Jan SlezákIEC 61850 in the ELVAC products
www.elvac.eu
IEC 61850 in the ELVAC products
Used mainly as an HMI (e.g. CEZ substations Havířov and Kojetín)
Support through a separate driver (similar to KomX module)
Two variants:
Classic application running on desktop – KomX_61850
System service running in the background – Kom61850
Configured by configuration file and by CSV files in the control folder
Each CSV file defines:
A connection to one IED
All points transferred from / controlled on this IED
www.elvac.eu | www.rtu.cz
IEC 61850 in the Mikrodispecink SCADA
Products for energetics
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
IEC 61850 in the Mikrodispecink SCADA
To work with the driver:
The Mikrodispecink must have a properly configured routes.
The configuration table of the routes is newly expanded.
www.elvac.eu | www.rtu.cz Products for energetics
IEC 61850 in the Mikrodispecink SCADA
Configuration GUI = Mikrodispecink Editor
www.elvac.eu | www.rtu.cz Products for energetics
To configure driver in the Mikrodispecink Editor:
Create folder ZIVY\61850 in the system folder of Mikrodispecink
(probably something like D:\MDisp\MD93)
Set control folder of driver to the newly created ZIVY\61850 folder
Create working folder EDITACE\61850 in the system folder of Mikrodispecink
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Three ways to configure driver:
a) Fully manual
b) With help of SCL file (description file of device or the whole substation)
c) Almost fully automatic based on SCL file and config. file from Siemens SICAM PAS
Assign IEC 61850 to systems (way a and b):
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Set parameters of devices - IEDs (way a):
Configure all desired points (way a):
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Save all three tables (repeat on each table) (all ways):
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Create configuration CSV file and send it to the driver (all ways):
To configure with help of SCL file (way b and c):
Copy the SCL file to editor folder for 61850 configuration (EDITACE\61850).
Rename copied file to form CfgNNNN.scd, where NNNN is the number of
Mikrodispecink system assigned to this IEC 61850 configuration. The cid extension
can be used instead of scd.
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Set parameters of devices - IEDs (way b):
Configure all desired points (way b):
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Configuration according to Siemens SICAM PAS
HMI – Mikrodispecink
KomX_61850
SCADA – Mikrodispecink
KomX or Communicator
data concentrator
SICAM PAS
IED IED IED
IEC 61850 level
IEC 60870-5-104 levelsubstation
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
To configure with help of SCL file and SICAM PAS file (way c):
Copy the SCL file to editor folder for 61850 configuration (EDITACE\61850).
Rename copied file to form CfgNNNN.scd, where NNNN is the number of
Mikrodispecink system assigned to this IEC 61850 configuration. The cid extension
can be used instead of scd.
Copy the XML file from SICAM PAS to the same folder as SCL file.
Rename copied file to form IECNNNN.xml, where NNNN is the number of
Mikrodispecink system assigned to this IEC 61850 configuration.
Copy configuration of IEC 60870-5-104 protocol from SCADA Mikrodispecink to HMI
Mikrodispecink.
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Assign IEC 61850 to systems and link it to IEC 60870-5-104 (way c):
Set parameters of devices - IEDs (way c):
IEC 61850 in the Mikrodispecink SCADA
www.elvac.eu | www.rtu.cz Products for energetics
Configure all desired points (way c):
IEC 61850 in the ELVAC products
Work in progress – available at the end of year
Future plans
Work in progress:
IEC 61850 client for connecting ELVAC RTUs to external devices. It will complement
current support for IEC 60870-5-103, DNP3, Modbus protocols. It will allow to read
data from IEC 61850 protections and to control them. Connection to controlling
system (SCADA) will be realized by already existing ways – by IEC 60870-5-10x,
DNP3 protocols.
Possibility to deploy to existing COMIO-PC2 hardware (and therefore into RTUs
already in the field).
Configured by “RTU User Center” application.
www.elvac.eu | www.rtu.cz
IEC 61850 in the ELVAC RTUs
Products for energetics
IEC 61850 in the ELVAC products
Future plans:
IEC 61850 server, goose messaging. It will allow to fully integrate the ELVAC RTUs to
the IEC 61850 infrastructure. For instance it will allow the ELVAC RTU to
communicate to the IEC 61850 HMI.
The new hardware (communication card) is needed. Temporarily called COMIO-PC3.
COMIO-PC3 will have two ethernet ports. This will allow to implement IEC 62439-3
protocol (Parallel Redundancy Protocol).
Configured by “RTU User Center” application or on the web interface of the RTU
itself.
www.elvac.eu | www.rtu.cz Products for energetics