Upload
juzaili-js
View
218
Download
0
Embed Size (px)
Citation preview
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 1/54
1
Application of Harmonic Filters Application of Harmonic Filters
JuneJune 20082008
Prepared by B. J. Park
PQ TECH INC.
2
IndexIndex
Design Considerations
Understanding Capacitors
(Construction, Process, Capacitor Types, Tests)
Filter Reactors
What is K factor?
Surge Arrestors
Switching Capacitors
Grounding versus Ungrounding
Banks Protections (Various Protection, Setting Philosophy)
Harmonic Filter Types
Bank Design
Steel Making Plant Harmonics
Case Study for Electrochemical Plant
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 2/54
2
3
Harmonic Filter Design ConsiderationsHarmonic Filter Design Considerations
Various Nonlinear Loads
Harmonic Voltage and or Current can cause damage to equipment
Voltage Current Distortion Guide Line
Harmonic Filter Locations
300
400 75
125
150 150
23kV
380V Bus 1
380V Bus 2
4
Key Filter Design ConsiderationsKey Filter Design Considerations
Reactive Power Requirements
Harmonic Limitations
Background Harmonics
Harmonic Filter Conditions (Ratings)
System Transient, abnormal conditions
Contingency Filter Conditions
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 3/54
3
5
Maximum and Minimum SizeMaximum and Minimum Size
The maximum bank size
a) Change in system voltage upon capacitor bank switching.
b) Switchgear continuous current limitations.
dV is limited in the range of 2%~3%, determined by load flow
The minimum bank sizea) Capacitor bank unbalance considerations
b) Fuse coordination
6
Construction of Capacitor ElementConstruction of Capacitor Element
ALUMINIUM FOIL
5um Edge Fold
Hazed Polypropylene Film
11- 15um
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 4/54
4
7
Air Shower Booth to Access W/R Air Shower Booth to Access W/R
8
RollRoll WindingWinding ProcessProcess
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 5/54
5
9
Extended Foil SolderingExtended Foil Soldering
10
Container TIG WeldingContainer TIG Welding
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 6/54
6
11
ImpregnationImpregnation FacilityFacility
12
ImpregnaImpregnanntt ,, JarylecJarylec C101C101
GoodGood performanceperformance in hin high temperatureigh temperatureLowLow dissipation factor dissipation factor
ExcellentExcellent absorbingabsorbing PDPD--characteristicscharacteristics
The fluid is non chlorineThe fluid is non chlorine biogradablebiogradable and contains no PCBsand contains no PCBs
CH2
CH3
CH2 CH2
CH3
Benzyltoluene 75% Dibenzyltoluene 25%
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 7/54
7
13
Impregnation, Under VacuumImpregnation, Under Vacuum 0.01 torrs0.01 torrs
Impregnant
Filling
Sealing
Drying
0
20
40
60
80
100
0 1 2 3 4
DAYS
T E M P o C
5
14
RoutinRoutinee Test,Test, IEC 60871IEC 60871
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 8/54
8
15
PD Test in Shield Room @ 2.15*UnPD Test in Shield Room @ 2.15*Un
16
Routine Test,Routine Test, IEC 60871IEC 60871
Each capacitor unit undergoes the foll owing:
Leakage test at 60 C for 24 hours
Partial Discharge Test at 2.15 Un
HV tests:
AC terminal t o terminal at 18kV for 10 sec
AC terminal t o case at 38kV for 10 secCapacitance and Dielectric loss angle at Un
Short circuit discharge test at 1.7Un
Internal discharge resistor test
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 9/54
9
17
All -fil m -Low dissipation, hazed, high
energy density
Folded foil – Good perf orm ance to the PD
and transients
Impregnation - Dribble penetration, extra
vacuum levels, long term filling.
Container -1.5mm 430 grade stainless steel,
can be supplied unpainted. TIG welding
Power Capacitor UnitsPower Capacitor Units
18
Harmonic FilterHarmonic Filter Capacitor Capacitor ss
D
Film
FoilExtended Foil
D
UE0
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 10/54
10
19
Between voltage gradient and failure rate, and assumed life can be described as
Assumed LifeVoltage Gradient
Failure rate
Where:L =Expected life
N = Number of elements
λ = Failure rate (0.01%/year)
Eo= Designed Voltage GradientE = Actual Voltage Gradient
α = Constant for Voltage Gradient (α = 6 ~17)
Capacitor Life ExpectancyCapacitor Life Expectancy
( )
-α
E o
E λ N L ⎥
⎦
⎤⎢⎣
⎡=
20
Many connection, fuses, more hands, degrade insulation, cost
Possible to continuing service after few fuses brownUnit rating around 10kV
Internally Fused Capacitor UnitInternally Fused Capacitor Unit
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 11/54
11
21
Unit rating 15~25kV
Externally Fused Capacitor UnitExternally Fused Capacitor Unit
22
All strings must be separated / simple process / good joint foil electrodes at dielectric fault
FuselessFuseless Capacitor UnitCapacitor Unit
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 12/54
12
23
Yes, but the is co ncern
the oil contamination
Europe
Less
Lower
No(hazard)
Smaller
6P12S
Higher
Impossible
Fuseless
Yes, but the is con cern
the oil contamination
Europe / Asia
No
Amer ica / A sia
Higher
Higher
yes
Higher
6P 12S
Lower
Easy to find
Externally
Fused
Less
Lower
No(hazard)
Smaller
12S 6P
Higher
Impossible
Internally Fused
Connection (example)
Replace cost
Visual check for faulty unit
Protection for terminal to c ase
fault
Popular using Area
Cost of protection
Sensitivity of unbalance
Continuing service of uni t at a
roll faulty
Delta C by faulty roll
Features & Types
Types of Capacitor UnitTypes of Capacitor Unit
24
Filter Capacitor Specification ExampleFilter Capacitor Specification Example
Rated voltage 9008 [V]
Rated curr ent 87.48 [A]
Rated output 788 [kVAr]
Type All film
Rated capacity 788 [kVAr]
Rated capacitan ce 30.91 [uF]
Rated frequency 50 [Hz]
Insulation level 30 [kVrms], 95 [kV BIL]
Number of phase Single Phase
Number of bushing 2
Dielectric Synthetic polypropylene filmElectrodes Fold/Laser cut aluminum foil
Impregnate with Non-PCB dielectric fluid
Protection method Internally fused
Painting color Munsell No. 5Y7 / 1
Painting method Vapor cure double layers Epoxy coated
Discharge device Built in resistors
Discharge time / unit <50V within 5 [min]
Standards IEC60871-1, 60871-2, 60871-4
Case material Stainless Steel 1.6 [mm]
Fixing hanger bracket 2 EA for both side
Continues allowable overvoltage 110 [%] Un
Maximum permissible kVAr 135 [%]
Tolerance of capacitance -0 ~ +15 [%] at 25 [
]
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 13/54
13
25
Probability of 2Probability of 2ndnd failure for Each Typesfailure for Each Types
IEEE summer meeting 1997IEEE summer meeting 1997
[1]>[2] 2nd Failure in the Same group
[1]>[11] 2nd Failure in the another group
26
24
26
6.40
6.20
λ
for [1]>[11]
“Random”
% / year
0.0150.4Fuseless
(Internal String)
132kV, 36 MVAr
Y-Y connection5
0.0452.6Fuseless
(conventional)
132kV, 36 MVAr
Y-Y connection4
0.0100.26Internally fused132kV, 36 MVAr
Y-Y connection3
0.0220.57Externally fused33 kV, 9 MVAr
Y-Y connection2
0.0100.26Internally fused33 kV, 9 MVAr
Y-Y connection1
Δ
c/c
%/ Year
λ
for [1]>[2]
“ Avalanche”
% / year
Capacitor TypeBankCase
26
Filter ReactorsFilter Reactors
Magnet wire is copper wire which has been coated (or enamelled) with a very thin layer of insulating material
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 14/54
14
27
Filter ReactorsFilter Reactors
28
10.1151.596
0.0160.0000.00525
0.0340.0000.00823
0.0160.0000.00621
0.0440.0000.01119
0.0940.0000.01817
0.0810.0000.01915
0.1060.0010.02513
0.3400.0030.05311
0.1570.0020.0449
0.7900.0160.1277
3.5530.1420.3775
3.8880.4320.6573
1.0001.0001.0001
I2 x h2I2Current (Pu)Harmonic
Ex)K factor = 6.34 PEC-R= 8% (Eddy current loss factor) I rms = 0.85 (pu)
2
2
h
h
I hK
I = ∑
∑
2
1
1
ECR
rms ECR
P I
KP
−+=
+´
What is K factor?What is K factor?
IEEE C57.110IEEE C57.110--19861986
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 15/54
15
29
Typical Air Core Dry Type Reactor Typical Air Core Dry Type Reactor
30
Magnetic ClearanceMagnetic Clearance
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 16/54
16
31
Filter Reactor Specification ExampleFilter Reactor Specification Example
Type Air Core, 6 [%]
System Voltage 132 [kV]
Rated Frequency 50 [Hz]
Rated Induc tance 59.0 [mH]
Rated Current 262.43 [A]
Insulation Level 275 / 650 [kV]
Number of Phase Single Phase
Temperature Rise 60.5 [
]
Color Munsell No. 5Y7 / 1
Standards IEC 289
Frame and Structure
Reactors shall have mechanical and electrical strength and it s hall be painted with Munsell No. 5Y7 / 1.
Installation Outdoor
Cooling Air-cooled with natural convection
Impedance calculation of the bank
Zf for Fundamental Frequency, Xcf = 308.94 Ohm, Xlf = 18.54 Ohm, Zf = 290.4 Ohm
Z5 for 5th harmo nic Fr equency, Xc5 = 61.79 Ohm, Xl5 = 92.7 Ohm, Z5 = 30.91 Ohm
Tests
The tests are carried out by manufactur er accordance with standard IEC 289.
The reports are attached herein.Routine tests
Measurement of windi ng resistance
Measurement of impedance at continuo us current
Separate source voltage with stand test
Induced over voltage withstand test
Type tests
Temperature ri se test
Lightning impulse test
Marking IEC 289.16
32
Surge ArrestorsSurge Arrestors
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 17/54
17
33
To prevent capacitor failures at a breaker restrike or failure.
To limit the risk of repeated breaker restrikes.
To prolong the service life of the capacitors by limiting high overvoltages.
To serve as an ”insurance” against unforeseen resonance conditions which otherwise
would lead to capacitor failures.
For overall limitation of transients related to capacitor bank switching which can be
transferred further in the system and cause disturbances in sensitive equipment.
For upgrading of capacitors by preventing high overvoltages and/or for increasing theservice voltage.
To serve as protection against lightning for capacitor banks connected to lines.
Using Surge ArrestorsUsing Surge Arrestors
34
Arrestor Positioning Arrestor Positioning
Continuous operating voltage
Rated voltage
Energy capability
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 18/54
18
35
Arrestor Positioning Arrestor Positioning
ExampleSystem voltage: 36 kV
Fault clearing time:10 s or lessSystem grounding: Ungrounded
Capacitor bank connection: Ungrounded wyeRated 3-phase power: 18 MVAr
Desired protective level : 2,4 p.u.
Summary of required arrester data for connection Phase-ground:
Rated voltage: 33 kV or moreProtective level at 3kA: 64,7 kV or less (switching surge)
Energy capability for capacitor discharges:2,8 kJ per kV rated voltage or more
Summary of required arrester data for connection Phase-neutral:Rated voltage: 33 kV or moreProtective level at 3kA: 69 kV or less (switching surge)
Energy capability for capacitor discharges:3,2 kJ per kV rated voltage or more
36
High duty-cycle
Most circuit breakers and protective devices operate a few times in their
entire life span.
Switch for capacitor bank gets to operate every day, sometimes several
operations per day.
Voltage spikeWhen capacito r swi tches do operate, they generate undesirable voltage
surges, which if unmitigated, can cause problems in Power Quality to the
users.
Re-strike
Common concern for older switching technologies.
Switching Capacitor BanksSwitching Capacitor Banks
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 19/54
19
37
Continuous current
ungrounded neutral banks – 1.25 times the nominal current
grounded neutral banks – 1.35 times the nominal currents
Inrush current dur ing energization
Nominal system voltage
Transient recovery voltage during de-energization
Switches must be capable of withstanding inrush current
Ipk = Peak of Inrush cur rent
Isc = available three phase fault current
I1 = capacitor bank current
141.1 I I I sc pk ⋅=
The Key Considerations for Switchgear The Key Considerations for Switchgear
38
Inrush current during back to back switching
Fs = system frequency in Hz
Ft = frequency of transient in kHz
Leq = total inductance between two banks in micro -henries
I1, I2 = being sw itched, already energized banks cur rents in A
VLL = line to line vol tage in kV
)(
)(1747
21
21
I I L
I I V I
eq
LL pk ⋅
⋅⋅=
)(
))()((5.9
21
21
I I L
I I V f f
eq
LLst ⋅
+⋅=
The Key Considerations for Switchgear The Key Considerations for Switchgear
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 20/54
20
39
Several hundred meters between overhead capacitor banks is usually an adequate
separation distance to limit the inrush current to an acceptable level, but configurationswhere the banks are very close together may require inrush current limiting reactors.
When switching is done at nominal system voltage, the switch recovery voltage reaches 2.0
per unit for a grounded-wye-connected bank and 2.5 per unit for an ungrounded-wyebank.
The Key Considerations for Switchgear The Key Considerations for Switchgear
Ec = Peak System Voltage
To = Beginning of Switching Opening
T1 = First Current Zero
T2 = 1/2 Cycle After First Current Zero
T3 = Switch Completely Opened
Switching Recovery Voltage
40
The 6% inductor to the capacitive reactance has been widely usedThe 6% inductor to the capacitive reactance has been widely used ,,
to reduce the inrush current less than 5 times the nominal curr eto reduce the inrush current less than 5 times the nominal curr entsnts
LC o
1=ω
LC Z Z =× 06.0
ω ω
1,11 =Ω== C C
Z C
)(sin t Z
V i o
o
o ω =
ω
ω ω
ω ×=
×
= 1.406.01
1o
ω
ω
06.0,06.0 =Ω== L L Z L
The Key Considerations for Switchgear The Key Considerations for Switchgear
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 21/54
21
41
ITI CurveITI Curve
42
Synchronous Type Circuit Breaker Synchronous Type Circuit Breaker
P1 : Graphs
0.1825 0.1850 0.1875 0.1900 0.1925 0.1950 0.1975 0.2000 0.2025 0.2050
-200
-150
-100
-50
0
50
100
150
200
y
Ap
A
B
C
Switching Sequence_ Ungrounded Capacitor Banks
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 22/54
22
43
Synchronous Type Circuit Breaker Synchronous Type Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
Without Series Reactor Without Series Reactor
44
Synchronous Type Circuit Breaker Synchronous Type Circuit Breaker
With 6% Series Reactor With 6% Series Reactor
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 23/54
23
45
Conventional Circuit Breaker Conventional Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
kA
kV
Without Series Reactor Without Series Reactor
1.6 Per unit peak
65 kA peak
46
Conventional Circuit Breaker Conventional Circuit Breaker
Case 19
0.160 0.180 0.200 0.220 0.240 0.260 0.280 0.300
-8.0
-6.0
-4.0
-2.0
0.0
2.0
4.0
6.0
8.0
y
step1-Ia step1-Ib step1-Ic
-300
-200
-100
0
100
200
300
y
Ap
With 6% Series Reactor With 6% Series Reactor
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 24/54
24
47
General Control StrategyGeneral Control Strategy
grounded neutral, the three poles
should close in succession with a
time separation of 1/6 cycle
(3.3 ms at 50 Hz or 2.8 ms at 60 Hz).
ungrounded neutral, two poles
should close simul taneously at
phase - phase voltage zero,
and the last o ne 1/4 cyc le later (5ms at 50 Hz or 4.2 ms at 60 Hz).
48
The advantages of the grounded w ye compared to the ungrounded
Initial cost is lower, the neutral does not needed to ful l system B IL
Recovery voltages are reduced
Mechanical duties less severe for the structure
Low impedance path to ground for ligh ting gives self protection from sur ge
System & cap bank be grounded at 121kV above _ IEEE C37.99-2000
The disadvantages of the grounded wye compared to the ungrounded
Higher inr ush curr ent may occur i n ground, it is needed NGR
Zero sequence harmonic current may draw to the ground
Usually m akes current lim iting fuses due to l ine to ground fault
GroundedGrounded vsvs UngroundedUngrounded
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 25/54
25
49
SR Location and Insulation CostSR Location and Insulation Cost
2nd
0 . 0 9 2 8 [ H ]
A _ c ur r
0 .2 1 [ oh m ]
3 7 . 9 4 [ uF ]
A_
c a p_
u
0 . 0 1 [ oh m ]
0 . 0 1 [ oh m ]
0 . 0 1 [ oh m ]
1 [ohm]
A_rr
3 7 . 9 4 [ uF ]
A_
c a p_
d
2nd
0 . 0 9
2 8 [ H ]
B _ c ur r
0 .2 1 [ oh m ]
3 7 . 9 4 [ uF ]
e_s
0 . 0 1 [ oh m ]
0 . 0 1 [ oh m ]
0 . 0 1 [ oh m ]
1 [ohm]
B_rr
3 7 . 9 4 [ uF ]
B_
c a p_
d
B_
r
A_
n g
B_
n g
Main : Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0
2.5k
5.0k
7.5k
10.0k
12.5k
15.0k
17.5k
20.0k
y
A cap u B r
Main: Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0
1.0k
2.0k
3.0k
4.0k
5.0k
6.0k
7.0k
8.0k
9.0k
10.0k
y
A_cap_d B_cap_d
Main: Graphs
0.00 0.10 0.20 0.30 0.40 0.50
0.0
2.5k
5.0k
7.5k
10.0k
12.5k
15.0k
17.5k
20.0k
y
e_s A_cap_u
Reactor Bushing Potential
Capacitor Bushing Potential
Capacitor Bushing Potential
50
Unbalance detection means ;
An in ternal element fai ls
→
voltage distribution & current flow c hange within a bank
Magnitude of changes
externally fused > internally fused
Purpose of the unbalance protection ;
alarm or disconnect the entire capacitor bank when morethan 10% over vol tages across the healthy capacito rs
More consideration required for ;
Types of unbalance protection
Over currents
Over & under voltage
Protecting the Harmonic Filter BanksProtecting the Harmonic Filter Banks
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 26/54
26
51
Neutral current
Neutral voltage
Current unbalance between neutrals
Phase voltage unbalance
Voltage difference
Current unbalance in br idge connection
Types of Unbalance ProtectionTypes of Unbalance Protection
52
Sensing Neutral Current & VoltageSensing Neutral Current & Voltage
Neutral Current Neutral Voltage
Star Connection with Neutral Grounded
Through a Current Transformer
Star Connection with Voltage Transformer
Between Neutral and Ground
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 27/54
27
53
Sensing dV & Current UnbalanceSensing dV & Current Unbalance
Voltage Difference Current Unbalance in
Bridge Connection
Star Connection with Grounded Neutral
and Voltage Transformers Connected in
differential Measurement
Bridge Connection
54
Sensing Unbalance Current & VoltageSensing Unbalance Current & Voltage
Current Unbalance Between
Neutrals
Phase Voltage
Unbalance
Double Star Connection wi th Ungrounded
Neutral
Star Connection with Ungrounded Neutral
and Voltage Transformers Connected in an
Open Delta
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 28/54
28
55
Summary of Capacitor Protection Methods Reference IEEE C37.99
Various schemes used,
suitability depends on banks
arrangements
Unbalance sensing with cu rrents or
voltage relays
Instantaneous relay action
necessary to limit fault damage
Unbalance relaying
Over current relayRack faultRack fault
To reduce inrush current
required series reactor
Switched or fixed impedance in
series with cap. BankInrush currentInrush current
Proper bank design Limit
number of cap. Unit
Individual unit fuse
Proper bank designDischarge current fromDischarge current from
parallel connected unitparallel connected unit
Not suitable for unmanned
substation for system overvoltages
Visual inspection phase overvoltage
relay
Continuous capacitorContinuous capacitor
unit over voltageunit over voltage
Coordination provided by
manufacture
Individual unit fuses (Expulsion or
current limiting)Over current due to unitOver current due to unit
failurefailure
Grounded capacitor banks
partially reduce surge voltageSurge arrestersSystem surgeSystem surge
Conventional methods applySupply breaker with OVR Power
fusesBus faultBus fault
RemarksRemarksType of ProtectionType of ProtectionConditionCondition
Summary of the Capacitor Banks ProtectionSummary of the Capacitor Banks Protection
56
1.01.0 1010 100100 1,0001,000 10,00010,000
Currents in amperes (Currents in amperes (r.m.sr.m.s.).)
1,0001,000
100100
1010
1.01.0
0.10.1
0.010.01
Time in SecondsTime in Seconds
Low probabilityLow probability
of case ruptureof case rupture
High probabilityHigh probability
of case ruptureof case rupture
Paper or paperPaper or paper
film dielectricfilm dielectric
All fil m di elect ric All fil m di elec tri c
Case Volum e 30,000CmCase Volum e 30,000Cm33
Typical Case Rupture CurvesTypical Case Rupture Curves
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 29/54
29
57
Meters A, V, Var, MVA, MW, pf, Hz
SCADA - Var and Voltage contro l
Main Bus
Sub Bus
TC
CC
C / T * 3
Ground SW
Arr ester s
Capacitor S. W
60MVAr
Capacitor
Bank
4 Levels of Unbalance Protection
4 Levels of Instantaneous OCP
Reactor Over Load TD Protection
Under Currents TD protection
Measurements Last Trip Record
Remote Control for Trip & Closing
Reactors
Neutral
Resistor
ID for
Faulty
Phase
PT 3P
In- Sensitivity 0.005A
51Q, 51G, 51N - 3Vo, 3V1, 3V2, 3Io, 3I1, 3I2
Event Waveform Oscillogr aph
Breaker Failure Detection
Failure Target for Each phase Group
Meters and Indicators for Alarm
Battery Voltage Measurement
1 Serial ports
1 Front, 3 rear
- integrating
relays to SCADA
An example Protection Scheme An example Protection Scheme
58
Conventional
3CTs
2P + 2P
Balanced DY
665kVAr, 96EA
ID faulty side, to be
checked 48EA for a
side
Advanced prot ecti on
7 CTs (KEPCO)
2P+2P
Balanced SYDB
665kVar, 96EA
ID the faulty phase,
to be checked 32EA for
a phase
Advanced prot ecti on
6 CTs
2P+2P
Balanced SYDB
665kVar, 96EA
ID the faulty phase,
to be checked 32EA fora phase
Conventional
1 CT
2P(L) + 1P(R)
Unbalanced DY
887kVAr, 77EA
Fail only, to be
checked 77EA forwhole bank
Grounded YY (Single Y Double Br)Grounded YY (Single Y Double Br)Grounded YGrounded Y--Y (Double Y)Y (Double Y)
Ungrounded YY (Single Y Double Br)Ungrounded YY (Single Y Double Br)Ungrounded YUngrounded Y--Y (Double Y)Y (Double Y)
NGRNGR
Various ConfigurationsVarious Configurations
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 30/54
30
59
Filter Capacitor BankFilter Capacitor Bank
60
Overview of Capacitor Banks ProtectionOverview of Capacitor Banks Protection
Aim of Unbalance Protection (Alarm, Trip)Isolate faulty capacitor banks
To prevent any of healthy units exposed to over than 110% of Un
Inherent unbalance current, Sufficient delay time to override external disturbances.
Overload Protection is to Protect from (Alarm, Trip)
Overcurrent, harmonic current, OvervoltageThe trip stage is based on the IEEE Std. C37.99 IEC60871-1 inverse time characteristics
Overcurrent Earth Fault Protection, Should be ConsiderSwitching inrush current
Time delay to clear the fuseSingle phase numerical type, standard inverse time
Overvoltage Protection is to Protect from the System Power Frequency Overvoltage
Undervoltage Protection, to trip the bank loss of system voltage, should be considered
Reenergizing capacitor bank with a trapped chargeEnergizing a cap bank without parallel load through a previously unenergized transformer
Delay time to override external faults
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 31/54
31
61
List of Relay UsedList of Relay Used
SWITCHSYNC
E113 ABBF25-POWPoint on Wave device7
KVGC 202 ALSTOMF90-AVC Automatic Volt age
Controller 6
KVFG 142 AREVAF27=UVUnder-voltage Interlock Relay5
P 922S AREVAF27-UVUnder-voltage protection4
P 922S AREVAF59-OVOver-voltage pr otection3
SPAJ 160C ABBF51 –UB &
F49- OL
Capacitor Unbalance
&Over-load pr otection2
P 123 AREVAF50/51OCOver-current & Earth
Fault protection1
TypeManufacturer DesignationFunctionNo.
62
Protection Scheme & Coordination PlotProtection Scheme & Coordination Plot
Protection Scheme for 132kV 60MVAr
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 32/54
32
63
Features of Protection RelayFeatures of Protection Relay
Current Unbalance and Over Current Unbalance and Over --load Protection [ABB SPAJ 160C]load Protection [ABB SPAJ 160C]
Current Unbalance Relays (-F51UB)
The relay receive the signal through neutral current transformer.
Two stages of alarm provided. If any capacitor element fails, the relay shall set to
alarm (Stage 1) at appropriate value and to trip (Stage 2) the capacitor bank if the
110% rated voltage appears on any remaining units in the same unit.
Over-load Relays (-F49OL)
Both inverse time current characteristic and definite time characteristic are
provided.
Two stages of operation for alarm and tripping are also provided
64
Over Over --current and Earthcurrent and Earth--Fault Protection (F50/51OC) [AREVA P123]Fault Protection (F50/51OC) [AREVA P123]
Over-current Relays (-F50/51)
Relays are of the three-single phase numerical type with both definite time and
standard inverse time characteristic and with an independent measuring unit for
each phase.
Earth fault Relays (-F50N/51N)
Relays are single-phase numerical type with both definite time and standard
inverse time characteristic and with an independent measuring unit for each
phase
Features of Protection RelayFeatures of Protection Relay
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 33/54
33
65
Over Over --volt age and Under volt age and Under --volt age Protection [AREVA P 922S]volt age Protection [AREVA P 922S]
Over-voltage Relays (-F59OV)
Time delay of both inverse time and definite characteristics types are provided.
The relay should be provided for tripping off the capacitor bank in case of
overvoltage condition occurring in the system such as due to sudden load loss.
Under-voltage Relays (-F27UV)
Voltage Input is taken from existing voltage selection scheme / busbar VT. If there
is no busbar VT then it is required that the voltage is taken from capacitor side VT,
with is supplemented with a blocking logic as below.
The relay should be provided for tripping off the capacitor bank in case of
temporary loss voltage such as during the line auto-reclosing, to prevent re-
closing of capacitor bank before the capacitor is fully discharged.
Features of Protection RelayFeatures of Protection Relay
66
Setting PhilosophySetting Philosophy
Over Over --current and Earth Fault (current and Earth Fault (--F5l OCEF) [AREVA P123]F5l OCEF) [AREVA P123]
The -F51 OCEF relay shall be set to operate as fast as possible in the occurrences of short circuitin the capacitor bank feeder since down-stream coordination are not required.
Characteristics of the -F51 OCEF relays will be determine from coordination studies. Both definitetime (DT) characteristic and IDMT-Extremely Inverse Characteristic are used to protect thebank.
Time over-current relay (510C) - For a shunt capacitor bank, pickup setting 130% (IEEE std37.99-2000; the desirable minimum pickup is 135% of IN for grounded wye banks and 125% of INfor ungrounded banks) of rated current of the capacitor bank is proposed. Selection of time
delay characteristic is based on coordination study. Both definite time and inverse timecharacteristic with time multiplier setting (TMS) higher than their respective overloadcharacteristics is recommended.
Instantaneous over-current relay (50OC) - For shunt capacitor bank, pickup at least 1.15 timespeak inrush to override inrush transient. (IEEE std. C37.99-2000 clause 7.2.3)
Time over-current relay (51 EF) - The capacitor bank is not grounded hence sensitive EF shouldbe set to 20% pickup with the same operating time as OC elements to detect and to providefast clearing for ground faults.
Instantaneous over-current relay (50EF) - Same as 51 OC or defeated if setting range notavailable.
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 34/54
34
67
Unbalance and Overload (Unbalance and Overload (--F5l UB/F5l UB/--F49OL) [AB B SPAJ 160C]F49OL) [AB B SPAJ160C]
F49OL - This is a protection against over-voltages and harmonics current. Capacitor shall be able
to carry continuous over-load current of 130% the rated current including due to harmonic andmaximum voltage variations. The over-voltage trip start setting should be at 110% of capacitor
bank rating, utilizing overload curve (at 1.1 pu). The alarm setting shall be at 110% of overloadstart setting with a time delay of 60 seconds and trip 115% with time delay 0.2seconds
F5l UB - The time delay of the unbalance relay trip should be minimized to reduce damage from anarcing fault within the bank structure and prevent exposure of the remaining capacitor units to
over-voltage conditions beyond their permissible limits.
Setting shall be followed by Annex 4) which is analyzed that the unbalance neutral current, andbased on over-voltage limit (per capacitor unit) when the internal fuse has blown up to three
elements, the terminal voltage of the faulty unit capacitor is less than 103.1% of Un.
Setting shall also be confirmed / compensated with neutral unbalance current afterexercitation. (with measurement)
Setting PhilosophySetting Philosophy
68
Setting PhilosophySetting Philosophy
Characteristic of the overload curve is related to over-voltage characteristic of ANSI-
1990 and IEC 60871-1. 1997 as tabulated below.
ANSI 1036-19926 cycles0.102.20
ANSI 1036-199215 cycles0.272.00
ANSI 1036-19921.00 s0.901.70
ANSI 1036-199215.0 s13.51.40
ANSI 1036-199260.0 s54.01.30
IEC 60871-1. 1997300 s2701.20
IEC 60871-1. 19971800 s16201.15
Standard durationTime (s)Overload
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 35/54
35
69
Setting PhilosophySetting Philosophy
Under & Over Under & Over --voltage (voltage (--F27UV/F27UV/--F59OV) [AREVA P922S]F59OV) [AREVA P922S]
F59OV - This protection as backup for the main protection. Inverse characteristic shall becoordinated with the allowable range as tabulated below. Alternatively, a definite time
characteristic can be used with pickup at the maximum system voltage limit (+10%). Operatingtime shall be coordinated wilt the AVR setting.
1min1.30
Voltage rise at light load5min1.20
System voltage regulation and fluctuation s30min in
every 24h1.15
System voltage regulation and fluctuation s8h in
every 24h1.10
Highest average value during any p eriod of
capacitor service.Continues1.00
Power Frequency
ObservationMaximum
Duration
Voltage factor
Un VrmsType
Capacitor allowable over-voltage range is as table 6 from IEC 60871-1. 1997 as follows
70
F27UV - Under voltage protection can be used to trip the capacitor bank and to block CB closingwhen its residual voltage is still high before being discharged after disconnection. The
tripping function may be required if loss of system voltage. VT source should be taken from
the busbar voltage selection to avoid blocking during normal closing if VT source fromcapacitor bank side.
Residual voltage allowable for capacitor discharging is less than 50Vdc from initial voltage of √2
of the rated voltage (Un). For this project, the bank is designed to reduce the residual voltageless then 50Vdc within 5 minutes. The manufacturer should provide discharge time to 50V inthe instruction manual or rating plate.
Setting PhilosophySetting Philosophy
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 36/54
36
71
Au tom atic Volt age Control ( Au tom atic Volt age Control (--F90AVC)F90AVC)
System operations shall advise the bandwidth setting. The setting depends on the local system
condition. Typical operating system voltage is between 1.0 to 1.05 p.u. The AVR setting for132kv system is recommended to regulate the system voltage between the normal operating
range. Recommended time delay to be set is 30s.
As per the operating experience we recommend the programmable timer setting, the daily closingtime is at 08:00 and opening time is at 23:00, it shall be determined by the system operator.
Setting PhilosophySetting Philosophy
72
Fault Level Calculation ExampleFault Level Calculation Example
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 37/54
37
73
Fault an AMPG Bus Under Peak LoadFault an AMPG Bus Under Peak Load
-79.625832.6TOTAL FAULT CURRENT (AMPS)NA
0.000.0TO SHUNT (AMPS)
999990.0049.35-82.404269.9 AMP/OHM213275.00 AMPG27588215
999990.0049.35-82.404269.9 AMP/OHM113275.00 AMPG27588215
5.91780.412.77-80.374319.4 AMP/OHM213132.00PMJU13288175
5.91780.412.77-80.374319.4 AMP/OHM113132.00PMJU13288175
4.20876.631.12-72.512692.9 AMP/OHM213132.00TWSA13288137
4.20876.631.12-72.512692.9 AMP/OHM113132.00TWSA13288137
5.91980.412.60-81.821661.4 AMP/OHM213132.00KLJTI13288121
5.91980.412.60-81.821661.4 AMP/OHM113132.00KLJTI13288121
APP X/R AN(Z+)/Z+/ AN(I+)/I+/I/ZCKT AREAX-----------FROM--------------X
THREE PHASE
FAULT
AT BUS 88120 AMPG132 132.00 Area 13 (kV L-G) V+: / 0.000/ 0.00
THEV. R, X, X/R : POSITIVE 0.00360 0.0168 4.605
PSSE/E SHORT CIRCUIT OUTPUT MON, MAY 16 2005 17:16 HOME BUS is 88120
2007 PEAK LOAD CASE AMPG 132.00
FAULTED BUS IS 88120 (AMPG132 132.00) 0 LEVELS AWAY
50 kA500kV
40/50* kA275kV
31.5 kA132kV
Short Circuit RatingVoltage Class TNB Planning criteriaTNB Planning criteria
74
Construction of the Unit Capacitor Construction of the Unit Capacitor Construction of t he Unit Capacitor
Rating : 9kV 1P 50Hz 591kvar, 23.18uF, 65.6A
Construction : 6Series x 10Para (60 Rolls)
Eco : 13.91uF Discharge Resistor : 375kΩ x 6 series =2.25MΩ
Fuse : 0.4Φ
Cupper Wire,Fuse Total length 20mΩ,
Fuse operating Length 13.5mΩ
Unit Capacitor
DischargeDischargeResistor Resistor
13.91uF
Unbalance CalculationUnbalance Calculation
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 38/54
38
75
Unbalance current and overvoltage characteristicsUnbalance current and overvoltage characteristics
99.612,971103.113,3141372,959357m3
99.812,888101.813,1501222,630214m2
99.912,901100.813,0201102,36993.8m1
100.012,912100.012,9121002,1522.76m0
Sound group
Unit % of Un
Sound group
unit VT-T[Vp]
Faulty Unit
% of Un
Faulty unit
VT-T[Vp]
Faulty Element
of Un
Faulty Element
Group [Vp]NCT [Ap]
No. of
faults
76
Typical Air Core Dry Type ReactorTypical Air Core Dry Type Reactor
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 39/54
39
77
Al lowable Overload Current for Reactor Al lowable Overload Current for Reactor
78
Typical Case Rupture Curve for ALL Film CapTypical Case Rupture Curve for ALL Film Cap
Typical case rupture curve for approximately 1800 cubic inchesTypical case rupture curve for approximately 1800 cubic inches-- case volume the dielectriccase volume the dielectric
material with Polypropylene film (ALL PP) quoted from IEEE Std.material with Polypropylene film (ALL PP) quoted from IEEE Std. 10361036--19921992
S’s typical clearing time of the internal fuse
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 40/54
40
79
Harmonic Filter TypesHarmonic Filter Types
80
Current Transformer
2:2A 20VA
R S T
Configurations of Single LineConfigurations of Single Line DwgDwg ..
9 Series / phase
4 Parallel / phase
9s x 4p x 3 = 108 Cans
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 41/54
41
81
Key Rating FactorsKey Rating Factors
/(1 )c pV V α = −
/ L c X X α =
2( / ) (1/(1 )) L eff
Xc V Q α = × −
/ 3P L
V V =
2(1/ ) L C X h X = ×
21/ hα =
L C X X α = ×
(1/(1 ))cphase pV V α = × −
/cunit cpha seV V Ns=/( /(1 ))
sr pV V α α = −
Three PhaseThree Phase -- Single PhaseSingle Phase
VLVsr
Vp
Vcphase
/(1 )cap eff
Q Q α = −
/capunit cap cap
Q Q N =
sr cap eff Q Q - Q=
82
Harmonic Filter designHarmonic Filter design
2
LLsys
eff
eff
kV X =
Q (Mvar)
2
21
C eff
h X X
h
⎛ ⎞= ⎜ ⎟−⎝ ⎠
2
C L
X X
h=
Xeff is the effective reactance of the harmonic filter,
Qeff is the effective reactive power (Mvar) of the harmonic filter,
VLLsys is the nominal system line-to-line voltage,XC is the capacitive reactance of the harmonic filter capacitor at the fundamental frequency,XL is the inductive reactance of the harmonic filter reactor at the fundamental frequency,
h is the harmonic number.
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 42/54
42
83
Numerical ExampleNumerical Example
A 30 MVA industrial load is supplied from a 34.5 kV bus.
The three-phase fault level at the bus is 10.0 kA rms symmetrical.
The load has a power factor of 0.85. It is desired that the power factor be raised to 0.95.
The load is a source of harmonic current.
The magnitude of the harmonic current suggests that the capacitor should be designed as a
harmonic filter.
Qeff (in kvar) = (multiplying factor)(load power in kilowatts)
Qeff = (0.291)(30 000 kVA)(.85) = 7420 kvar
84
Numerical ExampleNumerical Example
Because of Phase shift of h component
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 43/54
43
85
Numerical ExampleNumerical Example
86
Numerical ExampleNumerical Example
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 44/54
44
87
Harmonic Current EstimationHarmonic Current Estimation
jXL Rs
-jXC Xs
Ih
88
Configurations of 132kV 60MVArConfigurations of 132kV 60MVAr
(Ungrounded Double Y) Side view(Ungrounded Double Y) Side view
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 45/54
45
89
Configurations of 132kV 60MVArConfigurations of 132kV 60MVAr
(Ungrounded Double Y) Front view(Ungrounded Double Y) Front view
90
Steel Making Plant HarmonicsSteel Making Plant Harmonics
Changing cycle by cycleInterharmonics
Design Filter is not traditional
Interharmonics ->torsional and mechanical resonance
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 46/54
46
91
Steel Making Plant HarmonicsSteel Making Plant Harmonics
92
Steel Making FacilitiesSteel Making Facilities
Important Categories
Characteristic harmonics
Derive loads in the rolling mill
Non-characteristic harmonics
Third harmonic component
Even harmonic components
Shorter duration than conventional but important
Interharmonics
Fluctuating EAF, Cycloconverter
Should be capable of measurement
Statistical characteristics of the harmonic levels
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 47/54
47
93
Steel Making FacilitiesSteel Making Facilities
Statistically evaluation for interharmonic
12 cycles sample, bin size of 5Hz
Cumulative probability distribution
Specific values can be determined the distortion levels
Vh95%
VTHD95%
Vh99%
VTHD99%
Ih95%
ITDD95%
Ih99%
ITDD99%
The harmonic filters should not magnify interharmonic components,resulting in excessive levels.
94
Steel Making Plant HarmonicsSteel Making Plant Harmonics
Example filter design for arc furnace installations.
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 48/54
48
95
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
System Problems
The utility side transformer has excessive audio frequency noise and overheats.
Voltage THD on the 22 kV system is 7.7%, exceeding limits in IEEE Standard 519.
The rectifiers incur thyristor phase control malfunctions due to voltage sensing errors.
Utility and customer capacitor banks incur over currents and excessive noise.
Complaints are generated from adjacent customers due to device malfunctions, and in particular,standstill conditions created at a precision electrical facility
Increasing System Reliability Using Series TunedIncreasing System Reliability Using Series Tuned
Harmonic Filter Banks in a Chemical FacilityHarmonic Filter Banks in a Chemical Facility
16th Annual Power Quality Conference
October 25th -27th 2005
Baltimore Convention center
96
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Utility Data
The normal Utility operating voltage is approximately 154 kV.
The Utility three-phase short circuit MVA is 1,400 MVA, with an X/R ratio of 10.
The 45 MVA supply transformer has a primary delta and secondary ungrounded wye windingarrangement, and a 5% impedance.
The incoming line distance from utility is indeed 0.75 km, composed with single core copperconductor 400 mm2.
22.9kV line has two sets of the capacitor banks 5MVAr, 6% SR
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 49/54
49
97
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Ratings of Rectifier Converter
No.1 rectifier 5,810kW 3,210kVAr 6-pulse thyristor converter
No.2 rectifier 6,100kW 4,900kVAr 6-pulse thyristor converter
No.3 rectifier 5,810kW 3,210kVAr 6-pulse thyristor converter
No.4 rectifier 2,100kW 820kVAr 6-pulse thyristor converter
98
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Plant System with 6% SL Capacitors
UTIL 1400MVA
D-Y
154/22.9kV
45/65MVA
Z=5%
D-D
22.9/6.6kV
9MVA, 7%
D-D
22.9/3.3kV
5MVA, 7%
3.7MW
950kVAr
3.7MW
950kVAr
300kVA
6.3Ohm
5MVAr
22.9kV
CU500mm2
500mCU400mm2
750m
PCC
KPC23kV
DSN
PKCOM23
300kVA
6.3Ohm
5MVAr
22.9kV
6% Series
Reactors
22.9kV
1400kVAr
22.9kV
1500kVAr
22.9kV
900kVAr
D-Y
22.9/0.22kV
7.5MVA, 7.5%
D-Y
22.9/0.22kV
8.6MVA, 10%
D-Y
22.9/0.22kV
7.5MVA, 10%
D-Y
22.9/0.22kV
2.3MVA, 5.5%
5.8MW
3.21MVAR
6.1MW
4.91MVAR
5.8MW
3.21MVAR
2.1MW
0.821MVAR
UTIL 1400MVA
D-Y
154/22.9kV
45/65MVA
Z=5%
D-D
22.9/6.6kV
9MVA, 7%
D-D
22.9/3.3kV
5MVA, 7%
3.7MW
950kVAr
3.7MW
950kVAr
300kVA
6.3Ohm
5MVAr
22.9kV
CU500mm2
500mCU400mm2
750m
PCC
KPC23kV
DSN
PKCOM23
300kVA
6.3Ohm
5MVAr
22.9kV
6% Series
Reactors
22.9kV
1400kVAr
22.9kV
1500kVAr
22.9kV
900kVAr
D-Y
22.9/0.22kV
7.5MVA, 7.5%
D-Y
22.9/0.22kV
8.6MVA, 10%
D-Y
22.9/0.22kV
7.5MVA, 10%
D-Y
22.9/0.22kV
2.3MVA, 5.5%
5.8MW
3.21MVAR
6.1MW
4.91MVAR
5.8MW
3.21MVAR
2.1MW
0.821MVAR
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 50/54
50
99
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Impedance scan results and Harmonic spectrum
100
Passive Filter Passive Filter
Series Tuned Harmonic Filter
High voltage Class : 50 < Q < 150
Low voltage Class : 10 < Q < 50
LC
1
C
L
R
ω
C
L
RQ
1=
C ω
1 Lω
R
F Z
)(ω F Z
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 51/54
51
101
Passive Filter Passive Filter
Damped High Passive Filter (2nd Order)
LC
1
C
L
R
F Z
ω
C ω
1 Lω
R
)(ω F Z
b R
b R
C Rb
1
102
Without Filter: VTHD = 7.6%
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Without Filter
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 52/54
52
103
Plant System with Harmonic Filter Banks
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
UTIL 1400MVAD-Y
154/22.9kV
45/65MVA
Z=5%
D-D
22.9/6.6kV
9MVA, 7%
D-D
22.9/3.3kV
5MVA, 7%
3.7MW
950kVAr
3.7MW
950kVAr
300kVA
6.3Ohm
5MVAr
22.9kV
CU500mm
500mCU400mm
750m
PCC
KPC23kV DSN
PKCOM23
300kVA
6.3Ohm
5MVAr
22.9kV
D-Y
22.9/0.22kV
7.5MVA, 7.5%
D-Y
22.9/0.22kV
8.6MVA, 10%
D-Y
22.9/0.22kV
7.5MVA, 10%
D-Y
22.9/0.22kV
2.3MVA, 5.5%
5.8MW
3.21MVAR
6.1MW
4.91MVAR
5.8MW
3.21MVAR
2.1MW
0.821MVAR5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
1006kVAr, 1934kVAr, 3162kVAr, 2028kVAr, 1485kVAr
UTIL 1400MVAD-Y
154/22.9kV
45/65MVA
Z=5%
D-D
22.9/6.6kV
9MVA, 7%
D-D
22.9/3.3kV
5MVA, 7%
3.7MW
950kVAr
3.7MW
950kVAr
300kVA
6.3Ohm
5MVAr
22.9kV
CU500mm
500mCU400mm
750m
PCC
KPC23kV DSN
PKCOM23
300kVA
6.3Ohm
5MVAr
22.9kV
D-Y
22.9/0.22kV
7.5MVA, 7.5%
D-Y
22.9/0.22kV
8.6MVA, 10%
D-Y
22.9/0.22kV
7.5MVA, 10%
D-Y
22.9/0.22kV
2.3MVA, 5.5%
5.8MW
3.21MVAR
6.1MW
4.91MVAR
5.8MW
3.21MVAR
2.1MW
0.821MVAR5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
UTIL 1400MVAD-Y
154/22.9kV
45/65MVA
Z=5%
D-D
22.9/6.6kV
9MVA, 7%
D-D
22.9/3.3kV
5MVA, 7%
3.7MW
950kVAr
3.7MW
950kVAr
300kVA
6.3Ohm
5MVAr
22.9kV
CU500mm
500mCU400mm
750m
PCC
KPC23kV DSN
PKCOM23
300kVA
6.3Ohm
5MVAr
22.9kV
D-Y
22.9/0.22kV
7.5MVA, 7.5%
D-Y
22.9/0.22kV
8.6MVA, 10%
D-Y
22.9/0.22kV
7.5MVA, 10%
D-Y
22.9/0.22kV
2.3MVA, 5.5%
5.8MW
3.21MVAR
6.1MW
4.91MVAR
5.8MW
3.21MVAR
2.1MW
0.821MVAR5th_1, 11th_High, 5th HF, 7th HF, 11th HF
60.7 6.05 15.6 15.4 8.2 mH
1006kVAr, 1934kVAr, 3162kVAr, 2028kVAr, 1485kVAr
104
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Fr. scan results & modeling data TR / Filter
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 53/54
53
105
Name Type Comp IRMS kW Losses kVar Losses VSUM%
ADFL-5_1 Notch 59.589 4.134 1058.369 146.4%
ADFL-11A 2nd Ord R 2.081 4.807
L 55.943 0.290 82.018
C 55.990 110.5%
FL-5 Notch 95.393 1.204 490.719 116.6%
FL-7 Notch 65.681 0.473 265.355 114.5%
FL-11 Notch 46.222 0.201 94.608 111.9%
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Filter data for design
106
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
5th, 7th, 11th, 11th Hi-pass filter currents
8/9/2019 2008_harmonic Filter Web
http://slidepdf.com/reader/full/2008harmonic-filter-web 54/54
107
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
With Harmonic Filters
1.22.3K factor
0.7k0.76kCurrent Peak in Vp
19.1k20.9kVoltage Peak in Vp
471.9523.3Current Average in A
2.967.59~7.7Voltage Distortion %
6.73~7.0414.1~16.6Current Distortion %
0.980.88Power Factor
3,7009,870Power Q in kVAr
18,53018,440Power P in kW
18,90020,900Power S in kVA
Tuned Harmonic Filters6% SR CapacitorsDescription
Case Study for Electrochemical PlantCase Study for Electrochemical Plant
Summary of before and after power characteristics