Upload
barry-moody
View
221
Download
0
Tags:
Embed Size (px)
Citation preview
1
2009 Eaton Corporation. All rights reserved.
Measuring- and Communication Modulefor Molded Case Breakers and Switch Disconnectors
2202.Jul.2009 2009 Eaton Corporation. All rights reserved.
Measuring- and Communication Module
Energy costs Under strict control
3302.Jul.2009 2009 Eaton Corporation. All rights reserved.
Metering and Visualization
classic compact
+ all-purpose
- high amount of wiring
+ basic setup+ easy to install+ attractive price
4402.Jul.2009 2009 Eaton Corporation. All rights reserved.
XMC Products
• Optional Display
• For Premium version
• 96x96 front mounting
• Viewing of all parameters
• Preconfigured
5502.Jul.2009 2009 Eaton Corporation. All rights reserved.
Overview
XMC
Incorporated CTs
Dig S0 output
Voltage access
2 dig. I
2 dig. Q
Remote Control
Modbus
Display
6602.Jul.2009 2009 Eaton Corporation. All rights reserved.
Metering Data of Premium Version
Data via Modbus and Display accessible:
Phase voltages L-N und L-L Phase currents L1,L2,L3Active power per phase and directionActive power totalReactive energy per phaseReactive energy totalReactive energy capacitive/inductiveApparent power per phaseApparent power totalPower factor Cos PhiFrequency3 configurable time windows6 configurable alarms
7702.Jul.2009 2009 Eaton Corporation. All rights reserved.
Basics on Power
• Active power [Watt]• P=u*i cos phi
• Real power (billing)
• Reactive Power [var]• Q=u*i sin phi
• Unwanted, not unusable power; bouncing between generator and consumer
• Apparent Power [VA]• S=U*I
• Needed for wiring dimension
G M
G M
8802.Jul.2009 2009 Eaton Corporation. All rights reserved.
Device versions
Standard Version Premium Version
1 dig S0 Pulse-Outputfor Active Energy
Ideal to incorporate energy data via SmartWireDarwin
2 S0 Pulse-Outputsfor Active Energy
Display interface
Fieldbus interface (Modbus)
Expandable with max 2 cards:
NZM-XMC-1AO 1 analog output
NZM-XMC-2DO-R 2 relais output
NZM-XMC-4DO-R 4 Relais output
NZM-XMC-4DI-4DO 4 dig. input + 4 dig. output
9902.Jul.2009 2009 Eaton Corporation. All rights reserved.
Topology for PROFIBUS-DP or PROFINET
Metering BusModbus RTU
Typically 32 breakers
PROFIBUS-DPor
PROFINET
M S
M S
M S
Gatewayto PROFINET or PROFIBUS-DP
Scada
PLC
1010
02.Jul.2009 2009 Eaton Corporation. All rights reserved.
S0-pulse output
Typical signal according EN 62053-31
requirements
1111
02.Jul.2009 2009 Eaton Corporation. All rights reserved.
Assortment
NZM-XMC-COND3NZM-XMC-COND3NZM-XMC-KIT-630 3 630 Kit including conductors and terminalsNZM-XMC-KIT-TCP-630 3 630 Kit including conductors and terminals
and ModbusTCP Gateway
1212
02.Jul.2009 2009 Eaton Corporation. All rights reserved.
630 A KIT
1313
02.Jul.2009 2009 Eaton Corporation. All rights reserved.
• Voltage Measuring
• Range: 40...700V
• Error: 0.49% reading + 0,01%FS
• Current Measuring
• Range: 115% ... 1% Inom
• 300A: 350...3A
• 630A: 735...6.3A
• Error: 0.49% reading + 0,01% FS
• Power / Energy
• Error: 0.99% reading + 0,01% FS
Technical Data
1414
02.Jul.2009 2009 Eaton Corporation. All rights reserved.