Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
BASEBALLDIAMOND
PARKING
RATHGAR AVENUE
BERESFORD AVENUE
LILAC
STR
EET
ARGUE STREET
AREA OF WORK
FIRE STATION #13
KEY PLANSCALE: 1:500
1A0.0
ARCHITECT: 1x1 ARCHITECTURE INC120 FORT STREET, SUITE 103WINNIPEG, MANITOBA, R3C 1C7TEL: (204) 318-2010
FIRE STATION NO. 13INTERIOR RENOVATION
BID OPPORTUNITY 280-2020799 LILAC STREET, WINNIPEG, MANITOBA
ISSUED FOR CONSTRUCTION
JUNE 25, 2020
CONSULTANT TEAM
ABBREVATIONS
MAXIMUM
PLATE
PLYWOOD
LOCATIONMASONRY
MISCELLANEOUS
OVERHEAD
ON CENTER
MECHANICAL
OUTSIDE DIAMETER
OPENINGOPEN WEB STEEL JOIST
OUTSIDE FACE
METALNOT IN CONTRACT
MINIMUM
LONG
INSULATION
PRESSED STEELPREFINISHEDPANEL
PAINTED, PAINT
REINFORCED
REINFORCED CONCRETE
STEELSTAINLESS STEELSPECIFIED
SIMILAR
ROOM
PLASTIC LAMINATE
SIMEXTERIOREXT
FIRE HOSE CABINETF.H.C
ST, STL
SPEC'DS.S
CONCRETE BLOCK
CAST IN PLACE
COMPLETE WITH
CENTER LINE
CONTROL JOINT
EQUIPMENT
ELECTRICAL
C/W
EPOXELEC
EQUIP
ELEV
DWG, DRWG
EQ
EXP
EA
DNDTLD
ELEVATION
EQUAL
EXPOSED
EPOXY
DOWNDRAWINGEACH
DETAILDEEP
CONC
COL
C.I.P
CJ
CL
C.B
COLUMN
CONCRETE
REINFRM
R/CONCPTD, PT
PREFINPS
O.H
PL
PLYWP.LAM
PNL
O.W.S.JOPNG
O.C
O/FO.D
N.I.CMTL
BOTH SIDES
ABOVE FLOOR
BTWN
BOT, BTM
BLDGANODALUMA/FL
B.S
BM
ANODIZED
BOTTOM
BETWEEN
BEAMBUILDING
ALUMINUM MAS
MISC
MECHMIN
MAX
L
LOC
INSUL WATERPROOFED MEMBRANE
SUSPENDED
TOP OF
UNDER SIDE
STRUCTURALSURFACE MOUNTED
UNDER FLOORTYPICAL
STORAGE
WIDEWITH
VESTIBULE
VAPOUR BARRIERVEHICLEVERTICAL
GYPSUM WALL BOARDGRID LINE
HOLLOW METAL
GALVANIZED
GENERAL CONTRACTOR
HEAVY DUTY
HORIZONTAL
HOLLOW STEEL SECTIONHYDRAULICINSIDE DIAMETERINSIDE FACE
GWB
HYDR
HOR, HORIZ
INTI/FI.D
HT
HSSHR
H.M
H.DH
INTERIOR
HEIGHT
HOUR
HIGH
G.L
GALV
FLR, FL
G.C
GA
FIN
GAUGE
FINISHFLOOR
W/W.MEM
VERTVESTW
VEHV.B
SURF MTD
TYP
U/S
U/F
T.O.
STO, STOR
SUSP
STRUC
SLOPESLP
SHOWERSHWR
HAZARDOUS WASTEH.W
GALVALUMEGLUM
LIGHT WEIGHTL.W
CENTER POINTC.PC.L.F CHAIN LINK FENCE
THICK / THICKNESSTH
UNDER GROUNDU/G
TOP OF CONCRETET.O.C.
WEEPING TILEW.T.
FLOOR DRAINFD
ROUGH OPENINGR.O.
ROOF DRAINR.D.
MASONRY OPENINGM.O.MIRRORMR
INTERIOR WALL TYPES
DOOR NUMBER
ROOM NAME & NUMBER
STRUCTURAL GRID
WALL SECTION
DRAWING TITLE & REFERENCE
KEY NOTE
BUILDING SECTION
SECTION DETAIL
NORTH ARROW
SYMBOLS
INTERIOR ELEVATION
TITLEScale = 1:
#A#.#
100 000LOCATION
D000
ELEVATION POINTS IN PLAN
#
#A#.# SIM.
#A#.#
CEILING HEIGHT A.F.F.
GLAZING TYPE
HR FIRE RATING
# REVISION NUMBER
EXTERIOR ELEVATION#
A#.#
LOCATION100 000
BENCHMARK ELEVATION
ROOMRM#
NAME
1/A
#A#.#
EXTERIOR WALL TYPE
D#
A
BD
C
W#
W#
SEPARATION WITH F.R.R.R
W#
G#
FULL HEIGHT SEPARATIONFH
W#
0000
GENERAL DRAWING NOTESTHE DRAWINGS SHALL NOT BE SCALED. FOLLOW GIVEN DIMENSIONS ONLY.
THE CONTRACTOR SHALL SATISFY HIMSELF THAT ALL DIMENSIONS, ELEVATIONS, DATUMS, AND INFORMATION SHOWN ARE CORRECT. VERIFY ALL DIMENSIONS ON SITE. DIMENSIONS ARE AS FOLLOW UNLESS OTHERWISE NOTED: - FACE OF MASONRY WALLS - EXTERIOR FACE OF ALL INTERIOR WALLS
PRIOR TO COMMENCEMENT OF WORK, REPORT ANY DISCREPANCIES TO THE CONTRACT ADMINISTRATOR.
VARIATIONS AND MODIFICATIONS TO WORK SHOWN WILL NOT BE ALLOWED WITHOUT THE WRITTEN PERMISSION OF THE CONTRACT ADMINISTRATOR.
ALL DIMENSIONS ARE IMPERIAL UNLESS OTHERWISE NOTED.
NO REPRODUCTION OF THE DRAWINGS MAY BE MADE WITHOUT THE WRITTEN CONSENT OF THE CITY OF WINNIPEG AND ALL REPRODUCTION MUST BEAR THE NAME OF THE ARCHITECT.
GENERAL CONTRACTOR SHALL NOTIFY THE CONTRACT ADMINISTRATOR OF ANY MECHANICAL AND ELECTRICAL APPARATUS APPEARANCE WHICH MAY VARY FROM THAT INDICATED IN THE CONTRACT DOCUMENTS.
DRAWING LIST
MECHANICAL EPP SIEPMAN ENGINEERING INC.ENGINEER: 136 MARKET AVE
WINNIPEG, MANITOBA, R3B 3N2TEL: (204) 453-1080
ELECTRICAL EPP SIEPMAN ENGINEERING INC.ENGINEER: 136 MARKET AVE
WINNIPEG, MANITOBA, R3B 3N2TEL: (204) 453-1080
PRIME CONSULTANT:
MECHANICALM2.1 FLOOR PLANS - MECHANICAL
ELECTRICALE0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONSEL2.1 MAIN FLOOR - LIGHTING PLANEP2.1 MAIN FLOOR - POWER PLANE6.1 ELECTRICAL SCHEDULES
ARCHITECTURALA0.0 TITLE SHEETA1.0 FLOOR PLANSA1.1 REFLECTED CEILING PLANSA1.2 INTERIOR ELEVATIONS & MILLWORK
DETAILSA1.3 FLOOR FINISH PLANS, INTERIOR
ELEVATIONS & MILLWORK DETAILSA1.4 SCHEDULES & SPECIFICATIONS
NOTE:THE SCOPE OF THE RENOVATION DOES NOT CHANGE THE USE, OCCUPANT LOAD, MAJOR OCCUPANCY CLASSIFICATION OR EXIT CONFIGURATION OF THE BUILDING. IN OUR PROFESSIONAL OPINION, LIFE SAFETY WILL NOT BE AFFECTED BY THIS MODERNIZATION AND INTERIOR ALTERATION.
A1.019089A
FLOOR PLANS
WINNIPEG FPS FIRE STATION #13
NO.
0
DATE
25.06.2020
REVISION / ISSUANCE
-
1 DD.MM.YYYY -
2 DD.MM.YYYY -
3 DD.MM.YYYY -
4 DD.MM.YYYY -
Seal
Engineer
Project
Sheet Title
Project No.
Date
Sheet
25.06.2020
Architect
799 LILAC STREET
ISSUED FOR CONSTRUCTION
SPK30
1GR DW ST
MW
2222
18
18
3
3
3
3
3
3
3
18
18
3
3
3
18
18
18
ROOMG-04
PHONE
40
27
2020
29
5
6
FR
PO
P
FR
TD
7
7
9
10
35
32
12
13
14
15
3917
4
40
4040
21
21
21212121
21
21
3
40TYP.
19
22
23
24
CMCO
43
40
26
26
4
PH
PH
11
33
TYP.2
2
36
TT
8
4
4
30 34
34
38
WF
2
39
34
37
4
30
PH
FE
FE
FE
30
30
3016
16
4
4
3
18
3
18
29
25
2525
25
18
41TYP.
18
42
34
34
34
6
16
26
10
10
44 44 SPK
SPK
SPK
SPK
SPK
ROOMG-12
APPARATUS
VESTIBULEG-19
ROOMG-14
MECHANICAL
RECEPTIONG-02
ROOMG-23
CONTROL
OFFICEG-05
LIEUTENANT'S
OFFICEG-06
CAPTAIN'S
LOUNGEG-07
KITCHENG-08
CORRIDORG-03
CORRIDORG-13
WASHROOMG-16
MEN'S
SHOWERG-15
ROOMG-11
STATIONARY
WASHROOMG-09
UNISEX
ROOMG-17
LOCKER
DORMITORYG-18
VESTIBULEG-01
ROOMG-22
STORAGE
HOSE TOWERG-20
ROOMG-21
DRYING
UP
ROOMG-10
CLEANING
MAIN FLOOR PLAN - DEMOLITIONSCALE: 1/8" = 1'-0"
1A1.0
DEMOLITION PLAN NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
DEMOLISH ALL KITCHEN CABINETS & COUNTERS. G.C. TO CONFIRM IF OWNER TO RETAIN EXISTING APPLIANCES. REFER TO ELECT. & MECH.
REMOVAL OF EXISTING FURNITURE/EQUIPMENT FOR NEW FLOORING INSTALLATION TO BE COMPLETED BY OTHERS. FURNITURE TO BE RETURNED TO CONTRACT ADMINISTRATOR.
DEMOLISH EXISTING FLOORING & RUBBER BASEBOARD. PREPARE CONCRETE FLOOR FOR NEW FLOORING.
PATCH & REPAIR ABANDONED ELECTRICAL THROUGHOUT. IN DORM G-18, LOWER EXISTING JUNCTION BOXES/RECEPTACLES FOR EXISTING GYM EQUIPMENT AND PROVIDE NEW FACE PLATES. REFER TO ELECT.
DEMOLISH EXISTING WALL MOUNTED COUNTER. PATCH & MAKE GOOD & PAINT ALL ADJACENT SURFACES.
REMOVE EXISTING PHONE. REFER TO ELECTRICAL.
EXISTING FRIDGE TO BE REMOVED & RELOCATED FOR FLOORING INSTALLATION. REFER TO INTERIOR ELEVATIONS AND RENOVATION PLAN.
EXISTING HAND SANITIZER TO REMAIN. PROTECT DURING CONSTRUCTION.
REMOVE & RELOCATE EXISTING POPCORN MACHINE
REMOVE EXISTING SHELVING UNIT & RETURN TO OWNER.
DEMOLISH EXISTING HOOD & DUCT ABOVE FLAT GRILLE. PATCH & REPAIR DRYWALL. REFER TO MECH. RETURN FLAT GRILLE TO OWNER.
DEMOLISH JANITOR SINK, REFER TO MECHANICAL. PATCH & MAKE GOOD ALL SURFACES INCLUDING FLOORING.
DEMOLISH URINAL, REFER TO MECHANICAL. PATCH & MAKE GOOD ALL SURFACES.
DEMOLISH EXISTING SHELF & WALL SUPPORTS. PATCH & MAKE GOOD ALL ADJACENT SURFACES, TYP.
DEMOLISH EXISTING WALL HOOKS. PATCH & MAKE GOOD ALL ADJACENT SURFACES, TYP.
EXISTING FAUCET TO BE DEMOLISHED - TYPICAL. REFER TO MECH.
GENERAL NOTES:
THESE DRAWINGS SHALL NOT BE SCALED.
THE CONTRACTOR SHALL VISIT THE SITE AND SATISFY ONESELF ALL DIMENSIONS, DATUM, AN DETAILED INFORMATION SHOWN ARE CORRECT.
THE CONTRACTOR IS TO REVIEW AND COORDINATE ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS THROUGH FLOORS, WALLS, AND CEILINGS FOR DUCT, PIPE & ELECTRICAL RISERS AND ALL OPENINGS NOT SHOWN ON DRAWINGS.
ALL OPENINGS THROUGH FIRE ASSEMBLIES ARE TO BE FIRESTOPPED AND SEALED WITH ULC APPROVED FIRE STOPPING TO MAINTAIN THE INTEGRITY OF THE FIRE SEPARATION, AND PROVIDE A SMOKE-TIGHT BARRIER.
ALL PRODUCTS AND MATERIALS TO BE USED AND INSTALLED SHALL CONFORM WITH MANUFACTURER'S SPECIFICATIONS & APPLICABLE CODES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND MAKE GOOD ALL EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AND THE REMOVAL OF ALL ITEMS FORMING PART OF THE RENOVATION WORK.
WHERE NEW FLOORING AND BASE IS TO BE INSTALLED IN EXISTING AREAS (REFER TO FLOOR PLAN AND ROOM SCHEDULE) THE EXISTING FLOORING SURFACE AND BASE MUST BE REMOVED, UNLESS OTHERWISE NOTED. ALL FLOOR SURFACES SHALL BE PREPARED IN ACOORDANCE TO MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF NEW FLOOR.
WHERE PAINTING OF EXISTING WALLS & CEILINGS IS INDICATED ON THE ROOM SCHEDULE, THESE WALLS MUST BE CLEANED OF ANY EXISTING WALL COVERING, PATCHED & PREPARED TO ACCEPT NEW PAINT, UNLESS OTHERWISE NOTED.
ALL EXISTING FURNITURE, EQUIPMENT (INCLUDING GYM EQUIPMENT), AND WALL MOUNTED ITEMS/ ARTWORK/ MAPS/ EXIT PLANS ARE TO BE REMOVED AND REINSTALLED BY THE CITY OF WINNIPEG'S MOVERS (TO BE STORED IN THE APPARATUS ROOM OR A STORAGE CONTAINER AS REQ'D).
EMERGENCY LIGHTING TO BE REPLACED, REFER TO ELECTRICAL FOR SCOPE OF WORK.
ALL MISCELLANEOUS FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION.
ALL MECHANICAL WALL VENTS/GRILLES TO BE REMOVED & REINSTALLED FOR PAINTING.
ALL EXISTING DOORS ARE TO BE CUT DOWN OR ADJUSTED AS REQUIRED TO ACCOMMODATE NEW FLOORING THICKNESS. PATCH & MAKE GOOD ALL DOORS.
ALL FIRE EXTINGUISHERS TO BE REMOVED AND REINSTALLED FOR PAINTING.
WARNING:ASBESTOS MAY BE PRESENT BEHIND WALLS CEILING SPACE & FLOORS. IF ASBESTOS OR ANY HAZARDOUS MATERIAL IS FOUND STOP WORK IMMEDIATELY & CONTACT CITY OF WINNIPEG, CENTRAL CONTROLS PH: 204-986-2351.
SPK
SPK
SPK
SPK
SPK
ROOMG-12
APPARATUS
VESTIBULEG-19
ROOMG-14
MECHANICAL
RECEPTIONG-02
ROOMG-23
CONTROL
OFFICEG-05
LIEUTENANT'S
OFFICEG-06
CAPTAIN'S
LOUNGEG-07
KITCHENG-08
CORRIDORG-03
CORRIDORG-13
WASHROOMG-16
MEN'S
SHOWERG-15
ROOMG-11
STATIONARY
WASHROOMG-09
UNISEX
ROOMG-17
LOCKER
DORMITORYG-18
VESTIBULEG-01
ROOMG-22
STORAGE
HOSE TOWERG-20
ROOMG-21
DRYING
UP
ROOMG-10
CLEANING
11
A1.3
21
34
2222
2
2
2
2
W1
W2
W3
W4
W5W5W5W5
W5
21
21
21
21
21
40
21
16
21
21
21
37
31
5
23
6
3
DWMW
PO
P
FR
A1.2 5
W1
A1.2
6A1.27
4'-11"
7
38
38
44
20 3845
A1.3
3
24
6
TD
13
14
14
14
14
14
14
14
21
21
4
4
28 28
33
3333
3318
1919
35
25
25
25
25
12
CMCO
WADR
29
29
8
FR
13
17
WF
CG
CG 30
30
30 30
36
W1
17
11 CG
CG
A1.2
8
A1.2 9
22
14
10
43
FE
FE
DG05
15
FE
11
26
39
39
11
40
41
41
42±17'-6 1/2"
13
A1.3
32
9
23
5'-0
"5'
-0"
3'-6"
4646
4747
MAIN FLOOR PLAN - RENOVATIONSCALE: 1/8" = 1'-0"
3A1.0
SPK
SPK
SHOWER
HOSE TOWERG-20
DN
W5DORMITORY
M-01
RESCUEM-04
WATER
STAIRHALLM-03
W/CM-02
1TYP.
11 TYP. TYP.221
21
252533
2719
1414
14
FE
39
3422
MEZZANINE RENOVATION PLANSCALE: 1/8" = 1'-0"
4A1.0
RENOVATION PLAN NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
PATCH & PAINT EXISTING GWB IN WATER RESCUE ROOM, TYP.
PROVIDE NEW BLINDS AT ALL EXTERIOR WINDOWS, TYP. REFER TO WINDOW SCHEDULE AND SPECS.
INSTALL NEW WALL MOUNTED BATHROOM SHELF - REFER TO SPECIFICATIONS.
PAINT EXISTING METAL DOOR AND FRAME. PROVIDE KICKPLATE ON PUSH SIDE OF DOOR - REFER TO SPECS.
NEW DINING TABLES - REFER TO DETAILS & SPECIFICATIONS
EXISTING RECESSED FLOOR MAT TO REMAIN
RELOCATE EXISTING FRIDGE
EXISTING TOWEL BAR TO REMAIN. PROTECT DURING CONSTRUCTION.
NEW KITCHEN FAUCET - REFER TO MECH & SPECS
NEW VENT HOOD ABOVE - REFER TO MECH & INTERIOR ELEVATIONS
NEW ROOM DIVIDER PANELS - REFER TO SPECIFICATIONS. FINAL ROOM LAYOUT TO BE DETERMINED BY OWNER.
EXISTING TELEPHONE TO REMAIN
EXISTING MONITOR SCREEN C/W NEW ADJUSTABLE MONITOR ARM. CONTRACTOR TO SUPPLY AND INSTALL NEW ARM W/ EXISTING SCREEN. REFER TO SPEC.
PAINT EXISTING METAL DOOR FRAME. WOOD DOOR TO REMAIN UNPAINTED. CUT DOWN WOOD DOORS AS REQ'D FOR NEW TILE FLOORING. PROVIDE KICKPLATE ON PUSH SIDE OF DOOR - REFER TO SPECS.
NEW VENT IN TOE KICK - REFER TO MECH.
NEW WATCHDESK - REFER TO MILLWORK DETAILS
NEW BACKPAINTED GLASS MARKERBOARD - REFER TO SPECS & INTERIOR ELEVATIONS
INTERIOR RENOVATIONS
BID OPPORTUNITY 280-2020
EXISTING WALL TO BE DEMOLISHED
NEW WALL
EXISTING WALL TO REMAIN
EXISTING DOOR TO REMAIN
FLOOR PLAN LEGENDWF WATER FOUNTAINGR FLAT GRILLSPK SPEAKERFR FRIDGEPOP POPCORN MACHINETD TOWEL DISPENSERMW MICROWAVEDW DISHWASHERST STOVECO COFFEE GRINDERCM COFFEE MAKERCG CORNER GUARDWA WASHING MACHINEDR DRYERPH PHONESPK SPEAKERT THERMOSTATFE FIRE EXTINGUISHER
EXISTING CONC. BLOCK WALL TO REMAIN
NEW DOOR
EXISTING DOOR TO BE DEMOLISHED
FLOOR FINISH LEGENDWALL TYPES:
5/8" TYPE 'X' GYPSUM BOARD, PAINT FINISH3 5/8" STEEL STUDS @ 16" O.C.3 1/2" MINERAL FIBER INSULATION5/8" TYPE 'X' GYPSUM BOARD, PAINT FINISH
PARTITIONS TO RUN TO EXISTING CEILING HEIGHT OF ±9'-0"
W1
SPK
SPK
SHOWER
HOSE TOWERG-20
DN
W5DORMITORY
M-01
RESCUEM-04
WATER
STAIRHALLM-03
W/CM-023
4021
3
3128
3438
FE
16
25
18
2518
31
MEZZANINE DEMOLITION PLANSCALE: 1/8" = 1'-0"
2A1.0
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
DEMOLISH EXISTING WALL HOOKS. PATCH & MAKE GOOD ALL ADJACENT SURFACES, TYP.
EXISTING FAUCET TO BE DEMOLISHED - TYPICAL. REFER TO MECH.
DEMOLISH EXISTING STOVE & EXHAUST HOOD. REFER TO MECH & ELECT.
EXISTING FLOORING TO REMAIN.
DEMOLISH EXISTING WALL MOUNTED SHELF AND REDUNDANT BRACKETS. PATCH, REPAIR & PAINT ALL SURFACES.
DEMOLISH EXISTING WALL INCLUDING ALL EXISTING ELECTRICAL. PATCH & MAKE GOOD ALL ADJACENT SURFACES. REFER TO ELECT.
DEMOLISH EXISTING BLINDS. PATCH & REPAIR ALL SURFACES
DEMOLISH EXISTING SPEAKER - REFER TO ELECT. PATCH & MAKE GOOD ALL SURFACES.
EXISTING MICROWAVE TO BE RELOCATED. PROTECT DURING CONSTRUCTION.
EXISTING COFFEE MAKER & COFFEE GRINDER TO BE RELOCATED. PROTECT DURING CONSTRUCTION.
REMOVE EXISTING WHITEBOARD/CORKBOARD AND SALVAGE FOR REINSTALLATION.
REMOVE EXISTING WHITEBOARD/CORKBOARD & RETURN TO CONTRACT ADMINISTRATOR.
DEMOLISH EXISTING WALL INCLUDING ALL EXISTING ELECTRICAL. PATCH & MAKE GOOD ALL ADJACENT SURFACES. RELOCATE EXISTING HUMIDISTAT & SPEAKER VOLUME DIAL AS SHOWN ON RENOVATION PLAN. REFER TO ELECT/MECH.
EXISTING HVAC UNIT TO REMAIN - REFER TO MECH.
DEMOLISH EXISTING DOOR & FRAME.
DEMOLISH ALL EXISTING WALL SCONCES, TYP. REFER TO ELECT. PATCH & MAKE GOOD ALL WALL SURFACES.
EXISTING SHELVING UNIT TO REMAIN. PROTECT DURING CONSTRUCTION.
DEMOLISH KITCHEN SINK, REFER TO MECHANICAL.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
NEW WATCHDESK - REFER TO MILLWORK DETAILS
NEW BACKPAINTED GLASS MARKERBOARD - REFER TO SPECS & INTERIOR ELEVATIONS
PROVIDE NEW CUSTOM WALL MOUNTED SHELF. REFER TO DETAILS.
PATCH & PAINT ALL GWB SURFACES
NEW DISHWASHER - REFER TO MECHANICAL AND SPEC
PAINT ALL WALLS & INSTALL NEW FLOORING & BASEBOARD THROUGHOUT. REFER TO FLOOR FINISH PLAN AND ROOM SCHEDULE AND SPECS.
PAINT EXISTING STAIR RAILING & METAL STRINGERS, BOTH SIDES.
TV AND MOUNT SUPPLIED BY CONTRACT ADMINISTRATOR. CONTRACTOR TO PROVIDE BLOCKING AS REQ'D AND INSTALL TV & MOUNT.
NEW STACKED WASHER & DRYER. REFER TO SPECS, MECHANICAL & ELECTRICAL.
INSTALL EXISTING WHITEBOARD/CORKBOARD. CO-ORDINATE EXACT LOCATION WITH CONTRACT ADMINISTRATOR.
NEW GREASE INTERCEPTOR BELOW SINK - REFER TO MECH.
PATCH & PAINT ALL SIDES OF EXISTING GWB MECHANICAL SURROUND TO MATCH WALL.
PAINT EXISTING WINDOW FRAME. REFER TO ROOM SCHEDULE.
REMOVE EXISTING CLOCK FOR PATCHING AND PAINTING. REINSTALL IN ORIGINAL LOCATION, TYP.
REMOVE EXISTING ARTWORK FOR PATCHING AND PAINTING. REINSTALL IN ORIGINAL LOCATION, TYP.
RELOCATED GAS DETECTION - REFER TO ELECT/MECH.
RELOCATED HUMIDISTAT - REFER TO MECH.
REINSTALL EXISTING LOCKERS IN ORIGINAL LOCATIONS. FASTEN TO FLOOR AND WALL AS PER ORIGINAL CONDITION, TYP.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
45.
46.
47.
RELOCATED HUMIDISTAT - REFER TO MECH.
REINSTALL EXISTING LOCKERS IN ORIGINAL LOCATIONS. FASTEN TO FLOOR AND WALL AS PER ORIGINAL CONDITION, TYP.
PROVIDE RUBBER TREADS ON STAIR WITH CONTRASTING COLOUR STRIP. SEE SPECIFICATIONS.
EXISTING CLOSET ROD & SHELF TO REMAIN. PAINT SHELF & CLEATS TO MATCH WALL.
RELOCATED SPEAKER VOLUME DIAL - REFER TO ELECT.
NEW STORAGE CABINETS. REFER TO MILLWORK DETAILS.
NEW MILLWORK - REFER TO DETAILS
INSTALL NEW MOTION SENSOR FAUCETS - REFER TO MECH
PAINT ALL WALLS. REFER TO ROOM SCHEDULE AND SPECS. EXISTING FLOORING TO REMAIN.
CHAIRS (N.I.C.)
EXISTING FLOOR GRILLE TO REMAIN, TYP.
NEW WOOD DOOR & METAL FRAME - REFER TO SPECIFICATIONS. PROVIDE KICKPLATE ON PUSH SIDE OF DOOR - REFER TO SPECS.
NEW INTEGRATED STAINLESS STEEL SINK - REFER TO SPECS, DETAILS AND MECHANICAL.
NEW ELECTRIC RANGE - REFER TO ELECTRICAL & SPECIFICATIONS
INSTALL NEW MOISTURE RESISTANT GWB BEHIND THE ENTIRE LENGTH OF KITCHEN WALL TO 7'-8" HIGH & BEHIND STAINLESS STEEL BACKSPLASH. PATCH & MAKE GOOD ALL SURFACES. REFER TO INTERIOR ELEVATIONS.
ADD PUSH PLATE TO DOOR - REFER TO SPECS.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40.
41.
42.
43.
44.
EXISTING SHELVING UNIT TO REMAIN. PROTECT DURING CONSTRUCTION.
DEMOLISH KITCHEN SINK, REFER TO MECHANICAL.
REMOVE & REPLACE EXISTING WIREMOLD & EXTEND TO NEW MILLWORK - REFER TO INT. ELEVATIONS. PATCH ALL SURFACES.
REMOVAL & REINSTALLATION OF ALL EXISTING FURNITURE / EQUIPMENT FOR FLOORING INSTALLATION TO BE COMPLETED BY OTHERS, TYP. PROTECT ALL FURNITURE DURING CONSTRUCTION. (NOTE: NOT ALL FURNITURE/EQUIPMENT IS SHOWN).
REMOVE & RELOCATE EXISTING WALL MOUNTED TOWEL DISPENSER
EXISTING TOWEL BAR TO REMAIN. PROTECT DURING CONSTRUCTION.
RELOCATE EXISTING GAS DETECTOR - REFER TO ELECT & RENOVATION PLAN.
EXISTING GAS DETECTOR TO REMAIN. REFER TO ELECT.
DEMOLISH UNDERCOUNTER LIGHTING - REFER TO ELECT.
REMOVE EXISTING LOCKERS & STORE FOR REINSTALLATION.
EXISTING FLOOR GRILLE TO REMAIN, TYP. REFER TO FLOOR FINISH PLAN.
DEMOLISH EXISTING DISHWASHER
CONTRACTOR TO REMOVE & REINSTALL EXISTING SHELVING UNIT. DISASSEMBLE / REASSEMBLE AS REQ'D.
DEMOLISH EXISTING GWB BEHIND ENTIRE LENGTH OF KITCHEN WALL UP TO 7'-8" HIGH. REFER TO INTERIOR ELEVATIONS.
NOTE: CONTRACTOR TO PROVIDE NEW PENETRATION IN ROOF AS REQUIRED FOR MECHANICAL DUCTWORK. CONTRACTOR TO PROVIDE FLASHING AND SEAL AS PER INDUSTRY STANDARDS.
A1.119089A
REFLECTED CEILING PLANS
WINNIPEG FPS FIRE STATION #13
NO.
0
DATE
25.06.2020
REVISION / ISSUANCE
-
1 DD.MM.YYYY -
2 DD.MM.YYYY -
3 DD.MM.YYYY -
4 DD.MM.YYYY -
Seal
Engineer
Project
Sheet Title
Project No.
Date
Sheet
25.06.2020
Architect
799 LILAC STREET
ISSUED FOR CONSTRUCTION
±7'-4"
±9'-0"
±7'-4"
±7'-4"
±9'-0"
±9'-0"
±9'-0"±9'-0"
±9'-0"
±9'-0"
±9'-0" ±9'-0"
±9'-0"
±9'-0"
±9'-0"
±9'-0"
±9'-0"
ROOMG-12
APPARATUS
VESTIBULEG-19
ROOMG-14
MECHANICAL RECEPTIONG-02
ROOMG-23
CONTROL
OFFICEG-05
LIEUTENANT'S
OFFICEG-06
CAPTAIN'S
LOUNGEG-07
KITCHENG-08
CORRIDORG-03
CORRIDORG-13
WASHROOMG-16
MEN'S
SHOWERG-15
ROOMG-11
STATIONARY
WASHROOMG-09
UNISEX
DORMITORYG-18
VESTIBULEG-01
ROOMG-22
STORAGE
HOSE TOWERG-20
ROOMG-21
DRYING
ROOMG-10
CLEANING
6 6
7
7
7
2
2
3 3
3333
4
13
1
1
1
1
10
1
1
1
5
1
ROOMG-04
PHONE
3315
10
11
10
1010
10 10
10
10
10 10
12 12 12
121212
10
10
10
10
10
12
1212
12
22
2
2
13
1415
15
MAIN FLOOR RCP - DEMOLITIONSCALE: 1/8" = 1'-0"
1A1.1
±7'-4"
±9'-0"
±7'-4"
±7'-4"
±9'-0"
±9'-0"
±9'-0"±9'-0"
±9'-0"
±9'-0"
±9'-0" ±9'-0"
±9'-0"
±9'-0"
±9'-0"
±9'-0"
±9'-0"
ROOMG-12
APPARATUS
VESTIBULEG-19
ROOMG-14
MECHANICAL RECEPTIONG-02
ROOMG-23
CONTROL
OFFICEG-05
LIEUTENANT'S
OFFICEG-06
CAPTAIN'S
LOUNGEG-07
KITCHENG-08
CORRIDORG-03
CORRIDORG-13
WASHROOMG-16
MEN'S
SHOWERG-15
ROOMG-11
STATIONARY
WASHROOMG-09
UNISEX
DORMITORYG-18
VESTIBULEG-01
ROOMG-22
STORAGE
HOSE TOWERG-20
ROOMG-21
DRYING
ROOMG-10
CLEANING
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1 1
1
3
4
5
5
55
5
5
3
3
3
3
3 3
5 5 5 5
5555
5
5
3
5
5
3
3
5 5 5
555
33
33
33
3 3
3
3
3
3
3
6
6
6
5
5
±7'-4"
MAIN FLOOR RCP - RENOVATIONSCALE: 1/8" = 1'-0"
2A1.1
9
8
1
1 7
10
12
10 10
12
1 1 1
1
6 ±7'-10"±7'-10"
±7'-10"
±7'-10"
DORMITORYM-01
RESCUEM-04
WATER
STAIRHALLM-03
W/CM-02
MEZZANINE RCP - DEMOLITIONSCALE: 1/8" = 1'-0"
3A1.1
INTERIOR RENOVATIONS
BID OPPORTUNITY 280-2020
DEMOLITION RCP NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
EXISTING LIGHTING FIXTURES TO REMAIN, TYP.
EXISTING PENDANT FIXTURE TO BE REPLACED W/ POT LIGHT - REFER TO ELECT.
PREPARE EXISTING JUNCTION BOX FOR NEW POT LIGHT FIXTURE. PATCH & MAKE GOOD CEILING & ADJACENT SURFACES. PAINT EXISTING CEILING. REFER TO ELECTRICAL.
REMOVE EXISTING LIGHTING IN PHONE ROOM. REFER TO ELECTRICAL. PATCH & MAKE GOOD ALL ADJACENT SURFACES.
EXISTING SPEAKER TO REMAIN. PROTECT DURING CONSTRUCTION.
EXIT SIGN TO REMAIN. PROTECT DURING CONSTRUCTION.
EXISTING CEILING GRILLES TO REMAIN, TYP. PROTECT DURING CONSTRUCTION.
EXISTING DUCT TO REMAIN. REPAIR DRYWALL AROUND DUCT PENETRATION THROUGH CEILING.
EXISTING CEILING HATCH TO REMAIN. REPAIR DRYWALL AROUND HATCH OPENING.
EXISTING SURFACE MOUNTED FIXTURE TO BE REPLACED - REFER TO ELECT.
EXISTING WALL MOUNTED FIXTURE TO BE REPLACED - REFER TO ELECT.
EXISTING POT LIGHT FIXTURE TO BE REPLACED. REFER TO ELECT.
REMOVE EXISTING POT LIGHT FIXTURE IN LIEUTENANT'S OFFICE. REFER TO ELECTRICAL. PATCH & MAKE GOOD ALL SURFACES.
REMOVE SURFACE MOUNTED ELECTRICAL. PATCH & REPAIR ALL ADJACENT SURFACES. REFER TO ELECT.
RENOVATION RCP NOTES
1.
2.
3.
4.
5.
6.
PATCH & PAINT EXISTING CEILING - REFER TO ROOM SCHEDULE
NEW STEEL STUD GWB BULKHEAD. HEIGHT TO MATCH CEILING HEIGHT IN ROOM G-02.
NEW SURFACE MOUNTED LIGHT FIXTURE - REFER TO ELECT.
NEW WALL MOUNTED LIGHT FIXTURE - REFER TO ELECT.
NEW POT LIGHT FIXTURE - REFER TO ELECT.
UNDERCABINET LIGHTING - REFER TO ELECT.
±7'-10"±7'-10"
±7'-10"
±7'-10"
DORMITORYM-01
RESCUEM-04
WATER
STAIRHALLM-03
W/CM-02
111 5
3
5
3 3
1
MEZZANINE RCP - RENOVATIONSCALE: 1/8" = 1'-0"
4A1.1
NEW TILE FLOORING & BASE - REFER TO SPECIFICATIONS
NEW RESILIENT SHEET FLOORING & RUBBER BASE - REFER TO SPECIFICATIONS
NEW RUBBER TILE FLOORING & RUBBER BASE - REFER TO SPEC
NEW RUBBER STAIR TREADS C/W CONTRASTING COLOUR STRIP& PAINTED METAL STRINGERS - REFER TO SPECS
EXISTING FLOORING TO REMAIN
REFLECTED CEILING PLAN LEGEND
EXISTING STIPPLE CEILING - PATCH AND PAINT.- REFER TO ROOM SCHEDULE FOR FINISH
NEW GWB CEILING - REFER TO ROOM SCHEDULE FOR FINISH
EXISTING CEILING TO REMAIN. PATCH & PAINT.- REFER TO ROOM SCHEDULE FOR FINISH
EXISTING CEILING TO REMAIN.
13.
14.
15.
REMOVE EXISTING POT LIGHT FIXTURE IN LIEUTENANT'S OFFICE. REFER TO ELECTRICAL. PATCH & MAKE GOOD ALL SURFACES.
REMOVE SURFACE MOUNTED ELECTRICAL. PATCH & REPAIR ALL ADJACENT SURFACES. REFER TO ELECT.
EXISTING SURFACE MOUNTED FIXTURE TO BE REPLACED & RELOCATED - REFER TO ELECT. PATCH & MAKE GOOD ALL SURFACES.
GENERAL NOTES:
THESE DRAWINGS SHALL NOT BE SCALED.
THE CONTRACTOR SHALL VISIT THE SITE AND SATISFY ONESELF ALL DIMENSIONS, DATUM, AN DETAILED INFORMATION SHOWN ARE CORRECT.
THE CONTRACTOR IS TO REVIEW AND COORDINATE ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS THROUGH FLOORS, WALLS, AND CEILINGS FOR DUCT, PIPE & ELECTRICAL RISERS AND ALL OPENINGS NOT SHOWN ON DRAWINGS.
ALL OPENINGS THROUGH FIRE ASSEMBLIES ARE TO BE FIRESTOPPED AND SEALED WITH ULC APPROVED FIRE STOPPING TO MAINTAIN THE INTEGRITY OF THE FIRE SEPARATION, AND PROVIDE A SMOKE-TIGHT BARRIER.
ALL PRODUCTS AND MATERIALS TO BE USED AND INSTALLED SHALL CONFORM WITH MANUFACTURER'S SPECIFICATIONS & APPLICABLE CODES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND MAKE GOOD ALL EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AND THE REMOVAL OF ALL ITEMS FORMING PART OF THE RENOVATION WORK.
WHERE NEW FLOORING AND BASE IS TO BE INSTALLED IN EXISTING AREAS (REFER TO FLOOR PLAN AND ROOM SCHEDULE) THE EXISTING FLOORING SURFACE AND BASE MUST BE REMOVED, UNLESS OTHERWISE NOTED. ALL FLOOR SURFACES SHALL BE PREPARED IN ACOORDANCE TO MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF NEW FLOOR.
WHERE PAINTING OF EXISTING WALLS & CEILINGS IS INDICATED ON THE ROOM SCHEDULE, THESE WALLS MUST BE CLEANED OF ANY EXISTING WALL COVERING, PATCHED & PREPARED TO ACCEPT NEW PAINT, UNLESS OTHERWISE NOTED.
ALL EXISTING FURNITURE, EQUIPMENT (INCLUDING GYM EQUIPMENT), AND WALL MOUNTED ITEMS/ ARTWORK/ MAPS/ EXIT PLANS ARE TO BE REMOVED AND REINSTALLED BY THE CITY OF WINNIPEG'S MOVERS (TO BE STORED IN THE APPARATUS ROOM OR A STORAGE CONTAINER AS REQ'D).
EMERGENCY LIGHTING TO BE REPLACED, REFER TO ELECTRICAL FOR SCOPE OF WORK.
ALL MISCELLANEOUS FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION.
ALL MECHANICAL WALL VENTS/GRILLES TO BE REMOVED & REINSTALLED FOR PAINTING.
ALL EXISTING DOORS ARE TO BE CUT DOWN OR ADJUSTED AS REQUIRED TO ACCOMMODATE NEW FLOORING THICKNESS. PATCH & MAKE GOOD ALL DOORS.
ALL FIRE EXTINGUISHERS TO BE REMOVED AND REINSTALLED FOR PAINTING.
WARNING:ASBESTOS MAY BE PRESENT BEHIND WALLS CEILING SPACE & FLOORS. IF ASBESTOS OR ANY HAZARDOUS MATERIAL IS FOUND STOP WORK IMMEDIATELY & CONTACT CITY OF WINNIPEG, CENTRAL CONTROLS PH: 204-986-2351.
4A1.2
±7'-4
" (S
ITE
CO
NFI
RM
)
TO U
/S O
F N
EW
BU
LKH
EA
D6"
±12'-1"
SITE CONFIRMEQ. EQ. EQ. EQ.
LOCKABLE DOORS, TYP. (4) HEAVY DUTY HINGES AT EACH FULL HEIGHT DOOR. REFER TO SPECS.
COORDINATE LOCATION OF VENT IN PLAM KICK WITH MECHANICAL
PAINT GWB BULKHEAD
6"
ADJUSTABLE S.S. SHELVING
CONTINUOUS SEALANT
ADJUSTABLE S.S. SHELVING
REMOVABLE CLIP ON S.S.KICKPLATE
S.S. ADJUSTABLE BULLETFEET
S.S. DRAWER
NEW MOISTURE RESISTANT GWB TO 7'-8" HIGH & BEHIND S.S. BACKSPLASH. REFER TO FLOOR PLANS FOR LOCATIONS.
S.S. BACKSPLASH COUNTERTOP & WRAPAROUND NOSING
2'-6"2'-0" AT COFFEE STATION
1'-0"
2'-8
"
2'-0
"
1 1/
2"1"
1 1/
2"
7'-8
"
3'-0
"
STAINLESS STEEL BACK PANEL
1"
STAINLESS STEEL BACK PANEL
STAINLESS STEEL KICK PLATE AT SIDES, TYP.
1 1/
2"
1'-0"
2'-6"
1'-6
"
7'-8
"
3'-0
"
1 1/
2"1
1/2"
3'-2
"
CO
OR
DIN
ATE
W/ F
AUC
ET
3"
ADJUSTABLE S.S. SHELVING
CONTINUOUS SEALANT
INTEGRATED S.S.WELDED SINK
18"X30"X10"REFER TO SPECS
NEW MOISTURE RESISTANT GWB TO 7'-8" HIGH & BEHIND S.S. BACKSPLASH. REFER TO FLOOR PLANS FOR LOCATIONS.
S.S. BACKSPLASH COUNTERTOP & WRAPAROUND NOSING 3"
9"1
1/2"
1 1/
2"6"
6"
STAINLESS STEEL BACK PANEL
1'-6"
STAINLESS STEEL BACK PANEL
COORDINATE S.S. BACKSPLASH DIMENSIONS WITH FAUCET. PROVIDE BLOCKING AS REQ'D TO MOUNT FAUCET.
1"
CONTINUOUS SEALANT
S.S. SKIRT TO COVER SINK
STAINLESS STEEL BACK PANEL
STAINLESS STEEL BACKSPLASH
STAINLESS STEEL BACK PANEL
ADJUSTABLE S.S. SHELVING
GREASE INTERCEPTOR, REFER TO MECH. COORDINATE HOLE IN BASE OF S.S. MILLWORK W/ MECH.
NEW MOISTURE RESISTANT GWB TO 7'-8" HIGH & BEHIND S.S. BACKSPLASH. REFER TO FLOOR PLANS FOR LOCATIONS.
ELECTRICRANGE
DISHWASHER(DW)
EQ. EQ.
1 1/2" TYP.
DRAWER
1A1.2
AS REQ'D FORGREASE INTERCEPTOR
RELOCATEDMICROWAVE
RELOCATEDFRIDGE
AS REQ'D FOR RANGE ±6'-11"
EQ.
RELOCATEDTOASTER
3A1.2
VENT HOODREFER TO SPECS
& MECH
RELOCATEDFRIDGE
DRAWER
EQ.
S.S. BACKSPLASH
±5'-9"±6'-11"±6'-10 1/2"
EQ. EQ.
DRAWER DRAWER
6"
3'-2
"
CO
OR
DIN
ATE
W/ F
AUC
ET
7'-8
"
6"
3'-0
"1'
-6" 1'-0
"
S.S. CONTINUOUS BEHIND VENT HOOD & DUCT
UNDERCOUNTER LIGHTING, TYP. REFER TO ELECT.
2A1.2
RELOCATEDKNIFEBLOCK
KNIFE MAGNET BAR AS SPEC'D
AS REQ'D FOR DISHWASHER
±6'-11" GREASE INTERCEPTOR, REFER TO MECH. COORDINATE HOLE IN BASE OF S.S. MILLWORK W/ MECH.
NEW FAUCET,REFER TO SPECS.
6'-8
"
EQ. EQ.
STAINLESS STEEL BEHIND KITCHEN CABINETS, TYP.
STAINLESS STEEL BEHIND KITCHEN CABINETS, TYP.
STAINLESS STEEL BEHIND KITCHEN CABINETS, TYP.
AS REQ'D FOR HOOD
PATCH & PAINT ALL GWB (EXPOSED GWB SHOWN HATCHED)
PROVIDE REMOVABLE CLIP AND S.S. KICKPLATE ON FRONT & SIDES, TYP.
S.S. BACKSPLASH CONTINUOUS BEHIND RANGE
INTEGRATED S.S. SINK 18"X30"X10", REFER TO SPEC
UNDERCOUNTERLIGHTING, TYP.
REFER TO ELECT.
COORDINATE W/ ELECT FOR RECEPTACLE OPENING IN S.S. BACKSPLASH, TYP.
NEW MOISTURE RESISTANT GWB
NEW MOISTURE RESISTANT GWB TO 7'-8" HIGH & BEHIND S.S. BACKSPLASH.
A1.219089A
INTERIOR ELEVATIONS &
WINNIPEG FPS FIRE STATION #13
NO.
0
DATE
25.06.2020
REVISION / ISSUANCE
-
1 DD.MM.YYYY -
2 DD.MM.YYYY -
3 DD.MM.YYYY -
4 DD.MM.YYYY -
Seal
Engineer
Project
Sheet Title
Project No.
Date
Sheet
25.06.2020
Architect
799 LILAC STREET
ISSUED FOR CONSTRUCTION
INTERIOR ELEVATION - G-08 LIVING AREASCALE: 1/2" = 1'-0"
8A1.2
KITCHEN CABINETS - TYP. SECTION DETAILSCALE: 3/4" = 1'-0"
1A1.2
KITCHEN CABINETS - SECTION DETAILSCALE: 3/4" = 1'-0"
2A1.2
INTERIOR RENOVATIONS
BID OPPORTUNITY 280-2020
PULLS AS SPECIFIEDLOCKS AS SPECIFIED(4) HEAVY DUTY HINGES AT EACH FULL HEIGHT DOOR
6" BASEBOARD (PLAM-2)
CENTER SHELF FIXED ADJUSTABLE SHELVES RECESSED METAL STANDARDS
3/4" BIRCH SHELVES C/W 1" EDGE DETAIL WITH CLEAR COAT FINISH
DOOR FRONTS TO BE PLAM-2
±7'-4
" (S
ITE
CO
NFI
RM
)
TO U
/S O
F N
EW
BU
LKH
EA
D
6"
NEW GWB BULKHEAD. REFER TO REFLECTED CEILING PLANS.
COORDINATE LOCATION OF VENT IN PLAM KICK WITH MECHANICAL
EQ. EQ.
NEW POT LIGHT FIXTURE, REFER TO ELECT
2'-6"
PLAM-2 FILLER PANEL AT TOP OF CABINET
3/4" MELAMINE INTERIOR
1 1/
2"
STORAGE CABINETS - SECTION DETAILSCALE: 3/4" = 1'-0"
4A1.2
INTERIOR ELEVATION - STORAGE CABINETSSCALE: 1/2" = 1'-0"
5A1.2
INTERIOR ELEVATION - G-08 COFFEE STATIONSCALE: 1/2" = 1'-0"
7A1.2
1 1/
2"
3 1/2"
8"
3/4"
DRAWER FRONT FULL LENGTH SCALLOPED HANDLE (TYP).
FULL EXTENSION S.S. DRAWER SLIDE 20" LONG
EQ. EQ.
RELOCATEDPOPCORNMACHINE
RELOCATEDTOWEL
DISPENSER
9'-0"
RELOCATEDCOFFEEMAKER
RELOCATEDCOFFEEGRINDER
EQ. EQ.
9'-0"
1 1/2"TYP.
1A1.2
S.S. BACKSPLASH
DRAWER DRAWER DRAWER DRAWER
2'-0
"
7'-8
"
3'-0
"2'
-8"
1'-6
"
6"
UNDERCOUNTER LIGHTING, TYP. REFER TO ELECT.
RELOCATED TABLE
EXISTING SPEAKER TO BE DEMOLISHED, REFER TO ELECT.
RELOCATEDBLENDER
PATCH & PAINT ALL GWB(EXPOSED GWB
SHOWN HATCHED)
S.S. BEHIND KITCHEN CABINETS, TYP.
S.S. BEHIND KITCHEN CABINETS, TYP.
PROVIDE REMOVABLE CLIP AND S.S. KICKPLATE ON FRONT & SIDES, TYP.
COORDINATE W/ ELECT FOR RECEPTACLE OPENING IN S.S. BACKSPLASH, TYP.
KITCHEN CABINETS - SECTION DETAILSCALE: 3/4" = 1'-0"
3A1.2
S.S. DRAWER
1'-0"
2'-8
"
MICROWAVE
1'-0
"
2'-0
" 7'-8
"
3'-0
"
2'-6"
1'-8"
STAINLESS STEEL SHELF
CONTINUOUS SEALANT
ADJUSTABLE S.S.SHELVING
REMOVABLE CLIPON S.S.
KICKPLATES.S. ADJUSTABLE
BULLET FEET
NEW MOISTURE RESISTANT GWB TO 7'-8" HIGH & BEHIND S.S. BACKSPLASH. REFER TO FLOOR PLANS FOR LOCATIONS.
STAINLESS STEEL BACK PANEL
1 1/
2"
NEW TILE BASEBOARD - REFER TO SPECS
6"
PAINT, TYP.
EQ. EQ.
4'-6"
2'-4
1/2
"
4'-8
"
1 1/2" 1 1/2"
1 1/
2"
CL
CL
PULLS AS SPEC'D, TYP.
CONTRACTOR TO INSTALL TV MOUNT & TV AT EXISTING WALL - PROVIDE BLOCKING AS REQ'D.
55" TV - N.I.C.
EXISTING RECEPTACLE
ADJUSTABLE SHELF
REPLACE EXISTING WIREMOLD.EXTEND DATA TO MILLWORK/TV.
PROVIDE NEW WIREMOLD ASREQUIRED TO SUIT A/V REQUIREMENTS.
±5'-3"
TO SUIT EXISTING RECEPTACLE
NEW BLINDS - REFER TO SPECS.
GROMMET AT SIDE OF CABINET FOR DATAWIRING & AT COUNTERTOP/OPEN SHELF
(CENTERED ON DOORS) - GROMMETS ASSPEC'D. REFER TO DETAILS.
GROMMET LOCATED IN OPEN SHELF (CENTERED ON DOORS) & GABLE - GROMMETS AS SPEC'D. REFER TO DETAILS.
9A1.3
NOTE: CONFIRM LOCATION OF TV/TV CABINET WITH ARCHITECT PRIOR TO INSTALLATION OFELECTRICAL/ A/V EQUIPMENT & WIREMOLD
NEW BACKPAINTEDGLASS MAGNETICMARKERBOARD
NEW TILE BASEBOARD - REFER TO SPECS CUT DOWN WOOD DOOR AS REQ'D
FOR NEW FLOORING, TYP. PROVIDE NEW KICK PLATE AT PUSH SIDE OF DOOR, TYP. REFER TO SPECS.
12'-0"
4'-0
"
6"PAINT EXISTING METAL
DOOR FRAME. EXISTINGWOOD DOOR TO REMAIN.
PAINT, TYP.
PH
REMOVE & REINSTALLEXISTING CLOCK, TYP. CL
WHITEBOARD FRAME - REFER TO DETAILS
1 1/2"
DEMOLISH EXISTING PHONE - REFER TO ELECT.
12A1.3
NEW CORNER GUARD - REFER TO SPECS
INTERIOR ELEVATION - G-08 KITCHENSCALE: 1/2" = 1'-0"
6A1.2
INTERIOR ELEVATION - G-08 NEW MARKERBOARDSCALE: 1/2" = 1'-0"
9A1.2
MILLWORK DETAILS
GENERAL NOTES:
THESE DRAWINGS SHALL NOT BE SCALED.
THE CONTRACTOR SHALL VISIT THE SITE AND SATISFY ONESELF ALL DIMENSIONS, DATUM, AN DETAILED INFORMATION SHOWN ARE CORRECT.
THE CONTRACTOR IS TO REVIEW AND COORDINATE ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS THROUGH FLOORS, WALLS, AND CEILINGS FOR DUCT, PIPE & ELECTRICAL RISERS AND ALL OPENINGS NOT SHOWN ON DRAWINGS.
ALL OPENINGS THROUGH FIRE ASSEMBLIES ARE TO BE FIRESTOPPED AND SEALED WITH ULC APPROVED FIRE STOPPING TO MAINTAIN THE INTEGRITY OF THE FIRE SEPARATION, AND PROVIDE A SMOKE-TIGHT BARRIER.
ALL PRODUCTS AND MATERIALS TO BE USED AND INSTALLED SHALL CONFORM WITH MANUFACTURER'S SPECIFICATIONS & APPLICABLE CODES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND MAKE GOOD ALL EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AND THE REMOVAL OF ALL ITEMS FORMING PART OF THE RENOVATION WORK.
WHERE NEW FLOORING AND BASE IS TO BE INSTALLED IN EXISTING AREAS (REFER TO FLOOR PLAN AND ROOM SCHEDULE) THE EXISTING FLOORING SURFACE AND BASE MUST BE REMOVED, UNLESS OTHERWISE NOTED. ALL FLOOR SURFACES SHALL BE PREPARED IN ACOORDANCE TO MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF NEW FLOOR.
WHERE PAINTING OF EXISTING WALLS & CEILINGS IS INDICATED ON THE ROOM SCHEDULE, THESE WALLS MUST BE CLEANED OF ANY EXISTING WALL COVERING, PATCHED & PREPARED TO ACCEPT NEW PAINT, UNLESS OTHERWISE NOTED.
ALL EXISTING FURNITURE, EQUIPMENT (INCLUDING GYM EQUIPMENT), AND WALL MOUNTED ITEMS/ ARTWORK/ MAPS/ EXIT PLANS ARE TO BE REMOVED AND REINSTALLED BY THE CITY OF WINNIPEG'S MOVERS (TO BE STORED IN THE APPARATUS ROOM OR A STORAGE CONTAINER AS REQ'D).
EMERGENCY LIGHTING TO BE REPLACED, REFER TO ELECTRICAL FOR SCOPE OF WORK.
ALL MISCELLANEOUS FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION.
ALL MECHANICAL WALL VENTS/GRILLES TO BE REMOVED & REINSTALLED FOR PAINTING.
ALL EXISTING DOORS ARE TO BE CUT DOWN OR ADJUSTED AS REQUIRED TO ACCOMMODATE NEW FLOORING THICKNESS. PATCH & MAKE GOOD ALL DOORS.
ALL FIRE EXTINGUISHERS TO BE REMOVED AND REINSTALLED FOR PAINTING.
WARNING:ASBESTOS MAY BE PRESENT BEHIND WALLS CEILING SPACE & FLOORS. IF ASBESTOS OR ANY HAZARDOUS MATERIAL IS FOUND STOP WORK IMMEDIATELY & CONTACT CITY OF WINNIPEG, CENTRAL CONTROLS PH: 204-986-2351.
1
1
1
2
2
3
3
1
1
1
1
1
1111
1
1
1
8
5
5
5
5
4
155
PT-4
PT-4
PT-4
PT-4
PT-
4
PT-5
PT-
5
PT-4
5
4
3VESTIBULE
G-19
ROOMG-14
MECHANICAL
RECEPTIONG-02
ROOMG-23
CONTROL
OFFICEG-05
LIEUTENANT'S
OFFICEG-06
CAPTAIN'S
LOUNGEG-07
KITCHENG-08
CORRIDORG-03
CORRIDORG-13
WASHROOMG-16
MEN'S
SHOWERG-15
ROOMG-11
STATIONARY
WASHROOMG-09
UNISEX
ROOMG-17
LOCKER
DORMITORYG-18
VESTIBULEG-01
HOSE TOWERG-20
UP
ROOMG-10
CLEANING
MAIN FLOOR FINISH PLANSCALE: 1/8" = 1'-0"
1A1.3
A1.319089A
FLOOR FINISH PLANS, INTERIOR
WINNIPEG FPS FIRE STATION #13
NO.
0
DATE
25.06.2020
REVISION / ISSUANCE
-
1 DD.MM.YYYY -
2 DD.MM.YYYY -
3 DD.MM.YYYY -
4 DD.MM.YYYY -
Seal
Engineer
Project
Sheet Title
Project No.
Date
Sheet
25.06.2020
Architect
799 LILAC STREET
ISSUED FOR CONSTRUCTION
WATCH DESK ELEVATIONSCALE: 1/2" = 1'-0"
3A1.3
6 6
7
SHOWER
HOSE TOWERG-20
DN
W5DORMITORY
M-01
RESCUEM-04
WATER
STAIRHALLM-03
W/CM-02
MEZZANINE FLOOR FINISH PLANSCALE: 1/8" = 1'-0"
2A1.3
INTERIOR RENOVATIONS
BID OPPORTUNITY 280-2020
NEW DOOR
5/8" TYPE 'X' GYPSUM BOARD, PAINT FINISH3 5/8" STEEL STUDS @ 16" O.C.3 1/2" MINERAL FIBER INSULATION5/8" TYPE 'X' GYPSUM BOARD, PAINT FINISH
PARTITIONS TO RUN TO EXISTING CEILING HEIGHT OF ±9'-0"
FLOOR FINISH LEGEND
NEW TILE FLOORING & BASE - REFER TO SPECIFICATIONS
NEW RESILIENT SHEET FLOORING & RUBBER BASE - REFER TO SPECIFICATIONS
NEW RUBBER TILE FLOORING & RUBBER BASE - REFER TO SPEC
NEW RUBBER STAIR TREADS C/W CONTRASTING COLOUR STRIP& PAINTED METAL STRINGERS - REFER TO SPECS
EXISTING FLOORING TO REMAIN
CONTRACTOR TO CO-ORDINATE OPENING IN MILLWORK FOR EXISTING AND NEW ELECTRICAL RECEPTACLES AND CONDUITS ETC, TYP.
EQ.
55" TV - N.I.C.
CPU
RADIODISPATCH
UNITPHONE
OPEN ADJUSTABLE
SHELVINGCPU
EQ 10" EQ ±5'-3 1/2" ±7'-2 1/2"
EQ EQ EQEQ EQ EQ
NEW BACKPAINTEDGLASS MAGNETICMARKERBOARD
SUPPLY & INSTALLADJUSTABLE
MONITOR ARM W/EXISTING MONITOR,
REFER TO SPEC.
TRASH
EXISTING ELECTRICAL
NEW CORNERGUARD - REFER
TO SPECS
NEW TILE BASEBOARD - REFER TO SPECS
6"
NEW TILE BASEBOARD -REFER TO SPECS
EQ. EQ.
±3'-7"
±3'-7
1/2
"
TO M
ATC
H W
IND
OW
HE
IGH
T
EQ. EQ.
PAINT EXISTING METALDOOR & FRAME, TYP.
PROVIDE NEW KICK PLATEAT PUSH SIDE OF DOOR,
TYP. REFER TO SPECS.
EXISTINGELECTRICAL
PAINT EXISTING WINDOW FRAME
PAINT EXISTING WINDOW FRAME
PAINT, TYP.
EXISTING ELECTRICAL
PHONE
RADIO UNIT
DEFIBBATTERYCHARGER
DEFIBBATTERYCHARGER
RADIO CHARGERS
CL
7A1.3
5A1.3
6A1.3
8A1.3
10"2'-4"
NEW BLINDS - REFER TO SPECS
TV AND MOUNT BY CONTRACTADMINISTRATOR. CONTRACTOR TO
INSTALL TV MOUNT AND TV. PROVIDEBLOCKING AS REQUIRED.
SUPPLY & INSTALL ADJUSTABLE MONITOR ARM W/ EXISTING MONITOR, REFER TO SPEC.
EQ.EQ.
EXISTING FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION, TYP.
LOCKABLE DOORSLOCKABLE DRAWERS
P-LAM WALL CLEAT BELOW (PLAM-1)
P-LAM WALL CLEAT BELOW (PLAM-1)
GROMMET INVERTICAL GABLE
GROMMET IN VERTICAL GABLE
GROMMET IN COUNTER.PROVIDE CABLE RACEWAYBELOW COUNTER TO CPU
CABINET
GROMMET CENTERED IN COUNTER
RADIOCHARGERS
CL
GROMMET IN COUNTER. PROVIDE CABLE RACEWAY BELOW COUNTER TO CPU CABINET
FLOOR FINISH PLAN NOTES
1.
2.
3.
4.
5.
6.
7.
8.
REMOVE & REINSTALL ALL FLOOR GRILLES FOR INSTALLATION OF NEW FLOORING, TYP.
EXISTING RECESSED FLOOR MAT
REMOVE & REINSTALL EXISTING FLOOR RECEPTACLE AS REQ'D FOR NEW FLOORING INSTALLATION. REFER TO ELECT.
PROVIDE FLOORING TRANSITION (TR-2) FROM TILE TO RUBBER TILE FLOORING. REFER TO SPECS.
PROVIDE FLOORING TRANSITION (TR-3) FROM TILE TO EXISTING FLOORING. REFER TO SPECS.
PROVIDE FLOORING TRANSITION (TR-4) FROM RESILIENT SHEET FLOORING TO EXISTING FLOORING. REFER TO SPECS.
PROVIDE FLOORING TRANSITION FROM RESILIENT SHEET FLOORING TO RUBBER TREAD. REFER TO SPECS.
REMOVE EXISTING FLOOR GRILLE AND PROVIDE NEW DUCT EXTENSION TO GRILLE WITHIN STORAGE CABINETS. REFER TO MECH, INTERIOR ELEVATIONS AND DETAILS.
ELEVATIONS & MILLWORK DETAILS
FINISH PLAN GENERAL NOTES:
1. FINISH PLAN TO BE READ IN CONJUNCTION WITH THE PROJECT REQUIREMENTS.
2. REFER TO ROOM FINISH & SPEC ON A1.4 FOR ALL WALL AND FLOOR FINISHES.
3. REFER TO REFLECTED CEILING PLANS FOR FINISHES OF ALL CEILINGS, BULKHEADS AND SOFFITS.
4. REFER TO SPEC FOR FINISH CODES.
5. ALL EXISTING HOLLOW METAL DOORS AND FRAMES TO BE PAINTED UNLESS OTHERWISE NOTED.
6. ALL EXISTING MAPLE DOORS TO REMAIN AS IS.
7. PAINT EXPOSED SURFACES OF PAINTABLE GRILLES AND DIFFUSERS TO MATCH THE WALL OR CEILING COLOUR.
8. PAINT ALL PARTITIONS AND PERIMETER WALLS TO U/S OF STRUCTURE WHERE THEY ARE NOT INTERSECTED BY SUSPENDED CEILINGS.
9. PAINT SECURITY AND COMMUNICATIONS BACKBOARDS TO MATCH ADJACENT PARTITIONS.
10. ALL FLOORING CHANGES SHALL OCCUR UNDER CENTRELINE OF DOORS UNLESS OTHERWISE NOTED.
11. PROVIDE FLOOR TRANSITION STRIPS OR METAL DIVIDER STRIPS AS INDICATED ON PLAN AT MATERIAL CHANGES. FEATHER CONCRETE FLOORS WITH CONCRETE TOPPING AS REQUIRED TO BRING ADJACENT MATERIALS FLUSH. LAY OUT ACCURATELY AND MARK CLEARLY FOR CONSULTANT'S REVIEW, THE LOCATIONS OF ALL FLOOR PATTERNS AND MATERIAL CHANGES. ADJUST LOCATIONS AS REQUIRED BASED ON REVIEW. OBTAIN CONSULTANT'S APPROVAL OF LOCATIONS PRIOR INSTALLATION.
12. FLOOR FINISHES SHALL BE INSTALLED UNDER MILLWORK CABINETS PRIOR TO INSTALLATION OF MILLWORK.
13. PAINT ALL EXPOSED DUCTS, CONDUITS, JUNCTION BOXES, PIPING AND ANY MECHANICAL, ELECTRICAL OR ARCHITECTURAL FITTINGS.
14. PAINT ALL NEW AND EXISTING WIREMOLDS TO MATCH ADJACENT PARTITIONS.
(PLAM-1) BASE CABINET C/W (PLAM-1) DRAWERS W/ FULL EXSTENSION SLIDES & SOFT CLOSING MECHANISM. DRAWER INTERIOR TO HAVE MELAMINE ON ALL INSIDE FACES. LOCKS & PULLS AS SPEC'D.
6"
1'-8 1/2"
2'-6
"
2'-0"
2'-0
"
8 3/
4"5"
8 3/
4"
ADJUSTABLE SHELF
ADJUSTABLE SHELF
DRAWER
DRAWER
DRAWER
SOLID SURFACE COUNTERTOP (SSC-1) W/ MITERED LEADING EDGE.
SOLID SURFACE (SSC-1) RETURN BEYOND
PLASTIC LAMINATE (PLAM-1) KICK
3 1/2"
6"
2'-2 1/2"
3'-6
"
2'-6"
3'-0
"
SOLID SURFACE COUNTERTOP (SSC-1) W/ MITERED LEADING EDGE. SOLID SURFACE (SSC-1) RETURN BEYOND
PLASTIC LAMINATE BASE C/W 6" HIGH KICK W/ MITERED EDGE (PLAM-1), AND PLASTIC LAMINATE (PLAM-1) ADJUSTABLE SHELVES.
PLASTIC LAMINATE OPEN INTERIOR (PLAM-1)
3 1/2"
(3) GROMMETS AS SPEC'D IN BOTH GABLES
(1) GROMMET AS SPEC'D IN EACH ADJUSTABLE SHELF
CONTRACTOR TO CO-ORDINATEOPENING IN MILLWORK FOR
EXISTING ELECTRICALRECEPTACLES AND CONDUITS ETC,
TYP.
GROMMET AS SPEC'D - CENTEREDIN COUNTERTOP
6"
1'-8 1/2"
2'-6
"
2'-0"
2'-0
"
6"
1'-8 1/2"
ADJUSTABLE SHELF
ADJUSTABLE SHELF
2'-6
"
2'-0"
2'-0
"
CPU
PLASTIC LAMINATE (PLAM-1) BASE CABINET W/ 6" HIGH KICK (PLAM-1). CABINET INTERIOR TO HAVE MELAMINE ON ALL INSIDE FACES. PROVIDE (2) ADJUSTABLE MELAMINE SHELVES PER CABINET. CABINET DOORS, PLASTIC LAMINATE (PLAM-1). LOCKS & PULLS AS SPEC'D.
SOLID SURFACE COUNTERTOP (SSC-1) W/ MITERED LEADING EDGE.
SOLID SURFACE (SSC-1) RETURN BEYOND
SOLID SURFACE COUNTERTOP (SSC-1) W/ MITERED LEADING EDGE. SOLID SURFACE (SSC-1) RETURN BEYOND
PLASTIC LAMINATE (PLAM-1) BASE W/ KICK & MITERED EDGE
PLASTIC LAMINATE GABLE BEYOND (PLAM-1)
PLASTIC LAMINATE OPEN INTERIOR (PLAM-1)
3 1/2"SOLID SURFACE (SSC-1) RETURN BEYOND
3 1/2"
PLASTIC LAMINATE (PLAM-1) KICK
WATCH DESK SECTION DETAILSCALE: 3/4" = 1'-0"
5A1.3
WATCH DESK SECTION DETAILSCALE: 3/4" = 1'-0"
6A1.3
WATCH DESK SECTION DETAILSCALE: 3/4" = 1'-0"
7A1.3
WATCH DESK SECTION DETAILSCALE: 3/4" = 1'-0"
8A1.3
ADJUSTABLE SHELF
6"
1'-8 1/2"
2'-6
"
1'-4
1/2
"
SOLID SURFACE COUNTERTOP (SSC-1) W/ MITERED LEADING EDGE.
SOLID SURFACE (SSC-1) RETURN BEYOND
PLASTIC LAMINATE (PLAM-1) BASE C/W 6" HIGH KICK AND (1) PLASTIC LAMINATE (PLAM-1) ADJUSTABLE SHELF. INTERIOR TO HAVE MELAMINE ON ALL INSIDE FACES.
PLASTIC LAMINATE OPEN INTERIOR (PLAM-1)
3 1/2"
6"1
1/2"2'-0"
CONTRACTOR TOCO-ORDINATE OPENING
IN MILLWORK FOREXISTING ELECTRICAL
RECEPTACLE ANDCONDUITS ETC, TYP.
GROMMET AS SPEC'DIN COUNTERTOP
GROMMET ASSPEC'D IN GABLE
GROMMET AS SPEC'D INOPEN SHELF
TV CABINET SECTION DETAILSCALE: 3/4" = 1'-0"
9A1.3
3'-0
" A.F
.F.
PLASTIC LAMINATE SHELF (PLAM-1) W/ MITERED LEADING EDGE.
PLASTIC LAMINATE SHELF CLEATS (PLAM-1) ANCHORED TO WALL
1 1/
2"
CORNER SHELF ELEVATIONSCALE: 3/4" = 1'-0"
10A1.3
CORNER SHELF PLAN DETAILSCALE: 3/4" = 1'-0"
11A1.3
±1'-3
1/2
"
SIT
E C
ON
FIR
M
±2'-0"
SITE CONFIRM
±3'-2
"
SIT
E C
ON
FIR
M
±2'-9"SITE CONFIRM
10
A1.3
PLASTIC LAMINATE SHELF (PLAM-1) W/ MITERED LEADING EDGE.
PLASTIC LAMINATE SHELF CLEATS BELOW (PLAM-1) SHOWN DASHED
SOLID MAPLE WOOD SURROUND
1/4" THICK MAGNETIC BACK PAINTED GLASS WHITEBOARD (MWB1) INSTALLED W 5/8" 'Z-CLIP'. ENSURE 'Z'-CLIPS' ARE SECURED TO SOLID FRAMING THROUGH EXISTING WALL
SOLID MAPLE WOOD SURROUND C/W RECESSED MARKER TRAY
2'-6
"4'
-0"
NEW TILE BASEBOARD - REFER TO SPECS
PROVIDE (2) LAYERS OF 1/2" PLYWOOD BACKING SECURED TO EXISTING STUDS. SECURE SOLID MAPLE SURROUND TO PLYWOOD BACKING.
WHITEBOARD DETAILSCALE: 3/4" = 1'-0"
12A1.3
5'-0"
1 1/
2"2'
-8"
3'-6"
2'-8
"
CUSTOM QUARTZ (QZ-1) TOP
DOUBLE COLUMN 'T' BASE BY SPEC FURNITURE, REFER TO SPEC.
DOUBLE COLUMN 'T' BASE BY SPEC FURNITURE, REFER TO SPEC.
CUSTOM QUARTZ (QZ-1) TOP
DINING TABLESCALE: 1/2" = 1'-0"
4A1.3
CPU CPUOPEN
ADJUSTABLESHELVING
2'-0
"
DR
AW
ER
INSTALL ADJUSTABLE MONITOR ARM W/ EXISTING MONITOR, REFER TO SPECS.
ADJUSTABLESHELVING
ADJUSTABLESHELVING
ADJUSTABLESHELVING
2'-6
"
CONTRACTOR TO CO-ORDINATE OPENING IN MILLWORK FOR EXISTING AND NEW ELECTRICAL RECEPTACLES AND CONDUITS ETC, TYP.
INSTALL ADJUSTABLE MONITOR ARM W/ EXISTING MONITOR, REFER TO SPECS.
PROVIDE (3) GROMMETS AT EACH GABLE & (1) GROMMET AT THE BACK OF EACH ADJUSTABLE SHELF - REFER TO SECTION DETAILS
GROMMET INCOUNTER (ABOVE)
2'-0
"
EXISTING FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED
GROMMET INVERTICAL GABLE
GROMMET IN VERTICAL GABLE
DR
AW
ER
LOCKABLE DOORS
LOCKABLE DRAWERS
NEW CORNER GUARDSOLID SURFACE RETURN (SSC-1)
W/ MITERED EDGES.
1 1/2"1 1/2"1 1/2"
SOLID SURFACE RETURN (SSC-1)W/ MITERED EDGES.
SOLID SURFACE RETURN (SSC-1) W/ MITERED EDGES.
3 1/2"
1/2"
1 1/
2"
1/2"
WATCH DESK PLAN DETAILSCALE: 1/2" = 1'-0"
13A1.3
GENERAL NOTES:
THESE DRAWINGS SHALL NOT BE SCALED.
THE CONTRACTOR SHALL VISIT THE SITE AND SATISFY ONESELF ALL DIMENSIONS, DATUM, AN DETAILED INFORMATION SHOWN ARE CORRECT.
THE CONTRACTOR IS TO REVIEW AND COORDINATE ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS THROUGH FLOORS, WALLS, AND CEILINGS FOR DUCT, PIPE & ELECTRICAL RISERS AND ALL OPENINGS NOT SHOWN ON DRAWINGS.
ALL OPENINGS THROUGH FIRE ASSEMBLIES ARE TO BE FIRESTOPPED AND SEALED WITH ULC APPROVED FIRE STOPPING TO MAINTAIN THE INTEGRITY OF THE FIRE SEPARATION, AND PROVIDE A SMOKE-TIGHT BARRIER.
ALL PRODUCTS AND MATERIALS TO BE USED AND INSTALLED SHALL CONFORM WITH MANUFACTURER'S SPECIFICATIONS & APPLICABLE CODES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND MAKE GOOD ALL EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AND THE REMOVAL OF ALL ITEMS FORMING PART OF THE RENOVATION WORK.
WHERE NEW FLOORING AND BASE IS TO BE INSTALLED IN EXISTING AREAS (REFER TO FLOOR PLAN AND ROOM SCHEDULE) THE EXISTING FLOORING SURFACE AND BASE MUST BE REMOVED, UNLESS OTHERWISE NOTED. ALL FLOOR SURFACES SHALL BE PREPARED IN ACOORDANCE TO MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF NEW FLOOR.
WHERE PAINTING OF EXISTING WALLS & CEILINGS IS INDICATED ON THE ROOM SCHEDULE, THESE WALLS MUST BE CLEANED OF ANY EXISTING WALL COVERING, PATCHED & PREPARED TO ACCEPT NEW PAINT, UNLESS OTHERWISE NOTED.
ALL EXISTING FURNITURE, EQUIPMENT (INCLUDING GYM EQUIPMENT), AND WALL MOUNTED ITEMS/ ARTWORK/ MAPS/ EXIT PLANS ARE TO BE REMOVED AND REINSTALLED BY THE CITY OF WINNIPEG'S MOVERS (TO BE STORED IN THE APPARATUS ROOM OR A STORAGE CONTAINER AS REQ'D).
EMERGENCY LIGHTING TO BE REPLACED, REFER TO ELECTRICAL FOR SCOPE OF WORK.
ALL MISCELLANEOUS FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION.
ALL MECHANICAL WALL VENTS/GRILLES TO BE REMOVED & REINSTALLED FOR PAINTING.
ALL EXISTING DOORS ARE TO BE CUT DOWN OR ADJUSTED AS REQUIRED TO ACCOMMODATE NEW FLOORING THICKNESS. PATCH & MAKE GOOD ALL DOORS.
ALL FIRE EXTINGUISHERS TO BE REMOVED AND REINSTALLED FOR PAINTING.
WARNING:ASBESTOS MAY BE PRESENT BEHIND WALLS CEILING SPACE & FLOORS. IF ASBESTOS OR ANY HAZARDOUS MATERIAL IS FOUND STOP WORK IMMEDIATELY & CONTACT CITY OF WINNIPEG, CENTRAL CONTROLS PH: 204-986-2351.
A1.419089A
SCHEDULES & SPECS
WINNIPEG FPS FIRE STATION #13
NO.
0
DATE
25.06.2020
REVISION / ISSUANCE
-
1 DD.MM.YYYY -
2 DD.MM.YYYY -
3 DD.MM.YYYY -
4 DD.MM.YYYY -
Seal
Engineer
Project
Sheet Title
Project No.
Date
Sheet
25.06.2020
Architect
799 LILAC STREET
ISSUED FOR CONSTRUCTION
ROOM FINISH SCHEDULES
ROOM NO. ROOM NAME FLOOR CEILING BASEBOARD NORTHWALL BLINDS
EX
GENERAL NOTES: PATCH & REPAIR ALL EXISTING DAMAGE TO GWB WALLS REFER TO FLOOR FINISH PLANS, SPECIFICATIONS & REFLECTED CEILING PLANS
NOTES: 1. ALL WALLS TO BE PAINTED PT-1 UNLESS OTHERWISE NOTED. 2. ALL CEILINGS AND GB BULKHEADS TO BE PAINTED PT-2 UNLESS OTHERWISE NOTED. 3. ALL DOORS AND FRAMES TO BE PAINTED PT-3 UNLESS OTHERWISE NOTED. WINDOW FRAMES (WHERE PAINTING IS NOTED) TO BE PAINTED PT-3.4. PROVIDE TR-1/TR-2 WHERE ALL QT-1 FLOOR AND BASE IS SPECIFICIED. REFER TO FLOORING ACCESSORIES SPECIFICATION.5. PAINT EXISTING STEEL STAIR STRINGERS AND RAILING PT-3
ABBREVIATIONS:PT PAINTEPT EPOXY PAINTEX EXISTINGQT PORCELAIN QUARRY TILERSF RESILIENT SHEET FLOORINGRF RUBBER TILE FLOORINGRCB RUBBER COVE BASERST RUBBER STAIR TREADRS ROLLER SHADES
PT-1: (WALL COLOUR):MANUFACTURER: BENJAMIN MOORE PAINTSCOLOR: OC 17 WHITE DOVEFINISH: PEARL FINISH FOR DRYWALL; SEMI GLOSS FINISH FOR CONCRETE BLOCK WALLSSUGGESTED LOCATION: MAIN WALL PAINT
PT-2: (CEILINGS):MANUFACTURER: BENJAMIN MOORE PAINTSCOLOR: OC 17 WHITE DOVEFINISH: SATIN FINISH
PT-3 (DOORS & FRAMES): MANUFACTURER: DULUX PAINTSCOLOR: BLACK MAGIC DLX1001-7FINISH: SEMI GLOSS FINISH
PT-4: (ACCENT WALL COLOUR):MANUFACTURER: SHERWIN WILLIAMS PAINTCOLOR: SW 7641 COLONNADE GRAYFINISH: PEARL FINISH FOR DRYWALL; SEMIGLOSS FINISH FOR CONCRETE BLOCK WALLS
PT-5: (ACCENT WALL COLOUR):MANUFACTURER: DULUX PAINTSCOLOR: DLX1162-7 DRAGONFLY (CITY OF WINNIPEG BLUE)FINISH: PEARL FINISH FOR DRYWALL; SEMIGLOSS FINISH FOR CONCRETE BLOCK WALLS
EPT-1: (EPOXY PAINT)MANUFACTURER: STONHARD STONEGLAZE VSRCOLOR: TO MATCH BENJAMIN MOORE PAINTS- OC 17 WHITE DOVEFINISH: EPOXY
VESTIBULERECEPTIONG-02
G-01
CORRIDORG-03
LIEUTENANT'S OFFICECAPTAIN'S OFFICE
G-05
LOUNGE
G-06
G-07
G-08
G-09
G-10
STATIONARY ROOM
G-11
APPARATUS ROOM
G-12
CORRIDORG-13
MECHANICAL ROOM
G-14
SHOWERG-15
MEN'S WASHROOM
G-16
LOCKER ROOMG-17
DORM/GYMG-18
VESTIBULEG-19HOSE TOWERG-20
DRYING ROOMG-21
STORAGE ROOMG-22
KITCHEN
UNISEX WASHROOMCLEANING ROOM
DORMITORYM-01WASHROOMM-02STAIRHALLM-03
PT-1PT-1PT-1PT-4
SOUTHWALL
EASTWALL
WESTWALL
WATER RESCUEM-04
G-23 CONTROL ROOM
PT-1PT-1PT-4PT-1PT-1PT-1PT-1PT-4PT-1PT-1PT-1PT-1
PT-1PT-1PT-4PT-1
PT-1PT-1PT-1PT-4
PT-1PT-4PT-1PT-1
EPT-1EPT-1EPT-1EPT-1
EPT-1EPT-1EPT-1EPT-1
PT-1PT-1PT-1PT-1
EXEXEXEX
PT-1PT-1PT-1PT-1
EXEXEXEX
EPT-1EPT-1EPT-1EPT-1
EPT-1EPT-1EPT-1EPT-1
PT-1PT-1PT-1PT-1
PT-4PT-1PT-1PT-1
PT-1PT-1PT-1PT-1
EXEXEXEX
EXEXEXEX
EXEXEXEX
PT-1PT-1PT-1PT-4PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1PT-1
PT-2PT-2PT-2
PT-2
PT-2
PT-2
PT-2
EPT-1
EPT-1
PT-2
EX
PT-2
EX
EPT-1
EPT-1
PT-2
PT-2
PT-2
EX
EX
EX
PT-2PT-2PT-2PT-2PT-2
EX
EX
EX
EX
EX
EX
EXEX
EXEX
EXEX
EXEX
EXEX
EXEX
EX
PORCELAIN QUARRY TILE (QT-1)PRODUCT: C&S TILE CERAMSTONE COLLECTION- ICON COLLECTIONCOLOR: # 5224 JET BLACK; SIZE: 12” X 24” RECTIFIEDRATINGS: (HC) HEAVY COMMERCIAL; COF: >0.60; SLIP RESISTANT R10 MATT FINISH FROST PROOF (FP)TILE BASE: 6" HIGH, CUT TILE BASE TO MATCH. INSTALL SCHLUTER DILEX-AHK PROFILE AND JOLLY AT SPECIFIED. NECESSARY ACCESSORIES/CONNECTORS BETWEEN FLOOR TILE AND WALL BASE TILE TO PROVIDE AN INSIDE COVEPROFILE IN ALL KITCHEN AREAS OR WASHROOM AREAS.GROUT: EPOXY GROUT (GR-1) TO BE INSTALLED WITH FLOOR TILE. REFER TO SPECIFICATIONS.TYPICAL GROUT JOINT WIDTH: ¼”INSTALLATION METHOD: SUGGESTED PATTERN TO BE BRICK LAYOUT PORTLAND CEMENT AS PER NMS 095423 AND MANUFACTURER’SRECOMMENDED SPECIFICATIONS.
EPOXY GROUT (GR-1)PRODUCT: CUSTOM BUILDING PRODUCTS EPOXY CEG-LITE 100% SOLIDS COMMERCIAL EPOXY GROUTCOLOR: #19 PEWTERDESCRIPTION: TWO COMPONENT FORMULA; STAIN AND CHEMICAL RESISTANT.
RUBBER FITNESS FLOORING (RF-1)PRODUCT: VOYAGER ATHLETIC TILE RUBBER FITNESS MATTINGMANUFACTURER: EDGEWOOD ATHLETICSSIZE: 48” X 72”; THICKNESS: 9.5 MM; 6.7 LBS.COLOUR: BLACKDESCRIPTION: SMOOTH FACE TILE; CUT RESISTANT AND NON-ABSORBENT.CONSTRUCTION: POLYURETHANE BONDED RECYCLED RUBBER WITH 100% POST-CONSUMER RECYCLED CONTENT AND20% VIRGIN EPDM GRANULES.WARRANTY: 5 YEAR WARRANTY AVAILABLE.EDGING: EDGEWOOD ATHLETICS CARTSMART REGULAR DUTY RAMP EDGE 3.5” W X 3/8” HIGH FOR ACCESSIBILITY.EDGING INSTALLATION: TO BE INSTALLED WITH MANUFACTURERS RECOMMENDED DOUBLE SIDED 2” WIDE TAPE.
FLOORING ACCESSORIESMETAL TRIM EDGES/ TRANSITION PROFILE (TR-1)MANUFACTURER: SCHLUTERPRODUCT: DILEX-AHK PROFILE AND NECESSARY ACCESSORIES/CONNECTORSFINISH: ALUMINUMLOCATION: INSTALLED BETWEEN FLOOR TILE QT-1 AND WALL BASE TILE TO PROVIDE AN INSIDE COVE PROFILE
METAL TRIM EDGES / TRANSITION PROFILE (TR-2)MANUFACTURER: SCHLUTERPRODUCT: JOLLY 3/8"FINISH: ALUMINUMLOCATION: WALL BASE TOP CAP
METAL TRIM EDGES / TRANSITION PROFILE (TR-3)MANUFACTURER: SCHLUTERPRODUCT: RENO AEVT 100 B40FINISH: ALUMINUMLOCATION: INSTALLED WHERE QT-1 TRANSITIONS TO EXISTING FLOORING.
VINYL TRIM EDGES / TRANSITION PROFILE (TR-4)MANUFACTURER: TARKETTPRODUCT: REDUCER RRS-WG-BFINISH: 20 CHARCOALLOCATION: INSTALLED WHERE RSF-1 TRANSITIONS TO EXISTING
RUBBER COVED BASE (RCB-1)PRODUCT: TARKETT RUBBER (TP) COVED BASESTYLE: TRADITIONAL TOE TYPECOLOUR: 20 CHARCOALHEIGHT: 6” HIGH THICKNESS: 1/8” GAUGEFLAME SPREAD/ SMOKE DENSITY: CLASS B< 450 SMOKEFIRE RESISTANCE: (ASTM E 648) CLASS 1WARRANTY: LIMITED 5 YEAR WARRANTYSUSTAINABILITY: CRADLE TO CRADLE CERTIFICATION, FLOORSCORE CERTIFICATIONINSTALLATION METHOD: AS PER MANUFACTURERS RECOMMENDED ADHESIVE AND APPLICATION METHODS.
RUBBER STAIR TREADS (RST-1)PRODUCT: TARKETT STAIRWELL MANAGEMENT-RESILIENT RUBBER STRINGERS AND RISERSDESCRIPTION: THERMOPLASTIC RUBBER-10” DEEP STRINGER & 7” HIGH RISER (HEIGHT DEPENDING ON STAIR APPLICATION)STYLE: STRINGER- RS-XX RUBBER STRINGER; RISER: RR-XX WITH CONTRASTING TACTILE STRIPTACTILE EDGE STRIP COLOR: MUST MEET WADS STANDARDS FOR CONTRASTING COLORSCOLOUR: 20 CHARCOALTHICKNESS: STRINGER: 0.080” (2MM); RISER:FLAME SPREAD/ SMOKE DENSITY: ASTM E662 NFPA 258 CLASS B< 450 SMOKEFIRE RESISTANCE: (ASTM E 648) NFPA 253- CLASS 1WARRANTY: LIMITED 2 YEAR WARRANTYSUSTAINABILITY: CRADLE TO CRADLE CERTIFICATION, FLOORSCORE CERTIFICATIONINSTALLATION METHOD: AS PER MANUFACTURERS RECOMMENDATIONS AND ADHESIVE AND APPLICATION METHODS.
VINYL TACTILE WARNING SURFACE (VTS-1)PRODUCT: TARKETT STAIRWELL MANAGEMENT-VINYL TACTILE WARNING SURFACEDESCRIPTION: SOLID COLOR TACTILE WARNING SURFACE TILESIZE: 12” X 50’ 1/8”LOCATION: TO BE INSTALLED AT ALL STAIR TRANSITIONS, AS PER WADS, NBC AND MBC.COLOUR: TBD; 36 STANDARD COLORS AVAILABLEFLAME SPREAD/ SMOKE DENSITY: ASTM E662 NFPA 258 CLASS B< 450 SMOKEFIRE RESISTANCE: (ASTM E 648) NFPA 253- CLASS 1WARRANTY: LIMITED 2 YEAR WARRANTYSUSTAINABILITY: CRADLE TO CRADLE CERTIFICATION, FLOORSCORE CERTIFICATIONINSTALLATION METHOD: AS PER MANUFACTURERS RECOMMENDATIONS AND ADHESIVE AND APPLICATION METHODS.
APPLIANCES
COMMERCIAL ELECTRIC RANGE (R-1)PRODUCT: IMPERIAL RANGEMODEL: IR-6-ESIZE: 36”DESCRIPTION: 6 ROUND ELEMENTS; ELECTRIC RANGE; 240V; 72 AMP WITH 4 CASTOR SWIVEL FEETU.L/ ULC COMPLIANTWARRANTY: LIMITED 1 YEAR ONE PARTS AND LABOUR
OVERHEAD HOOD RANGE (OHR-2)PRODUCT: KITCHENAID 36 INCH COMMERCIAL STYLE WALL MOUNT RANGE HOODSIZE: 36” WIDE X 18” HIGH X 25” DEEPMODEL: KVWC906JSS:DESCRIPTION: 108K BTU, 3 SPEED, STAINLESS STEEL FINISH WALL MOUNT CANOPY RANGE HOOD, 10” DUCT; 120VMOUNTING HEIGHT: TO BE DETERMINED ON SITE. NOTE- MUST BE MOUNTED HIGH ENOUGH SO STAFF DO NOT HIT THEIR HEADS.U.L/ ULC COMPLIANTWARRANTY: LIMITED 1 YEAR PARTS AND LABOUR
RESIDENTIAL DISHWASHER (DW-2)PRODUCT: BOSCH 800 SERIES UNDERCOUNTER BUILT IN DISHWASHERSIZE: 23.54” W X 23.7” D X 33.7/8” HFINISH: STAINLESS STEEL6 WASH CYCLES, SANITIZE SETTING, STAINLESS STEEL TUB, FRAME, FILL AND DRAIN TYPE OPERATIONLEAK PROTECTION, 24/7 AQUA STOP; 3RD RACK SYSTEM; UL LISTEDWARRANTY: LIMITED 1 YEAR PARTS AND LABOUR WARRANTY
BATHROOM FAUCET (FCT-1)PRODUCT: DELTA HANDS FREE 591T SERIES ELECTRONIC FAUCET C/W THERMOSTATIC MIXING VALVEDESCRIPTION: SURFACE MOUNT CONTROL BOX BATTERY OPERATED WITH SENSOR CLEARANCE FINISH: CHROME PLATEDMODEL NO.: 591T1220DIMENSIONS: 5.3” HIGH X 6.5”EXT X 6.25” WIDEINSTALLATION MOUNTING: 4” ON CENTRETHERMOSTATIC MIXING VALVE REQUIRED: MODEL NO.: DELTA #R3070-MIXLFWARRANTY: 5 YEAR LIMITED COMMERCIAL WARRANTY
KITCHEN FAUCET (FCT-2)PRODUCT: T&S BRASS AND BRONZE WORKS INC. COMMERCIAL KITCHEN PULL DOWN FAUCETDESCRIPTION: PRE-RINSE UNIT; 8” WALL MOUNT MIXING FAUCET WITH LEVER HANDLES AND 44” FLEXIBLE STAINLESS STEEL HOSEMODEL NO.: B-0133-BDIMENSIONS: 12 5/8” WIDE X 33 3/8” H X 14 1/16” EXT.TO BE WALL MOUNTED; 1.15 GPM SPRAY VALVE
WASHER & DRYER (STACKING) WASHERPRODUCT: LG 5.2 CU. FT. ULTRA LARGE SMART WI-FI ENABLED FRONT LOAD WASHERMODEL: WM3700HVASIZE: 27" W X 30 3/4" D X 39" HWARRANTY: LIMITED 1 YEAR PARTS AND LABOUR WARRANTY
DRYERPRODUCT: LG 7.4 cu. ft. ULTRA LARGE CAPACITY SMART WI-FI ENABLED ELECTIC DRYERMODEL: DLEX3700VSIZE: 27" W X 30 3/4" D X 39" HWARRANTY: LIMITED 1 YEAR PARTS AND LABOUR WARRANTYSPECIAL: PROVIDE STACKING KIT KSTK1
DIVISION 01 - GENERAL REQUIREMENTS
1. CONTRACTOR TO OBTAIN ALL NECESSARY BUILDING PERMITS & CERTIFICATES.
2. CONTRACTOR MUST HAVE A WRITTEN WORKPLACE SAFETY AND HEALTH PROGRAM IN ACCORDANCE WITH THE WORKPLACE SAFETY AND HEALTH ACT (MANITOBA).
3. CONTRACTOR SHALL BE THE PRIME CONTRACTOR AND SHALL SERVE AS, AND HAVE THE DUTIES OF THE PRIME CONTRACTOR IN ACCORDANCE WITH THE WORKPLACE SAFETY AND HEALTH ACT (MANITOBA).
4. COORDINATE PROGRESS SCHEDULE AND COORDINATE WITH CONTRACT ADMINISTRATOR DURING CONSTRUCTION.
4. RESTRICT USE OF SITE TO AREA AFFECTED BY RENOVATION.
5. PROMPTLY REPORT ALL ACCIDENTS AND POTENTIAL LIABILITY CLAIMS TO THE CONTRACT ADMINISTRATOR.
6. PROTECT EXISTING FINISHES AND EQUIPMENT FROM DAMAGE DURING CONSTRUCTION.
7. AT COMPLETION OF OPERATIONS, CONDITION OF EXISTING WORK TO BE EQUAL OR BETTER THAN THAT WHICH EXISTED BEFORE NEW WORK STARTED.
8. SHOP DRAWING SUBMITTALS REQUIRED: • DOORS & DOOR HARDWARE• DINING ROOM TABLE & BASES• MOVABLE PARTITION• FLOORING AND TRIMS• WALL PROTECTION• PAINT SAMPLES• GLASS MARKER BOARD & FRAMES• WINDOW COVERINGS• APPLIANCES AND EQUIPMENT• WASHROOM ACCESSORIES• MILLWORK & MILLWORK HARDWARE• KITCHEN ACCESSORIES• BLINDS & ROLLER SHADES• ALL MECHANICAL AND ELECTRICAL EQUIPMENT (REFER ALSO TO MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL SHOP DRAWING SUBMITTAL REQUIREMENTS).
9. CLOSE-OUT SUBMITTALS REQUIRED: MANUFACTURER’S LITERATURE FOR ALL PRODUCTS, FINISHES AND/OR EQUIPMENT REQUIRED FOR THIS PROJECT, INCLUDING OPERATING AND MAINTENANCE INFORMATION AS WELL AS PRODUCT WARRANTY. ALL INFORMATION TO BE SUBMITTED DIGITALLY (ONE CD/DVD, PDF FORMAT) AND A SINGLE HARD COPY IN A “D” RING BINDER WITH SPINE AND FACE POCKETS. COVER AND SPINE TO IDENTIFY PROJECT AND SUBJECT MATTER. ARRANGE CONTENT BY SECTION NUMBERS AND SEQUENCE OF TABLE OF CONTENTS.
10. AS-BUILT DRAWINGS: AT THE COMPLETION OF THE PROJECT, THE CONTRACTOR IS TO SUBMIT ONE (1) PAPER COPY (24” x 36”) AND ONE (1) ELECTRONIC COPY (PDF FORMAT) OF “RED-LINED” DRAWINGS AS MAINTAINED AT THE SITE DURING CONSTRUCTION.
11. MECHANICAL BALANCING AND TESTING REPORT(S) AND FIRE ALARM VERIFICATION TO BE SUBMITTED UPON COMPLETION OF WORK (REFER TO MECHANICAL AND ELECTRICAL).
12. WARRANTY FOR ALL WORK RELATED TO THIS PROJECT TO BE MINIMUM ONE (1) YEAR.
13. CONTRACTOR TO NOTIFY CONSULTANT IMMEDIATELY UPON DISCOVERY OF ANY UNKNOWN HAZARDOUS MATERIAL DISCOVERED ON SITE. NO WORK TO BE CONDUCTED IN AREA OF HAZARDOUS MATERIAL UNTIL WRITTEN INSTRUCTION AND APPROVAL HAS BEEN RECEIVED FROM THE CONSULTANT.
14. CONSULTANTS AND CONTRACT ADMINISTRATOR TO HAVE UNRESTRICTED ACCESS TO THE WORK.
15. UTILITIES AND SERVICES, INCLUDING WATER SUPPLY, HEATING AND VENTILATION, AND POWER AND LIGHTING WILL BE AVAILABLE ON SITE. ANY MODIFICATION TO SUCH SERVICES AS REQUIRED BY THIS PROJECT TO BE COORDINATED WITH THE CONTRACT ADMINISTRATOR.
16. EXISTING FACILITIES ARE TO BE PROTECTED FROM DAMAGE AND TO BE KEPT CLEAN AND AT ALL TIMES.
17. CONTRACTOR WILL BE RESPONSIBLE FOR MAINTAINING TEMPORARY FIRE PROTECTION EQUIPMENT DURING PERFORMANCE OF WORK REQUIRED BY GOVERNING CODES, REGULATIONS AND BYLAWS.
18. CONSTRUCTION OFFICE AND TOOLS AND EQUIPMENT STORAGE ARE TO BE THE RESPONSIBILITY OF THE CONTRACTOR. LOCATION OF, AND SERVICES FOR, ANY SUCH TEMPORARY FACILITIES ARE TO BE COORDINATED WITH THE CONTRACT ADMINISTRATOR.
19. DELIVER, STORE AND HANDLE ALL MATERIALS AND PRODUCTS IN ACCORDANCE WITH MANUFACTURER’S WRITTEN INSTRUCTIONS. STORE OFF GROUND, INDOORS IN A DRY WELL VENTILATED AREA. PROTECT FROM NICKS, SCRATCHES OR BLEMISHES AND REPLACE DEFECTIVE OR DAMAGED MATERIALS WITH NEW.
20. MAINTAIN WORK IN TIDY CONDITION, FREE FROM ACCUMULATION OF WASTE PRODUCTS AND DEBRIS.
21. CLEAN INTERIOR AREAS PRIOR TO START OF FINISHING WORK AND MAINTAIN AREAS FREE OF DUST AND OTHER CONTAMINANTS DURING FINISHING OPERATIONS.
22. PROVIDE ADEQUATE VENTILATION CONDITIONS DURING USE OF VOLATILE OR NOXIOUS SUBSTANCES. USE OF BUILDING VENTILATION SYSTEMS IS NOT PERMITTED FOR THIS PURPOSE.
23. CONTRACTOR TO ARRANGE FINAL REVIEW WITH THE CONSULTANT ONCE THE FOLLOWING CHECKLIST HAS BEEN COMPLETED:• WORK HAS BEEN COMPLETED AND INSPECTED BY THE CONTRACTOR FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS;• DEFECTS AND DEFICIENCIES HAVE BEEN CORRECTED AND COMPLETED;• EQUIPMENT AND SYSTEMS HAVE BEEN TESTED, ADJUSTED, BALANCED AND ARE FULLY OPERATIONAL;• CERTIFICATES REQUIRED BY THE AUTHORITY(IES) HAVING JURISDICTION HAVE BEEN SUBMITTED;• OPERATION OF SYSTEMS HAVE BEEN DEMONSTRATED TO THE CONTRACT ADMINISTRATOR’S PERSONNEL;• WASTE PRODUCTS AND DEBRIS HAVE BEEN REMOVED, ALL AREAS AFFECTED BY THE WORK HAVE BEEN CLEANED (ACCORDING TO PROPRIETARY LITERATURE FOR INDIVIDUAL PRODUCTS OR COMPONENTS) AND IS SUITABLE FOR OCCUPANCY.
24. IF DECLARED SUBSTANTIALLY COMPLETE BY THE CONSULTANT, CONTRACTOR TO APPLY FOR CERTIFICATE OF SUBSTANTIAL PERFORMANCE. LIEN AND WARRANTY PERIOD TO COMMENCE UPON DATE OF CONTRACT ADMINISTRATOR’S ACCEPTANCE OF SUBMITTED DECLARATION OF SUBSTANTIAL PERFORMANCE.
DIVISION 02 - EXISTING CONDITIONS
02 41 19 SELECTIVE DEMOLITION• DISCONNECT REMOVE, AND IDENTIFY DESIGNATED UTILITIES WITHIN DEMOLITION AREAS.• DEMOLISH IN AN ORDERLY AND CAREFUL MANNER. PROTECT EXISTING SUPPORTING STRUCTURAL MEMBERS.• REMOVE DEMOLISHED MATERIALS FROM SITE EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. DO NOT BURN OR BURY MATERIALS ON SITE. • REMOVE MATERIALS AS WORK PROGRESSES. UPON COMPLETION OF WORK, LEAVE AREAS IN CLEAN CONDITION.
DIVISION 06 – WOOD, PLASTICS AND COMPOSITES
06 40 00 ARCHITECTURAL WOODWORK
DIVISION 09 - FINISHES
09 21 16 GYPSUM BOARD ASSEMBLIES
WALL FINISH: • CGC TYPE X, 5/8” THICK X 4’0” WIDTHS, ENDS SQUARE CUT, EDGES TAPERED, APPLICATION AND FINISHING OF GYPSUM BOARD TO BE IN ACCORDANCE WITH ASTM C840. FINISH FACE PANEL JOINTS, INTERNAL ANGLES, SCREW HEAD DEPRESSIONS WITH JOINT SYSTEM CONSISTING OF JOINT COMPOUND, JOINT TAPE AND TAPING COMPOUND INSTALLED ACCORDING TO MANUFACTURER’S DIRECTIONS AND FEATHERED ONTO PANEL FACES. FINISH CORNER BEADS AND TRIM AS REQUIRED WITH TWO COATS OF JOINT COMPOUND AND ONE COAT OF TAPING COMPOUND FEATHERED OUT ONTO PANEL FACES. COMPLETED INSTALLATION TO BE SMOOTH, LEVEL OR PLUMB, FREE FROM WAVES AND OTHER DEFECTS, READY FOR SURFACE FINISH.
MOISTURE-RESISTANT INTERIOR GYPSUM BOARD:• TO ASTM C 1396M, MOISTURE-RESISTANT, TREATED CORE, MOULD RESISTANCE RATING 10 TO ASTM D 3273. TYPE X, 5/8” THICK FOR WALLS, 1/2” THICK FOR CEILINGS BY 48” WIDE BY MAXIMUM PRACTICAL LENGTH, ENDS SQUARE CUT, LONG EDGES BEVELLED. LOCATION: WASHROOMS AND WHERE INDICATED. STANDARD OF ACCEPTANCE: USG/CGC SHEETROCK BRAND GLASS-MAT PANELS MOLD TOUGH VHI FIRECODE X. ACCESSORIES AS APPROVED BY MANUFACTURER. LEVEL 5 FINISH.
CEILING AND BULKHEAD FINISH: • STANDARD GYPSUM BOARD TO ASTM C1396/C1396M, REGULAR, 5/8” THICK X 4’-0” WIDTHS, ENDS SQUARE CUT, EDGES TAPERED. APPLICATION AND FINISHING OF GYPSUM BOARD TO BE IN ACCORDANCE WITH ASTM C840. FINISH FACE PANEL JOINTS, INTERNAL ANGLES, SCREW HEAD DEPRESSIONS WITH JOINT SYSTEM CONSISTING OF JOINT COMPOUND, JOINT TAPE AND TAPING COMPOUND INSTALLED ACCORDING TO MANUFACTURER’S DIRECTIONS AND FEATHERED ONTO PANEL FACES. FINISH CORNER BEADS AND TRIM AS REQUIRED WITH TWO COATS OF JOINT COMPOUND AND ONE COAT OF TAPING COMPOUND FEATHERED OUT ONTO PANEL FACES. COMPLETED INSTALLATION TO BE SMOOTH, LEVEL OR PLUMB, FREE FROM WAVES AND OTHER DEFECTS, READY FOR SURFACE FINISH.
09 22 16 NON-STRUCTURAL METAL STUD FRAMING• WALLS TO BE CONSTRUCTED WITH NON-LOAD BEARING CHANNEL STUD FRAMING AND TRACKS TO ASTM C645, ROLL FORMED FROM HOT DIPPED GALVANIZED STEEL SHEET, FOR SCREW ATTACHMENT OF GYPSUM BOARD. KNOCK-OUT SERVICE HOLES AT 16” CENTERS. METAL CHANNEL STIFFENERS 3/4” X 16 GAUGE COLD ROLLED STEEL COATED WITH RUST INHIBITIVE COATING.• CONTRACTOR TO DETERMINE APPROPRIATE GAUGE OF STEEL STUD FOR WALL HEIGHT.• REFER TO WALL TYPES FOR WALL FOR STUD SIZING• PROVIDE EXPANSION TRACK AT ALL WALLS THAT GO TO U/S OF STRUCTURE. REFER TO DETAIL.
09 91 99 PAINTING FOR MINOR WORKS
PAINTING• ENSURE ALL SURFACES TO BE PAINTED ARE CLEANED AND DE-GREASED PRIOR TO ANY PAINTING WORK. ENSURE VENTILATION, LIGHT LEVELS, TEMPERATURE, HUMIDITY AND SUBSTRATE MOISTURE CONTENT LEVELS ARE WITHIN THE MANUFACTURER’S PUBLISHED INSTALLATION GUIDE LIMITS.
• SUBMIT 8”x10” OF EACH PAINT WITH THE SPECIFIED PAINT IN COLOURS, GLOSS/SHEEN AND TEXTURES REQUIRED TO MPI (MASTER PAINTERS INSTITUTE) PAINTING SPECIFICATION MANUAL STANDARDS SUBMITTED ON THE FOLLOWING SUBSTRATE MATERIALS: 1/8” PLATE STEEL FOR FINISHES OVER METAL SURFACES, 2” CONCRETE BLOCK FOR FINISHES OVER CONCRETE MASONRY SURFACES, 1/2” GYPSUM BOARD FOR FINISHES OVER GYPSUM BOARD SURFACES.• REFER TO DRAWINGS AND ROOM FINISH SCHEDULE FOR PAINTED SURFACES• IN THE OPEN OFFICE, PAINT ALL EXPOSED STRUCTURE (INCLUDING JOISTS & ROOF DECK), CONDUITS, PIPING, AND OTHER MECHANICAL (INCLUDING DUCT WORK) AND ELECTRICAL EQUIPMENT WITH COLOUR AND FINISH TO MATCH ADJACENT SURFACES, EXCEPT AS NOTED OTHERWISE.
KITCHEN STAINLESS BASE CABINET• 18GA S.S. BASE AND INTERMEDIATE SHELVES• INTERMEDIATE SHELVES TO BE ADJUSTABLE WITH STAINLESS PILASTER STRIPS AND CLIPS• CABINET ENDS AND DIVIDERS TO BE 20GA S.S. T304#4 FINISH• BACK PANEL-20GA S.S. T304#4• REINFORCING 16GA SATINCOAT C-SECTION, DOUBLE - FACE TAPE TO TOP (3 REQ'D)• 16GA SATINCOAT OR GALVANIZED SUPPORT CHANNELS FOR BASE SHELF• 1 5/8" OD - 16GA S.S. ORNAMENTAL TUBULAR LEGS• S.S. ADJ. BULLET FEET• 16GA S.S. T304#4 6" REMOVABLE S.S. KICK PLATE - FRONT & ENDS• 16GA S.S. SKIRTING TO COVER FRONTS OF SINK
KITCHEN STAINLESS DRAWERS• DOUBLE PAN CONSTRUCTION-FRONT-18GA S.S. T304#4• 1" INSULATION BETWEEN PANS• 16GA S.S. T304#4 DRAWER PAN x 8" DEEP FASTENED TO THE BACK PAN OF THE DRAWER FRONT• STAINLESS DRAWER SLIDES x 20"LONG - FULL EXTENSION WEIGHT CAPACITY 80-100 lbs• DRAWER HOUSING - 16GA S.S. T304#4• FASTEN DRAWERS TO UNDERSIDE OF STAINLESS TOP
KITCHEN STAINLESS WALL MOUNTED SHELVES - CABINET STYLE• 18GA S.S. T304#4 BODY, TOP AND SHELVES• SHELVES TO BE ADJUSTABLE C/W S.S. PILASTER STRIP AND CLIPS
MILLWORK HARDWARELOCKS:HAFELE CYLINDER MODULE SYSTEMVERTICAL INSTALLATION DOOR LOCK MODEL: 235.08.358 P516
PULLS:RICHELIEU: CONTEMPORARY ALUMINUM EDGE PULL - 9898LENGTH: 212mm TYPICAL, 436mm AT FULL HEIGHT CABINETS, 96mm AT TV CABINET BRUSHED BLACK FINISHREFER TO ELEVATIONS & DETAILS
HEAVY DUTY HINGES:PRODUCT: CONCEALED HINGE (HEAVY DUTY)MANUFACTURER: HAFELE MODEL: SUGATSUNE J95DESCRIPTION: HEAVY DUTY, FULL OVERLAY, SCREW MOUNT, NICKEL-PLATED; (2) HINGES CAPABLE OF SUPPORTING 55LBSINSTALLATION: PROVIDE (4) HINGES FOR EACH FULL HEIGHT STORAGE CABINET DOOR
GROMMETS:RICHELIEU: METAL GROMMET - 20694170SIZE: 75mm DIAMETERSTAINLESS STEEL FINISHREFER TO ELEVATIONS & DETAILS
MONITOR ARMS:MANUFACTURER: ESIMODEL: EDGE SINGLE MONITOR ARMFINISH: EDGE-BLK BLACKREFER TO ELEVATIONS & DETAILS
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
07 21 16 BLANKET INSULATION
INTERIOR WALL INSULATION: • BATT AND BLANKET MINERAL FIBRE INSULATION• THICKNESS: AS NOTED IN DRAWINGS• PRODUCT: ROCKWOOL SAFE'n'SOUND, OR APPROVED EQUAL
DIVISION 08 - OPENINGS
08 11 00 METAL DOORS AND FRAMES: INTERIOR DOOR FRAME• 16 GAUGE HOLLOW METAL, 2” FACE PROFILE:• HOLLOW METAL FRAME, PAINTED• PROVIDE SHOP DRAWINGS FOR CONSULTANT REVIEW• STANDARD OF ACCEPTANCE: ALLMAR STANDARD SERIES HOLLOW METAL FRAME• REFER TO DOOR SCHEDULE
08 14 16 FLUSH WOOD DOORS • SOLID PARTICLEBOARD CORE WITH DENISTY OF 28-32lbs PER CUBIC FOOT• 1/8" THICK VENEER STILE, TOP AND BOTTOM RAILS, LONGITUDINALLY LAMINATED BY HOT PRESSING W/ TYPE 1 STRUCTURAL GLUE• WOOD VENEER FACES (MAPLE VENEER, 2 PLY PLYWOOD) GLUED TO COMPOSITE CROSS-BAND. VENEER TO MATCH ADJACENT DOOR. MANUFACTURER TO CONFIRM SPECIES PRIOR TO FABRICATION. • STAIN TO MATCH EXISTING DOORS• REFER TO DOOR SCHEDULE
QT-1 QT-1
QT-1 QT-1
QT-1 QT-1
QT-1 QT-1
QT-1 QT-1
QT-1 QT-1
RSF-1 RCB-1
QT-1 QT-1
QT-1 QT-1
QT-1 QT-1
RF-1 RCB-1
EX EX
QT-1 QT-1
RSF-1/RST-1 RCB-1/ -
EX EX
TOILET AND BATH ACCESSORIES
WALL MOUNTED SHELFMANUFACTURER: BOBRICKPRODUCT: B-296 X 18 STAINLESS STEEL SHELF DESCRIPTION: 18-GAUGE (1.2MM) SHELF, TYPE 304 STAINLESS STEEL, SATIN FINISH. 3/4″ (19MM) RETURN EDGE; FRONT EDGE IS HEMMED FOR SAFETY. BRACKETS ARE 16-GAUGE (1.6MM).SIZE: 18" L X 6" WIDE
WALL PROTECTIONCORNER GUARDS-STAINLESS STEEL (CG-1)MANUFACTURER: FROSTPRODUCT: MODEL 1117 CORNER GUARDDESCRIPTION: 18 GAUGE; TYPE 304 STAINLESS STEELFINISH: NO. 4 BRUSHED FINISHSIZE: 4”D X 4” W X 40” HWARRANTY: 1 YEAR WARRANTYINSTALLATION METHOD: FULL LENGTH SELF ADHESIVE BACKING AS PER MANUFACTURERS RECOMMENDATIONS AND APPLICATION METHODS
DIVISION 10 – MISCELLANEOUS SPECIALTIES
MAGNETIC BACKPAINTED GLASS MARKERBOARD (MBG-1)MANUFACTURER: GOLDRAYPRODUCT: FULLY TEMPERED LOW IRONDESCRIPTION: MINIMUM THICKNESS 5/16” (8MM) COMPRISED OF ONE LAYER OF ¼” (6MM) GLASS PERMANENTLY BONDED TO A PARAMAGNETIC MATERIAL ON THE UNEXPOSED SURFACE.COLOUR: DECORATOR'S WHITESIZE: REFER TO ELEVATIONSEDGE: FLAT POLISHEDACCESSORIES: Z-BAR HANGER CLIPS, NO VISIBLE MOUNTING HARDWARE. STRUCTURALMOUNTING HARDWARE CONCEALED BEHIND THE GLASS.
WINDOW COVERINGSMANUAL ROLLER BLACKOUT SHADES (RS-1)PRODUCT: ALTEX SUNPROJECT- TEXOPAQUE ECO 6100 BLACKOUT ROLLER SHADESSTANDARD WIDTH: 299.7 CM/ (118”)STANDARD LENGTH: 27.4 M/ (30 L/YD.)WEIGHT: 12.14 OZ. /YD.FABRIC THICKNESS: 0.356MM (0.014”)FABRIC COMPOSITION: 100% POLYESTER WITH ACRYLIC BACKING- PVC FREE; -FABRIC TO BE SAME COLOR BOTH SIDES OF SHADE.FIRE CLASSIFICATION: NFPA 701; CAN/ ULC-S 109-03; NFPA 101 CLASS A RATING; IBC SECTION 803 1.1 CLASS A RATINGBACTERIAL AND FUNGAL RESISTANCE: ASTM E 2180, ASTM G21SOLAR HEAT CONTROL PROPERTIES- IN ACCORDANCE WITH ASHRAE STANDARD 74-1988ENVIRONMENTAL: MEETS GREENGUARD GOLD; RECYCLABLE; LEAD FREE FABRICCASSETTE: ALUMINUM FINISH; SQUARE CASSETTE; CHAIN FOR OPERATINGWARRANTY: 1 YEAR WARRANTY
QT-1 QT-1
N/ARS-1N/A
RS-1
RS-1
RS-1
RS-1
RS-1
RS-1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/AN/A
N/A
08 71 00 DOOR HARDWARE• ALL HARDWARE TO BE COMMERCIAL GRADE HARDWARE• PROVIDE THRESHOLDS, WEATHERSTRIPPING, SEALS AND DOOR GASKETS AS REQUIRED• PROVIDE SMALL FORMAT INTERCHANGABLE CORES (SFIC)• PROVIDE MAINTENANCE TOOLS AND ACCESSORIES SUPPLIED BY HARDWARE COMPONENT MANUFACTURER.• ALL KEYING TO BE COMPLETED BY CONTRACT ADMINISTRATOR • ALL HANDLES TO BE LOCKABLE LEVER TYPE HANDLES, UNLESS NOTED OTHERWISE. REFER TO ELEVATION. • ACCEPTABLE SUPPLIERS: SCHLAGE, SATIN CHROMIUM FINISH OR EQUAL• EXACT DOOR HARDWARE TO BE DETERMINED BY THE DOOR HARDWARE SUPPLIER AND APPROVED BY CONTRACT ADMINISTRATORS. PROVIDE SHOP DRAWINGS. • 3 HINGES TO MATCH EXISTING • KICK PLATES: 12" ROCKWOOD KICKPLATES - K1050 12” US32D RO
BRUSHED STAINLESS FINISH• PUSH PLATES: 111 x 70C US32 RO• ROCKWELL 461 US26D RO
ROOM PARTITIONSPRODUCT: LINKING PANELS OR APPROVED EQUALMANUFACTURER: GLOBAL CONTRACTCOLOUR: PANELS & FRAMES TO BE IN DESIGNER WHITE (DWT)SIZE: EQUAL PANELS TO DIVIDE DORM G18 - SITE CONFIRM DIMENSIONS. REFER TO RENOVATION PLAN. 2 ADDITIONAL PANELS AT 5'-0" WIDE FOR PRIVACY AT BEDS.ALL PANELS TO BE 66" HIGH.LOCATION: DORM G-18PARTITIONS TO BE MOVABLE (NOT FIXED). PROVIDE ALL FRAMES, CONNECTORS, CASTORS AND LEVELERS.SPECIAL: SUBSTITUTES CAN BE PROPOSED TO CONSULTANT FOR REVIEW AND APPROVAL.
DINING TABLE BASEPRODUCT: MANHATTAN MNT2 DOUBLE COLUMN 'T' BASE OR APPROVED EQUALW/ CUSTOM QUARTZ (QZ-1) TOPMANUFACTURER: SPECBASE COLOUR: BLACK SIZE: 42" X 60" LOCATION: KITCHEN G-08SPECIAL: SUBSTITUTES CAN BE PROPOSED TO CONSULTANT FOR REVIEW AND APPROVAL.
KITCHEN ACCESSORIES
MAGNETIC KNIFE HOLDERMANUFACTURER: OMCANPRODUCT: MAGNETIC KNIFE BAR 23592FINISH: STAINLESS STEEL SIZE: 17.75" X 1.75"
STAINLESS INTEGRAL KITCHEN SINK• 16GA S.S. T304#4 MINIMUM - ALL COVED WELDED INTEGRAL INTO COUNTERTOP - WELDS CLEANED AND POLISHED TO BLEND WITH S.S. TOP.• SEE SIZES ON DRAWING• 3 1/2" S.S. STRAINER ASSEMBLIES C/W 1 1/2" DRAIN
SOLID SURFACE COUNTERTOPS (SSC-1)MANUFACTURER: WILSONARTPRODUCT: SOLID SURFACECOLOUR: CHILLED EARTH 9228SSFINISH: MATTETHICKNESS: 1/2” THICKSHEET SIZE: 30” W X 144”FIRE PERFORMANCE: CAN/ULC-S102.2; SMOKE DEVELOPED VALUE 5WARRANTY: 10 YEAR LIMITED PRODUCT WARRANTYENVIRONMENTAL: GREENGUARD INDOOR AIR QUALITY CERTIFIED; NSF CERTIFIED.
QUARTZ COUNTERTOPS (QZ-1)MANUFACTURER: HANSTONE PRODUCT: QUARTZCOLOUR: TOFINOFINISH: POLISHED SURFACE ON ALL EDGES; NON-PORUS, SCRATCH RESISTANT; MOULD RESISTANT; CORNERS TO BE ROUNDED. THICKNESS: ½” THICKCOMPRESSION STRENGTH: ASTM C170SURFACE BURNING CHARACTERISTICS: CLASS A; ASTM E84; FLAME SPREAD INDEX-10 OR LESS; ENVIRONMENTAL: GREENGUARD CERTIFIED, NSF CERTIFIEDWARRANTY: 10 YEAR COMMERCIAL WARRANTYLOCATION: CUSTOM COMMON AREA DINING TABLETOP
SOLID COMPACT LAMINATE (PLAM-1)MANUFACTURER: FORMICAPRODUCT: COMPACT STRUCTURAL LAMINATE, GRADE S6COLOUR: AGED ASH 8844TEXTURE: MATTETHICKNESS: ½”SURFACE BURNING CHARACTERISTICS: CLASS B; ASTM E84WARRANTY: 1 YEARLOCATION: MILLWORK VERTICAL SURFACES AND EXPOSED CABINET BASES WHERE POSSIBLE.SPECIAL: RUN WOODGRAIN IN HORIZONTAL ORIENTATION
SOLID COMPACT LAMINATE (PLAM-2)MANUFACTURER: FORMICAPRODUCT: COMPACT STRUCTURAL LAMINATE, GRADE S6COLOUR: STORM SOLIDZ 3505TEXTURE: MATTETHICKNESS: ½”SURFACE BURNING CHARACTERISTICS: CLASS B; ASTM E84WARRANTY: 1 YEARLOCATION: MILLWORK VERTICAL SURFACES AND EXPOSED CABINET BASES WHERE POSSIBLE.
STAINLESS STEEL COUNTERTOPS (SS-1) – KITCHENTYPICAL COUNTERTOPS: 16 GAUGE TYPE T304 #4 STAINLESS STEEL COMPLETE WITH MARINE EDGE LIP AND FRONT AND SIDES (TYPICAL)KITCHEN SINKS: KITCHEN COUNTERTOPS TO RECEIVE INTEGRAL STAINLESS STEEL SINK INTO COUNTERTOP
EXISTING WALL & CEILING FINISHES:• PREPARE TO RECEIVE NEW PAINT FINISH. REMOVE ALL LOOSE OR DAMAGEDMATERIALS, RAKE CRACKS TO A MINIMUM DEPTH OF 1/8” AND SKIM-COAT WITHGYPSUM-BASED COMPOUND TO PROVIDE SMOOTH, PAINTABLE FINISH. APPLY INMULTIPLE COATS AS REQUIRED
FLOORINGRESILIENT SHEET FLOORING (RSF-1)PRODUCT: ARMSTRONG FLOORING HETEROGENEOUS SHEET FLOORINGSTYLE: CORLONCOLOUR: 88702 WHITE CLIFFSCONSTRUCTION: INLAID; TRUE THROUGH-PATTERN WEAR LAYERTHICKNESS: 2.0 MM -PRODUCT; 1.27 MM WEAR LAYERROLL WIDTH: 6FT (1.83M)COORDINATED WELD ROD: ARMSTRONG STONE GREY #WS168BACKING: TEXTURED TYPE 1, CLASS A BACKINGLIGHT REFLECTANCE: 45-49%SMOKE DENSITY: ASTM E 662FACTORY FINISH: COMMERCIAL UV CURED POLYURETHANE COATINGWARRANTY: 5 YEAR COMMERCIAL RESILIENT LIMITED WARRANTYSUSTAINABILITY: LOW VOC; ENVIRONMENTAL PRODUCT DECLARATION, FLOORSCORE CERTIFICATIONINSTALLATION METHOD: FULL SPREAD; AS PER MANUFACTURERS RECOMMENDATIONS
DOORS & FRAMES:•FINISH EXISTING HOLLOW METAL FRAMES & DOORS AS PER MANUFACTURER’S PUBLISHED INSTALLATION GUIDE WITH ONE COAT PRIMER AND TWO COATS OF A HIGH-QUALITY LATEX, SEMIGLOSS FINISH PAINT. STANDARD OF ACCEPTANCE: PRIMER: SHERWIN WILLIAMS PRO-CRYL UNIVERSAL PRIMER; TOP COAT: SHERWIN WILLIAMS SOLO ACRYLIC INTERIOR/EXTERIOR LATEX (SUBMIT COLOUR SAMPLE TO CONSULTANT FOR APPROVAL).
EPOXY PAINT (EPT-1): MANUFACTURER: STONGLAZEPRODUCT: STONHARD, INC.; STONGLAZE VSR. STONGLAZE VSR AS DISTRIBUTED BY STONHARD DIVISION, RPM CANADA, IS A NOMINAL 10-12 MIL (250 TO 300 MICRON) THICK SYSTEM COMPRISED OF A TWO-COMPONENT, GENERAL SERVICE, POLYAMIDE EPOXY PRIMER AND A TWO-COMPONENT, HIGH PERFORMANCE, HIGH SOLIDS, EPOXY GLAZE COATING. HIGH GLOSS FINISH.DESCRIPTION: RESINOUS WALL SYSTEM INCLUDES A PENETRATING, TWO-COMPONENT, EPOXY POLYAMIDE PRIMER AND A TWO-COMPONENT, HIGH PERFORMANCE, HIGH SOLIDS, PIGMENTED EPOXY GLAZE COATING. COLOUR: CUSTOM COLOR TO MATCH BENJAMIN MOORE #OC-17 WHITE DOVE.HARDNESS: 80-85 (ASTM D-2240/ SHORE D DUROMETER)BOND STRENGTH: >300 PSI (ASTM D-7234)IMPACT RESISTANCE: EXCEEDS 80 IN. LBS (ASTM D-2794) (NO CRACKING, CRAZING OR LOSS OF ADHESION)ABRASION RESISTANCE: 0.08 GM MAX WEIGHT LOSS (ASTM D-4060, TABER ABRADER CS-17 WHEEL)MOCKUP: APPLY FULL-THICKNESS MOCKUPS ON 48-INCH- (1200-MM-) SQUARE WALL AREA SELECTED BY CONTRACT ADMINISTRATOR.
SPECIFICATION NOTES:
ALL FINISHES LISTED ON THE DRAWINGS ARE THE SELECTED PRODUCTS OF THE WINNIPEG FIRE PARAMEDIC SERVICE BASED ON INDUSTRY STANDARDS, DURABILITY, QUALITY, AND MAINTENANCE PURPOSES FOR A HEAVY USE 24/7 ENVIRONMENT. HOWEVER ALTERNATE FINISHES AND/OR PRODUCTS MAY BE CONSIDERED AS AN APPROVED SUBSTITUTE IN ACCORDANCE WITH MATERIALS MANAGEMENT POLICY B7 AS PER THE TENDER DOCUMENTS.
INTERIOR RENOVATIONS
2'-8
1/2
"S
ILL
HE
IGH
T
2'-8
1/2
"S
ILL
HE
IGH
T
2'-8
1/2
"S
ILL
HE
IGH
T
3'-3
1/4
"S
ILL
HE
IGH
T
4'-1
"3'-10 1/2" 2'-7 1/2"
4'-1
"
3'-3
1/4
"S
ILL
HE
IGH
T
4'-5
1/2
"
9'-10 1/2"7'-4"
4'-5
1/2
"
5'-9"
4'-5
1/2
"
W1 W2 W3 W4 W5
QUANTITY: 1 QUANTITY: 1 QUANTITY: 1 QUANTITY: 1 QUANTITY: 6
NOTE: SITE CONFIRM ALL EXISTING WINDOW DIMENSIONS FOR NEW BLINDS. REFER TO SPECS & ROOM SCHEDULE FOR BLIND TYPES.
WINDOW SCHEDULE
BID OPPORTUNITY 280-2020
DOOR SCHEDULE
DOOR TYPE 1 FRAME TYPE 1
7'-0
"
3'-4
"
2" T
YP
3'-0" 3'-0"
7'-0
"
GENERAL NOTES:
THESE DRAWINGS SHALL NOT BE SCALED.
THE CONTRACTOR SHALL VISIT THE SITE AND SATISFY ONESELF ALL DIMENSIONS, DATUM, AN DETAILED INFORMATION SHOWN ARE CORRECT.
THE CONTRACTOR IS TO REVIEW AND COORDINATE ALL ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS THROUGH FLOORS, WALLS, AND CEILINGS FOR DUCT, PIPE & ELECTRICAL RISERS AND ALL OPENINGS NOT SHOWN ON DRAWINGS.
ALL OPENINGS THROUGH FIRE ASSEMBLIES ARE TO BE FIRESTOPPED AND SEALED WITH ULC APPROVED FIRE STOPPING TO MAINTAIN THE INTEGRITY OF THE FIRE SEPARATION, AND PROVIDE A SMOKE-TIGHT BARRIER.
ALL PRODUCTS AND MATERIALS TO BE USED AND INSTALLED SHALL CONFORM WITH MANUFACTURER'S SPECIFICATIONS & APPLICABLE CODES.
THE CONTRACTOR SHALL BE RESPONSIBLE TO PATCH AND MAKE GOOD ALL EXISTING CONSTRUCTION AFFECTED BY DEMOLITION AND THE REMOVAL OF ALL ITEMS FORMING PART OF THE RENOVATION WORK.
WHERE NEW FLOORING AND BASE IS TO BE INSTALLED IN EXISTING AREAS (REFER TO FLOOR PLAN AND ROOM SCHEDULE) THE EXISTING FLOORING SURFACE AND BASE MUST BE REMOVED, UNLESS OTHERWISE NOTED. ALL FLOOR SURFACES SHALL BE PREPARED IN ACOORDANCE TO MANUFACTURER'S RECOMMENDATIONS FOR INSTALLATION OF NEW FLOOR.
WHERE PAINTING OF EXISTING WALLS & CEILINGS IS INDICATED ON THE ROOM SCHEDULE, THESE WALLS MUST BE CLEANED OF ANY EXISTING WALL COVERING, PATCHED & PREPARED TO ACCEPT NEW PAINT, UNLESS OTHERWISE NOTED.
ALL EXISTING FURNITURE, EQUIPMENT (INCLUDING GYM EQUIPMENT), AND WALL MOUNTED ITEMS/ ARTWORK/ MAPS/ EXIT PLANS ARE TO BE REMOVED AND REINSTALLED BY THE CITY OF WINNIPEG'S MOVERS (TO BE STORED IN THE APPARATUS ROOM OR A STORAGE CONTAINER AS REQ'D).
EMERGENCY LIGHTING TO BE REPLACED, REFER TO ELECTRICAL FOR SCOPE OF WORK.
ALL MISCELLANEOUS FLOOR MOUNTED ELECTRICAL TO BE REMOVED & REINSTALLED FOR FLOORING INSTALLATION.
ALL MECHANICAL WALL VENTS/GRILLES TO BE REMOVED & REINSTALLED FOR PAINTING.
ALL EXISTING DOORS ARE TO BE CUT DOWN OR ADJUSTED AS REQUIRED TO ACCOMMODATE NEW FLOORING THICKNESS. PATCH & MAKE GOOD ALL DOORS.
ALL FIRE EXTINGUISHERS TO BE REMOVED AND REINSTALLED FOR PAINTING.
WARNING:ASBESTOS MAY BE PRESENT BEHIND WALLS CEILING SPACE & FLOORS. IF ASBESTOS OR ANY HAZARDOUS MATERIAL IS FOUND STOP WORK IMMEDIATELY & CONTACT CITY OF WINNIPEG, CENTRAL CONTROLS PH: 204-986-2351.
UP
SP
K
ROOM
G-10
CLEANING
ROOM
G-21
DRYING
HOSE TOWER
G-20
ROOM
G-22
STORAGE
VESTIBULE
G-01
DORMITORY
G-18
ROOM
G-17
LOCKER WASHROOM
G-09
WOMEN'S
ROOM
G-11
STATIONARY
SHOWER
G-15
WASHROOM
G-16
MEN'S
CORRIDOR
G-13
CORRIDOR
G-03
KITCHEN
G-08LOUNGE
G-07
OFFICE
G-06
CAPTAIN'S
OFFICE
G-05
LIEUTENANT'S
ROOM
G-23
CONTROL
RECEPTION
G-02
ROOM
G-14
MECHANICAL
VESTIBULE
G-19
ROOM
G-12
APPARATUS
SPK
SP
K
SP
K
SP
K
SP
K
ROOM
G-04
PHONE
UP
SP
K
ROOM
G-10
CLEANING
ROOM
G-21
DRYING
HOSE TOWER
G-20
ROOM
G-22
STORAGE
VESTIBULE
G-01
DORMITORY
G-18
ROOM
G-17
LOCKER WASHROOM
G-09
WOMEN'S
ROOM
G-11
STATIONARY
SHOWER
G-15
WASHROOM
G-16
MEN'S
CORRIDOR
G-13
CORRIDOR
G-03
KITCHEN
G-08LOUNGE
G-07
OFFICE
G-06
CAPTAIN'S
OFFICE
G-05
LIEUTENANT'S
ROOM
G-23
CONTROL
RECEPTION
G-02
ROOM
G-14
MECHANICAL
VESTIBULE
G-19
ROOM
G-12
APPARATUS
SPK
SP
K
SP
K
SP
K
SHOWER
DN
W/C
M-02
STAIRHALL
M-03
RESCUE
M-04
WATER
DORMITORY
M-01
HOSE TOWER
G-20
SPK
SPK
UP
FE
SHOWER
DN
W/C
M-02
STAIRHALL
M-03
RESCUE
M-04
WATER
DORMITORY
M-01
HOSE TOWER
G-20
SPK
SPK
1
2
3
45
6
7
8
9
10
(TYP)
11
13
14
15
1617
18
19
--1S
14 X 4
20 X 4
20
(TYP)
21
SK - 1
DW - 1
WM - 1
6Ø
10Ø
LAV - 1LAV - 1
(TYP. of 3)
22 2223GI - 1
1
12
LAV - 1 22
A. CONFORM TO APPLICABLE CODE FOR DEMOLITION WORK, DUST CONTROL, PRODUCTS REQUIRING ELECTRICAL DISCONNECTION OR RECONNECTION.
B. CONFORM TO APPLICABLE REGULATORY PROCEDURES WHEN DISCOVERING HAZARDOUS OR CONTAMINATED MATERIALS.
C. CLOSE OPENINGS IN EXTERIOR SURFACES TO PROTECT EXISTING WORK FROM WEATHER AND EXTREMES OF TEMPERATURE AND HUMIDITY.
D. PROVIDE, ERECT, AND MAINTAIN TEMPORARY BARRIERS WHERE NEEDED TO CONTAIN CONSTRUCTION DEBRIS AND DUST. PROVIDE A MINIMUM MERV 8 FILTRATION ON EXISTING INLETS AND RETURN AIR DUCTS AND SYSTEMS.
E. PROTECT EXISTING MATERIALS, EQUIPMENT, AND SYSTEMS WHICH ARE NOT TO BE DEMOLISHED.F. CONDUCT DEMOLITION TO MINIMIZE INTERFERENCE WITH OCCUPIED BUILDING AREAS.G. DISCONNECT, REMOVE, CAP, AND IDENTIFY DESIGNATED UTILITIES WITHIN DEMOLITION AREAS.H. REMOVE, CUT, AND PATCH WORK IN A MANNER TO MINIMIZE DAMAGE AND TO PROVIDE MEANS OF RESTORING
SYSTEMS TO ORIGINAL CONDITION.I. CAREFULLY DISMANTLE EXISTING MECHANICAL EQUIPMENT TO BE REMOVED OR RELOCATED. TEMPORARILY
DISCONNECT, REMOVE, AND REINSTALL EXISTING EQUIPMENT, PIPING, DUCTWORK, CONDUIT, LIGHT FIXTURES, AND SIMILAR ITEMS, WHICH INTERFERE WITH THE NEW INSTALLATION AFTER COMPLETION OF NEW WORK OR OF EXISTING INSTALLATIONS TO BE DEMOLISHED. STORE EQUIPMENT AND MATERIALS ON THE PREMISES AS DIRECTED BY THE OWNER.
J. DEMOLISH IN AN ORDERLY AND CAREFUL MANNER. REMOVE DEMOLISHED MATERIALS FROM SITE EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. UPON COMPLETION OF WORK, LEAVE AREAS IN CLEAN CONDITION.
K. ALL USABLE SALVAGED EQUIPMENT AND MATERIALS SHALL REMAIN THE PROPERTY OF THE OWNER UNLESS SPECIFICALLY NOTED OTHERWISE.
L. FIRESTOP ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL ASSEMBLIES WHERE PIPES OR DUCTS WERE REMOVED. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND TYPE OF RATINGS.
M. THE ABANDONMENT OF EXISTING EQUIPMENT AND MATERIAL IN PLACE IS NOT ACCEPTABLE. ALL REDUNDANT SERVICES ARE TO BE REMOVED BACK TO ACTIVE MAINS, WHICH SHALL THEN BE CAPPED AT EXISTING POINT OF CONNECTION.
N. FIRESTOP ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED FLOOR AND WALL ASSEMBLIES. SEE ARCHITECTURAL DRAWINGS FOR LOCATION AND TYPE OF RATINGS.
O. THE CONTRACTOR SHALL SIZE AND COORDINATE PLUMBING VENTING AND COORDINATE DOMESTIC WATER AND SANITARY PIPE ROUTING. THE CONTRACTOR SHALL ALLOW FOR THE POSSIBILITY OF INTERFERENCES AND SHALL RESOLVE WITH OTHER TRADES ON SITE. ANY CHANGES TO THE DESIGN INTENT REQUIRE APPROVAL BY THE ENGINEER.
P. ALL NEW CORING FOR PLUMBING SERVICES SHALL BE DONE BY MECHANICAL CONTRACTOR. COORDINATE WITH ALL OTHER TRADES.
Q. CONTRACTOR SHALL SCAN FOR REBAR AND CONDUIT AND PROVIDE RESULTS OF SCAN IN WRITING TO OWNER PRIOR TO CORING OR DRILLING IN ANY CONCRETE WALL OR FLOOR.
R. COORDINATE FINAL THERMOSTAT INSTALLATION HEIGHT AND DISTANCE FROM DOOR WITH ARCHITECT.
MECHANICAL GENERAL NOTES
x architecture inc.120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7 204 318 2010
Seal
Engineer
Project
Sheet Title
NO. DATE REVISION / ISSUANCE
SheetProject No .
Date
Architect
19089A
BID OPPORTUNITY 280-2020
799 LILAC STREET
20-06-09
FLOOR PLANS - MECHANICAL
WINNIPEG FPS FIRE STATION #13INTERIOR RENOVATIONS
M2.1
16 PROVIDE DOMESTIC WATER AND SANITARY ROUGH IN FOR DISHWASHER AND CONNECT TO PREVIOUSLY DEMOLISHEDDISHWASHER PIPING. CONNECT TO SINK DRAIN WITH CONNECTED DISHWASHER CONNECTION. CONTRACTOR TO ENSUREPIPING IS INSTALLED NEATLY WITHIN OPEN CABINETS.
17 NEW RANGE HOOD ABOVE ELECTRIC STOVE (PROVIDED BY OTHERS). PROVIDE DUCT CONNECTION FOR RANGE HOODOPERATION. DUCTING SHALL RUN TIGHT TO WALL AND EXIT THROUGH HOOD. HOOD SHALL BE PREMANUFACTUREDPAINTED STEEL, SUITABLE FOR INSTALLATION ON A PITCHED SHINGLED ROOF, COMPLETE WITH BACKDRAFT DAMPERAND BIRD SCREEN. COORDINATE HOOD INSTALLATION WITH GENERAL CONTRACTOR. INSULATE RANGE HOOD EXHAUSTDUCTING FOR ENTIRE LENGTH WITHIN ATTIC.
18 INSTALL EXISTING HUMIDISTAT ON WALL. EXTEND AND MODIFY EXISTING WIRING AS REQUIRED. COORDINATE ANYREQUIREMENTS WITH ELECTRICAL.
19 INSTALL EXISTING CO MONITOR ON WALL. INSTALL MONITOR IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS ANDCODE REQUIREMENTS. COORDINATE INSTALLATION WITH ELECTRICAL CONTRACTOR AND ENSURE ANY REQUIREDINTERLOCKS AE FUNCTIONAL.
20 PROVIDE NEW GRILLE MOUNTED WITHIN CABINET TOEPLATE. CONNECT TO EXISTING DUCT. MODIFY AND EXTEND ASREQUIRED TO RUN WITHIN TOESPACE OF CABINET TO GRILLE.
21 REINSTALL ALL SUPPLY AND RETURN GRILLES AS REQUIRED AFTER CONSTRUCTION HAS BEEN COMPLETED. TYPICALALL.
22 PROVIDE NEW HANDS FREE ELECTRONIC FAUCET FOR EACH LAVATORY. PROVIDE NEW CHROME PLATED COPPERSUPPLY PIPING FROM VALVE STOP TO NEW MIXING VALVE AND TO FAUCET. LOCATE MIXING VALVE AND FAUCETCONTROLLER NEATLY BELOW LAVATORY, TIGHT TO WALL, OUT OF VIEW. LOOSE EQUIPMENT OR WIRING IS NOTACCEPTABLE.
23 PROVIDE NEW GREASE INTERCEPTOR BELOW KITCHEN SINK. INSTALL AS PER MANUFACTURERS GUIDELINES ANDENSURE CLEARANCE IS MAINTAINED FOR ACCESS TO COVER.
1 EXISTING WASHROOM FIXTURES AND TRIM TO REMAIN UNLESS OTHERWISE NOTED. DEMOLISH EXISTING LAVATORYFAUCET(S) AND PIPING BACK TO VALVE STOPS. LAVATORIES TO RECEIVE NEW FAUCET DURING RENOVATION.
2 DEMOLISH EXISTING DOMESTIC WATER AND SANITARY CONNECTIONS TO DISHWASHER. RETAIN CONNECTIONS FORFUTURE DISHWASHER INSTALLATION DURING RENOVATION.
3 DEMOLISH EXISTING EXHAUST SYSTEM SERVING GRILLE ENTIRELY.
4 REMOVE EXISTING RANGE HOOD AND TURN OVER TO OWNER.
5 DEMOLISH EXISTING SINK AND ASSOCIATED TRIM. DEMOLISH DOMESTIC WATER AND SANITARY PIPING TO WITHIN WALLCAVITY. PIPING SHALL BE EXTENDED TO SERVE NEW SINK. REFER TO RENOVATION PLAN.
6 DEMOLISH EXISTING SERVICE SINK AND ASSOCIATED TRIM. DEMOLISH SANITARY PIPING BACK TO WITHIN CRAWLSPACE.PIPING TO BE EXTENDED TO NEW WASHING MACHINE BOX. REFER TO RENOVATION PLAN. COORDINATE FLOOR PATCHINGWHERE EXISTING PIPING WAS REMOVED WITH GENERAL CONTRACTOR.
7 DEMOLISH EXISTING FLOOR MOUNTED GRILLE. DUCTWORK TO REMAIN FOR USE IN CONSTRUCTION. REFER TORENOVATION PLAN.
8 DEMOLISH EXISTING URINAL. DEMOLISH DOMESTIC WATER AND SANITARY PIPING SO THAT IT IS FLUSH WITH WALL.PROVIDE CHROME PLATED COVER PLATES.
9 REMOVE EXISTING CO MONITOR. MONITOR TO BE RELOCATED DURING CONSTRUCTION. REFER TO RENOVATION PLAN.
10 REMOVE EXISTING HUMIDISTAT. HUMIDISTAT TO BE RELOCATED DURING CONSTRUCTION. REFER TO RENOVATION PLAN.
11 REMOVE EXISTING FLOOR MOUNTED SUPPLY GRILLE TO ALLOW FOR INSTALLATION OF NEW FLOORING. REINSTALLGRILLE AFTER FLOORING IS COMPLETE. SEAL OFF DUCTWORK DURING CONSTRUCTION, ASSOCIATED FURNACE SHALLBE OFF WITH ALL DUCTWORK COVERED DURING DEMOLITION AND RENOVATION PHASE. TYPICAL ALL.
12 EXISTING EXHAUST FAN AND ASSOCIATED DUCTING TO REMAIN.
13 PROVIDE NEW RECESSED WASHING MACHINE BOX. EXTEND AND MODIFY EXISTING DOMESTIC WATER WITHIN WALLCAVITY TO SUIT NEW FIXTURE LOCATION. SANITARY PIPING SHALL DROP CONCEALED WITHIN WALL AND CONNECT INTOEXISTING WITHIN CRAWLSPACE.
14 ALUMINUM DRYER DUCT TO RUN TIGHT TO WALL AND TERMINATE AT ROOF THROUGH HOOD. HOOD SHALL BEPREMANUFACTURED PAINTED ALUMINUM ROOF HOOD, SUITABLE FOR INSTALLATION ON A PITCHED SHINGLED ROOF,COMPLETE WITH BACKDRAFT DAMPER AND BIRD SCREEN. COORDINATE HOOD INSTALLATION WITH GENERALCONTRACTOR. INSULATE DRYER DUCTING FOR ENTIRE LENGTH WITHIN ATTIC. ALLOW FOR FLEXIBLE DUCT CONNECTIONFROM DRYER DUCTING TO DRYER TERMINATION.
15 PROVIDE NEW TRIM FOR INTEGRAL KITCHEN SINK. EXTEND AND MODIFY EXISTING DOMESTIC WATER PIPING ASREQUIRED TO SUIT NEW LOCATION. PLUMBING PIPING SHALL RUN CONCEALED WITHIN WALL AND ONLY PENETRATEDIRECTLY BELOW NEW SINK WITH NEW CHROME PLATED VALVE STOPS WITH VALVE WHEEL. SANITARY PIPING SHALLDROP WITHIN MILLWORK AFTER CONNECTION TO GREASE INTERCEPTOR TO CRAWLSPACE AND CONNECT TO EXISTING.EXTEND AND MODIFY VENTING AS REQUIRED.
PLUMBING FIXTURE PIPE SIZE SCHEDULE
MARK DCW DHW SANITARY VENT
DW 1 0" 0 mm 1/2" 13 mm 1 1/2" 38 mm 1 1/4" 32 mm
LAV 1 1/2" 13 mm 1/2" 13 mm 1 1/4" 32 mm 1 1/4" 32 mm
SK 1 1/2" 13 mm 1/2" 13 mm 1 1/2" 38 mm 1 1/4" 32 mm
WM 1 1/2" 13 mm 1/2" 13 mm 2" 51 mm 1 1/2" 38 mm
* FOLLOW PIPE SIZES GIVEN IN ABOVE CHART UNLESS DRAWING SHOWS DIFFERENTLY.
400 - 136 Market AvenueWinnipeg, MB R3B 0P4
T 204 453 1080
M2.1 SCALE: 1/8" = 1'-0"1 MAIN FLOOR PLAN - MECHANICAL DEMOLITION
M2.1 SCALE: 1/8" = 1'-0"2 MAIN FLOOR PLAN - MECHANICAL RENOVATION
M2.1 SCALE: 1/8" = 1'-0"3 MEZZANINE FLOOR PLAN - MECHANICAL DEMOLITION
M2.1 SCALE: 1/8" = 1'-0"4 MEZZANINE FLOOR PLAN - MECHANICAL RENOVATION
DIFFUSER & GRILLES SCHEDULE
MARK
MODEL NOTES
S 1 20x4/LBP15A/L/66/500F/D 1,2
1. EH PRICE LINEAR BAR GRILLE, NARROW SPACING, STREAMLINED BLADES.2. SUITABLE FOR INSTALLATION IN CABINET TOE PLATE.
MECHANICAL FIXTURE BASIS OF DESIGN:
SK-1: (Trim Only) T&S Brass B-0133-B, chrome plated, wall mount, pre-rinse unit, 8" wall mount mixing faucet with lever handles, 1.15 gpm spray valve, 44" flexble stainless steel hose. Chrome plated drainage piping.GI-1: Zurn GT2700-10 , 10 GPM/20 lbs grease capacity, corrosion-resistant coated fabricated steel with no-hub connections, flow diffusing baffle, integral trap, vented inlet flow control device, gas/water tight cover, certified to ASME A112.14.3 (type C) and CSA B481.1 standards.LAV-1: (Faucet Only) Delta 591T1220 hands free, battery operated faucet c/w Delta R3070-MIXLF thermostatic mixing valve. Chrome plated, 4" on center mounting, surface mount control box, 5 Year limited warranty.WM-1: Oatey Quadtro, PVC enclosure, DCW, DHW, 2" drain knockout, backflow preventor, shutoff valves with water hammer arrestors on water connections.
KEY NOTES
Certificate of Authorization
Epp Siepman Engineering Inc.
No. 4035
0 20-06-25 Issued for Construction
FL01A-12b
A-14
E
A-16
d
LPN-102
1
ELECTRICAL SYMBOL NOTESTHE LIGHTING FIXTURE TYPE IS INDICATED BY UPPER CASE LETTERS AND NUMBERS.THE CIRCUIT DESIGNATION IS INDICATED BY LETTERS AND NUMBERS SEPARATED BY DASH. THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.EXAMPLE 1: LIGHTING FIXTURE TYPE "FL01" IS CONNECTED TO PANEL A, CIRCUIT 12 AND CONTROLLED BY SWITCH "b".
EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING.SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROWON ILLUMINATED FACE(S). THE SIGNAGE TYPE IS INDICATED BY UPPER CASE LETTERS AND NUMBERS PRECEDING THE "/". THE ASSOCIATED BATTERY BANK IS INDICATED BY UPPERCASE LETTERS AND NUMBERS FOLLOWING THE "/". THE AC CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: THE WALL MOUNTED EXIT LIGHT TYPE "EX1" WITH SINGLE FACE AND DIRECTIONAL ARROW IS CONNECTED TO BATTERY BANK "BU1" AND AC CIRCUIT 14 FROM PANEL A .
DEVICES. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER. EXAMPLE: SPLIT DUPLEX RECEPTACLE IS CONNECTED TO PANEL A, CIRCUIT 16 AND ONE RECEPTACLE OUTLET IS CONTROLLED BY A SWITCH.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE:SINGLE POLE SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OFRECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATIONCODES.KEYNOTE. SEE THE KEYED NOTES ON THAT SHEET FOR THE NOTE NUMBER INDICATED. (TYP) INDICATES THAT THE NOTE IS TYPICAL OF THE APPLICATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNITTYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
EX1/BU1
(TYP)
ELECTRICAL DRAWINGS
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPEREAC ABOVE COUNTER OR AIR
CONDITIONERACLG ABOVE CEILINGADO AUTOMATIC DOOR OPENERAF AMP FRAMEAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAFI ARC FAULT CIRCUIT
INTERRUPTERAHU AIR HANDLING UNITAL ALUMINUMALT ALTERNATEAMP AMPEREAMPL AMPLIFIERANNUN ANNUNCIATORAPPROX APPROXIMATELYARCH ARCHITECT, ARCHITECTURALAUX AUXILIARYAV AUDIO VISUALAWG AMERICAN WIRE GAUGE
BATT BATTERYBD BOARD BLDG BUILDINGBMS BUILDING MANAGEMENT SYSTEM
C CONDUITCAB CABINETCAT CATALOGCATV CABLE TELEVISIONCB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISIONCKT CIRCUITCKTP COOKTOPCLG CEILINGCOMB COMBINATIONCONST CONSTRUCTIONCONT CONTINUATION OR CONTINUOUSCONTR CONTRACTORCPR COPIERCTR CENTERCU COPPERC/W COMPLETE WITH
DET DETAILDISC DISCONNECTDIST DISTRIBUTIONDN DOWNDPR DAMPERDR DEDICATED CIRCUIT RECEPTACLEDS SAFETY DISCONNECT SWITCHDT DOUBLE THROWDW DISHWASHERDWG DRAWING
EC ELECTRICAL CONTRACTORELEC ELECTRIC, ELECTRICALELEV ELEVATOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEP ELECTRIC PNEUMATICEQUIP EQUIPMENTEWC ELECTRIC WATER COOLEREXIST EXISTINGEXH EXHAUST
FIXT FIXTUREFLR FLOORFR REFRIGERATORFZ FREEZER
GC GENERAL CONTRACTORGEN GENERATORGFI GROUND FAULT CIRCUIT
INTERRUPTERGND GROUNDGYP BD GYPSUM BOARD
HORIZ HORIZONTALHT HEIGHT
HRV HEAT RECOVERY VENTILATIONHTG HEATINGHTR HEATERHV HIGH VOLTAGEHVAC HEATING, VENTILATING AND
AIR CONDITIONINGHWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITYIG ISOLATED GROUNDINT INTERCOMIPLC INTELLIGENT PARKING LOT
CONTROLLERIR INFRAREDI/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLTKVA KILOVOLT-AMPEREKW KILOWATTKWH KILOWATT HOUR
LOC LOCATE OR LOCATIONLT LIGHTLTG LIGHTINGLV LOW VOLTAGE
MAX MAXIMUMMC MECHANICAL CONTRACTORMC MICROWAVEMCB MAIN CIRCUIT BREAKERMDP MAIN DISTRIBUTION PANELMEC MECHANICAL CONTRACTOR
MIC MICROPHONEMIN MINIMUMMISC MISCELLANEOUSMLO MAIN LUGS ONLYMW COORDINATED IN MILLWORK
NEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NIC NOT IN CONTRACTNTS NOT TO SCALE
PA PUBLIC ADDRESSPF POWER FACTORPH PHASEPNL PANELPP POWER POLEPR PRINTERPT POTENTIAL TRANSFORMERPVC POLYVINYL CHLORIDE (CONDUIT)PWR POWER
QP QUADPLEX RECEPTACLEQUAN QUANTITY
R RELOCATEDRCPT RECEPTACLEREQD REQUIREDRM ROOMRMC RIGID METAL CONDUIT
SC SURFACE CONDUITSEC SECONDARYSHT SHEETSIM SIMILARS/N SOLID NEUTRALSPEC SPECIFICATIONSPKR SPEAKERSP SPARES/S STOP/START PUSHBUTTONSSTA STATION
STD STANDARDSURF SURFACE MOUNTEDSW SWITCHSYS SYSTEMTEL TELEPHONETEL/DATA TELEPHONE/DATAT-STAT THERMOSTATTV TELEVISIONTYP TYPICAL
UC UNDER COUNTERUSB USB RECEPTACLE
V VOLTVSR VOLTAGE SENSING RELAYVA VOLT-AMPERESVDT VIDEO DISPLAY TERMINALVERT VERTICALVFD VARIABLE FREQUENCY DRIVEVOL VOLUME
W WATTW/ WITHWG WIRE GUARDW/O WITHOUTWS WASHER
XFMR TRANSFORMER
∠ ANGLE@ ATΔ DELTA' FEET" INCHES# NUMBERØ PHASECL CENTER LINEPL PLATE
ELECTRICAL ABBREVIATIONS LIST
GENERAL ELECTRICAL NOTES
A. THE GENERAL NOTES AS DESCRIBED HEREIN, APPLY TO ALL DRAWINGS IN THIS PACKAGE WHERE APPLICABLE.
B. PENETRATIONS IN WALLS OR SEPARATIONS, REQUIRING PROTECTED OPENINGS SHALL BE FIRESTOPPED WITH AN APPROVED MATERIAL. REFER TO ARCHITECTURAL SPECIFICATIONS FOR PRODUCT REQUIREMENTS.
C. EXPOSED WIRING SHALL NOT BE PERMITTED. WIRING SHALL BE RECESSED IN WALL, OR WHERE WALLS ARE NOT ACCESSIBLE DUE TO WALL CONSTRUCTION (CONCRETE BLOCK, CONCRETE, BRICK, ETC), PROVIDE CONDUIT AS REQUIRED TO CONCEAL SAME.
D. REFER TO ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND DETAILS, INCLUDING MILLWORK DETAILS AND SHOP DRAWINGS FOR COORDINATION OF ELECTRICAL DEVICE LOCATIONS, METHOD OF INSTALLATION & MOUNTING HEIGHTS. ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND DETAILS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON ELECTRICAL DRAWINGS.
E. EQUIPMENT SHUTDOWN AND THE INTERRUPTION OF ANY SERVICES SHALL BE COORDINATED IN ADVANCE WITH THE BUILDING END USER AND SHALL BE KEPT TO A MINIMUM.
F. UNLESS NOTED OTHERWISE, THE CIRCUITING INDICATED ON THE DRAWINGS IS REPRESENTATIONAL ONLY. CONFIRM CIRCUITING REQUIREMENTS ON SITE.
G. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING AND VOLTAGE DROP REQUIREMENTS, UNLESS INDICATED OTHERWISE.
H. MINIMUM CONDUIT SIZE SHALL BE 21mm (3/4") UNLESS NOTED OTHERWISE.
I. EMPTY CONDUIT SHALL BE C/W PULL WIRE AND PLASTIC BUSHINGS.
J. ALL CONDUCTORS OPERATING AT 50 VOLTS OR GREATER SHALL BE IN RACEWAY. ALL RACEWAY WITHIN THE STRUCTURE ABOVE THE FLOOR SLAB SHALL BE METAL.
K. ALL LOW VOLTAGE CABLES OR CONDUCTORS OPERATING AT LESS THAN 50 VOLTS SHALL BE IN METAL RACEWAY WHERE INSTALLED WITHIN WALLS OR INACCESSIBLE SPACES.
L. WHERE CONNECTED TO A 20A. BRANCH CIRCUIT SUPPLYING AN INDIVIDUAL RECEPTACLE (SIMPLEX OR DUPLEX), THE RECEPTACLE SHALL BE RATED AT 20A.
M. CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL ITEMS SHOWN ON THE DRAWINGS, INCLUDING THE FOLLOWING, UNLESS NOTED OTHERWISE:A. TELEPHONE OUTLETS, DATA OUTLETS, FIRE ALARM DEVICES SHALL CONSIST OF A BACK BOX WITH CONDUIT STUBBED ABOVE THE ACCESSIBLE CEILING, VERIFY SIZE OF BACK BOX REQUIRED WITH DEVICE TO BE
INSTALLED. LOCATE BACK BOXES 6" FROM ADJACENT POWER RECEPTACLE INTENDED FOR COMPUTER USE.N. REFER TO ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF DEMOLITION AND CONSTRUCTION. COORDINATE WITH GENERAL CONTRACTOR.
O. ALL LIFE-SAFETY SYSTEMS SHALL BE MAINTAINED AND OPERABLE AT ALL TIMES DURING CONSTRUCTION.
P. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEYNOTES IN THIS DRAWING PACKAGE, UNLESS NOTED OTHERWISE, THE TERM "DEMOLISH" SHALL INCLUDE THE COMPLETE REMOVAL OF THE EXISTING ITEM IDENTIFIED, C/W ASSOCIATED WIRING, CONDUIT AND JUNCTION BOXES BACK TO LAST REMAINING DEVICE OR SOURCE. CIRCUITS FREED UP FROM DEMOLISHED ELECTRICAL, SHALL BECOME SPARE. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.
Q. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEYNOTES IN THIS DRAWING PACKAGE, UNLESS NOTED OTHERWISE, THE TERM "REMOVE & REPLACE" SHALL INCLUDE THE COMPLETE REMOVAL & REPLACEMENT OF THE EXISTING ITEM IDENTIFIED IN ITS CURRENT LOCATION, WITH A NEW ITEM, UTILIZING THE EXISTING OUTLET BOX AND WIRING. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.
R. AS INDICATED IN THE GENERAL NOTES, DEMOLITION NOTES, AND KEY NOTES, UNLESS NOTED OTHERWISE, THE TERM "RELOCATE" SHALL INCLUDE THE COMPLETE RELOCATION OF THE EXISTING ITEM IDENTIFIED IN ITS CURRENT LOCATION ON THE DEMOLITION DRAWINGS, TO THE NEW LOCATION AS INDICATED ON THE RENOVATION DRAWINGS. INCLUDE ALL LABOUR AND MATERIALS TO REROUTE/EXTEND/REFEED THE EXISTING CIRCUITRY AS REQUIRED TO ACCOMMODATE THE RELOCATION. REFER TO THE RENOVATION DRAWING KEY NOTES FOR FURTHER REQUIREMENTS.
S. SITE CONFIRM ANY ELECTRICAL WITHIN AREAS OF RENOVATION REQUIRING RELOCATION TO ACCOMMODATE THE RENOVATION.
T. PROVIDE WIRE AND CONDUIT AS REQUIRED FOR CONTINUITY OF ANY FEEDERS OR BRANCH CIRCUITS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY ELECTRICAL EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.
U. PROVIDE CONDUIT AND/OR COMMUNICATIONS/DATA WIRING AS NECESSARY FOR CONTINUITY OF ANY COMMUNICATIONS/DATA SYSTEMS ORIGINATING OUTSIDE THE DEMOLITION AREA THAT SERVES ANY COMMUNICATIONS/DATA EQUIPMENT OR DEVICES TO REMAIN AFTER DEMOLITION. MODIFY OR REPLACE AS REQUIRED.
V. PROVIDE BLANK COVERPLATES OVER ALL EXISTING UNUSED OPENINGS.
W. DRAWING RECORDS OF THE EXISTING FLOOR PLANS HAVE BEEN COMPILED FROM INFORMATION SUBMITTED BY THE OWNER AND FROM SITE OBSERVATIONS AS NOTED BY THE CONSULTANT. THE ACCURACY OF THESE DRAWING RECORDS IS LIMITED TO THE EXTENT OF KNOWN CONSTRUCTION INFORMATION.
X. DEMOLISH ALL ELECTRICAL DEVICES IN WALLS, FLOORS OR CEILINGS TO BE DEMOLISHED. CONFIRM EXTENT OF DEMOLITION WITH ALL DISCIPLINE DRAWINGS. REROUTE/EXTEND/RE-FEED EXISTING ELECTRICAL AS REQUIRED TO MAINTAIN EXISTING SYSTEMS NOT INDICATED TO BE REMOVED.
Y. REMOVE ANY UNUSED OR ABANDONED WIRING AND CONDUIT WITHIN RENOVATION AREA, INCLUDING BRANCH CIRCUIT WIRING, VOICE/DATA CABLING AND SYSTEMS CABLING TO SOURCE OF SUPPLY.
Z. WHERE EXISTING WIRING AND CONDUIT ARE RE-USED, VERIFY EXISTING CONDITIONS. MODIFY AND SUPPLEMENT EXISTING FASTENING AND SUPPORT TO MEET CODE REQUIREMENTS.
AA. CONTRACTOR SHALL CONFIRM ALL EXISTING SYSTEMS TO BE IN WORKING CONDITION PRIOR TO CARRYING OUT MODIFICATIONS. WHERE EXISTING SYSTEMS ARE NOT OPERABLE, NOTIFY THE CONSULTANT PRIOR TO CARRYING OUT WORK.
BB. ALL NEW WIRING SHALL BE CONCEALED WHERE POSSIBLE. UTILIZE ACCESSIBLE CEILING SPACE TO RUN NEW WIRING AS REQUIRED AND FISH INTO WALLS/MILLWORK.
CC. WHERE EXISTING WALLS ARE TO BE OPENED FOR INSTALLATION OF NEW WIRING, COORDINATE WITH GENERAL CONTRACTOR ROUTING OF SAME. ARRANGE AND PAY FOR ALL CUTTING/REPAIR/PATCHING AS REQUIRED.
DD. RELOCATE EXISTING LIGHT SWITCHES AS REQUIRED TO ACCOMMODATE NEW DOOR CONFIGURATIONS.
EE. RISER DIAGRAMS ARE SCHEMATIC AND REPRESENTATIONAL ONLY. LOCATIONS AND QUANTITIES OF EQUIPMENT/DEVICES/LUMINAIRES SHALL BE COORDINATED WITH THE ELECTRICAL FLOOR PLANS.
FF. WHERE REMOTE HEADS ARE INDICATED, PROVIDE ZONE SENSING AT THE ASSOCIATED BATTERY BANK TO PICK UP LIGHTING CIRCUITS WITHIN THAT AREA AS REQUIRED.
GG. OUTLETS OR EQUIPMENT SHALL BE MOVED TO ANY POINT WITHIN A 10’ RADIUS WHEN THE CONSULTANT REQUESTS RELOCATION BEFORE THE WORK HAS BEEN SUBSTANTIALLY COMPLETED, WITHOUT ADDITIONAL COST.
HT AFF
AS NOTED
AS NOTED
12"*
47"
47"
18"
6"******
AS NOTED
SYMBOL
㐂
㐃
㐅
㐏
㐐
㐟
㐰
㐾
㑀
㑉
㑊
㑌
㑝
DESCRIPTION
LIGHTING
SURFACE LIGHT
SURFACE LIGHT
RECESSED LIGHT(TYPE DENOTED)
EMERGENCY LIGHT - REMOTE HEAD
EXIT LIGHT
LIGHTING CONTROL
SINGLE POLE SW
OCCUPANCY SENSOR(TYPE DENOTED)
RECEPTACLES
DUPLEX RECEPT
SPECIAL RECEPT(TYPE DENOTED)
RECEPT C/W NEMA 5-20R CONFIG
RECEPT MTD IN FLOOR(DUPLEX SHOWN)
RECEPT MTD ABOVE COUNTER(DUPLEX SHOWN)
EQUIPMENT
JUNCTION BOX
HT AFF
18"
48"***
18"
84"
18"
59"
47"
8"****
SYMBOL
㑮
㒱
㒲
㒳
㒴
㒵
㓩
㓮
㓰
㓴
㓹
㓽
㔁
㔄
㔣
DESCRIPTION
DIRECT POWER CONNECTION
GENERAL ELECTRIC
LIGHT SYMBOL INDICATES EXISTING
DASHED SYMBOL INDICATES REMOVED
KEYED NOTE(SEE SCHEDULE)
DEMOLITION NOTE(SEE SCHEDULE)
REVISION TAG
COMMUNICATION
COMMUNICATIONS OUTLET(TYPE DENOTED)
WALL INTERCOM OUTLET
TELEPHONE
MULTIPLE SERVICE FLOOR OUTLET (TYPE DENOTED)
SPEAKER
INTERCOM STATION
FIREFIGHTER OR EMERGENCY TELEPHONE
VOLUME CONTROL
FIRE ALARM
SMOKE DETECTOR(TYPE & CO DENOTED)
ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 1200mm MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 1200mm. DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEIVCE AT 1200mm. * DISTANCE ABOVE TOP OF DOOR
FRAME ** DISTANCE TO TOP OF EQUIPMENT OR DEVICE *** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT **** DISTANCE BELOW CEILING ***** DISTANCE TO BOTTOM OF DEVICE ****** DISTANCE ABOVE COUNTER"
ELECTRICAL SYMBOL LEGEND
FIRE PROTECTION REQUIREMENTS
A. PENETRATIONS IN WALLS REQUIRING PROTECTED OPENINGS MUST BE FIRESTOPPED WITH AN APPROVED MATERIAL.
1. CONDUITS MAY PENETRATE WALLS OR PARTITIONS, PROVIDED THEY ARE FIRE-STOPPED.
2. OPENINGS FOR STEEL ELECTRICAL BOXES NOT EXCEEDING 16 SQUARE INCHES ARE PERMITTED PROVIDED OPENINGS DO NOT AGGREGATE MORE THAN 100 SQUARE INCHES FOR ANY 100 SQUARE FEET OF WALL OR PARTITION.
3. OUTLET BOXES ON OPPOSITE SIDES OF WALLS OR PARTITIONS MUST BE SEPARATED BY A HORIZONTAL DISTANCE OF 24 INCHES.
B. LIGHT FIXTURES AND OTHER APPARATUS INSTALLED IN AN ACOUSTICAL CEILING GRID SHALL BE INDEPENDENTLY SUPPORTED.
C. RECESSED LIGHTING FIXTURES INSTALLED IN FIRE RATED CEILING ASSEMBLIES SHALL BE FIRE RATED FIXTURES BEARING THE ULC FIRE RATED LABEL. FIXTURES SHALL BE INSTALLED IN ACCORDANCE WITH THE ULC FIRE RESISTANCE DIRECTORY, AND SHALL INCLUDE A FIRE RATED ENCLOSURE INSTALLED OVER THE FIXTURE THAT MEETS THE REQUIREMENTS OF THE ULC FIRE RESISTANCE DIRECTORY.
SPECIFIC CODE NOTES
x architecture inc.120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7 204 318 2010
Seal
Engineer
Project
Sheet Title
NO. DATE REVISION / ISSUANCE
SheetProject No .
Date
Architect
19089A
BID OPPORTUNITY 280-2020
799 LILAC STREET
20-06-09
ELECTRICAL SYMBOLS ANDABBREVIATIONS
WINNIPEG FPS FIRE STATION #13INTERIOR RENOVATIONS
E0.1
SYMBOLS & ABBREVIATIONS E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
LIGHTING PLANS EL2.1 MAIN FLOOR - LIGHTING PLAN
POWER PLANS EP2.1 MAIN FLOOR - POWER PLAN
SCHEDULES E6.1 ELECTRICAL SCHEDULES
400 - 136 Market AvenueWinnipeg, MB R3B 0P4
T 204 453 1080
Certificate of Authorization
Epp Siepman Engineering Inc.
No. 4035
0 20-06-25 Issued for Construction
UP
SPK
GR DW ST
MW
FR
POP
FR
TD CMCO
PHPH
PHTT
FE
WF
ROOMG-10
CLEANING
ROOMG-21
DRYING
HOSE TOWERG-20
ROOMG-22
STORAGE
VESTIBULEG-01
DORMITORYG-18
ROOMG-17
LOCKER WASHROOMG-09
WOMEN'S
ROOMG-11
STATIONARYSHOWER
G-15
WASHROOMG-16
MEN'S
CORRIDORG-13
CORRIDORG-03
KITCHENG-08 LOUNGE
G-07
OFFICEG-06
CAPTAIN'S
OFFICEG-05
LIEUTENANT'S
ROOMG-23
CONTROLRECEPTION
G-02
ROOMG-14
MECHANICALVESTIBULE
G-19
ROOMG-12
APPARATUS
SPK
SPK
SPK
SPK
SPK
ROOMG-04
PHONE
BU#
OS
OS
OS33
OS
OS
OS
OS
OS
3333
33
33
SHOWER
DN
W/CM-02
STAIRHALLM-03
RESCUEM-04
WATER
DORMITORYM-01
HOSE TOWERG-20
SPK
SPKOS
OS
A. WHERE NEW TOGGLE SWITCHES, OR DIMMER CONTROLS ARE ADJACENT EACH OTHER, PROVIDE GANGED SWITCHING TO ACCOMODATE TOTAL NUMBER OF SWITCHES, UNLESS NOTED OTHERWISE.
B. ALL MOUNTING HEIGHTS FOR LUMINAIRES ARE TO THE BOTTOM OF THE LUMINAIRE UNLESS NOTED OTHERWISE.
C. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR OR INTERIOR LUMINAIRES.
D. UTILIZE SPARE/FREED UP CIRCUITS FROM DEMOLITION AS REQUIRED TO ACCOMMODATE THE ADDITIONAL CIRCUITING REQUIREMENTS IN THE RENOVATION.
E. WHERE REMOTE HEADS ARE INDICATED, PROVIDE ZONE SENSING AT THE ASSOCIATED BATTERY BANK TO PICK UP LIGHTING CIRCUITS WITHIN THAT AREA AS REQUIRED.
GENERAL NOTES
(TYP)3
SL1A-3
SL1A-3
SL1A-3
SL1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-3
RD1A-4
RD1A-4
RD1A-4
RD1A-4
RD1A-4 RD1
A-4
RD1A-2
RD1A-2
RD1A-5
RD1A-5
RD1A-7
RD1A-7
RD1A-7
RD1A-7
RD1A-7RD1
A-7
SL1A-1
SL1A-1
SL1A-1
SL1A-1
SL1A-1SL1
A-2
SL1A-2
SL1A-6
SL1A-6
SL1A-6
SL1A-6
SL1A-6
SL1A-6
SL1A-6
SL1A-7
SL1A-7
SL1A-7
SL1A-7
SL1A-7
SL1A-7
SL1A-7
SL1A-4
SL1A-4
SL1A-4
SL1A-4
SL1A-4
SL1A-2
SL1A-5
SL1A-5
SL1A-5
SL1A-4
SL1A-4
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
ELA26BU1
UC01A-3
UC01A-3
W2A-2
DT3
DT3 DT3
DT3
ELA26BU1
Pnl C Pnl B Pnl A Pnl D
BU1B-11
STORAGE ROOMG-22
DRYING ROOMG-21
HOSE TOWERG-20
APPARATUS ROOMG-12
VESTIBULEG-19
MECHANICAL ROOMG-14
STATIONARY ROOMG-11
WOMEN'S WASHROOMG-09
CLEANING ROOMG-10
MEN'S WASHROOMG-16
VESTIBULEG-01
CAPTAIN'S OFFICEG-06
LOUNGEG-07
DORMITORYG-18
LIEUTENANT'S OFFICEG-05
KITCHENG-08
LOCKER ROOMG-17 CORRIDOR
G-13
CORRIDORG-03
CONTROL ROOMG-23
1
22
RD1
RD1
UC01A-3
1
1
1
1
SL1A-8
SL1A-8
SL1A-8
SL1A-8
SL1A-8
SL1A-8 RD1
A-8RD1A-8
ELA26BU1
DT3DT3
HOSE TOWERG-20
DORMITORYM-01 W/C
M-02
STAIRHALLM-03
WATER RESCUEM-042
x architecture inc.120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7 204 318 2010
Seal
Engineer
Project
Sheet Title
NO. DATE REVISION / ISSUANCE
SheetProject No .
Date
Architect
19089A
BID OPPORTUNITY 280-2020
799 LILAC STREET
20-06-09
MAIN FLOOR - LIGHTING PLAN
WINNIPEG FPS FIRE STATION #13INTERIOR RENOVATIONS
EL2.1
400 - 136 Market AvenueWinnipeg, MB R3B 0P4
T 204 453 1080
1 EXISTING LIGHT FIXTURES IN THIS AREA TO REMAIN.2 EXISTING EXIT SIGNS TO BE CONNECTED TO NEW BATTERY BANK BU1.3 DEMOLISH ALL WALL SCONCES.
EL2.1 SCALE: 1/8" = 1'-0"1 MAIN FLOOR PLAN - LIGHTING DEMOLITION
EL2.1 SCALE: 1/8" = 1'-0"2 MAIN FLOOR PLAN - LIGHTING
EL2.1 SCALE: 1/8" = 1'-0"3 MEZZANINE FLOOR PLAN - LIGHTING DEMOLITION
EL2.1 SCALE: 1/8" = 1'-0"4 MEZZANINE FLOOR PLAN - LIGHTING
Certificate of Authorization
Epp Siepman Engineering Inc.
No. 4035
0 20-06-25 Issued for Construction
KEY NOTES
UP
SPK
GR DW ST
MW
FR
POP
FR
TD CMCO
PHPH
PHTT
FE
WF
ROOMG-10
CLEANING
ROOMG-21
DRYING
HOSE TOWERG-20
ROOMG-22
STORAGE
VESTIBULEG-01
DORMITORYG-18
ROOMG-17
LOCKER WASHROOMG-09
WOMEN'S
ROOMG-11
STATIONARYSHOWER
G-15
WASHROOMG-16
MEN'S
CORRIDORG-13
CORRIDORG-03
KITCHENG-08 LOUNGE
G-07
OFFICEG-06
CAPTAIN'S
OFFICEG-05
LIEUTENANT'S
ROOMG-23
CONTROLRECEPTION
G-02
ROOMG-14
MECHANICALVESTIBULE
G-19
ROOMG-12
APPARATUS
SPK
SPK
SPK
SPK
SPK
ROOMG-04
PHONE
14-50R14-50R
2D
2D
DW
V
J
J
J
V2D 2D
J2D
S
S
S
S
V
2D J
2D 2D 2D
SCOCO
S V
CO
S
J
UP
SPK
DW FR FRMIC
2D
2D
WS
14-30R
V
V2D 2D
J2D
S
S
S
SV 2D J
2D 2D 2D
SCOCO
S V
CO
2D
SHOWER
DN
W/CM-02
STAIRHALLM-03
RESCUEM-04
WATER
DORMITORYM-01
HOSE TOWERG-20
SPK
SPK
CO
S
UPFE
SHOWER
DN
S
COCO
A. PROVIDE NEW TYPEWRITTEN PANEL DIRECTORIES TO ACCOMMODATE UPDATED CIRCUITING. NEW BREAKERS IN DISTRIBUTION PANELS SHALL BE LABELLED USING LAMACOIDS.
B. WHERE BRANCH CIRCUIT BREAKERS ARE REMOVED, PROVIDE FILLER PLATES FOR BREAKER SPACES.
C. CIRCUIT BREAKERS SHALL MATCH EXISTING. CONFIRM SHORT CIRCUIT RATING AND TYPE ON SITE, PRIOR TO FINALIZING PRICING.
D. UTILIZE SPARE/FREED UP CIRCUITS FROM DEMOLITION AS REQUIRED TO ACCOMMODATE THE ADDITIONAL CIRCUITING REQUIREMENTS IN THE RENOVATION.
E. FOR ALL STRUCTURED WIRING OUTLETS, PROVIDE NUMER OF JACKS AS INDICATED AND THE CORRESPONDING NUMBER OF CABLES IN CONDUIT STUB INTO CEILING SPACE, THEN HOME RUN TO THE DATA RACK. TERMINATE CABLES IN PATCH PANELS AND IN JACKS AT OUTLET LOCATIONS.
GENERAL NOTES
3
7
7
(TYP)8
Pnl DPnl APnl BPnl C
R
Pnl APnl BPnl C Pnl D
1111
2
B-1
B-13
ES-1B-3,5
B-2
B-4 B-6B-7 B-8 B-9
B-10,12
B-14 4R
B-16B-16
STORAGE ROOMG-22
DRYING ROOMG-21
HOSE TOWERG-20
APPARATUS ROOMG-12
VESTIBULEG-19
MECHANICAL ROOMG-14
STATIONARY ROOMG-11
WOMEN'S WASHROOMG-09
CLEANING ROOMG-10
MEN'S WASHROOMG-16
VESTIBULEG-01
CAPTAIN'S OFFICEG-06
LOUNGEG-07
DORMITORYG-18
LIEUTENANT'S OFFICEG-05
KITCHENG-08
LOCKER ROOMG-17
CORRIDORG-13
CORRIDORG-03
CONTROL ROOMG-23
5
B-15
B-15
B-15B-15
B-15
B-15
6
B-17
QPB-16
9
B-16
B-18
B-18
B-18
B-17
10
HOSE TOWERG-20
DORMITORYM-01
W/CM-02
STAIRHALLM-03
WATER RESCUEM-04
x architecture inc.120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7 204 318 2010
Seal
Engineer
Project
Sheet Title
NO. DATE REVISION / ISSUANCE
SheetProject No .
Date
Architect
19089A
BID OPPORTUNITY 280-2020
799 LILAC STREET
20-06-09
MAIN FLOOR - POWER PLAN
WINNIPEG FPS FIRE STATION #13INTERIOR RENOVATIONS
EP2.1
400 - 136 Market AvenueWinnipeg, MB R3B 0P4
T 204 453 1080
1 EXISTING DEVICE LOCATED BELOW DESK.2 RELOCATE EXISTING VOLUME CONTROL FROM DEMOLISHED WALL TO THIS POSITION.3 EXISTING RECEPTACLES AND JUNCTION BOXES AT 16" AFFL IN THIS SPACE TO BE DEMOLISHED.
NEW RECEPTACLES TO BE PROVIDED AT 18" AFFL4 RELOCATE EXISTING CO ALARM FROM DEMOLISHED WALL TO THIS POSITION.5 HOME RUN DATA CABLES TO EXISTING DATA RACK LOCATED IN MECHANICAL ROOM G-14.6 EXISTING DATA CABINET.7 EXISTING WALL TELEPHONE TO BE DEMOLISHED.8 REMOVE AND REINSTALL FLOOR OUTLETS AS REQUIRED TO ACCOMODATE RENOVATION
WORKS.9 PROVIDE NEW QUAD RECEPTACLE LOCATED BELOW DESK.10 PROVIDE WIREMOLD FOR HDMI CABLES FROM TV CABLE BOX TO WALL MOUNTED TV.
COORDINATE LENGTH WITH ARCHITECTURAL ELEVATIONS.
EP2.1 SCALE: 1/8" = 1'-0"1 MAIN FLOOR PLAN - POWER DEMOLITION
EP2.1 SCALE: 1/8" = 1'-0"2 MAIN FLOOR PLAN - POWER & SYSTEMS
EP2.1 SCALE: 1/8" = 1'-0"3 MEZZANINE FLOOR PLAN - POWER DEMOLITION
EP2.1 SCALE: 1/8" = 1'-0"4 MEZZANINE FLOOR PLAN - POWER & SYSTEMS
Certificate of Authorization
Epp Siepman Engineering Inc.
No. 4035
0 20-06-25 Issued for Construction
KEY NOTES
LIGHTING FIXTURE SCHEDULE
A. EMERGENCY LIGHTING MODEL NUMBERS ARE BASED ON LUMACELL PRODUCT LINE. EMERGILITE, BEGHELLI, AND AIMLITE MEETING PERFORMANCE SPECIFICATIONS ARE APPROVED SUBSTITUTIONS.B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.
GENERAL NOTES:
EMERGENCY BATTERY BANK SCHEDULE
A. EMERGENCY LIGHTING MODEL NUMBERS ARE BASED ON LUMACELL PRODUCT LINE. EMERGILITE, BEGHELLIE, AND AIMLITE MEETING PERFORMANCE SPECIFICATIONS ARE APPROVED EQUAL.B. WHERE "APPROVED EQUAL" IS LISTED IN THE MANUFACTURER COLUMN, FIXTURES MUST BE SUBMITTED AS A SUBSTITUTION FOR APPROVAL PRIOR TO BID SUBMISSION.C. BATTERY BANK SHALL BE C/W CORD AND 5-15P PLUG. PROVIDE 5-15R/5-20R RECEPTACLE TO MATCH CIRCUIT RATING.
GENERAL NOTES:
LIGHTING CONTROL DEVICE SCHEDULE
SCHEDULE NOTES:
1. PROVIDE 24 VDC POWER PACK WITH INPUT TO MATCH LIGHTING FIXTURE VOLTAGE, SWITCHING CONTACT RATED FOR 20A. BALLAST.
x architecture inc.120 Fort Street, Suite 103 Winnipeg, Manitoba R3C 1C7 204 318 2010
Seal
Engineer
Project
Sheet Title
NO. DATE REVISION / ISSUANCE
SheetProject No .
Date
Architect
19089A
BID OPPORTUNITY 280-2020
799 LILAC STREET
20-06-09
ELECTRICAL SCHEDULES
WINNIPEG FPS FIRE STATION #13INTERIOR RENOVATIONS
E6.1
TYPE Description LENS-LOUVER MOUNTING LAMPBALLAST /
DRIVER VOLT WATTMFR
CATALOG SERIESELA26 DOUBLE HEAD EMERGENCY LIGHTING
DECORATIVE REMOTE. DIE CASTALUMINUM CONSTRUCTION. WHITE
--- WALL 2 x 6W LED50000HR
540 LUMENS
--- 12 V 12 W LUMACELL DR
RD1 114mm (6") DIAMETER DIMMABLE LEDDOWNLIGHT WITH REMOTE PHOSHORLENS ASSEMBLY, 50° CUTOFF.
PHOSPHORLENS
ASSEMBLY ANDCOMFORT
CLEAR DIFFUSEREFLECTOR
RECESSED LED 2000lm3500K
60000 HR
0-10VDIMMING
LED DRIVER
120 V 24 W LIGHTOLIER LDN6
SL1 305mm x 1220mm (1 Foot X 4 Foot) LED K12 ACRYLIC1/8in THICK
SURFACEMOUNTEDON GWB
LED4000lm80+CRI3500K
60000HR
0-10VDIMMING
LED DRIVER
120 V 40 W LITHONIA BTL
UC01 UNDERCABINET TAPE LIGHT MOUNTED INALUMINUM EXTRUSION
FROSTED SURFACE LED 0-10VDC10%
DIMMABLELED DRIVER
120 V MAGICLITE LP-5060
W2 LINEAR WALL MOUNTED VANITY FROSTED SURFACEWALL
LED 1500lm3500K
60000 HR
0-10VDIMMING
LED DRIVER
120 V 56 W FINELITE HP-2
ID DESCRIPTIONBATTERY
SIZE HEADSNUMBER
OF HEADSWATTS
PER HEAD VSRAC
VOLTDC
VOLTSUPPLIED
FROMTOTAL
DC LOADTOTAL DC LOAD WITH
SAFETY FACTORMAX WATT
30 MIN MFR MODELBU1 BATTERY BANK, STEEL CABINET COMPLETE
WITH AC/DC TERMINAL BLOCKS.360 W YES 2 6 YES 120 V 12 V B 157 W 197 W 360 W LUMACELL RG12S360
400 - 136 Market AvenueWinnipeg, MB R3B 0P4
T 204 453 1080
NOTES: EXISTING 120/240V 1PH 3W 42CCT PANEL.
EST. DEMAND CURRENT: 10 ACONNECTED CURRENT: 10 A
ESTIMATED DEMAND: 2427 VACONNECTED LOAD: 2427 VA
LITES 2427 VA 100.00% 2427 VALOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 7 A 15 ATOTAL LOAD: 1 kVA 2 kVA
A-41 A-42A-39 A-40A-37 A-38A-35 A-36A-33 A-34A-31 A-32A-29 A-30A-27 A-28A-25 A-26A-23 A-24A-21 A-22A-19 A-20A-17 A-18A-15 A-16A-13 A-14A-11 A-12A-9 A-10
LITES DORMITORY G-18 15 A 1 A-7 0.4 0.3 A-8 1 15 A LITESLITES CORRIDOR G-13 15 A 1 A-5 0.2 0.3 A-6 1 15 A LITES LOCKER ROOM G-17LITES KITCHEN G-08 15 A 1 A-3 0.6 0.4 A-4 1 15 A LITES LIEUTENANT'S OFFICE G-05LITES CONTROL ROOM G-23 15 A 1 A-1 0.2 0.2 A-2 1 15 A LITES CORRIDOR G-03
LOAD DESCRIPTION BKR P CCT# A B CCT# P BKR LOAD DESCRIPTION
BUS AMPS: 200 AMPSMAIN DEVICE: 150 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICALLOCATION: MECHANICAL ROOM G-14 VOLTAGE: 120/240 Single V. 1 ...
PANELBOARD: A
NOTES: EXISTING 120/240V 1PH 3W 42CCT PANEL.
EST. DEMAND CURRENT: 17 ACONNECTED CURRENT: 65 A
SPEC 0 VA 0.00% 0 VA ESTIMATED DEMAND: 4132 VALITES 145 VA 100.00% 145 VA CONNECTED LOAD: 15499 VARCPT 15360 VA 26.00% 3994 VALOAD CLASSIFICATION CONNECTED DEMAND ESTIMATED PANEL TOTALS
TOTAL AMPS: 69 A 60 ATOTAL LOAD: 8 kVA 7 kVA
B-41 B-42B-39 B-40B-37 B-38B-35 B-36B-33 B-34B-31 B-32B-29 B-30B-27 B-28B-25 B-26B-23 B-24B-21 B-22B-19 B-20
RCPT DORMITORY G-18 15 A 1 B-17 0.2 0.4 B-18 1 15 A RCPT KITCHEN G-08RCPT DORMITORY G-18 15 A 1 B-15 0.7 0.5 B-16 1 15 A RCPT CONTROL ROOM G-23RCPT KITCHEN G-08 20 A 1 B-13 0.6 1.2 B-14 1 15 A RCPT CLEANING ROOM G-10BU1 15 A 1 B-11 0.1 2.9 B-12RCPT KITCHEN G-08 15 A 1 B-9 1.2 2.9 B-10
2 30 A DRYER RECEPTACLE
RCPT KITCHEN G-08 15 A 1 B-7 1.2 1.2 B-8 1 15 A RCPT KITCHEN G-08B-5 0.0 0.6 B-6 1 20 A RCPT KITCHEN G-08
ELECTRIC STOVE ES-1 90 A 2B-3 0.0 0.6 B-4 1 20 A RCPT KITCHEN G-08
RCPT KITCHEN G-08 15 A 1 B-1 1.2 0.0 B-2 1 15 A SPEC MEN'S WASHROOM G-16LOAD DESCRIPTION BKR P CCT# A B CCT# P BKR LOAD DESCRIPTION
BUS AMPS: 200 AMPSMAIN DEVICE: 200 A MAIN CB SPECIAL:
MOUNTING: SURFACE NEMA 1 A.I.C. RATING: 10,000 AMPS SYMMETRICALLOCATION: MECHANICAL ROOM G-14 VOLTAGE: 120/240 Single V. 1 ...
PANELBOARD: B
TYPE DESCRIPTIONMANUFACTURE
R CATALOG No. WATTS VOLTS NOTESDT3 DUAL TECHNOLOGY PASSIVE INFRARED AND
ULTRASONIC OCCUPANCY SENSOR, 360°COVERAGE, MINIMUM 1000 SQUARE FEET.
nLIGHT NCM PDT 10RJB
0 W 0 V 1
OS COMBINATION ULTRASONIC OCCUPANCYSENSOR/SWITCH, WALL MOUNTED, LOWVOLTAGE, WITH ON-OFF PUSHBUTTON ANDDIMMING.
nLIGHT nWSX PDTLV DX WH
0 W 0 V 1
Certificate of Authorization
Epp Siepman Engineering Inc.
No. 4035
0 20-06-25 Issued for Construction