up.

    F. Contactthemanufacturer,supplier,orcompetentconsulting

    agencyifyouhaveanyquestionsabouttheapplicationorinstallation of PVC, ABS and CPVC pipe.

    G. Takethetimeandefforttodoaprofessionaljob.Shortcutswillonlycauseyouproblemsanddelaysinstart-up.Byfar,

    themajorityoffailuresinPVC,ABSandCPVCsystemsare

    theresultofshortcutsand/orimproperjoiningtechniques.

    2. selectIon of MaterIals

    CuttingDevice-SaworPipeCutter

    DeburringTool,Knife,File,orBevelingMachine(2[5cm]andabove)

    Brush-PureBristle

    Rag-Cotton(NotSynthetic)

    PrimerandCleaner

    SolventCement- PVCforPVCComponents and CPVCfor

    CPVCComponentsandABSforABScomponents.

    Containers-MetalorGlasstoholdPrimerandCement.Select

    thetypeofPVC,ABSorCPVCmaterialstobeusedonthebasis

    oftheirapplicationwithrespecttochemicalresistance,pressurerating,temperaturecharacteristics,etc.

    InsertionTool - Helpful forlarger diameter pipeand ttings6

    inches(15.2cm)andabove.

  • 8/9/2019 185885-001 Water Heater

    21/36

    21

    prIMer

    ItisrecommendedthatTetrahydrofuran(THF)beusedtopreparethe

    surfacesofpipeandttingsforsolventwelding.Donotusewater,

    rags,gasolineoranyothersubstitutesforcleaningPVC,ABSor

    CPVCsurfaces.AchemicalcleanersuchasMEKmaybeused.

    ceMent

    Thecementshouldbeabodiedcementofapproximately500to

    1600centipoiseviscositycontaining10-20%(byweight)virginPVC

    material solvated withtetrahydrofuran(THF). Smallquantities of

    dimethylformamide(DMF)maybeincludedtoactasaretarding

    agenttoextendcuringtime.Selectthepropercement;Schedule40

    cementshouldbeusedforSchedule40pipe.Neveruseall-purpose

    cements,commercialgluesandadhesivesorABScementtojoin

    PVCorCPVCpipeandttings.

    applIcators

    Selectasuitablepurebristletypepaintbrush.Useaproperwidth

    brushorrollertoapplytheprimerandcement(seechartbelow).

    Speedyapplication ofcement isimportant due toits fast drying

    characteristics.

    recoMMended Brush* sIZe for prIMer

    and ceMent applIcatIons

    nmi pi (Ips) siz B wi (Ins.)

    3 1-1/2 2-1/2

    *use onlY natural BrIstle

    3. MaKInG the joInt

    a. cig

    Pipemustbesquarelycuttoallowfortheproperinterfacingofthe

    pipeendandthettingsocketbottom.Thiscanbeaccomplished

    withamiterboxsaworwheeltypecutter.Wheeltypecuttersare

    notgenerallyrecommendedforlargerdiameterssincetheytendtoarethecornerofthepipeend.Ifthistypeofcutterisused,

    theareontheendmustbecompletelyremoved.

    NOTE:Powersawsshouldbespecicallydesignedtocutplastic

    pipe.

    step a

    B. dbig

    Useaknife,plasticpipedeburringtool,orletoremoveburrs

    fromtheendofsmalldiameterpipe.Besuretoremoveallburrs

    fromaroundtheinsideaswellastheoutsideofthepipe.Aslight

    chamfer(bevel)ofabout10-15shouldbeaddedtotheend

    topermiteasierinsertionofthepipeintotheendofthetting

    Failuretochamfertheedgeofthepipemayremovecementfrom

    thettingsocket,causingthejointtoleak.

    step B

    C. Test dry t of the joint

    Taperedttingsocketsaredesigned sothataninterfaced

    shouldoccurwhenthepipeisinsertedabout1/3to2/3ofthe

    wayintothesocket.Occasionally,whenpipettingdimensions

    areatthetoleranceextremes,itwillbepossibletofullyinserdrypipetothebottomofthettingsocket.Whenthishappens,

    asufcientquantityofcementmustbeappliedtothejointtoll

    thegapbetweenthepipeandtting.Thegapmustbelledto

    obtainastrong,leak-freejoint.

    d. Ii, ig, imig

    Visuallyinspecttheinsideofthe pipe andtting sockets and

    removealldirt,greaseormoisturewithacleandryrag.Ifwiping

    failstocleanthesurfaces,achemicalcleanermustbeused.

    Checkforpossibledamagesuchassplitsorcracksandreplace

    ifnecessary.

    d--y

    MarkingthedepthofentryisawaytocheckifthepipehasreachedthebottomofthettingsocketinStepF.Measure

    thettingdepthandmarkthisdistanceonthepipeO.D.You

    maywanttoaddseveralinchestothedistanceandmakea

    secondmarkastheprimerandcementwillmostlikelydestroy

    yourrstone.

  • 8/9/2019 185885-001 Water Heater

    22/36

    22

    Applyprimertothesurfaceofthepipeandttingsocketwitha

    naturalbristlebrush.ThisprocesssoftensandpreparesthePVC,

    ABSorCPVCforthesolventcementingstep.Movequicklyand

    withouthesitationtothecementingprocedurewhilethesurfaces

    arestillwetwithprimer.

    e. aii m

    Applythesolventcementevenlyandquicklyaroundtheoutsideofthe

    pipeatawidthalittlegreaterthanthedepthofthettingsocket.

    Applyalightcoatofcementevenlyaroundtheinsideofthe

    ttingsocket.Avoidpuddling. Applyasecondcoatofcementtothepipeend.

    step e

    f. ji mby

    Workingquickly,insertthepipeintothettingsocketbottomand

    givethepipeorttinga1/4turntoevenlydistributethecement.

    Donotcontinuetorotatethepipeafterithashitthebottomofthe

    ttingsocket.Agoodjointwillhavesufcientcementtomakea

    beadallthewayaroundtheoutsideofthettinghub.Thetting

    willhaveatendencytoslidebackwhilethecementisstillwet

    soholdthejointtogetherforabout15seconds.

    step f

    G. c i mm

    Removeallexcesscementfromaroundthepipeandttingwitha

    drycottonrag.Thismustbedonewhilethecementisstillsoft.

    Thejointshouldnotbedisturbedimmediatelyafterthecementing

    procedure,andsufcienttimeshouldbeallowedforpropercuringofthejoint.Exactdryingtimeisdifcultto predictbecauseit

    dependsonvariablessuchastemperature,humidityandcement

    integrity.Formorespecicinformation,youshouldcontactyour

    solventcementmanufacturer.

    step G

  • 8/9/2019 185885-001 Water Heater

    23/36

    23

  • 8/9/2019 185885-001 Water Heater

    24/36

    24

    Due tothenatureof the typical gas waterheater, the water

    temperatureincertainsituationsmayvaryupto30F(16.7C)

    higherorloweratthepointofusesuchas,bathtubs,showers,

    sink,etc.

    Itisrecommendedthatlowerwatertemperaturesbeusedtoavoid

    theriskofscalding.Itisfurtherrecommended,inallcases,that

    thewatertemperaturebesetforthelowesttemperaturewhichsatisesyourhotwaterneeds.Thiswillalsoprovidethemost

    energyefcientoperationofthewaterheater.

    HOTWATERCANSCALD:Waterheatersareintendedtoproduce

    hotwater.Waterheatedtoatemperaturewhichwillsatisfyspace

    heating,clothes washing, dishwashing,and other sanitizing

    needscanscaldandpermanentlyinjureyouuponcontact.Some

    peoplearemorelikelytobepermanentlyinjuredbyhotwater

    than others.These includetheelderly, children,the inrm,or

    physically/mentallydisabled.Ifanyoneusinghotwaterinyour

    hometsintooneofthesegroupsorifthereisalocalcodeor

    statelawrequiringacertaintemperaturewateratthehotwater

    tap,thenyoumusttakespecialprecautions.Inadditiontousing

    thelowestpossibletemperaturesettingthatsatisesyourhot

    waterneeds,ameanssuchasamixingvalveshouldbeusedat

    thehotwatertapsusedbythesepeopleoratthewaterheater.

    Mixingvalvesareavailableatplumbingsupplyorhardwarestores,

    seeFigure2.Followmanufacturersinstructionsforinstallationof

    thevalves.Beforechangingthefactorysettingonthethermostat,

    see Figure 31.

    Neverallowsmallchildren tousea hotwater tap, orto draw

    theirownbathwater.Neverleaveachildorhandicappedperson

    unattendedinabathtuborshower.

    Thewaterheatershouldbelocatedinanareawherethegeneralpublicdoesnothaveaccess.Ifasuitableareaisnotavailable,

    a cover should be installedover thethermostat to prevent

    tampering.

    The watertemperature setting was factory set at thelowest

    temperature; Pressingthe COOLER buttondecreases

    temperatureandpressingtheHOTTER buttonincreases

    thetemperature.

    Settingthewaterheatertemperatureat120F(49C)(Approx.

    markontemperaturesettingofgascontrolvalve)willreduce

    theriskofscalds.Somestatesrequiresettingsatspeciclower

    temperatures.

    teMperature reGulatIonToavoidanyunintentionalchangesinwatertemperaturesettings,

    thegascontrolvalvehasatamperresistantfeatureforchanging

    thetemperaturesetting.Tochangethetemperaturesettingfollow

    theseinstructions:

    1.WakeUpthetemperatureindica torsbyholdingdownboth

    COOLERandHOTTERtemperatureadjustmentbuttons

    atthesametimeforonesecond,seeFigure31.Oneortwoofthetemperatureindicatorswilllightup.Theseindicators

    willonlyremainonfor30secondsifnofurtherbuttonsare

    pressed.After30secondsthecontrolwillgobacktoSleep

    mode.

    2.Releasebothofthetemperatureadjustmentbuttons.

    a.TodecreasethetemperaturepressandreleasetheCOOLER

    buttonuntilthedesiredsettingisreached.

    b.ToincreasethetemperaturepressandreleasetheHOTTER

    buttonuntilthedesiredsettingisreached.

    NOTE:Holdingdownthebuttonwillnotcontinuetolowerorraisethetemperaturesetting.Thebuttonmustbepressedandreleased

    foreachtemperaturechangedesired.

    Shouldoverheatingoccurorthegassupplyfailtoshutoff,turn

    offthemanualgascontrolvalvetotheappliance.

    Gas control valve - front vIew

    tm sig

    diy

    A B C

    tim p 2

    3 dg B

    a ski

    C-Flashing=approx.160F(71C) About1/2second

    C=approx.150F(66C) About1-1/2seconds

    B=approx.140F(60C) Less than 5 seconds

    A=approx.130F(54C) About30seconds

    =approx.120F(49C) Morethan5minutes

    WARM=approx.80F(27C) - - - - - - - - - - - - -

    fIGure 31.

  • 8/9/2019 185885-001 Water Heater

    25/36

    25

    for Your InforMatIonstart up condItIons

    condensate

    Whenever the waterheater isfi l led with cold water, some

    condensatewillformwhiletheburnerison.Awaterheatermay

    appeartobeleakingwheninfactthewateriscondensate.This

    usuallyhappenswhen:

    a. Anewwaterheaterislledwithcoldwaterforthersttime.

    b. Burninggasproduceswatervaporinwaterheaters,particularly

    highefciencymodelswhereuetemperaturesarelower.

    c. Largeamountsofhotwaterareusedinashorttimeandtherell

    waterinthetankisverycold.

    Moisturefromtheproductsofcombustioncondenseonthecooler

    tanksurfacesandformdropsofwaterwhichmayfallontotheburner

    orotherhotsurfacestoproduceasizzlingorfryingnoise.

    Becauseofthesuddennessandamountofwater,condensatewater

    maybediagnosedasatankleak.Afterthewaterinthetankwarms

    up(about1-2hours),theconditionshoulddisappear.

    Donotassume the waterheater isleakinguntil therehasbeenenoughtimeforthewaterinthetanktowarmup.

    Anundersizedwaterheaterwillcausemorecondensation.Thewater

    heatermustbesizedproperlytomeetthefamilysdemandsforhot

    waterincludingdishwashers,washingmachinesandshowerheads.

    Excessivecondensate maybe noticed duringthe winter and

    early spring months whenincoming watertemperaturesare at

    their lowest.

    Goodventingisessentialforagasredwaterheatertooperate

    properlyaswellastocarryawayproductsofcombustionandwater

    vapor.

    sMoKe/odor

    Itisnotuncommontoexperienceasmallamountofsmokeandodor

    duringtheinitialstart-up.Thisisduetoburningoffofoilfrommetal

    parts, and will disappear in a short while.

    closed water sYsteMs

    Watersupplysystemsmay,becauseofcoderequirementsorsuch

    conditionsas highline pressure,among others, haveinstalled

    devicessuchaspressurereducingvalves,checkvalves,andback

    owpreventers.Devicessuchasthesecausethewatersystemto

    beaclosedsystem.

    therMal eXpansIon

    Aswaterisheated,itexpands(thermalexpansion).Inaclosed

    systemthevolumeofwaterwillgrowwhenitisheated.Asthe

    volumeofwatergrowstherewillbeacorrespondingincreasein

    waterpressureduetothermalexpansion.Thermalexpansioncan

    causeprematuretankfailure(leakage).Thistypeoffailureisno

    coveredunderthelimitedwarranty.Thermalexpansioncanalso

    causeintermittenttemperature-pressurereliefvalveoperation

    waterdischargedfromthevalveduetoexcessivepressurebuild

    up.Thisconditionisnotcoveredunderthelimitedwarranty.The

    temperature-pressurereliefvalveisnotintendedfortheconstanreliefofthermalexpansion.

    Aproperlysized thermal expansion tankshould be installed

    onallclosedsystemstocontroltheharmfuleffectsofthermal

    expansion.Contactalocalplumbingserviceagencytohavea

    thermalexpansiontankinstalled.

    stranGe sounds

    Possiblenoisesduetoexpansionandcontractionofsomemeta

    partsduringperiodsofheat-upandcool-downdonotnecessarily

    representharmfulordangerousconditions.

    Condensationcausessizzlingandpoppingwithintheburnerareaduringheatingandcoolingperiodsandshouldbeconsiderednormal

    SeeCondensateinthissection.

    operatIonal condItIons

    aIr In hot water faucets

    HYDROGEN GAS: Hydrogen gascanbe produced ina ho

    watersystemthathasnotbeenusedforalongperiodoftime

    (generally twoweeks or more). Hydrogengas isextremely

    flammableand explosive.Topreventthe possibilityof injury

    under these conditions, werecommend thehot water faucet

    located farthest away, beopenedfor several minutes before

    anyelectricalapplianceswhichareconnectedtothehotwate

    systemareused(suchasadishwasherorwashingmachine).Ifhydrogengasispresent,therewillprobablybeanunusualsound

    similartoairescapingthroughthepipeasthehotwaterfauce

    isopened.Theremustbenosmokingoropenflamenearthe

    faucetatthetimeitisopen.

    hIGh water teMperature shut off sYsteM

    This water heateris equipped with anautomaticgas shut-of

    system.Thissystemworkswhenhighwatertemperaturesare

    present.TurnOFFtheentiregassupplytothewaterheater

    Thehightemperatureshut-offisbuiltintothegascontrolvalve.

    Itisnon-resettable.Ifthehightemperatureshut-offactivates,the

    gascontrolvalvemustbereplaced.Contactyourgassupplier

    orserviceagency.

  • 8/9/2019 185885-001 Water Heater

    26/36

    26

    ventInG sYsteM InspectIon

    Atleastonceayearavisualinspectionshouldbemadeoftheventing

    system.Youshouldlookfor:

    1.Obstructionswhich couldcause improper venting. The

    combustionandventilationairowmustnotbeobstructed.

    2.Damageordeteriorationwhichcouldcauseimproperventingor

    leakageofcombustionproducts.

    Besuretheventpipingisproperlyconnectedtopreventescapeof

    dangerousuegasseswhichcouldcausedeadlyasphyxiation.

    Obstructionsanddeterioratedventsystemsmaypresentserious

    healthriskorasphyxiation.

    Chemicalvaporcorrosionoftheueandventsystemmayoccur

    ifairforcombustioncontainscertainchemicalvapors.Spraycan

    propellants, cleaning solvents,refrigeratorand air conditioner

    refrigerants,swimmingpoolchemicals,calciumandsodiumchloride,

    waxes,bleachandprocesschemicalsaretypicalcompoundswhich

    arepotentiallycorrosive.

    Ifafterinspectionoftheventsystemyoufoundsootingor

    deterioration, somethingis wrong. Callthe localgas utilityto

    correcttheproblemandcleanorreplacetheueandventingbefore

    resumingoperationofthewaterheater.

    Burner operatIon and InspectIon

    Flooddamageto awaterheatermaynot bereadilyvisible or

    immediatelydetectable.However,overaperiodoftimeaooded

    water heater will create dangerous conditions which can cause

    DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.

    Contacta qualified installer orserviceagency toreplacea

    oodedwaterheater.Donotattempttorepairtheunit!Itmustbe

    replaced!

    Atleastoncea year avisualinspectionshould bemadeof the

    mainburnerandthehotsurfaceigniterassemblyforproperame

    perIodIc MaIntenancecharacteristicsandignitionsequences.Thiscanbedonebyviewing

    themainburneroperationthroughtheViewportontheOuterDoor,

    seeFigure1.Themainburnershouldprovidecompletecombustion

    ofgas,igniterapidly,givereasonablyquietoperation,andcause

    noexcessiveameliftingfromtheburnerports.Iftheproperame

    characteristicsarenotevidentasinFigure32,makesurethatthe

    owofcombustionandventilationairisnotblockedintheventing

    system.

    Youshouldalsocheckforsooting.Sootisnotnormalandwillimpair

    propercombustion.AvisualinspectionofthemainburnerandHSI

    igniterassembly shouldalsobe doneat least once ayear, see

    Figure 32.

    Sootbuild-upindicatesaproblemthatrequirescorrectionbefore

    furtheruse.TurnOFFgastowaterheaterandleaveoffuntilrepairs

    aremade,becausefailuretocorrectthecauseofthesootingcan

    resultinarecausingdeath,seriousinjury,orpropertydamage.

    fIGure 32.

    Burner cleanInG

    Intheeventyourburnerorburnerairopeningsrequirecleaning,turntheblowerswitchtotheOFFpositionandallowtheburnertocool.

    Callaserviceagencytoremoveandcleantheburnerandcorrect

    theproblemthatrequiredtheburnertobecleaned.

    houseKeepInG

    Vacuumaroundbaseofwaterheaterfordust,dirt,andlintona

    regularbasis.

  • 8/9/2019 185885-001 Water Heater

    27/36

    27

    anode rod

    Eachwaterheatercontainsatleastoneanoderod,whichwillslowly

    deplete whileprotectingthe glass-linedtank fromcorrosion and

    prolonging the life of the water heater. Once the anode is depleted,

    thetankwillstarttocorrode,eventuallydevelopingaleak.Certain

    waterconditionswillcauseareactionbetweenthisrodandthewater.

    Themostcommoncomplaintassociatedwiththeanoderodisa

    "rotteneggsmell"producedfromthepresenceofhydrogensulde

    gasdissolvedinthewater.IMPORTANT:Donotremovethisrod

    permanentlyasitwillvoidanywarranties.Thepartslistincludes

    aspecialanodethatcanbeorderedifwaterodorordiscolorationoccurs.NOTE:Thisrodmayreducebutnoteliminatewaterodor

    problems.Thewatersupplysystemmayrequirespecialaeration

    or chlorination equipmentfrom a waterconditioning company to

    successfullyeliminateallwaterodorproblems.

    Theuseofawatersoftenermaydecreasethelifeofthewaterheater

    tank.Theanoderodshouldberemovedfromthewaterheatertank

    every3yearsforinspection.Thefollowingaretypical(butnotall)

    signsofadepletedanoderod:

    Themajorityoftherod'sdiameterislessthan3/8".

    Signicantsectionsofthesupportwire(approx.1/3ormoreof

    theanoderod'slength)arevisible.

    Iftheanoderodshowssignsofeitherorbothitshouldbereplaced.

    NOTE:Whetherre-installingorreplacingtheanoderod,checkfor

    anyleaksand immediatelycorrect iffound.In situations where

    clearanceabovethewaterheaterislimiteditmaybenecessaryto

    bendtheanoderodforremoval.Flexibleanoderodsareavailable

    forreplacement.

    Inreplacingtheanode:

    1. Turnoffgassupplytothewaterheater.

    2. Shutoffthewatersupplyandopenanearbyhotwaterfaucetto

    depressurizethewatertank.

    3. Drainapproximately5gallonsofwaterfromthetank(Referto

    the"DrainingandFlushing"sectionforproperprocedures).Close

    drainvalve.

    4. Removeoldanoderod.

    5. UseTeontapeorapprovedpipesealantonthreadsandinstall

    new anode rod.

    6. Turnonwatersupplyandopennearbyhotwaterfaucettopurge

    air from water system.Check foranyleaksandimmediately

    correctanyiffound.

    7. Restartthewaterheaterasdirected underthe"OperatingYou

    WaterHeater"section.Seethe"RepairPartsIllustration"section

    for anode rod location.

    teMperature-pressure

    relIef valve operatIon

    Thetemperature-pressurereliefvalvemustbemanuallyoperated

    atleastonceayear.

    fIGure 33.

    Whenchecking the temperature-pressure reliefvalve operation

    makesurethat(1)nooneisinfrontoforaroundtheoutletofthe

    temperature-pressurereliefvalvedischargeline,and(2)thatthe

    waterdischargewillnotcauseanypropertydamage,asthewater

    maybeextremelyhot,seeFigure33.

    Ifaftermanuallyoperatingthevalve,itfailstocompletelyresetand

    continuestoreleasewater,immediatelyclosethecoldwaterinle

    to the water heater, follow the draining instructions, and replace the

    temperature-pressurereliefvalvewithanewone.

    Ifthetemperature-pressurereliefvalveontheapplianceweepsor

    dischargesperiodically,thismaybeduetothermalexpansion.You

    mayhaveacheckvalveinstalledinthewaterlineorawatermete

    withacheckvalve.Consultyourlocalwatersupplierorservice

    agencyforfurtherinformation.Donotplugthetemperature-pressure

    reliefvalve.

    draInInG

  • 8/9/2019 185885-001 Water Heater

    28/36

    28

    Thewaterheatershouldbedrainedifbeingshutdownduringfreezing

    temperatures.Alsoperiodicdrainingandcleaningofsedimentfrom

    thetankmaybenecessary.

    1.SettheblowerswitchtotheOFFposition.

    2.CLOSEthecoldwaterinletvalvetothewaterheater.

    3.OPEN a nearbyhot water faucet andleaveopento allow for

    draining.

    4.Connectahosetothedrainvalveandterminatetoanadequate

    drain.

    5.OPENthewaterheaterdrainvalvetoallowfortankdraining.

    note: I i gig b i

    x i, i b i

    ig mi

    i.

    6.CLOSEthedrainvalve.

    7.FollowinstructionsintheFillingTheWaterHeatersection.

    8.Followthelightinginstructionsonthelabelorseepage23under

    LightingInstructionstorestartthewaterheater.

    draIn valve washer replaceMent

    (SeeFigure34)

    1.TurnOFFgassupplytowaterheater.

    2.FollowDraininginstructions.

    3.Turningcounterclockwise( ),removethehexcapbelowthe

    screw handle.

    4.Removethewasherandputthenewoneinplace.

    5.Screwthehandleandcapassemblybackintothedrainvalveand

    retighten using a wrench. DO NOT OVER TIGHTEN.

    6.FollowinstructionsintheFillingTheWaterHeatersection.

    7.Checkforleaks.

    8.FollowthelightinginstructionsintheLightingsectiontorestart

    the water heater.

    fIGure 34.

    servIce

    Ifaconditionpersistsoryouareuncertainabouttheoperationofthe

    waterheatercontactaserviceagency.

    UsethisguidetocheckaLeakingwaterheater.Manysuspected

    Leakersarenotleakingtanks.Oftenthesourceofthewatercan

    befoundandcorrected.

    Ifyouarenotthoroughlyfamiliarwithgascodes,yourwaterheater,

    andsafetypractices,contactyourgassupplierorqualiedinstaller

    tocheckthewaterheater.

  • 8/9/2019 185885-001 Water Heater

    29/36

    29

    leaKaGe checKpoIntsReadthismanualrst.Thenbeforecheckingthewaterheatermake

    surethegassupplyhasbeenturnedOFF,andneverturnthegas

    ONbeforethetankiscompletelyfullofwater.

    Neveruse this waterheaterunless itis completelylledwith

    water.Topreventdamagetothetank,thetankmustbelledwith

    water.Watermustowfromthehotwaterfaucetbeforeturning

    ONgastothewaterheater.

    A. Waterattheblowerassemblyiswatervaporwhichhascondensed

    outofthecombustionproducts.Thisiscausedbyaproblemin

    thevent.Contactthegasutility.

    B.*Condensationmaybeseenonpipesinhumidweatherorpipe

    connectionsmaybeleaking.

    C.*Theanoderodttingmaybeleaking(anodeislocatedunde

    theBlowerAssembly).

    D.Smallamountsofwaterfromtemperature-pr essurereliefvalve

    maybeduetothermalexpansionorhighwaterpressurein

    yourarea.

    E.*Thetemperature-pressurereliefvalve may beleakingat the

    tanktting.

    F.Waterfromadrainvalvemaybeduetothevalvebeingslightly

    opened.

    G.*Thedrainvalvemaybeleakingatthetanktting.

    H.Co mb u sti o n p r o d u cts co n ta i n wa te r va p o r wh i ch ca n

    condenseonthecoolersurfacesofthetank.Dropletsform

    anddripontotheburnerorrunonthefloor.Thisiscommon

    atthetimeofstart-upafterinstallationandwhenincoming

    water is cold.

    I. Waterinthe waterheater bottomor onthefloormaybe

    fromcondensation,loose connections, orthe relief valve

    DO NOT replace the water heater until a full inspection o

    allpossiblewatersourcesismadeandnecessarycorrective

    stepstaken.

    Leakage fromother appliances,water lines,or ground seepage

    shouldalsobechecked.

    * Tocheckwhere threadedportionenters tank, insertcotton

    swabbetweenjacketopeningandtting.Ifcottoniswet,follow

    DraininginstructionsinthePeriodicMaintenancesection

    andthenremovetting.PutpipedopeorTeontapeonthethreadsandreplace.ThenfollowFillingtheWaterHeater

    instructionsintheInstallingtheNewWaterHeatersection.

  • 8/9/2019 185885-001 Water Heater

    30/36

    30

    repaIr parts lIst

    Ky n. p dii

    1 v c /s

    2 a, f Mig

    3 5' aBs s 40 v pi (50 g. 65,000)

    3 5' cpvc s 40 v pi (75 g.)

    4 90 aBs s 40 eb (50 g. 65,000)

    4 90 cpvc s 80 eb (75 g. )

    5 v/B a

    6 B

    7 f a Gk (6' x 10.102")

    8 B Gk

    9 vig; M r si

    10 v h amby

    11 ji Bx

    12 t & p v

    13 di tb

    14 a r

    15 fv s Bk

    16 di p

    17 h s Igi i amby

    18 Orice

    19 B amby

    20 I d

    21 di v

    22 Mi

    23 rig a d /Gk

    24 l a d /Gk

    25a a d ci (2)

    25B jk/a d ci (6)26 fv s

    27 G c v

    28 p si (ai)

    29 Flue Bafe Assembly

    30 Bafe Adaptor Collar Assembly

    31 oi (dx) hiz v Ki

    32 otinal (3") pvc hrizntal vent Kit (75 Galln only)

    Nowthatyouhavepurchasedthiswaterheater,shouldaneedeverexistforrepairpartsorservice,simplycontactthecompanyitwaspurchasedfromordirectfromthemanufacturerlistedontheratingplate on the water heater.

    Besuretoprovideallpertinentfactswhenyoucallorvisit.

    sig i i b i i bi iig i y i b bi igy.

    ThemodelnumberofyourGasWaterHeaterwillbefoundontheratingplatelocatedabovethegascontrolvalve.

    WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THEFOLLOWINGINFORMATION:

    MODELNUMBER

    TYPEGAS(NATURALORPROPANE(L.P.)

    SERIALNUMBER

    PARTDESCRIPTION

    thIs Is a repaIr parts lIst, not a pacKInG lIst.

  • 8/9/2019 185885-001 Water Heater

    31/36

    31

    trouBleshootInG GuIdelInesTheseguidelinesshouldbeutilizedbyaqualiedserviceagent.Whencallingforservicenotifytheserviceagent

    thatthisisaFlammableVaporIgnitionResistantProduct.

    # led status proBleM solutIon

    1Thegascontrolvalvehassensed

    inadequate or no earth ground.

    1 Ensurethewalloutlet(powersupply)isproperly

    grounded.

    2 Ensure all ground connections/wires on the water

    heateraresecurelyconnected.

    2

    Thegascontrolvalvehassensed

    reversedpolarityinthe120VAC

    powersupply.

    1 Ensurethewalloutlet/powersupplyisproperlywired.

    2 Ensure all internal 120 VAC wiring connections and

    wiringharnesshavenoreversedwires.120VAC"hot"

    wiremustconnecttotheon/offswitch.

    3

    Pressureswitchcircuitremaining

    closedformorethan5seconds

    afterheatingcyclebegins.

    B my i i

    ii.

    1 Ensure air pressure switch circuit wiring is correct and

    theairpressureswitchisnotjumpered.

    2 Replace the air pressure switch.

    4

    Pressureswitchcircuitremains

    open longer than 5 seconds after

    theblowerisenergized.

    B my iy i

    i ii.

    1 Ensuretheairpressureswitchsensingtubeisproperlyconnectedatbothendsandisnotkinkedordamaged.

    2 Ensurethecorrectsizeofventandintakeairpipe(direct

    ventproducts)wasusedpertheinstallationinstructions

    inthemanualthatcamewiththewaterheater.

    3 Ensuremaximumnumberofelbowsormaximum

    equivalentfeetofventorintakeairpipehasnotbeen

    exceededpertheinstallationinstructionsinthemanual

    thatcamewiththewaterheater.

    4 Ensuretherearenoobstructionsintheventorintake

    air pipe.

    5Thegascontrolvalvehasdetected

    an open igniter circuit.

    1 Checkwiringtothehotsurfaceigniterassembly-

    replaceigniterassemblyifwiringisdamagedorworn.

    2 Checkresistanceoftheigniteratigniterassemblyplug

    -shouldbebetween11and18ohms-replaceigniterif

    open or shorted.

    3 Checkigniterassemblyplugandthesocketonthe

    bottomofthegascontrolvalveforgoodconnection.

    4 Replaceigniterassemblyiftheplugiswornor

    damaged.

    5 Replacethegascontrolvalveiftheigniterassembly

    socketonthebottomofthecontroliswornordamaged.

    6

    Ignition/amefailure.

    Thegascontrolvalvehasreached

    themaximumnumberorretries(3)

    forignitionandiscurrentlylocked

    out for one hour.

    Cyclethepowertothewaterheater

    off and on to reset.

    1 Gassupplyisturnedoff-pressureistoolow.

    2 Ensuretheamesensorisclean-usenesteelwool

    tocleantheamesensor.

    3 Manifoldgaspressuretotheburneristoolow.

    4 Checkigniterassemblyplugandthesocketonthebottom

    ofthegascontrolvalveforgoodconnection.Replace

    igniterassemblyiftheplugiswornordamagedreplace

    thegascontrolvalveifsocketiswornordamaged.

    5 Replaceigniterassembly.

  • 8/9/2019 185885-001 Water Heater

    32/36

    32

    trouBleshootInG GuIdelInestrouBleshootInG GuIdelInesTheseguidelinesshouldbeutilizedbyaqualiedserviceagent.Whencallingforservicenotifytheserviceagent

    thatthisisaFlammableVaporIgnitionResistantProduct.

    # led status proBleM solutIon

    7

    8

    9

    Thegascontrolvalvehasdetected

    aproblemwiththegasvalvedriver

    circuit,internalmicroprocessor,or

    other internal circuits.

    1 Turn the power off for 10-20 seconds then on again to

    clear these error codes.

    2 Ifanyoftheseerrorcodespersistorcannotbecleared

    -replacethegascontrolvalve.

    10

    Thegascontrolvalvehassensed

    mainburnerameoutofproper

    sequence.

    1 Turn the power off for 10-20 seconds then on again to

    clear these error codes.

    2 Replacethegascontrolvalveifthiserrorcodepersists.

    11

    Thegascontrolvalvehasdetected

    excessivewatertemperatureinthe

    tankandhasactivatedtheECO

    (energycutoff)hightemperature

    limit.

    1 Turn the power off for 10-20 seconds then on again to

    clear these error codes.

    2 Replacethegascontrolvalveiftheerrorcodepersists.

    12 Thegascontrolvalvehasdetectedthatoneorbothofthetemperature

    adjustbuttonsarestuck.

    1 Pressandreleasebothtemperatureadjustbuttons

    severaltimes-cyclewaterheaterpoweroffandon.

    2 Replacethegascontrolvalveiftheerrorcodepersists.

    13

    Thegascontrolvalvehasdetected

    thewatertemperaturesensor

    (locatedinthecontrolvalve's

    immersionprobe)iseitheropenor

    shorted.

    1 Turn the power off for 10-20 seconds then on again to

    clear these error codes.

    2 Replacethegascontrolvalveiftheerrorcodepersists.

    14

    Thegascontrolvalvehasdetected

    theFV(ammablevapor)sensoris

    either open or shorted.

    1 Ensure all FV sensor wiring is correct and the igniter

    assemblyplugandsocketconnectionsonthebottom

    ofthegascontrolvalvearemakinggoodcontact.

    2 Replace the FV sensor.

    15

    Thegascontrolvalvehasdetected

    thepresenceofammablevapors

    fromtheFV(ammablevapor)

    sensor.

    1 Donottouchanyelectricalswitch,donotuseany

    phoneinyourbuilding,anddonottrytolightanyappliance.

    2 Smellaroundthewaterheatertoensurethereareno

    gasleaksatthegascontrolvalve,inthesupplygas

    line(s),oranyothertypeofammablevapor(s)inthe

    area.

    3 Carefullyinspecttheareasurroundingthewaterheater

    foranysubstancessuchasgasoline,paint,paint

    thinners,varnish,orcleanersthatcouldemitammable

    vapors.Removeanythingthatcanpotentiallyemit

    ammablevaporsfromtheareaandstoreitproperlyin

    a different location.

    4 Callthetechnicalinformationsupportphonenumbershownonthewaterheaterlabelingforfurther

    assistance.

    16

    Thegascontrolvalvehasdetected

    the air pressure switch circuit is

    openingrepeatedlyduringone

    heatingcycle.

    LDO(Lint,Dust,andOil)lockout

    condition.

    1 Onmodelsequippedwithadilutionairintakescreenon

    theblowerassembly-check/cleanthisscreen.

    2 Onmodelsequippedwithacombustionairintake

    screenonthebasering(bottom)ofthewaterheater

    -check/cleanthescreen.

    3 Ensureintakeairscreen(s)onmodelssoequippedare

    notobstructed.

  • 8/9/2019 185885-001 Water Heater

    33/36

    33

    Theseguidelinesshouldbeutilizedbyaqualiedserviceagent.Whencallingforservicenotifytheserviceagent

    thatthisisaFlammableVaporIgnitionResistantProduct.

    proBleM cause solutIon

    not enouGh or

    no hot water

    1. Blower will not run.

    A) "ON/OFF"controlswitchturnedoff. Turnswitchtothe"ON"position.

    B) Blowerunplugged. Plugblowerbackinto115vac.outlet.

    C) Nopoweratoutlet. Repairservicetooutlet.

    D) Thermostatdefective. Replacethermostat.

    E) Controlharnessdefective. Replace control harness.

    F) Highlimitcontrolcircuitopen. Replace ECO.

    G) Blowermotordefective. Replaceblowerassembly.

    3. Thermostatproblems

    A) Thermostatsettoolow. Turntemperaturecontrolhigher.

    B) T he rmo st at o r ECO de fe ct ive . Re pl ac e th ermo st at o r ECO as req uired .

    4. Others

    A) Heaterundersized. Reduce hot water use.

    B) L ow g as p re ss ure. Contact dealer.

    C) Incomingwaterisunusuallycold. Allowmoretimeforheatertoreheat.

    D) Leakinghotwaterpipesorxtures. Haveplumbercheckandrepairleaks.

    vent pIpe too hot

    (aBove 170 f)

    Defectiveairowrestrictor.Ta ke u ni t o ut o f se rvic e i mmed iat el y; c all a s ervi cerepresentative.

    Notenoughdilutionairtomixwithuegasesininletelbow.

    Properdilutionairmustbeprovidedforcombustionanddilutionof

    uetemperature.Refertothe"INSTALLINGTHENEWWATER

    HEATER"sectioninthemanual.

    Dilutionairtoohotformixingwithuegases.Supply airis toohot. Check forheat sourcesaroundintake

    terminalandblockageofdilutionairleg.

    Wrongburnerorice. Installcorrectorice.

    Yellow flaMe

    Dirtinburnerports. Turnoffheaterandgas,cleanburnerhead.

    Combustionairpathrestricted. Checkintakeventingarrangementforobstructions.

    Notenoughdilutionairforpropercombustion. Checkintakeventingarrangementforobstructions.

    condensatIon

    Wat er on the oorunder heater. See"CONDENSATION"sect ion.

    Waterdrippingfromblowerassembly.Providedrip"TEE"tocatchcondensationfromhorizontalsection

    ofexhaustventclosetoblowerassembly.

    water leaKs

    Improperly sealed hot or cold supply connections, relief

    valve,drainvalveorthermostatthreads.Tighten threaded connections.

    Leakagefromotherappliancesorwaterlines. Inspect other appliances near water heater.

    Condensation of ueproduct s. See"CONDENSATION"sect ion.

    leaKInG t & p valve

    Thermalexpansioninclosedwatersystem. Installthermalexpansiontank(DONOTplugT&Pvalve).

    Improperlyseatedvalve.Checkreliefvalveforproperoperation(DONOTplugT&P

    valve).

    hot water odors (r

    cathodIc protectIon)

    Highsulfateormineralcontentinwatersupply. Drainandushheaterthoroughlythenrell.

    Bacteriainwatersupply. Chlorinatewatersupply.

    water too hot Thermostatset too high. Ref er to"TEMPERATUREREGULATION"sect ion.

    water heater sounds

    sIZZlInG - ruMBlInG

    Co nde ns at io n drip pi ng on b urner. Se e "CON DEN SATI ON" se ct io n.

    Sedimentatbottomofheatertank.Cleansedimentfromtank.Referto"DRAINING"instructionsin

    the"MAINTENANCE"section.

    sootInG Impropercombustion.Refer to the "COMBUSTION AIR AND VENTILATION"section.

    heater lIGht Goes out

    In 45 secondsOutletpolarityisreversed. Testpolarityandcorrect.

    vent Gas odors

    Lackofairsupply.

    Immediatelyshutdownthewaterheaterandcontactaservice

    agencytodeterminecause.

    Improperlyinstalledventpiping.

    Downdraft.

    PoorCombustion.

    trouBleshootInG GuIdelInestrouBleshootInG GuIdelInes

  • 8/9/2019 185885-001 Water Heater

    34/36

    34

    resIdentIal Gas warrantY

    Thiswarrantyshallapplyonlywhentheheateris:

    ownedbytheoriginalpurchaser; installedforindooroperationonly; used attemperaturesnotexceeding the maximum calibratedsettingofitsthermostat; used at waterpressurenot exceeding theworking pressureshownontheheater; lledwithpotablewater,freetocirculateatalltimesand withthetankfreeofdamagingwatersedimentorscale deposits; u s ed i n a n o n- c o rr o si v e a n d n o n- c on t am i na t ed atmosphere; usedwithfactoryapprovedanode(s)installed; initsoriginalinstallationlocation; intheUnitedStates,its territories orpossessions, and

    Canada; sizedin accordancewithproper sizing techniquesfor residentialwaterheaters; bearingaratingplatewhichhasnotbeenaltered,defaced orremovedexceptasrequiredbythewarrantor; usedinanopensystemorinaclosedsystemwith a properlysizedandinstalledthermalexpansiontank; operatedwithproperlyinstalleddripleginthegassupply line; redwiththefuelforwhichitwasfactorybuilt; redatthefactoryratedinput; operatedwith the innerandouter combustionchamber doors in placeandal l factorysealstocombustion

    chamberintact. installed withno attempted,noractualmodicationor alterationof the waterheatersdesign in anyway, including but not l imited to,theattachment ofnon-

    companyapprovedappliancesorequipment.

    Anyaccidenttothewaterheateroranypartthereof(includingfreezing, re, oods,or lightning), anymisuse,abuseoralteration ofit,any operation ofit ina modiedform, anyoperation of thewater heateron desalinated(deionized)water, or anydamage causedby attemptsto repairtankleaksor parts, willvoidthiswarranty. This warranty doesnotcoverwaterheatersreplacedforcosmeticreasonsorforreasonsofnoise,taste,odor,discoloredand/orrustywater.

    Thiswarrantydoesnotapplytowaterheatersusedtoheatpools,whirlpoolsorhottubsorusedforspaceheatingwhereitssizingdoesnotconformwithspecicationsoftheheatingcomponentmanufacturer.

    Thiswarrantygives you specic legal rights,and youmayhaveotherrightswhichvaryunderthelawsofeachprovince.Ifanyprovisionofthiswarrantyisprohibitedorinvalidunderapplicableprovincelaw,thatprovisionshallbeineffectivetotheextentof theprohibitionor invaliditywithoutinvalidatingtheremainderoftheaffectedprovisionortheotherprovisionsofthiswarranty.

    THIS WARRANTY IS APPLICABLE TO THE ORIGINAL

    OWNER ONLY,in accordancewiththewarrantytermsand

    conditionsspeciedbelow.

    StateWaterHeaters(thewarrantor)willfurnishtheORIGINAL

    OWNER,1)areplacementStatewaterheaterofequivalent

    sizeand current model ifthe glass-lined tankin thiswater

    heaterleaksand,2)areplacementpartforanycomponent

    part which fails.

    THE STATE WATER HEATERS REPLACEMENT MODEL OR

    PART WILL BE WARRANTED FOR ONLY THE UNEXPIRED

    PORTIONOF THEORIGINALWARRANTY. Thewarranty

    periodwillbedeterminedbytheoriginaldateofpurchaseofthe

    waterheater,orintheabsenceofaBillofSaleverifyingsaid

    date,fromthedateofmanufactureindicatedonratingplateafxedtothiswaterheater.Thiswarrantyisnottransferrable

    andappliestomodelslistedbelow:

    Whenthewaterheaterhasbeenusedforotherthansingle

    familyresidentialapplication;

    1.Thetankwarrantyshallbereducedto1yearfor6year

    models.

    2. Theparts warranty shallbe reducedto 1 year forall

    models.

    condItIons and eXceptIons

    This warranty shall applyonlywhen thewaterheater is

    installedandoperatedinaccordancewith1)alllocalfire

    codesandplumbingcodes,ordinancesandregulations,2)

    theprinted instructionsprovidedwith it,3) goodindustry

    practices,and4)propersafetypracticessuchasbutnot

    limitedtoaproperlysizeddrainpanifinstalledinanarea

    whereleakagefromthetankoritsconnectionswouldresult

    indamagetotheareaadjacenttotheheater.Inaddition,a

    newtemperatureandpressurereliefvalve,certifiedbythe

    CanadianGasAssociationmusthavebeenproperlyinstalled

    and piped to the nearest drain.

    serIes tk p

    s 6-Y M 6-y 6-y

    Gs6

  • 8/9/2019 185885-001 Water Heater

    35/36

    35

    servIce and laBor responsIBIlItY

    UNDER THIS LIMITED WARRANTY, THE WARRANTOR

    WILL PROVIDE ONLY A REPLACEMENT WATER HEATER

    OR PART THEREOF. THE OWNER IS RESPONSIBLE FOR

    ALLOTHERCOSTS.Suchcostsmayincludebutarenot

    limitedto:

    a. Labor chargesfor service,removal, or reinstallationofthe water heater or part thereof.

    b. Shippinganddeliverychargesforforwardingthenewwater

    heateror replacement partfrom thenearest distributor

    andreturningtheclaimeddefectiveheaterorparttosuch

    distributor.

    c. Al l costnecessary or incidental for handl ing and

    administrativecharges,and foranymaterialsand/or

    permitsrequiredforinstallationofthereplacementheater

    or part.

    lIMItatIon