63
1 2016 Update to the California Building Standards Code Webinar Series Webinar 1 — Fire and Life Safety Provisions May 1, 2017 Welcome Amber McEwen California Hospital Association

2016 CA Building Code Webinar 1 - FINAL · 2019-11-18 · SFM, but with amendments. 27 Separation required Group I-2 — Nursing Homes (cont.) 407.2.6 Nursing home cooking facilities

  • Upload
    others

  • View
    2

  • Download
    1

Embed Size (px)

Citation preview

1

2016 Update to the California Building Standards Code Webinar Series

Webinar 1 — Fire and Life Safety Provisions

May 1, 2017

Welcome

Amber McEwenCalifornia Hospital Association

2

Overview and Introductions

Cheri HummelVice President, Emergency Management & FacilitiesCalifornia Hospital Association

4

Nanci Timmins is chief fire and life safety officer for the Office of Statewide Health Planning and Development (OSHPD) and has served 20 years in the fire industry. Prior to her role with OSHPD, she was a fire marshal for the State of Michigan. Ms. Timmins has certifications from the National Fire Protection Association (NFPA) and holds degrees in psychology and fire science from the University of Maryland.

Faculty

3

5

John Donelan has 45 years of experience in the California fire service, including 15 years as an assistant fire marshal and fire marshal with two municipalities, four years as a deputy state fire marshal with the State Fire Marshal’s Office, 12 years with OSHPD as a fire and life safety officer and a regional compliance officer, among others. Mr. Donelan is a state-certified fire officer, fire investigator, fire service instructor, apparatus operator instructor and public education instructor.

Faculty

Nanci Timmins Chief Fire & Life Safety Officer, OSHPD

John DonelanFire & Life Safety Officer II, OSHPD, and

HBSB Member

Fire & Life Safety Provisions

Hospital Building Safety Board May 1, 2017

4

Building Code Topics

• AdministrationChapters 1 and 2

• Building PlanningChapters 3 through 6

• Fire ProtectionChapters 7 through 9

• Building Services, Special Devices and Special Conditions

Chapters 27 through 34A

7

DEFINITIONS

Definitions

5

Definitions202. Exit, Horizontal. A path of egress travel from one building to an area in another building on approximately the same level, or a path of egress travel through or around a wall or partition to an area on approximately the same level in the same building, which affords safety from fire and smoke from the area of incidence and areas communicating therewith.

Absolutely the dumbest definition/description of an extremely important component of a means of egress system.

Through or around a wall or partition? Really? What does that mean? Therewith? Who talks like that?

A source of confusion for decades.

9

Definitions (cont.)

The new definition for a horizontal exit:

202. Horizontal Exit. An exit component consisting of fire-resistance-rated construction and opening protectives intended to compartmentalize portions of a building thereby creating refuge areas that afford safety from the fire and smoke from the area of fire origin.

10

6

Special Detailed Requirements Based on Use and Occupancy

BUILDING PLANNING

7

Special Detailed Requirements

404. Atriums

13

Atriums

404.5 Smoke control. A smoke control system shall be installed in accordance with Section 909.

Exception: In other than Group I-2 and R-2.1, smoke control is not required for atriums that connect only two stories.

Oops! What now?

A two-story atrium in a hospital will require smoke control, or it must be separated from the Group I-2 by an occupancy separation.

This change deletes Group I-2 and R-2.1 from the smoke control exception for two-story atriums. For Group I-2 and R-2.1, the revision reverts back to the 2001 California Building Code requirement based on the 1997 Uniform Building Code.

14

8

Group I-2 — Corridors407.2.1 Waiting and similar areas. Waiting areas and similar spaces constructed as required for corridors shall be permitted to be open to a corridor, only where all of the following criteria are met:

1. The spaces are not occupied as care recipients’ sleeping rooms, treatment rooms, incidental uses listed in Table 509 or hazardous uses.

2. The open space is protected by an automatic smoke detection system installed in accordance with Section 907.

3. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic smoke detection system installed in accordance with Section 907, and the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.

15

Group I-2 — Corridors (cont.)

International Building Code (IBC): While not the intent

of the IBC, fire sprinklers can be considered fire detectors.

California Building Code (CBC): To avoid confusion, State Fire Marshal (SFM)

identifies required detection as smoke detection.

16

9

Group I-2 — Corridors (cont.)

Belts and suspenders?

The IBC requires fire detection in the corridor or fire sprinklers throughout the smoke compartment.

The CBC (SFM) requires both smoke detection in the corridor and fire sprinklers throughout the smoke compartment.

17

Group I-2 — Corridors (cont.)

Belts and suspenders? No. Two very different functions.

Fire control Early warning

18

10

Group I-2 — Corridors (cont.)

407.2.1 Waiting and similar areas (open to a corridor, cont.)

4. The space is arranged so as not to obstruct access to the required exits.

5. Each space is located to permit direct visual supervision by the facility staff.

19

Group I-2 — Nursing Homes

Household Model Nursing Home:

20

11

Group I-2 — Nursing Homes

407.2.5 Nursing home housing units

The 2015 International Building Code adopts additional allowances applicable only to nursing homes permitting shared living spaces, group meeting areas or multipurpose therapeutic spaces in areas open to corridor systems (known as the household model). These provisions are further amended by the State Fire Marshal in the California Building Code.

21

Group I-2 — Nursing Homes (cont.)

22Group I-2 shared living space

12

Group I-2 — Nursing Homes (cont.)

407.2.5 Nursing home housing units. In Group I-2, Condition 1,occupancies, in areas where nursing home residents are housed, shared living spaces, group meeting or multipurpose therapeutic spaces, shall be permitted to be open to the corridor, where all of the following criteria are met:

1. The walls and ceilings of the space are constructed as required for corridors.

2. The spaces are not occupied as resident sleeping rooms, treatment rooms, incidental uses in accordance with Section 509, or hazardous uses.

3. The open space is protected by an automatic smoke detection system installed in accordance with Section 907.

23

The 2015 IBC identifies two conditions for Group I-2. These conditions (Condition 1 and Condition 2) identify different levels of nursing and medical care. Condition 1 describes nursing homes. Condition 2 pertains to hospitals.

The State Fire Marshal does not adopt these conditions.

When enforcing fire life safety provisions, the State Fire Marshal does adopt specific requirements related to householdmodel nursing homes. These requirements are found in CBC Sections 407.2.5 and 407.2.6.

24

Group I-2 — Nursing Homes (cont.)

13

Group I-2 — Nursing Homes (cont.)

407.2.5 Nursing home housing units (cont.)

4. The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic smoke detection system installed in accordance with Section 907, and the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.

5. The space is arranged so as not to obstruct access to the required exits.

6. Each space is located to permit direct visual supervision by the facility staff.

25

Group I-2 — Nursing Homes (cont.)407.2.6 Nursing home cooking facilities

The 2015 IBC adopts additional allowances applicable only to nursing homes permitting cooking facilities open to corridor systems. These provisions are amended by the State Fire Marshal in the CBC.

26

14

Group I-2 — Nursing Homes (cont.)

Domestic cooking facility. Adopted by SFM, but with amendments.

27

Separation required

Group I-2 — Nursing Homes (cont.)

407.2.6 Nursing home cooking facilities. In Group I-2, Condition 1,occupancies, rooms or spaces that contain a cooking facility with domestic cooking appliances shall be permitted in fully sprinkleredbuildings where all of the following criteria are met:

1. The number of care recipients housed in the smoke compartment is not greater than 30.

2. The number of care recipients served by the cooking facility is not greater than 30.

3. Only one cooking facility area is permitted in a smoke compartment.

28

15

Group I-2 — Nursing Homes (cont.)407.2.6 Nursing home cooking facilities (cont.)

4. The types of domestic cooking appliances permitted are limited to ovens, cooktops, ranges, warmers and microwaves.

5. A domestic cooking range hood installed and constructed in accordance with the California Mechanical Code is provided over the cooktop or range.

29

Group I-2 — Nursing Homes (cont.)

407.2.6 Nursing home cooking facilities (cont.)

6. A portable fire extinguisher shall be installed in accordance with Section 906 of the California Fire Code.

30

16

Group I-2 — Nursing Homes (cont.)

The IBC contains additional requirements pertaining to the arrangement of domestic cooking appliances in areas open to the corridor, including:

• The installation of UL300A extinguishing systems• The interconnection of the extinguishing system to fuel and

electrical shutoffs• A remote location for shutoff of fuel and power• A timer that automatically shuts off the cooking appliances

within 120 minutes

Rather than imposing these additional installation requirements, the CBC (SFM) requires that these facilities be separated from the corridor.

31

Group I-2 — Care Suites

32

17

Group I-2 — Care Suites

407.4.4.5 Care suites containing sleeping room areas 407.4.4.5.1 Area. Care suites containing sleeping rooms shall be not greater than 5,000 square feet in area.

Exceptions:1. Care suites containing sleeping rooms shall be permitted to be not

greater than 7,500 square feet in area where an automatic fire sprinkler system is provided throughout the Group I-2 fire area.

2. Care suites containing sleeping rooms shall be permitted to be not greater than 10,000 square feet in area where an automatic fire sprinkler system is provided throughout the Group I-2 fire area and where an automatic smoke detection system is provided throughout the care suite and installed in accordance with Section 907.

33

Group I-2 — Care Suites (cont.)

Where a Group I-2 care suite containing sleeping rooms is located in a fire area protected by fire sprinklers, the suite is now permitted to be 7,500 sq. ft.

Where both sprinklers and smoke detection are provided, these suites can now be 10,000 sq. ft.

34

18

Group I-2 — Care Suites (cont.)

407.4.4.5.3 Travel distance. The travel distance between any point in a care suite containing sleeping rooms and an exit access door from that care suite shall be not greater than 100 feet.

This is not a change from the 2013 CBC; however, it was omitted from the IBC and is inserted here as an amendment to the 2016 CBC. This requirement is consistent with National Fire Protection Association (NFPA) 101-2012, Section 18.2.5.7.2.4(A).

35

Group I-2 — Care Suites (cont.)

407.4.4.6.1 Area. Care suites of rooms, other than sleeping rooms, shall have an area not greater than 10,000 square feet.

The IBC was revised to permit care suites of rooms, other than sleeping rooms, to have an allowable area of 12,500 sq. ft. and 15,000 sq. ft. where a smoke detection system is provided in the suite. These increases, however, are not permitted by NFPA101-2012, Section 18.2.5.7.3.3. The CBC is amended to continue the requirement for a floor area of not more than 10,000 sq. ft. for these suites. This avoids a conflict with NFPA 101-2012, The Life Safety Code®.

36

19

Group I-2 — Care Suites (cont.)

407.4.4.6.2 Exit access. Any room or care suite, other than sleeping rooms, with an area of more than 2,500 square feet shall have no fewer than two exit access doors from the room or care suite located in accordance with Section 1007.1.

Any room or care suite with an area greater than 2,500 sq. ft. requires at least two exit access doors. 2015 IBC language contained the requirement for care suites, but omitted the requirement for rooms. This is also a requirement of NFPA101-2012, Section 18.2.5.5.2.

37

Group I-2 — Care Suites (cont.)

407.4.3 Reserved

This section of the 2015 IBC adopts additional allowances applicable only to nursing homes that permit furniture located within corridor systems. These provisions are not adopted by the CBC.

These provisions conflict with the requirements of the State Fire Marshal contained in Title 19, CCR, Section 3.11.

38

20

Group I-2 — Smoke Barriers407.5 Smoke barriers. Smoke barriers shall be provided to subdivide every story used by persons receiving care, treatment or sleeping, and to divide other stories with an occupant load of 50 or more persons, regardless of occupancy or use, into no fewer than two smoke compartments.

A source of some confusion, it is now clearly stated that smoke barrier requirements are a concern on stories that are not necessarily used for patient care, treatment or sleeping, or otherwise classified as a Group I-2 occupancy.

This is consistent with requirements of NFPA 101-2012, The Life Safety Code®.

39

Group I-2 — Smoke Barriers (cont.)

407.5 Smoke barriers (cont.)

Such stories shall be divided into smoke compartments with an area of not more than 22,500 square feet in Group I-2, Condition 1, and not more than 40,000 square feet in Group I-2, Condition 2, and the distance of travel from any point in a smoke compartment to a smoke barrier door shall be not greater than 200 feet. The smoke barrier shall be in accordance with Section 709.

The 2015 IBC increased the maximum floor area of smoke compartments in hospitals from 22,500 square feet to 40,000 square feet. In NFPA 101-2012, The Life Safety Code®, the maximum area of a smoke compartment is 22,500 square feet. To avoid a conflict, the increase in floor area is not adopted.

40

21

Group I-2 — Smoke Barriers (cont.)

407.5 Smoke barriers

The maximum area for smoke compartments in all Group I-2 occupancies remains 22,500 square feet.

41

22,500 sq. ft.

Group I-2 — Smoke Barriers (cont.)

407.5 Smoke barriers

Exceptions:3. This requirement shall not apply to

the following:

3.1 Any story, not containing a Group I-2 or I-2.1 occupancy, that is located above a story containing a Group I-2 or I-2.1 occupancy.

42

22

Group I-2 — Smoke Barriers (cont.)

Exceptions (cont.):3.2. Areas that do not contain a Group I-2 or I-2.1 occupancy, where such

areas are separated from the Group I-2 or I-2.1 occupancy by a horizontal exit in accordance with Section 1025.2.

43

Group I-2 — Smoke Barriers (cont.)

Exceptions (cont.):3.3. Any story, not containing a

Group I-2 or I-2.1 occupancy, that is located more than one story below a story containing a Group I-2 or I-2.1 occupancy.

44

23

Group I-2 — Smoke Barriers (cont.)

Exceptions (cont.):3.4. Any story housing only

mechanical equipment where such story is located below a story containing a Group I-2 or I-2.1 occupancy and is separated from the story above by a horizontal assembly having not less than a 2-hour fire-resistance rating.

45

Group I-2 — Smoke Barriers (cont.)

407.5 Smoke barriers

The new Exception 3, with its four subsections, further clarifies that there are specific conditions under which a smoke barrier is not required on other floors or in other areas that are not Group I-2 or Group I-2.1 and are not used for patient care, treatment or sleeping.

This exception is consistent with NFPA 101-2012, the Life Safety Code®, Section 18.3.7.2.

46

24

General Building Height and

Area Limitations

BUILDING PLANNING

General Building Height & Area

503.1 General. Unless otherwise specifically modified in Chapter 4 and this chapter, building height, number of stories and building area shall not exceed the limits specified in Sections 504 and 506 based on the type of construction as determined by Section 602 and the occupancies as determined by Section 302 except as modified hereafter. Building height, number of stories and building area provisions shall be applied independently. Each portion of a building separated by one or more fire walls complying with Section 706 shall be considered to be a separate building.

Introduction to the reformatting of the building height and area tables.

48

25

General Building Height & Area (cont.)

What is happening here?

This is big news.

Table 503 is retired.

It has been replaced by three new tables that separate general building limitations into allowable height, allowable number of stories and allowable area, each of which must be applied independently.

49

General Building Height & Area (cont.)

50

504.3 Height in feet. The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3.

Sprinkler increase is now included in table information.

26

General Building Height & Area (cont.)

504.4 Number of stories. The maximum number of stories of a building shall not exceed the limits specified in Table 504.4.

51

Sprinkler increase is now included in table information.

General Building Height & Area (cont.)

For SFM-regulated occupancies, SFM adds (without area increase) to sprinkler information in tables to clarify double dipping is not permitted.

SFM-regulated occupancies: A, E, H, I, L, R and High Rise.

52

27

General Building Height & Area (cont.)506.2 Allowable area determination. The allowable area of a building shall be determined in accordance with the applicable provisions of Sections 506.2.1 through 506.2.4 and Section 506.3.

53

TABLE 506.2a,b,n

NS: Nonsprinklered S1: Sprinklered One Story SM: Sprinklered Multistoried

General Building Height & Area (cont.)

For SFM-regulated occupancies, SFM adds (without height increase) to sprinkler information in table to clarify double dipping is not permitted.

54

28

Separation of Occupancies

e. [SFM] Group I and F-1 occupancies and Group R-2.1 and F-1 occupancies shall have a 3-hour separation.

f. [SFM] Commercial kitchens not associated with cafeterias and similar dining facilities in Group I-2 and Group R-2.1 shall have a 2-hour separation and shall be protected by an automatic sprinkler system.

55

Separation of Occupancies (cont.)

What just happened here?

Model Code provisions of Table 508.4 require a 2-hour separation between Group I-2 and Group F-1.

SFM amendment (footnote e) requires a 3-hour separation between Group I-2 and Group F-1.

2015 Model Code revision classifies a separate commercial kitchen >2,500 sq. ft. as a Group F-1.

SFM amendment (footnote f) permits a 2-hour separation between commercial kitchen in Group I-2.

56

29

Incidental Uses509. Incidental Uses

57

Incidental Uses (cont.)

58

Footnote “a” is

missing

509. Incidental Uses

30

Incidental Uses (cont.)

509.3 Area limitations. The aggregate floor area of incidental uses shall not occupy more than 10 percent of the building area of the story in which they are located.

The intent of the 10 percent area limitation of incidental uses has been clarified. Not only any individual incidental use, but also all incidental uses together, shall not exceed 10 percent of the area of any one story.

59

Fire & Smoke Protection Features

FIRE PROTECTION

31

Projections The requirements for projections were first included in a table in the

2012 IBC. Now the table has been amended:

61

Projections (cont.)

705.2 Projections

Minimum distance from projections examples:

62

FSD: Fire separation distance

32

Projections (cont.)

705.2 Projections

Minimum distance from projections examples:

63

Projections (cont.)

705.2.3 Combustible projections. Combustible projections extending to within 5 feet of the line used to determine the fire separation distance shall be of not less than 1-hour fire-resistance-rated construction, Type IV construction, fire-retardant-treated wood or as required by Section 1406.3.

Exception: Type VB construction shall be allowed for combustible projections in Group R-3 and U occupancies with a fire separation distance greater than or equal to 5 feet.

Language has been deleted simplifying the requirements.

64

33

Projections (cont.)

705.2.3 Combustible projections

Previously, three separate thresholds were established to identify the scope of the requirement. Where any one of the three thresholds was exceeded, the limitations on combustible projections would apply. As a result, the most restrictive condition was always applied. With the revision, only the 5-foot fire separation distance threshold is now the controlling point for where the additional protection requirements apply.

65

Projections (cont.)

705.2.3 Combustible projections

Example:

66

34

Fire Wall Stability

706.2 Structural stability. Fire walls shall be designed and constructed to allow collapse of the structure on either side without collapse of the wall under fire conditions. Fire walls designed andconstructed in accordance with NFPA 221 shall be deemed to comply with this section.

67

Fire Wall Stability (cont.)

706.2 Structural Stability

CBC no longer points to using only double fire walls. NFPA 221 includes additional criteria for tied walls (example) or cantilever fire walls (not so common).

68

35

Smoke Barrier Walls

709. Smoke Barriers

709.4.1 Smoke-barrier walls separating smoke compartments. Smoke-barrier walls used to separate smoke compartments shall form an effective membrane continuous from outside wall to outside wall.

Really? Well not exactly.

69

Smoke Barrier Walls (cont.) From the IBC 2015 Code and Commentary:

Unintended consequences: Reformatting now forces smoke compartments to be formed with walls that must continue to the outside wall. Therefore, although the basic intent of smoke compartments is to form two completely separated spaces where smoke does not spread from one to the other, the text requires that the floor level must be divided from outside wall to outside wall, even though allowing a smoke barrier to terminate at another smoke barrier or back to itself may also create two adequately separated compartments.

70

36

Smoke Barrier Walls (cont.)

From the IBC 2015 Code and Commentary:

However, it seems reasonable that the building official could still allow smoke compartments to be formed by terminating at another smoke barrier by using the alternate method provisions of Section 104.11.

Reasonable to require an alternate method to comply with the intent?

71

Smoke Barrier Walls (cont.)709.4.2 Smoke-barrier walls enclosing areas of refuge or elevator lobbies. Smoke-barrier walls used to enclose areas of refuge in accordance with Section 1009.6.4, or to enclose elevator lobbies in accordance with Section 405.4.3, 3007.6.2 or 3008.6.2, shall form an effective membrane enclosure that terminates at a fire barrier wall having a level of fire protection rating not less than 1 hour, another smoke-barrier wall or an outside wall. A smoke and draft control door assembly as specified in Section 716.5.3.1 shall not be required at each elevator hoistway door opening or at each exit doorway between an area of refuge and the exit enclosure.

72

37

Smoke Barrier Walls (cont.)

73

709. Smoke Barriers

Corridor Dampers

202. Definitions

CORRIDOR DAMPER. A listed device intended for use where air ducts penetrate or terminate at horizontal openings in the ceilings of fire-resistance-rated corridors, where the corridor ceiling is permitted to be constructed as required for the corridor walls.

DAMPER. See “Ceiling radiation damper,” “Combination fire/smoke damper,” “Corridor damper,” “Fire damper” and “Smoke damper.”

74

38

Corridor Dampers (cont.)

Corridor damper

Where it goes:

75

Corridor Dampers (cont.)

Corridor damper – the details:

717.3.1 Damper testing. Dampers shall be listed and labeled in accordance with the standards in this section.

5. Corridor dampers shall comply with requirements of both UL 555 and UL 555S. Corridor dampers shall demonstrate acceptable closure performance when subjected to 150 feet per minute velocity across the face of the damper during the UL 555 fire exposure test.

UL 555: Fire Dampers/UL 555S: Smoke Dampers

Must be fire/smoke & dynamic

76

39

Corridor Dampers (cont.)

717.3.2.4 Corridor damper ratings. Corridor dampers shall have the following minimum ratings:

1. One-hour fire-resistance rating,

2. Class I or II leakage rating as specified in Section 717.3.2.2.

77

Corridor Dampers (cont.)715.5 Where required; ceiling radiation dampers and corridor dampers

717.5.4.1 Corridors. Duct and air transfer openings that penetrate corridors shall be protected with dampers as follows.

1. A corridor damper shall be provided where corridor ceilings, constructed as required for the corridor walls as permitted in Section 708.4, Exception 3, are penetrated.

2. A ceiling radiation damper shall be provided where the ceiling membrane of a fire-resistance-rated floor-ceiling or roof-ceiling assembly, constructed as permitted in Section 708.4, Exception 2, is penetrated.

3. A listed smoke damper designed to resist the passage of smoke shall be provided at each point a duct or air transfer opening penetrates a corridor enclosure required to have smoke and draft control doors in accordance with Section 716.5.3.

78

40

Fire Protection Systems

FIRE PROTECTION

Limited Area Sprinkler Systems

903. Automatic Sprinkler Systems

903.3.8 Limited area sprinkler systems. Limited area sprinkler systems shall be in accordance with the standards listed in Section 903.3.1 except as provided in Sections 903.3.8.1 through 903.3.8.5.

903.3.8.1 Number of sprinklers. Limited area sprinkler systems shall not exceed six sprinklers in any single fire area.

903.3.8.2 Occupancy hazard classification. Only areas classified by NFPA 13 as Light Hazard or Ordinary Hazard Group 1 shall be permitted to be protected by limited area sprinkler systems.

80

41

Limited Area Sprinkler Systems (cont.)

903.3.8 Limited Area Sprinkler Systems

81

Limited Area Sprinkler Systems (cont.)

Where are limited area sprinkler systems required?

In existing health care facilities, NFPA 101-2012, The Life Safety Code®, Section 19.3.5.9 requires such systems for the protection of hazardous areas.

NFPA 101-2012, The Life Safety Code®, Section 9.7.1.2 also limits the number of sprinklers to not more than six.

82

42

Visible Fire Alarms

83

Visible Fire Alarms – Group I-2 & I-2.1

907.5.2.3 Visible alarms. Visible alarm notification appliances shall be provided in accordance with Sections 907.5.2.3.1 through 907.5.2.3.4.

Exceptions:1. In other than Group I-2 and I-2.1, visible alarm notification appliances are not

required in alterations, except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed.

2. Visible alarm notification appliances shall not be required in enclosed exit stairways, enclosed exit ramps, exterior exit stairs and exterior exit ramps.

3. Visible alarm notification appliances shall not be required in elevator cars.

4. Visual alarm notification appliances are not required in critical care areas of Group I-2 Condition 2 occupancies that are in compliance with Section 907.2.6, Exception 2.

84

43

Smoke Control

85

Smoke Control909.4.7 Smoke control system interaction. The design shall consider the interaction effects of the operation of multiple smoke control systems for all design scenarios.

It is not uncommon for a high-rise building to contain multiple systems, such as an atrium with smoke control, pressurized stairways and hoistway pressurization used as an option for compliance with enclosed elevator lobby requirements. If these three smoke control systems are running simultaneously, they may not work as intended unless the interaction effects are evaluated during the design for all possible design fire scenarios.

86

44

Smoke Control (cont.)

909.5.3 Opening protection. Openings in smoke barriers shall be protected by self-closing devices or automatic closing devices actuated by the required controls for the mechanical smoke control system. Door openings shall be protected by fire door assemblies complying with Section 716.5.3.

87

Smoke Control (cont.)909.5.3 Opening protection

Exceptions:3. In Group I-2, I-2.1, R-2.1 and ambulatory care facilities, where a

pair of opposite swinging doors are installed across a corridor in accordance with Section 909.5.3.1, the doors shall not be required to be protected in accordance with Section 716. The doors shall be close fitting within operational tolerances and shall not have a center mullion or undercuts in excess of ¾ inch, louvers or grilles. The doors shall have head and jamb stops and astragals or rabbets at meeting edges. Positive-latching devices are required. Doors installed across corridors shall comply with Section 1010.1.1.

88

45

Smoke Control (cont.)909.5.3 Opening protection

Exceptions:4. In Group I-2, I-2.1 and ambulatory care facilities, where such

doors are special-purpose horizontal sliding, accordion or folding door assemblies installed in accordance with Section 1010.1.4.3 and are automatic closing by smoke detection in accordance with Section 716.5.9.3. The doors shall be close fitting within operational tolerances, and shall not have undercuts in excess of ¾ inch, louvers or grilles. Where permitted by the manufacturer’s listing, positive-latching devices are not required. Doors installed across corridors shall comply with Section 1010.1.1.

89

Means of Egress

MEANS OF EGRESS

46

Means of Egress — Ceiling Height1003.2 Ceiling height

1003.3 Protruding objects1003.3.1 Headroom. Protruding objects are permitted to extend below the minimum ceiling height required by Section 1003.2 provided a minimum headroom of 80 inches shall be provided for any walking surface, including walks, corridors, aisles and passageways. In other than Group I-2 and Group I-2.1 occupancies, 50 percent of the ceiling area of a means of egress shall be permitted to be reduced in height by protruding objects.

Exception: Door closers and stops shall not reduce headroom to less than 78 inches.

A barrier shall be provided where the vertical clearance is less than 80 inches high. The leading edge of such a barrier shall be located 27 inches maximum above the floor.

91

Means of Egress — Ceiling Height (cont.)

Health care occupancies where smoke zones are provided require additional ceiling volume for the accumulation of smoke. This is known as “bank down” capacity.

92

Permitted Ceiling Projections

47

Means of Egress — Occupant Load

Section 1004

OCCUPANT LOAD

93

Means of Egress — Occupant Load

1004.1.1 Cumulative occupant loads

1004.1.1.1 Intervening spaces or accessory areas. Where occupants egress from one or more rooms, areas or spacesthrough others, the design occupant load shall be the combined occupant load of interconnected accessory or intervening spaces. Design of egress path capacity shall be based on the cumulative portion of occupant loads of all rooms, areas or spaces to that point along the path of egress travel.

NOTE: Design of egress path egress capacity refers only to means of egress sizing. Calculations are not to be used for determining the number of exits.

94

48

Means of Egress — Occupant Load (cont.) 1004.1.1 Cumulative occupant loads

1004.1.1.1 Intervening spaces or accessory areas

95

150 + 10 = 160160 x .5 = 80

+ 20 100

Cumulative occupant loads for intervening spaces

Means of Egress — Number of Exits

1006. NUMBERS OF EXITS AND EXIT ACCESS DOORWAYS

1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1.

The content of Table 1014.3, Common Path of Egress Travel, and Table 1015.1, Spaces with One Exit or Exit Access Doorway, have been combined into a new Table 1006.2.1.

96

49

Means of Egress — Number of Exits (cont.)1006.2.1 Egress based on occupant load and common path of egress travel distance

Exceptions:

1. In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and the common path of egress travel does not exceed 125 feet.

2. Care suites in Group I-2 occupancies complying with Section 407.4.

97

Means of Egress – Number of Exits (cont.)1006. NUMBERS OF EXITS AND EXIT ACCESS DOORWAYS

98

50

Means of Egress – Number of Exits (cont.) A closer look at Table 1006.2.1 Group I-2 requirements.

99

Means of Egress – Number of Exits (cont.)

There could be a conflict between the maximum occupant load and the common path of egress travel requirements for the number of exits. Both requirements must be reviewed and the most restrictive shall apply.

100

51

Means of Egress – Number of Exits (cont.)

There are many existing unsprinklered Group I-2 occupancies. However, there are no criteria for an unsprinklered Group I-2 in the table. NFPA 101-2012, The Life Safety Code®, does not regulate the common path of egress travel in existing health care occupancies.

101

Means of Egress

102

Section 1007

EXIT AND EXIT ACCESS

DOORWAY CONFIGURATION

52

Means of Egress — Separation Distance1007.1.1.1 Measurement point. The separation distance required in Section 1007.1.1 shall be measured in accordance with the following:

1. The separation distance to exit or exit access doorways shall be measured to any point along the width of the doorway.

103

Means of Egress — Separation Distance (cont.)

1007.1.1.1 Measurement point (cont.).The separation distance required in Section 1007.1.1 shall be measured in accordance with the following:

2. The separation distance to exit access stairways shall be measured to the closest riser.

3. The separation distance to exit access ramps shall be measured to the start of the ramp run.

Do not confuse these requirements with interior exit stairways and interior exit ramps, which will always have enclosures with exit doors.

104

53

Means of Egress

105

Section 1009

ACCESSIBLE MEANS OF EGRESS

Means of Egress — Two-Way Communication

1009.8 Two-Way Communication. A two-way communication system complying with Sections 1009.8.1 and 1009.8.2 shall be provided at the landing serving each elevator or bank of elevatorson each accessible floor that is one or more stories above or below the story of exit discharge.

Two-way communication is required unless there is an exception.

106

54

Means of Egress — Two-Way Communication (cont.)1009.8 Two-Way Communication

Exceptions:

1. Two-way communication systems are not required at the landing serving each elevator or bank of elevators where the two-way communication system is provided within areas of refuge in accordance with Section 1009.6.5.

2. Two-way communication systems are not required on floors provided with ramps conforming to the provisions of Section 1012.

3. Two-way communication systems are not required at the landings serving only service elevators that are not designated as part of the accessible means of egress or serve as part of the required accessible route into a facility.

107

Means of Egress — Two-Way Communication (cont.)1009.8 Two-Way Communication

Exceptions (cont.):

4. Two-way communication systems are not required at the landings serving only freight elevators.

5. Two-way communication systems are not required at the landing serving a private residence elevator.

108

55

Means of Egress

109

Section 1010

DOORS, GATES AND TURNSTILES

Means of Egress — Delayed Egress1010.1.9.7 Delayed egress

5. The egress path from any point shall not pass through more than one delayed egress locking system.

Exception: In Group I-2 or I-3 occupancies, the egress path from any point in the building shall pass through not more than two delayed egress locking systems provided the combined delay does not exceed 30 seconds.

110

+

56

Means of Egress — Electrical Rooms

1010.1.10 Panic and fire exit hardware.

Electrical rooms with equipment rated 800 amperes or more and over 6-feet wide, and that contain overcurrent devices, switching devices or control devices with exit or exit access doors, shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.

111

Means of Egress

112

Section 1023INTERIOR

EXIT STAIRWAYS AND RAMPS

57

Means of Egress — Interior Exit Stairway Extension1023.3.1 Extension. Where interior exit stairways and ramps are extended to an exit discharge or a public way by an exit passageway, the interior exit stairway and ramp shall be separated from the exit passageway by a fire barrier constructed in accordance with Section 707 or a horizontal assembly constructed in accordance with Section 711, or both. The fire-resistance rating shall be not less than that required for the interior exit stairway and ramp. A fire door assembly complying with Section 716.5 shall be installed in the fire barrier to provide a means of egress from the interior exit stairway and ramp to the exit passageway. Openings in the fire barrier other than the fire door assembly are prohibited. Penetrations of the fire barrier are prohibited.

113

Means of Egress — Interior Exit Stairway Extension (cont.)

1023.3.1 Extension

Exceptions:

1. Penetrations of the fire barrier in accordance with Section 1023.5 shall be permitted.

2. Separation between an interior exit stairway or ramp and the exit passageway extension shall not be required where there are no openings into the exit passageway extension.

114

58

Means of Egress — Interior Exit Stairway Extension (cont.) Interior Exit Stairway extension:

Yes, the separation might seem redundant, but this change affirms that it is not. The passageway may have penetrations, but it must have no openings if the separation is omitted.

115

116

EXISTING STRUCTURES

Existing Buildings

59

Existing Buildings Chapter 34A of the California Building Code continues to be published.

This chapter is now applicable only to OSHPD 1 buildings.

117

Existing Buildings (cont.) Chapter 34, Existing Structures,

has been deleted from the 2016 CBC.

The 2016 California Building Standards Code now includes Title 24, Part 10, the 2016 California Existing Building Code.

All existing structures except OSHPD 1 are now regulated by the 2016 California Existing Building Code.

118

60

119

Referenced Standards

NFPA STANDARDS

NFPA Standards

13-2016 Installation of Sprinkler Systems

14-2013 Installation of Standpipe and Hose Systems

17A-2013 Wet Chemical Extinguishing Systems

20-2016 Installation of Stationary Fire Pumps for Fire Protection

24-2016 Installation of Private Fire Service Mains and their Appurtenances

37-2015 Installation and Use of Stationary Combustion Engines and Gas Turbines

58-2014 Liquefied Petroleum Gas

120

61

NFPA Standards (cont.)72-2016 National Fire Alarm and Signaling Code

80-2016 Fire Doors and Other Opening Protectives

99-2015 Health Care Facilities Code

110-2016 Emergency and Standby Power Systems

418-2011 Standard for Heliports

704-2012 Standard System for the Identification of the Hazards of Materials for Emergency Response

2001-2015 Clean Agent Fire Extinguishing Systems

121

Yes, We’re Done

122

62

Thank You

Nanci TimminsChief Fire and Life Safety Officer, [email protected]

John DonelanFire and Life Safety Officer II, OSHPDMember, Hospital Building Safety [email protected]

123

Questions

Online questions:Type your question in the Q & A box, hit enter

Phone questions:To ask a question, hit *1

63

Upcoming Programs

2016 Update to the California Building Standards Code Webinar Series

Webinar 2 – Administrative, Architectural, MEP Systems and Pharmacy ProvisionsMay 15, 2017, 1:30 – 3:30 p.m., Pacific Time

Webinar 3 – Structural ProvisionsMay 22, 2017, 1:30 – 3:30 p.m., Pacific Time

For additional information, visit www.calhospital.org/2016-CBSC-updates.

Thank You and Evaluation

Thank you for participating in today’s seminar. An online evaluation will be sent to you shortly. Full attendance and completion of the online evaluation and attestation are required to receive CEs. CEs are complimentary and available for the registrant only.

For education questions, contact Amber McEwen at (916) 552-7578 or [email protected].