21.00-00ADWG.
21.07-01TERMINAL POLE, SINGLE-PHASE AND TWO-PHASE CUTOUT ASSEMBLY21.07-03TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY
HORIZONTAL CONSTRUCTION, 200 AMP 21.07-05
21.10-01BTERMINAL POLE, SUBSTATION PILASTER
21.10-03
VERTICAL CONSTRUCTION, 200 AMP 21.07-04A
200 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.07-06
TERMINAL POLE, 600 AMP SWITCH ASSEMBLY
SECONDARY RISER POLE
VENTILATOR BOOT INSTALLATION, ALL 500 & 1000 KCM PRIMARY RISERS
21.08-08
21.08-01A
TERMINAL POLE, SUBSTATION PILASTER 21.10-01A
FAULTED CIRCUIT INDICATOR, 600 AMP TERMINAL POLE
TERMINAL POLE, 600 AMP SWITCH ASSEMBLY
SUBSTATION CONNECTIONS, STANDARD TWO-BANK SUBSTATION 21.10-02
21.08-01B21.08-03
21.09-01
SECTION 21 - OH-UG TRANSITION
TABLE OF CONTENTS
SUBSTATION CONNECTIONS, HIGH DENSITY SUBSTATION
600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07A600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07B
21.05-05AU-GUARD FILL21.05-05BCABLE GRIP APPLICATION
0
2
1
APPR.REVISED BY CK'D
3
21.10-01CTERMINAL POLE SUBSTATION PILASTER, DOUBLE CIRCUIT
ELKINS10/12/10 CECCONI GUINN
ELKINS4/11/11 CECCONI BURLISON
SINGLE-PHASE REVERSE RISER - 200 AMP URD TO OVERHEAD 21.01-0221.01 SINGLE-PHASE PRIMARY RISERS
ELKINS4/17/12 KATIGBAK BURLISON
21.05 CABLE GUARD, U-GUARD AND CONDUIT RISERS
21.07 TERMINAL POLES, SMALL CABLE
21.08 TERMINAL POLES, LARGE CABLE
21.09 RISERS POLES, SECONDARY
21.10 SUBSTATION FEEDER EXITS
VERTICAL CONSTRUCTION, 200 AMP DOUBLE CIRCUIT 21.07-04B
ADCOCK4/4/13 KATIGBAK DANNA
NOTES:
1. MAKE LEAD FROM BOTTOM OF ARRESTER TO GROUND BRAIDS AS SHORT AS POSSIBLE. GROUND BRAID LENGTH
4/17/12 BURLISON BURLISON ELKINS
SINGLE-PHASE REVERSE RISER - 200 AMP
URD TO OVERHEAD0
1
APPR.REVISED BY CK'D
2
DETAIL 'A' - WARNING SIGNCN 9220150597
3
2. INSTALL WARNING SIGN BETWEEN SWITCH BRACKET AND NEUTRAL.
3. FUSE SWITCH PER ENGINEERING INSTRUCTIONS.
24"
72"
4"
TOP BRACKET
#2 WP
#6 SD BC
#6 WP
BRAIDS TO #4 SD BC ANDCONNECT TO SYSTEM NEUTRAL
CABLE UGUARDTO BE IN QUARTEROF POLE
SIDE VIEW
#6 SD BC
5"
4"
BOLT
6"
NEUTRAL - ATTACH GROUND
SEE NOTE 2
SEE DETAIL 'B'CN 9220201401SWITCH BRACKET
DETAIL 'B'CABLE CLAMP
RUBBER PAD
MOUNTING BRACKETCN 9220234384
12"
5/31/13 DANNA DANNA ADCOCK
12/17/14 EANES FLETCHER ADCOCK
SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.
21.01-02
DEF
X
DEPDEMDEC
21.05-05ADWG.10/12/10 DANNA GUINN ELKINS
U-GUARD FILL0
3
2
1
APPR.REVISED BY CK'D
U-GUARD SIZE FOR PRIMARY UNDERGROUND CABLE RUNS
PRIMARY CONCENTRIC NEUTRAL CABLE2-CABLE
U-GUARD SIZE
1-CABLE 3-CABLE
-
2"
-
3"
5"
3"1/0 AL SOL 15KV 175 MILS
500 KCM AL 15KV 175 MILS
SECONDARY CABLE
U-GUARD SIZE FOR SECONDARY UNDERGROUND CABLE RUNS
1-CIRCUIT
U-GUARD SIZE
3-CIRCUIT2-CIRCUIT
3"
3"
3"
2"
2"
2"
5"
5"
5"
3"
3"
2"
5"
5"
5"
5"
5"
3"
1"
1"
1"
2"
2"
2"
-
2"
2"
#2 AL UG TPX XLP
350 MCM AL UG TPX XLP
500 MCM AL UG QPX
4/0 AL UG QPX XLP
4/0 AL UG TPX XLP
2/0 AL UG TPX XLP
2 #6 AL ST. LT. CABLE
2 #10 CU ST. LT. CABLE
- - 5"1000 KCM AL 15KV 175 MILS
500 MCM AL UG TPX
5/24/12 DANNA BURLISON ELKINS
21.05-05BDWG.10/12/10 DANNA GUINN ELKINS
CABLE GRIP APPLICATION R
0
3
2
1
APPR.REVISED BY CK'D
CABLE GRIP SIZE FOR PRIMARY UNDERGROUND CABLE RUNS
PRIMARY CONCENTRIC NEUTRAL CABLE CABLE GRIP SIZE PER CONDUCTOR
2" X 2-1/2"
1" X 1-1/4"1/0 AL SOL 15KV 175 MILS
500 KCM AL 15KV 175 MILS
SECONDARY CABLE
CABLE GRIP SIZE FOR SECONDARY UNDERGROUND CABLE RUNS
2" X 2-1/2"
3" X 2-1/2"
3" X 2-1/2"
2" X 2-1/2"
2" X 2-1/2"
2" X 2-1/2"
1" X 1-1/4"
1" X 1-1/4"
1" X 1-1/4"
#2 AL UG TPX XLP
350 MCM AL UG TPX XLP
500 MCM AL UG QPX
4/0 AL UG QPX XLP
4/0 AL UG TPX XLP
2/0 AL UG TPX XLP
2 #6 AL ST. LT. CABLE
2 #10 CU ST. LT. CABLE
3" X 2-1/2"1000 KCM AL 15KV 175 MILS
500 MCM AL UG TPX
RECOMMENDED CABLE GRIP SIZE PER CIRCUIT
1. MOUNT SECOND CUTOUT AND BRACKET ON OPPOSITE SIDE FOR TWO-PHASE TERMINAL POLE.
3. USE #2 WP COPPER JUMPER WIRE FROM CUTOUT TO HOT LINE CLAMP.
CH
AN
CE
10/12/10 DANNA GUINN ELKINS
1
2
3
TERMINAL POLE, SINGLE-PHASE AND TWO-PHASE
CUTOUT ASSEMBLY
8" 4"
4. FORM THE 18" PIN STEM CONNECTOR AS SHOWN BEING CAREFUL NOT TO BEND THE #1/0 SOLIDAS IT ENTERS THE WATER SEAL AT CONNECTOR.
5. MAKE THE #6 SOFT DRAWN BARE COPPER LEAD FROM THE BOTTOM OF THE ARRESTER TO THE GROUND BRAIDSAS SHORT AS POSSIBLE WHILE MAINTAINING NOT LESS THAN 6" CLEARANCE BETWEEN CUTOUT IN THE OPENPOSITION AND THE GROUND BRAIDS. GROUND BRAID LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS
6. CHECK THAT CUTOUT DOOR WILL FALL CLEAR OF TERMINATOR AND CABLE.
7. ALL TERMINATOR POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.
8. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.
#6 SD BC
TO CLOSEST24" MIN.
PHASE WIRE
6"
SEENOTE
5
6
0
APPR.REVISED BY CK'D
43
2
1 ARUGTP10F
BILL OF MATERIALS
CATALOG
153534
CUTOUT, 15KV, 100ABRACKET, CUTOUTBOLT, MACHINE, 5/8" X 10"WASHER, SQUARE, 2-1/4"WASHER, SPRING COIL, 5/8"
CONNECTOR, STEM, ARRESTERARRESTER, 10KV, LIGHTNING
DESCRIPTION
220208013264
BKTCOSNGSTLF013308152106311263
FUSE15CO100F 22111211
1
1
QTY
11
11
1111
PERCU
NUMBERMACRO UNIT
CA1T15FM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
NOTES:
CH
ANC
E
KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0
2. TERMINATOR WITH 18" PIN STEM CONNECTOR ISSUED SEPARATELY. SEE DWG. 21.07-06.
21.07-01
DEF
X
DEPDEMDEC
5
RCRISERN2CUF 9220218857 WIRE, COPPER, #2 SOLID15 126 1 1KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0
KHLC7933F 9220184794 CLAMP, HOT LINE, ALUM, LARGE, 336-79516 1
4
5 8/1/14 LOOSIER DANNA ADCOCK
6 12/17/14 EANES FLETCHER ADCOCK
#4 SD BC
GROUNDBRAIDS
POSSIBLE.
7 4/10/17 LOOSIER BURLISON ADCOCK
3
2
10/12/10 DANNA GUINN ELKINS
TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY
4" 8"
CLOSESTPHASE WIRE
24" TO
#6 SD BC
NOTES:
1. TERMINATOR WITH 18" PIN STEM CONNECTOR ISSUED SEPARATELY.2. USE #2 WP COPPER JUMPER WIRE FROM CUTOUT TO HOT LINE CLAMP.3. FORM THE 18" PIN STEM CONNECTOR AS SHOWN BEING CAREFUL NOT TO BEND THE #1/0 SOLID AS IT ENTERS THE WATER SEAL AT
CONNECTOR.4. MAKE THE #6 SOFT DRAWN BARE COPPER LEAD FROM THE BOTTOM OF THE ARRESTER TO THE GROUND BRAIDS AS SHORT AS
POSSIBLE WHILE MAINTAINING NOT LESS THAN 6" CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS.GROUND BRAID LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.
5. CHECK THAT CUTOUT DOOR WILL FALL CLEAR OF TERMINATOR AND CABLE.6. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.7. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.8. ROTATE OUTSIDE CUTOUTS FOR CLEARANCE AS NECESSARY.
SEENOTE
4
1
0
APPR.REVISED BY CK'D
43
2
1
BILL OF MATERIALS
CATALOGDESCRIPTION
32
1
3
QTYPERCU
NUMBERMACRO UNIT
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
CA3T15FM
9
SEE NOTE 2
5 2
6 2
CONNECTOR, STEM ARRESTERARRESTER, 19KV LIGHTINGWASHER, SPRING COIL, 5/8"WASHER, SQUARE, 2-1/4"BOLT, MACHINE, 5/8"X10"BRACKET, CUTOUT, TRI-MOUNTCUTOUT, 15KV, 100AINSULATOR, POST, POST,TIE,TOP,15/25KVSTUD, LINE POST, LP 5/8"X 12"WASHER, LOCK, SPRING,DOUBLE COILWIRE, TIE, #6, SOLID SD BARE COPPER
11222111118
153534220208013264013308152106070104221112080212072367013264
11061009
ARUGTP10F
BKTCOTRISTLF
FUSE15CO100FIHPTT15F
ISSTUDBOLT5812F
HTIEN6CSDF
4 5 6
SEE DWGS. 21.07-04AAND 21.07-04B.
21.07-03
DEF
X
DEPDEMDEC
RCRISERN2CUF 9220218857 WIRE, COPPER, #2 SOLID38 12
8
7 3 CLAMP, HOT LINE, ALUM, SMALL, 4/019220184790KHLC40N6F
7
9 3 1KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0KHLC7933F 9220184794 CLAMP, HOT LINE, ALUM, LARGE, 336-79539 1
8 8/15/14 LOOSIER DANNA ADCOCK
12/17/14 EANES FLETCHER ADCOCK9
GROUND BRAIDS
#4 SD BC
4/10/15 LOOSIER BURLISON ADCOCK10
NOTES:
2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILE MAINTAINING 6"
MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS. GROUND
4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.
4/5/13 DANNA DANNA ADCOCK
VERTICAL CONSTRUCTION, 200 AMP
1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DWG. 21.07-01.
0
APPR.REVISED BY CK'D
FRONT VIEWSIDE VIEWFRONT VIEW
36"
36"
24"
6"
42"
4" MAX
5"
36"
36"
24"
6"
42"
4" MAX.
FRONT VIEW
THREE-PHASE DEADEND CONSTRUCTION
5"
72"
24"
6"
42"
4" MAX.
5"
THREE-PHASE TANGENT CONSTRUCTION
SINGLE-PHASE DEADEND CONSTRUCTION SINGLE-PHASE TANGENT CONSTRUCTION
72"
4"
3
#6 SD BC #6 SD BC
#6 SD BC
72"
24"
42"
6"
5"
4" MAX.
72"
#2 WP COPPERCU RCRISERN2CUF
21.07-04A
DEF
X
DEPDEMDEC
8/1/14 DANNA DANNA ADCOCK
#6 SD BCGROUNDBRAIDS
#4 SD BC
#6 SD BC
GROUNDBRAIDS
#6 SD BC
#6 SD BC
#4 SD BC
#6 SD BC
GROUNDBRAIDS
GROUNDBRAIDS
4 12/17/14 EANES FLETCHER ADCOCK
FRONT VIEWSIDE VIEW
BRAIDS LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.
#6 SD BC
#4 SD BC
GROUNDBRAIDS
#4 SD BCTO SYSTEMNEUTRAL
#6 SD BC
#4 SD BC
GROUNDBRAIDS
#4 SD BCTO SYSTEMNEUTRAL
5 3/18/15 DANNA EANES ADCOCK
7. MAINTAIN 8" CLEARANCE BETWEEN LOWEST GUY WIRE AND CUTOUT.
4"
4"
NOTES:
2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILE MAINTAINING 6"
MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS. GROUND BRAID LENGTH SHOULD
4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.
4/4/13 DANNA DANNA ADCOCK
VERTICAL CONSTRUCTION, 200 AMP
DOUBLE CIRCUIT
1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DWG. 21.07-01.
0
2
1
APPR.REVISED BY CK'D
SIDE VIEW
3
IPIN23F
BKTFPIN18F
18"
36"
36"
5"
8"
24"
6"
42"
72"
FRONT VIEW
6"
6"
(FROM LEFT SIDE)
#6 SD BC
7. CAN BE CONSTRUCTED ON DOUBLE CIRCUIT POLES FRAMED WITH STEEL STAND OFF BRACKETS.
6" 6"
8/7/14 SALAS
#2 WP COPPERCU RCRISERN2CUF
21.07-04B
DEF
X
DEPDEMDEC
DANNA ADCOCK
12/17/14 EANES FLETCHER ADCOCK
NEUTRAL
#4 SD BC
#6 SD BC
#6 SD BC
GROUND BRAIDS
#4 SD BC
ALSO BE MAINTAINED AS SHORT AS POSSIBLE.
4" MAX.
NOTES:
2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.
3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILEMAINTAINING 6" MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAID.GROUND BRAID LENGTH SHOULD BE MAINTAINED AS SHORT AS POSSIBLE.
4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.
5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATER ATTACHED.
6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.
10/12/10 DANNA GUINN ELKINS
HORIZONTAL CONSTRUCTION, 200 AMP
1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DETAILS ON DWG. 21.07-01.
0
3
2
1
APPR.REVISED BY CK'D
FRONT VIEW SIDE VIEW
#6 SD BC
24"
6"
42"
4" MAX.
44" 16" 28"
44" 16" 28"
FRONT VIEW
#6 SD BC
SIDE VIEW
#6 SD BC
24"
6"
42"
4" MAX.
5"
8/31/11 DANNA BURLISON ELKINS
KHLC40N6F
KHLC7933FOR
12/12/11 BURLISON
ALL RISER LEADSTO BE #2 WP CU
RISER MAY BECONNECTED TO ANYPHASE AS DESIGNATEDBY ENGINEERING
BURLISON ELKINS
21.07-05
DEF
X
DEPDEMDEC12/17/14 EANES FLETCHER ADCOCK
#6 SD BC
#6 SD BC
#4 SD BC
#6 SD BC
GROUND BRAIDS
GROUND BRAIDS
5" KHLC40N6F
KHLC7933FOR
#4 SD BCTO SYSTEMNEUTRAL
GROUNDBRAIDS
GROUNDBRAIDS
1
4" MAX
200 AMP TERMINAL POLE, CABLE RISER ASSEMBLY
NOTES:
0
3
APPR.REVISED BY CK'D
SIDE VIEW
NEUTRAL
A
SECTION A-A
INSTALL CABLEGUARD IN BACKQUARTER OF POLE
#6 SD BC
3
2
1. IF DIRECT BURIED CABLE, INSTALL CABLE GUARD 12"BELOW GROUND LEVEL.
3. INSTALL LAG SCREW IN EACH HOLE OF MOLDING.
4. FOR OTHER CABLE SIZES, MATERIAL ITEMS SUCH ASCABLE GUARDS, GRIPS, AND CONNECTORS WILL CHANGE.SEE DWGS. 21.05-05A, 21.05-05B, 26.06-10A.
A
#6 SD BC
SEE NOTES
2. IF CABLE IN CONDUIT, INSTALL CABLE GUARD 4" BELOWCONDUIT.
1 AND 2
321 CRIS1UGPVC225WF
BILL OF MATERIALS - TERMINAL POLE RISER SINGLE-PHASE #1/0
TERM, KIT, 1/0, 200 AMP
RISER, U-GUARD, 2-1/4"CABLE GRIP, 1" X 1-1/4"
DESCRIPTION
CABGRP1X125FTRM10AL215KITF 1
13
MACRO UNIT
TMP1P10FM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
321 CRIS1UGPVC35WF
BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE #1/0
TERM, KIT, 1/0, 200 AMP
RISER, U-GUARD, 3-1/2"CABLE GRIP, 1" X 1-1/4"
DESCRIPTION
CABGRP1X125FTRM10AL215KITF 3
33
MACRO UNIT
TMP3P10FM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
10/26/10 DANNA GUINN ELKINS
5. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10'SECTION OF CABLE GUARD.
6. WHEN THE CABLE IS INSTALLED IN 4 INCH CONDUIT, USE
5/24/12 DANNA
4 INCH CONDUIT TO THE 3 INCH U-GUARD.
THE 3" VENTILATOR BOOT ( CU CRISVENTBOOT3F ,ITEM # 9220239095) TO MAKE THE TRANSITION FROM
7. ORIENT U-GUARD WITH BELL ENDS ON BOTTOM. WHENINSTALLING VENTILATOR BOOT, INSTALL U-GUARD OVERTHE FIRST STEP OF THE VENT BOOT.
BURLISON ELKINS
4 12/7/12 DANNA DANNA ADCOCK
ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F
21.07-06
DEF
X
DEPDEMDEC5 11/18/15 DANNA BURLISON ADCOCK
10/12/10 DANNA GUINN ELKINS
TERMINAL POLE, 600 AMP SWITCH ASSEMBLY0
APPR.REVISED BY CK'D
NOTES:
1. SEE DWG. 21.08-01B FOR BILL OF MATERIALS AND TERMINATOR CONNECTION DETAIL.
2. USE GROUND BRAIDS FOR NEUTRAL AND CROSS BONDING CONNECTIONS.
2
3. IT IS ACCEPTABLE TO LOCATE SWITCH AND UGUARD ON OTHER SIDE OF GUYS IFNECESSARY. LOCATING UGUARD AWAY FROM TRAFFIC IS PREFERRED.
3
FRONT VIEWSIDE VIEW
4
2
7
11
10
#6 SD BC
1
4"
36"
GROUNDBRAID
12"
36"
36"
5"
BRACKET
24"
30"
28-3/4"
4"
SEE NOTE 3
SEE NOTE 3
#2 SD BC
5
3
8 9BOLT
BOTTOM
12/22/11 BURLISON BURLISON ELKINS
5/31/13 McCONNELL DANNA ADCOCK
SEE NOTE 4SEE NOTE 4
4. INSTALL FAULT INDICATOR AS SHOWN ON DWG. 21.08-08.
12
4 7/16/14 LOOSIER
21.08-01A
DEF
X
DEPDEMDEC
6
4 5 6
DANNA ADCOCK
TERMINAL POLE, 600 AMP SWITCH ASSEMBLY0
APPR.REVISED BY CK'D
NOTES:
1. SEE DWG. 21.08-01A FOR DESIGN SPECIFICATIONS.
3
8
1
12
ARUGTP10F
KLC2H1KUF
GUFTPE2F
BKTSBDSWSTLF
KH10N2ALF
STIEF795ALF
SW156SBDF
IHPTT15F
S600TPFM
ISSTUDBOLT5810F
12
8 12
8/10/10 DANNA GUINN ELKINS
7/16/14 LOOSIER
21.08-01B
DEF
X
DEPDEMDEC
9
KLC2HUF
SEE NOTE 2
2. SEE DWGS. 21.08-07A AND 21.08-07B FOR CABLE RISER ASSEMBLY DETAIL.
11
12
10
9
8
7
6
54
3
2
1
NUT, HEX, 1/2 IN, SS, THREAD,1/2"
WASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD2 HOLE SPADE WITH STEMCONNECTOR H FRAME COMPRESSION #1/0 TO #2 ALUMINUM
CONNECTOR LUG COMPRESSION 2-HOLE 795 MCM ALUMINUMWASHER, ROUND, RD,1/2,SS,1.375" ODWASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLT
BILL OF MATERIALS
CATALOG
220208
SWITCH OH 15KV 600 A SGL BLADE DIS NL BRK
BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADCONNECTOR LUG COMPRESSION 2-HOLE 1000 MCM UG ONLYCONNECTOR HOT LINE CLAMP #4/0 TO #6
INSULATOR SUPPORT STUDBOLT 5/8 IN X 10 IN STLINSULATOR POST, HORIZONTAL, TIE TOP, STUD BASE 15/25 KVSIDE TIE, F NECK, 795 KCM ALUMINUM
GND UG PEFTERM POLE WIRE ONLY # 2 CU SD
ARRESTER, UG RISER TERMINAL POLE10 KV CLASS
BRACKET FOR SOLID BLADE DISCONNECT SWITCH, STEEL
DESCRIPTION
070282
9220162221
121434080212072366
260136
9220184790155334
155331
153111311221010928012277013163
3
3
3
3
3
3
3
2
2
2
3
2
42211
124
QTY
1
12
1
11
1
5
1
1
PERCU
NUMBERMACRO UNIT
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
CONNECTOR, STEM, ARRESTER153534 1
MACHINE BOLT,SQ,NUT,5/8"X12" WASHER, SQUARE, 2-1/4",GALVWASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COIL013264
013308152107 2
22
3
CONNECTOR, 2,BOLT,#4/0,CUCONNECTOR, GROUND, TF,GND,EYEBOLTCONNECTOR, GND,5/8,ROD,2,CUBOLT, HEX HEAD, MACH,SQ,NUT,3/4"X18"152125
160123160182161234
1
2
11
3
WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COIL013264 1
ROUND,FLAT,STAINLESS,STEEL, FOR 1/2" BOLTBOLT, MACHINE, 1/2 IN, 2 IN, STEEL, HEX HD
WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD010928
012277013128013407152074 2
44
4
8
KHLC40N6F
KLC2H79ALF
WASHER, ROUND, RD,1/2,SS,1.375" OD10542504 2
WASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD
422
WASHER, ROUND, RD,1/2,SS,1.375" OD2
010928012277013163
10542504
010928012277013163
10542504
DANNA ADCOCK
4 3/18/15 LOOSIER EANES ADCOCK
5 4/10/15 DANNA DANNA ADCOCK
21.08-03DWG.
NOTES:
1. INSTALL BACKING PLATE BELOW CONDUIT IF REQUIRED
2. INSTALL VENTILATOR CABLE BOOT FLUSH WITH GRADE.
3. INSTALL CABLE GUARD (ENLARGED END) OVER TOP OF VENTILATOR BOOT
COUPLING
80 LB BAGS OF CONCRETE
WOOD POLE
1/4" x 2" LAG
POLES - USE
SCREWS FOR WOODPOLES - STAINLESSSTEEL BANDINGFOR CONCRETE
ENLARGED AREA OF PLASTICCABLE FOR OVERLAPPINGEACH SECTION
5" PLASTIC CABLE GUARD
VENTILATOR BOOTCN 323437
10/26/10 DANNA GUINN ELKINS
VENTILATOR BOOT INSTALLATION,
ALL 500 AND 1000 KCM PRIMARY RISERS
6"
GRADE
R
0
3
2
1
APPR.REVISED BY CK'D
2 BANDS
4/11/11 DANNA BURLISON ELKINS
600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY0
2
1
APPR.REVISED BY CK'D
SECTION A-A
INSTALL U-GUARD ANDCENTER TERMINALS INBACK QUARTER OF POLE
GROUND BRAIDS
3
A
NOTES:
1. INSTALL LAG SCREWS IN EACH HOLE OF MOLDING.
3. SEE DWG. 21.08-07B FOR BILL OF MATERIALS.
2. SEE DWG. 21.08-08 FOR FAULT INDICATOR DETAILS.
2
1
4
#6 SD BC
CONNECTOR
X
4. WHEN INSTALLED PROPERLY, THE LC SHIELD GROUND BRAID HAS TWO LEADS. USE ONE TO DO THE CROSSBOND AND THE OTHER TO CONNECT TO THE NEUTRAL.
SEE NOTE 4
12" MAX. APPLIES TO600 AMP LC SHIELD
#2 BOLTED CONNECTOR
H-BLOCK
(GROUNDING NOT SHOWN FOR CLARITY)
PRIMARY CABLE ONLY
3
XX
XX
X
XX
XX
XX
XX
XX
XX
5. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10' SECTION OF CABLE GUARD.
21.08-07A
DEF
X
DEPDEMDEC
11/18/15 DANNA BURLISON ADCOCK
#2 SD BC
H-BLOCK
ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F
21.08-07BDWG.
600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY R
0
3
2
1
APPR.REVISED BY CK'D
NOTES:
1. SEE DWG. 21.08-07B FOR BILL OF MATERIALS.
2. MATERIAL ITEMS SUCH AS CABLE GUARDS, CONNECTORS, ETC. WILL CHANGE FOR OTHER CABLE SIZES. SEEDWGS. 21.05-05A, 21.05-05B AND 26.06-10A.
4321 CRIS1UGPVC50WF
BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE 500MCM
VENT BOOTTERM KIT, 500 KCMIL
U-GUARD, 10'-5"CABLE GRIP, 2 X 2-1/2"
DESCRIPTION
CABGRP2X250FTRM500AL615KITFCRISVENTBOOTF 1
333
MACRO UNIT
TMP3P500FM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
4321 CRIS1UGPVC50WF
BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE 1000MCM
VENT BOOTTERM KIT, 1000 KCMIL
U-GUARD, 10'-5"CABLE GRIP, 2 X 2-1/2"
DESCRIPTION
CABGRP3X250FTRM1KAL615KITFCRISVENTBOOTF 1
333
MACRO UNIT
TMP3P1KFM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
4/11/11 DANNA BURLISON ELKINS
21.08-08DWG.
NOTES:
AND CABLE NEUTRAL
AND PLASTIC WIRE TIETO POLE WITH STAPLECOIL LEADS AND SECURE
SEE DETAIL "B"
BETWEEN TERMINATORBE INSTALLEDSENSOR UNIT MUST
UNDER STAPLEPLASTIC WIRE TIE
CONDUCTOROVER FAULT INDICATORDO NOT STAPLE
BELOW TERMINATORIMMEDIATELY
WATER STOP
INSTALL FCI
FAULTED CIRCUIT INDICATOR,
600 AMP TERMINAL POLE
1. CROSS BOND ALL 600A TERMINATORS PER DWG. 21.08-07A.
DETAIL "B"
1
DETAIL "A"
SEE DETAIL "A"
R
GROUND BRAID
0
3
2
1
APPR.REVISED BY CK'D
TIE, CABLE, PLASTIC MARKER, 'ZIP'INDICATOR, FAULT, 3 PH, LG, DISBRACKET, OH, FAULT, IND, MOUNTINGSTAPLE, GALVANIZED, 1/4" X 1-1/2"SCREW, LAG, 1/4" X 2"
BILL OF MATERIALS
CATALOGDESCRIPTION
014111015271
FCIOLD12N3PFF 070284323457443303
1
31132
QTYPERCU
NUMBERCOMPATIBLE
UNITQTY
REQ'D
X X X X X X XXXX
XX
XX
XX XX
4/11/11 DANNA BURLISON ELKINS
NEUTRAL
4" MAX
10/26/10 DANNA GUINN ELKINS
SECONDARY RISER POLE
12"
36"
0
2
1
APPR.REVISED BY CK'D
2
1 CRIS1UGPVC_F
BILL OF MATERIALS
ITEM
014111
GRIP, CABLE (VARIES WITH WIRE SIZE)
SCREW, LAG, 1/4" X 2"GUARD, CABLE (VARIES WITH WIRE SIZE)
DESCRIPTION
-CABGRP_F -1
3
QTY
1115
PERCU
NUMBERMACRO UNIT
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
-
NOTES:
1. INSTALL LAG SCREW IN EVERY HOLE.2. IF DIRECT BURIED CABLE, INSTALL CABLE GUARD 12" BELOW GROUND LEVEL.3. IF CABLE IS INSTALLED IN 4" OR 6" CONDUIT, USE APPROPRIATE VENTILATOR BOOT. FOR 5" U-GUARD, USE
4. SEE DWGS. 21.05-05A AND 21.05-05B FOR GUARD AND GRIP SIZES.
1
2
5. USE APPROPRIATE H-BLOCK, BOLT-ON OR INSULINK CONNECTORS FOR SECONDARY TO SECONDARY ORSECONDARY TO TRANSFORMER CONNECTIONS. SECONDARY PEDESTAL CONNECTORS ARE NOTAPPROVED FOR THESE APPLICATIONS.
3
#6 SD BCSEE NOTE 6
6. INSTALL GROUND WIRE (IF REQUIRED) ON OUTSIDE OF CABLE GUARD.7. INSTALL CABLE GUARD ON QUARTER OF POLE.8. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10' SECTION OF CABLE GUARD.
11/10/11 ROBESON BURLISON ELKINS
5/24/12 DANNA
CU CRISVENTBOOTF, ITEM # 323437. FOR 3" U-GUARD, USE CU CRISVENTBOOT3F , ITEM # 9220239095.
9. ORIENT U-GUARD WITH BELL ENDS ON BOTTOM. WHEN INSTALLING VENTILATOR BOOT, INSTALL U-GUARDOVER THE FIRST STEP OF THE VENTILATOR BOOT.
BURLISON ELKINS
ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F
21.09-01
DEF
X
DEPDEMDEC11/18/15 DANNA BURLISON ADCOCK
TERMINAL POLE, SUBSTATION PILASTER0
2
1
APPR.REVISED BY CK'D
DETAIL 'A'CLUSTER MOUNT BRACKET DETAIL
NOTES:
1. SEE DWG 21.10-01B FOR BILL OF MATERIALS.2. GROUND ON POLE PROVIDED BY SUBSTATION CONSTRUCTION.
GROUND BRAIDS
SEE DETAIL 'A'
4
5
6
2
8
SEE NOTE 2
18"
1
GROUND PROVIDEDBY SUBSTATIONCONSTRUCTION3
3
X
XX
XX
XX
XX
XX
XX
XX
X
7
THREE-PHASETERMINATORBRACKETITEM # 9220197866
3. BOND U-GUARD TO POLE. USE 3 BANDS ON EACH 10' U-GUARD SECTION. USE 2 BANDSON VENTILATOR BOOT.
7
8/10/10 DANNA GUINN ELKINS
3/8/12 BURLISON BURLISON ELKINS
PILASTER POLEITEM # 328732
9INSTALL CABLE PROTECTORCU CRISPROT35F
21.10-01A
DEF
X
DEPDEMDEC11/18/15 DANNA BURLISON ADCOCK
4. BOND BRACKET TO POLE GROUND.
21.10-01BDWG.10/12/10 DANNA GUINN ELKINS
TERMINAL POLE, SUBSTATION PILASTER R
0
1
APPR.REVISED BY CK'D
NOTES:
1. SEE DWG 21.10-01A FOR DESIGN SPECIFICATIONS.
2
3
87654321 CRIS1UGPVC50CF
BILL OF MATERIALS
CATALOG
-
LUG, 2-HOLE, ARRESTER TYPELUG, 2-HOLE, 795
ARRESTER, LIGHTNING, RP, 10KVBKT AND MISC MAT FOR PILASTER POLE TERMINATIONTERMINATOR, 1000 KCM, 15KVGUARD, VENT, CABLE BOOT, 4" - 5"
CABLE GUARD, PVC, 5" X 10', CONCRETE/STEEL POLEGRIP, SINGLE EYE, 2-1/2" X 3"
DESCRIPTION
CABGRP3X250F -CRISVENTBOOTF -TRM1KAL615KITF -BKTTMP1000KPF -
ARUGTP10F -KLC2HUF -
KLC2H79ALF -33
13
3132
QTY
11
11
1111
PERCU
NUMBERMACRO UNIT
TMP3P1KPFM
CUITEMNO.
COMPATIBLE UNIT
QTYREQ'D
3/8/12 BURLISON BURLISON ELKINS
9 PILASTER POLEPCC18PILASTERF 3287321 1-
10/5/12 BURLISON BURLISON ADCOCK
TERMINAL POLE
SUBSTATION PILASTER, DOUBLE CIRCUIT0
2
1
APPR.REVISED BY CK'D
3
10/12/10 DANNA GUINN ELKINS
NOTES:
GROUND BRAIDS
18"
GROUND PROVIDEDBY SUBSTATIONCONSTRUCTION
2. BAND U-GUARD TO POLE. USE 3 BANDS ON 10' U-GUARD SECTION. USE 2 BANDS ON VENTILATORBOOT.
1. SEE DWG. 21.01-01B FOR BILL OF MATERIAL. ORDER QUANTITY OF 2 OF MACRO UNIT.
BANDING DETAIL
U-G
UARD
POLE
U-G
UARD
BAND EACH U-GUARDSECTION DIRECTLY TOPOLE
PILASTER POLEITEM # 328732
3/8/12 BURLISON BURLISON ELKINS
INSTALL CABLE PROTECTORCU CRISPROT35F
21.10-01C
DEF
X
DEPDEMDECDANNA BURLISON ADCOCK11/18/15
3. BOND BRACKET TO POLE GROUND.
21.10-02DWG.
NOTES:
VENTILATED BOOT
CONSTRUCTION TOSUBSTATION
FOR ADDITIONAL SPACE.SUBSTATION DEPT.REQUIRED CONTACTIF REGULATORS ARE
TERM. LUG
TERM. LUG
795 AAC
AMPAC WEDGE
2. INSTALL VENTILATED BOOT ON ALL FEEDER TERMINATIONS.
10/12/10 DANNA GUINN ELKINS
SUBSTATION CONNECTIONS,
STANDARD TWO-BANK SUBSTATION
CN 155464
CN 165277
CN 155328
8' MINIMUM
R
0
3
2
1
APPR.REVISED BY CK'D
PROVIDE GROUND
SUBSTATION GROUND GRID
1. DISTRIBUTION CONSTRUCTION WILL INSTALL 795 AAC CONDUCTORS FROM UG TERMINATION TO THE CIRCUIT BREAKER LINE DISCONNECT AND TO THE BYPASS SWITCH. DISTRIBUTION CONSTRUCTION WILL ALSO MAKE CABLE NEUTRAL CONNECTION TO THE GROUND (NEUTRAL) PROVIDED BY SUBSTATION CONSTRUCTION ON THE PILASTER POLE.
21.10-03DWG.
SUBSTATION BUS
AND MAKE CONNECTIONTO BUS AND CONNECT
DISTRIBUTION PERSONNELWILL INSTALL CONDUCTOR
VENTILATED BOOT
795 JUMPER
4 HOLE LUG
SUBSTATION PERSONNELTO DRILL TERMINAL MOUNTING HOLES ONBUS WORK
PER STATION GENERAL LAYOUT
10/12/10 DANNA GUINN ELKINS
SUBSTATION CONNECTIONS,
HIGH DENSITY SUBSTATION
4'-0" 4'-0"
R
0
3
2
1
APPR.REVISED BY CK'D
NEUTRAL (GROUND).CABLE NEUTRAL TO POLE
GROUND GRID
#6 SD BC
GROUNDBRAID
#6 SD BC
# 2 BC CROSS BOND
SEE NOTE 2
NOTES:
1. INSTALL VENTILATED BOOT ON ALL FEEDER TERMINATIONS.
2. CONNECT EACH INDIVIDUAL GROUNDING BRAID FROM TERMINATOR TO THE NEUTRAL.
SUBSTATION CONSTRUCTIONTO PROVIDE NEUTRAL ON POLE