21.00-00A DWG. 21.07-01 TERMINAL POLE, SINGLE-PHASE AND TWO-PHASE CUTOUT ASSEMBLY 21.07-03 TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY HORIZONTAL CONSTRUCTION, 200 AMP 21.07-05 21.10-01B TERMINAL POLE, SUBSTATION PILASTER 21.10-03 VERTICAL CONSTRUCTION, 200 AMP 21.07-04A 200 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.07-06 TERMINAL POLE, 600 AMP SWITCH ASSEMBLY SECONDARY RISER POLE VENTILATOR BOOT INSTALLATION, ALL 500 & 1000 KCM PRIMARY RISERS 21.08-08 21.08-01A TERMINAL POLE, SUBSTATION PILASTER 21.10-01A FAULTED CIRCUIT INDICATOR, 600 AMP TERMINAL POLE TERMINAL POLE, 600 AMP SWITCH ASSEMBLY SUBSTATION CONNECTIONS, STANDARD TWO-BANK SUBSTATION 21.10-02 21.08-01B 21.08-03 21.09-01 SECTION 21 - OH-UG TRANSITION TABLE OF CONTENTS SUBSTATION CONNECTIONS, HIGH DENSITY SUBSTATION 600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07A 600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07B 21.05-05A U-GUARD FILL 21.05-05B CABLE GRIP APPLICATION 0 2 1 APPR. REVISED BY CK'D 3 21.10-01C TERMINAL POLE SUBSTATION PILASTER, DOUBLE CIRCUIT ELKINS 10/12/10 CECCONI GUINN ELKINS 4/11/11 CECCONI BURLISON SINGLE-PHASE REVERSE RISER - 200 AMP URD TO OVERHEAD 21.01-02 21.01 SINGLE-PHASE PRIMARY RISERS ELKINS 4/17/12 KATIGBAK BURLISON 21.05 CABLE GUARD, U-GUARD AND CONDUIT RISERS 21.07 TERMINAL POLES, SMALL CABLE 21.08 TERMINAL POLES, LARGE CABLE 21.09 RISERS POLES, SECONDARY 21.10 SUBSTATION FEEDER EXITS VERTICAL CONSTRUCTION, 200 AMP DOUBLE CIRCUIT 21.07-04B ADCOCK 4/4/13 KATIGBAK DANNA

21.01 SINGLE-PHASE PRIMARY RISERS 21.05 … 2 10/12/10 DANNA GUINN ELKINS TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY 4" 8" CLOSEST PHASE WIRE 24" TO #6 SD BC NOTES: 1. TERMINATOR WITH

Embed Size (px)

Citation preview

21.00-00ADWG.

21.07-01TERMINAL POLE, SINGLE-PHASE AND TWO-PHASE CUTOUT ASSEMBLY21.07-03TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY

HORIZONTAL CONSTRUCTION, 200 AMP 21.07-05

21.10-01BTERMINAL POLE, SUBSTATION PILASTER

21.10-03

VERTICAL CONSTRUCTION, 200 AMP 21.07-04A

200 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.07-06

TERMINAL POLE, 600 AMP SWITCH ASSEMBLY

SECONDARY RISER POLE

VENTILATOR BOOT INSTALLATION, ALL 500 & 1000 KCM PRIMARY RISERS

21.08-08

21.08-01A

TERMINAL POLE, SUBSTATION PILASTER 21.10-01A

FAULTED CIRCUIT INDICATOR, 600 AMP TERMINAL POLE

TERMINAL POLE, 600 AMP SWITCH ASSEMBLY

SUBSTATION CONNECTIONS, STANDARD TWO-BANK SUBSTATION 21.10-02

21.08-01B21.08-03

21.09-01

SECTION 21 - OH-UG TRANSITION

TABLE OF CONTENTS

SUBSTATION CONNECTIONS, HIGH DENSITY SUBSTATION

600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07A600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY 21.08-07B

21.05-05AU-GUARD FILL21.05-05BCABLE GRIP APPLICATION

0

2

1

APPR.REVISED BY CK'D

3

21.10-01CTERMINAL POLE SUBSTATION PILASTER, DOUBLE CIRCUIT

ELKINS10/12/10 CECCONI GUINN

ELKINS4/11/11 CECCONI BURLISON

SINGLE-PHASE REVERSE RISER - 200 AMP URD TO OVERHEAD 21.01-0221.01 SINGLE-PHASE PRIMARY RISERS

ELKINS4/17/12 KATIGBAK BURLISON

21.05 CABLE GUARD, U-GUARD AND CONDUIT RISERS

21.07 TERMINAL POLES, SMALL CABLE

21.08 TERMINAL POLES, LARGE CABLE

21.09 RISERS POLES, SECONDARY

21.10 SUBSTATION FEEDER EXITS

VERTICAL CONSTRUCTION, 200 AMP DOUBLE CIRCUIT 21.07-04B

ADCOCK4/4/13 KATIGBAK DANNA

NOTES:

1. MAKE LEAD FROM BOTTOM OF ARRESTER TO GROUND BRAIDS AS SHORT AS POSSIBLE. GROUND BRAID LENGTH

4/17/12 BURLISON BURLISON ELKINS

SINGLE-PHASE REVERSE RISER - 200 AMP

URD TO OVERHEAD0

1

APPR.REVISED BY CK'D

2

DETAIL 'A' - WARNING SIGNCN 9220150597

3

2. INSTALL WARNING SIGN BETWEEN SWITCH BRACKET AND NEUTRAL.

3. FUSE SWITCH PER ENGINEERING INSTRUCTIONS.

24"

72"

4"

TOP BRACKET

#2 WP

#6 SD BC

#6 WP

BRAIDS TO #4 SD BC ANDCONNECT TO SYSTEM NEUTRAL

CABLE UGUARDTO BE IN QUARTEROF POLE

SIDE VIEW

#6 SD BC

5"

4"

BOLT

6"

NEUTRAL - ATTACH GROUND

SEE NOTE 2

SEE DETAIL 'B'CN 9220201401SWITCH BRACKET

DETAIL 'B'CABLE CLAMP

RUBBER PAD

MOUNTING BRACKETCN 9220234384

12"

5/31/13 DANNA DANNA ADCOCK

12/17/14 EANES FLETCHER ADCOCK

SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.

21.01-02

DEF

X

DEPDEMDEC

21.05-05ADWG.10/12/10 DANNA GUINN ELKINS

U-GUARD FILL0

3

2

1

APPR.REVISED BY CK'D

U-GUARD SIZE FOR PRIMARY UNDERGROUND CABLE RUNS

PRIMARY CONCENTRIC NEUTRAL CABLE2-CABLE

U-GUARD SIZE

1-CABLE 3-CABLE

-

2"

-

3"

5"

3"1/0 AL SOL 15KV 175 MILS

500 KCM AL 15KV 175 MILS

SECONDARY CABLE

U-GUARD SIZE FOR SECONDARY UNDERGROUND CABLE RUNS

1-CIRCUIT

U-GUARD SIZE

3-CIRCUIT2-CIRCUIT

3"

3"

3"

2"

2"

2"

5"

5"

5"

3"

3"

2"

5"

5"

5"

5"

5"

3"

1"

1"

1"

2"

2"

2"

-

2"

2"

#2 AL UG TPX XLP

350 MCM AL UG TPX XLP

500 MCM AL UG QPX

4/0 AL UG QPX XLP

4/0 AL UG TPX XLP

2/0 AL UG TPX XLP

2 #6 AL ST. LT. CABLE

2 #10 CU ST. LT. CABLE

- - 5"1000 KCM AL 15KV 175 MILS

500 MCM AL UG TPX

5/24/12 DANNA BURLISON ELKINS

21.05-05BDWG.10/12/10 DANNA GUINN ELKINS

CABLE GRIP APPLICATION R

0

3

2

1

APPR.REVISED BY CK'D

CABLE GRIP SIZE FOR PRIMARY UNDERGROUND CABLE RUNS

PRIMARY CONCENTRIC NEUTRAL CABLE CABLE GRIP SIZE PER CONDUCTOR

2" X 2-1/2"

1" X 1-1/4"1/0 AL SOL 15KV 175 MILS

500 KCM AL 15KV 175 MILS

SECONDARY CABLE

CABLE GRIP SIZE FOR SECONDARY UNDERGROUND CABLE RUNS

2" X 2-1/2"

3" X 2-1/2"

3" X 2-1/2"

2" X 2-1/2"

2" X 2-1/2"

2" X 2-1/2"

1" X 1-1/4"

1" X 1-1/4"

1" X 1-1/4"

#2 AL UG TPX XLP

350 MCM AL UG TPX XLP

500 MCM AL UG QPX

4/0 AL UG QPX XLP

4/0 AL UG TPX XLP

2/0 AL UG TPX XLP

2 #6 AL ST. LT. CABLE

2 #10 CU ST. LT. CABLE

3" X 2-1/2"1000 KCM AL 15KV 175 MILS

500 MCM AL UG TPX

RECOMMENDED CABLE GRIP SIZE PER CIRCUIT

1. MOUNT SECOND CUTOUT AND BRACKET ON OPPOSITE SIDE FOR TWO-PHASE TERMINAL POLE.

3. USE #2 WP COPPER JUMPER WIRE FROM CUTOUT TO HOT LINE CLAMP.

CH

AN

CE

10/12/10 DANNA GUINN ELKINS

1

2

3

TERMINAL POLE, SINGLE-PHASE AND TWO-PHASE

CUTOUT ASSEMBLY

8" 4"

4. FORM THE 18" PIN STEM CONNECTOR AS SHOWN BEING CAREFUL NOT TO BEND THE #1/0 SOLIDAS IT ENTERS THE WATER SEAL AT CONNECTOR.

5. MAKE THE #6 SOFT DRAWN BARE COPPER LEAD FROM THE BOTTOM OF THE ARRESTER TO THE GROUND BRAIDSAS SHORT AS POSSIBLE WHILE MAINTAINING NOT LESS THAN 6" CLEARANCE BETWEEN CUTOUT IN THE OPENPOSITION AND THE GROUND BRAIDS. GROUND BRAID LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS

6. CHECK THAT CUTOUT DOOR WILL FALL CLEAR OF TERMINATOR AND CABLE.

7. ALL TERMINATOR POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.

8. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.

#6 SD BC

TO CLOSEST24" MIN.

PHASE WIRE

6"

SEENOTE

5

6

0

APPR.REVISED BY CK'D

43

2

1 ARUGTP10F

BILL OF MATERIALS

CATALOG

153534

CUTOUT, 15KV, 100ABRACKET, CUTOUTBOLT, MACHINE, 5/8" X 10"WASHER, SQUARE, 2-1/4"WASHER, SPRING COIL, 5/8"

CONNECTOR, STEM, ARRESTERARRESTER, 10KV, LIGHTNING

DESCRIPTION

220208013264

BKTCOSNGSTLF013308152106311263

FUSE15CO100F 22111211

1

1

QTY

11

11

1111

PERCU

NUMBERMACRO UNIT

CA1T15FM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

NOTES:

CH

ANC

E

KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0

2. TERMINATOR WITH 18" PIN STEM CONNECTOR ISSUED SEPARATELY. SEE DWG. 21.07-06.

21.07-01

DEF

X

DEPDEMDEC

5

RCRISERN2CUF 9220218857 WIRE, COPPER, #2 SOLID15 126 1 1KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0

KHLC7933F 9220184794 CLAMP, HOT LINE, ALUM, LARGE, 336-79516 1

4

5 8/1/14 LOOSIER DANNA ADCOCK

6 12/17/14 EANES FLETCHER ADCOCK

#4 SD BC

GROUNDBRAIDS

POSSIBLE.

7 4/10/17 LOOSIER BURLISON ADCOCK

3

2

10/12/10 DANNA GUINN ELKINS

TERMINAL POLE, THREE-PHASE CUTOUT ASSEMBLY

4" 8"

CLOSESTPHASE WIRE

24" TO

#6 SD BC

NOTES:

1. TERMINATOR WITH 18" PIN STEM CONNECTOR ISSUED SEPARATELY.2. USE #2 WP COPPER JUMPER WIRE FROM CUTOUT TO HOT LINE CLAMP.3. FORM THE 18" PIN STEM CONNECTOR AS SHOWN BEING CAREFUL NOT TO BEND THE #1/0 SOLID AS IT ENTERS THE WATER SEAL AT

CONNECTOR.4. MAKE THE #6 SOFT DRAWN BARE COPPER LEAD FROM THE BOTTOM OF THE ARRESTER TO THE GROUND BRAIDS AS SHORT AS

POSSIBLE WHILE MAINTAINING NOT LESS THAN 6" CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS.GROUND BRAID LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.

5. CHECK THAT CUTOUT DOOR WILL FALL CLEAR OF TERMINATOR AND CABLE.6. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.7. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.8. ROTATE OUTSIDE CUTOUTS FOR CLEARANCE AS NECESSARY.

SEENOTE

4

1

0

APPR.REVISED BY CK'D

43

2

1

BILL OF MATERIALS

CATALOGDESCRIPTION

32

1

3

QTYPERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

CA3T15FM

9

SEE NOTE 2

5 2

6 2

CONNECTOR, STEM ARRESTERARRESTER, 19KV LIGHTINGWASHER, SPRING COIL, 5/8"WASHER, SQUARE, 2-1/4"BOLT, MACHINE, 5/8"X10"BRACKET, CUTOUT, TRI-MOUNTCUTOUT, 15KV, 100AINSULATOR, POST, POST,TIE,TOP,15/25KVSTUD, LINE POST, LP 5/8"X 12"WASHER, LOCK, SPRING,DOUBLE COILWIRE, TIE, #6, SOLID SD BARE COPPER

11222111118

153534220208013264013308152106070104221112080212072367013264

11061009

ARUGTP10F

BKTCOTRISTLF

FUSE15CO100FIHPTT15F

ISSTUDBOLT5812F

HTIEN6CSDF

4 5 6

SEE DWGS. 21.07-04AAND 21.07-04B.

21.07-03

DEF

X

DEPDEMDEC

RCRISERN2CUF 9220218857 WIRE, COPPER, #2 SOLID38 12

8

7 3 CLAMP, HOT LINE, ALUM, SMALL, 4/019220184790KHLC40N6F

7

9 3 1KHLC40N6F 9220184790 CLAMP, HOT LINE, ALUM, SMALL, 4/0KHLC7933F 9220184794 CLAMP, HOT LINE, ALUM, LARGE, 336-79539 1

8 8/15/14 LOOSIER DANNA ADCOCK

12/17/14 EANES FLETCHER ADCOCK9

GROUND BRAIDS

#4 SD BC

4/10/15 LOOSIER BURLISON ADCOCK10

NOTES:

2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILE MAINTAINING 6"

MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS. GROUND

4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.

4/5/13 DANNA DANNA ADCOCK

VERTICAL CONSTRUCTION, 200 AMP

1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DWG. 21.07-01.

0

APPR.REVISED BY CK'D

FRONT VIEWSIDE VIEWFRONT VIEW

36"

36"

24"

6"

42"

4" MAX

5"

36"

36"

24"

6"

42"

4" MAX.

FRONT VIEW

THREE-PHASE DEADEND CONSTRUCTION

5"

72"

24"

6"

42"

4" MAX.

5"

THREE-PHASE TANGENT CONSTRUCTION

SINGLE-PHASE DEADEND CONSTRUCTION SINGLE-PHASE TANGENT CONSTRUCTION

72"

4"

3

#6 SD BC #6 SD BC

#6 SD BC

72"

24"

42"

6"

5"

4" MAX.

72"

#2 WP COPPERCU RCRISERN2CUF

21.07-04A

DEF

X

DEPDEMDEC

8/1/14 DANNA DANNA ADCOCK

#6 SD BCGROUNDBRAIDS

#4 SD BC

#6 SD BC

GROUNDBRAIDS

#6 SD BC

#6 SD BC

#4 SD BC

#6 SD BC

GROUNDBRAIDS

GROUNDBRAIDS

4 12/17/14 EANES FLETCHER ADCOCK

FRONT VIEWSIDE VIEW

BRAIDS LENGTH SHOULD ALSO BE MAINTAINED AS SHORT AS POSSIBLE.

#6 SD BC

#4 SD BC

GROUNDBRAIDS

#4 SD BCTO SYSTEMNEUTRAL

#6 SD BC

#4 SD BC

GROUNDBRAIDS

#4 SD BCTO SYSTEMNEUTRAL

5 3/18/15 DANNA EANES ADCOCK

7. MAINTAIN 8" CLEARANCE BETWEEN LOWEST GUY WIRE AND CUTOUT.

4"

4"

NOTES:

2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILE MAINTAINING 6"

MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAIDS. GROUND BRAID LENGTH SHOULD

4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATOR ATTACHED.6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.

4/4/13 DANNA DANNA ADCOCK

VERTICAL CONSTRUCTION, 200 AMP

DOUBLE CIRCUIT

1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DWG. 21.07-01.

0

2

1

APPR.REVISED BY CK'D

SIDE VIEW

3

IPIN23F

BKTFPIN18F

18"

36"

36"

5"

8"

24"

6"

42"

72"

FRONT VIEW

6"

6"

(FROM LEFT SIDE)

#6 SD BC

7. CAN BE CONSTRUCTED ON DOUBLE CIRCUIT POLES FRAMED WITH STEEL STAND OFF BRACKETS.

6" 6"

8/7/14 SALAS

#2 WP COPPERCU RCRISERN2CUF

21.07-04B

DEF

X

DEPDEMDEC

DANNA ADCOCK

12/17/14 EANES FLETCHER ADCOCK

NEUTRAL

#4 SD BC

#6 SD BC

#6 SD BC

GROUND BRAIDS

#4 SD BC

ALSO BE MAINTAINED AS SHORT AS POSSIBLE.

4" MAX.

NOTES:

2. INSTALL ARRESTER USING HOT LINE CLAMP AND ARRESTER PREBENT STEM CONNECTOR.

3. MAKE THE LEAD FROM THE BOTTOM OF ARRESTER TO THE GROUND BRAIDS AS SHORT AS POSSIBLE WHILEMAINTAINING 6" MINIMUM CLEARANCE BETWEEN CUTOUT IN THE OPEN POSITION AND THE GROUND BRAID.GROUND BRAID LENGTH SHOULD BE MAINTAINED AS SHORT AS POSSIBLE.

4. OUTSIDE CUTOUTS MAY BE ROTATED FOR CLEARANCE IF NECESSARY.

5. ALL TERMINAL POLE ARRESTERS MUST HAVE VISIBLE ISOLATER ATTACHED.

6. BOND GROUND BRAIDS TO SYSTEM NEUTRAL USING #4 SD BC.

10/12/10 DANNA GUINN ELKINS

HORIZONTAL CONSTRUCTION, 200 AMP

1. BEND 18" PIN STEM CONNECTOR AND INSTALL IN CUTOUT. SEE DETAILS ON DWG. 21.07-01.

0

3

2

1

APPR.REVISED BY CK'D

FRONT VIEW SIDE VIEW

#6 SD BC

24"

6"

42"

4" MAX.

44" 16" 28"

44" 16" 28"

FRONT VIEW

#6 SD BC

SIDE VIEW

#6 SD BC

24"

6"

42"

4" MAX.

5"

8/31/11 DANNA BURLISON ELKINS

KHLC40N6F

KHLC7933FOR

12/12/11 BURLISON

ALL RISER LEADSTO BE #2 WP CU

RISER MAY BECONNECTED TO ANYPHASE AS DESIGNATEDBY ENGINEERING

BURLISON ELKINS

21.07-05

DEF

X

DEPDEMDEC12/17/14 EANES FLETCHER ADCOCK

#6 SD BC

#6 SD BC

#4 SD BC

#6 SD BC

GROUND BRAIDS

GROUND BRAIDS

5" KHLC40N6F

KHLC7933FOR

#4 SD BCTO SYSTEMNEUTRAL

GROUNDBRAIDS

GROUNDBRAIDS

1

4" MAX

200 AMP TERMINAL POLE, CABLE RISER ASSEMBLY

NOTES:

0

3

APPR.REVISED BY CK'D

SIDE VIEW

NEUTRAL

A

SECTION A-A

INSTALL CABLEGUARD IN BACKQUARTER OF POLE

#6 SD BC

3

2

1. IF DIRECT BURIED CABLE, INSTALL CABLE GUARD 12"BELOW GROUND LEVEL.

3. INSTALL LAG SCREW IN EACH HOLE OF MOLDING.

4. FOR OTHER CABLE SIZES, MATERIAL ITEMS SUCH ASCABLE GUARDS, GRIPS, AND CONNECTORS WILL CHANGE.SEE DWGS. 21.05-05A, 21.05-05B, 26.06-10A.

A

#6 SD BC

SEE NOTES

2. IF CABLE IN CONDUIT, INSTALL CABLE GUARD 4" BELOWCONDUIT.

1 AND 2

321 CRIS1UGPVC225WF

BILL OF MATERIALS - TERMINAL POLE RISER SINGLE-PHASE #1/0

TERM, KIT, 1/0, 200 AMP

RISER, U-GUARD, 2-1/4"CABLE GRIP, 1" X 1-1/4"

DESCRIPTION

CABGRP1X125FTRM10AL215KITF 1

13

MACRO UNIT

TMP1P10FM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

321 CRIS1UGPVC35WF

BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE #1/0

TERM, KIT, 1/0, 200 AMP

RISER, U-GUARD, 3-1/2"CABLE GRIP, 1" X 1-1/4"

DESCRIPTION

CABGRP1X125FTRM10AL215KITF 3

33

MACRO UNIT

TMP3P10FM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

10/26/10 DANNA GUINN ELKINS

5. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10'SECTION OF CABLE GUARD.

6. WHEN THE CABLE IS INSTALLED IN 4 INCH CONDUIT, USE

5/24/12 DANNA

4 INCH CONDUIT TO THE 3 INCH U-GUARD.

THE 3" VENTILATOR BOOT ( CU CRISVENTBOOT3F ,ITEM # 9220239095) TO MAKE THE TRANSITION FROM

7. ORIENT U-GUARD WITH BELL ENDS ON BOTTOM. WHENINSTALLING VENTILATOR BOOT, INSTALL U-GUARD OVERTHE FIRST STEP OF THE VENT BOOT.

BURLISON ELKINS

4 12/7/12 DANNA DANNA ADCOCK

ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F

21.07-06

DEF

X

DEPDEMDEC5 11/18/15 DANNA BURLISON ADCOCK

10/12/10 DANNA GUINN ELKINS

TERMINAL POLE, 600 AMP SWITCH ASSEMBLY0

APPR.REVISED BY CK'D

NOTES:

1. SEE DWG. 21.08-01B FOR BILL OF MATERIALS AND TERMINATOR CONNECTION DETAIL.

2. USE GROUND BRAIDS FOR NEUTRAL AND CROSS BONDING CONNECTIONS.

2

3. IT IS ACCEPTABLE TO LOCATE SWITCH AND UGUARD ON OTHER SIDE OF GUYS IFNECESSARY. LOCATING UGUARD AWAY FROM TRAFFIC IS PREFERRED.

3

FRONT VIEWSIDE VIEW

4

2

7

11

10

#6 SD BC

1

4"

36"

GROUNDBRAID

12"

36"

36"

5"

BRACKET

24"

30"

28-3/4"

4"

SEE NOTE 3

SEE NOTE 3

#2 SD BC

5

3

8 9BOLT

BOTTOM

12/22/11 BURLISON BURLISON ELKINS

5/31/13 McCONNELL DANNA ADCOCK

SEE NOTE 4SEE NOTE 4

4. INSTALL FAULT INDICATOR AS SHOWN ON DWG. 21.08-08.

12

4 7/16/14 LOOSIER

21.08-01A

DEF

X

DEPDEMDEC

6

4 5 6

DANNA ADCOCK

TERMINAL POLE, 600 AMP SWITCH ASSEMBLY0

APPR.REVISED BY CK'D

NOTES:

1. SEE DWG. 21.08-01A FOR DESIGN SPECIFICATIONS.

3

8

1

12

ARUGTP10F

KLC2H1KUF

GUFTPE2F

BKTSBDSWSTLF

KH10N2ALF

STIEF795ALF

SW156SBDF

IHPTT15F

S600TPFM

ISSTUDBOLT5810F

12

8 12

8/10/10 DANNA GUINN ELKINS

7/16/14 LOOSIER

21.08-01B

DEF

X

DEPDEMDEC

9

KLC2HUF

SEE NOTE 2

2. SEE DWGS. 21.08-07A AND 21.08-07B FOR CABLE RISER ASSEMBLY DETAIL.

11

12

10

9

8

7

6

54

3

2

1

NUT, HEX, 1/2 IN, SS, THREAD,1/2"

WASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD2 HOLE SPADE WITH STEMCONNECTOR H FRAME COMPRESSION #1/0 TO #2 ALUMINUM

CONNECTOR LUG COMPRESSION 2-HOLE 795 MCM ALUMINUMWASHER, ROUND, RD,1/2,SS,1.375" ODWASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLT

BILL OF MATERIALS

CATALOG

220208

SWITCH OH 15KV 600 A SGL BLADE DIS NL BRK

BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEADCONNECTOR LUG COMPRESSION 2-HOLE 1000 MCM UG ONLYCONNECTOR HOT LINE CLAMP #4/0 TO #6

INSULATOR SUPPORT STUDBOLT 5/8 IN X 10 IN STLINSULATOR POST, HORIZONTAL, TIE TOP, STUD BASE 15/25 KVSIDE TIE, F NECK, 795 KCM ALUMINUM

GND UG PEFTERM POLE WIRE ONLY # 2 CU SD

ARRESTER, UG RISER TERMINAL POLE10 KV CLASS

BRACKET FOR SOLID BLADE DISCONNECT SWITCH, STEEL

DESCRIPTION

070282

9220162221

121434080212072366

260136

9220184790155334

155331

153111311221010928012277013163

3

3

3

3

3

3

3

2

2

2

3

2

42211

124

QTY

1

12

1

11

1

5

1

1

PERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

CONNECTOR, STEM, ARRESTER153534 1

MACHINE BOLT,SQ,NUT,5/8"X12" WASHER, SQUARE, 2-1/4",GALVWASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COIL013264

013308152107 2

22

3

CONNECTOR, 2,BOLT,#4/0,CUCONNECTOR, GROUND, TF,GND,EYEBOLTCONNECTOR, GND,5/8,ROD,2,CUBOLT, HEX HEAD, MACH,SQ,NUT,3/4"X18"152125

160123160182161234

1

2

11

3

WASHER, LOCK, 5/8 IN, STEEL, GLV, SPRING,DOUBLE COIL013264 1

ROUND,FLAT,STAINLESS,STEEL, FOR 1/2" BOLTBOLT, MACHINE, 1/2 IN, 2 IN, STEEL, HEX HD

WASHER, ROUND, BELLEVILLE SPRING, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD010928

012277013128013407152074 2

44

4

8

KHLC40N6F

KLC2H79ALF

WASHER, ROUND, RD,1/2,SS,1.375" OD10542504 2

WASHER, FLAT, 1/2 IN, SILICON BRONZE, ROUND, FOR 1/2" BOLTNUT, HEX, 1/2 IN, SS, THREAD,1/2"BOLT, MACHINE, 1/2 IN, 2 IN, STAINLESS STEEL, 304, HEX HEAD

422

WASHER, ROUND, RD,1/2,SS,1.375" OD2

010928012277013163

10542504

010928012277013163

10542504

DANNA ADCOCK

4 3/18/15 LOOSIER EANES ADCOCK

5 4/10/15 DANNA DANNA ADCOCK

21.08-03DWG.

NOTES:

1. INSTALL BACKING PLATE BELOW CONDUIT IF REQUIRED

2. INSTALL VENTILATOR CABLE BOOT FLUSH WITH GRADE.

3. INSTALL CABLE GUARD (ENLARGED END) OVER TOP OF VENTILATOR BOOT

COUPLING

80 LB BAGS OF CONCRETE

WOOD POLE

1/4" x 2" LAG

POLES - USE

SCREWS FOR WOODPOLES - STAINLESSSTEEL BANDINGFOR CONCRETE

ENLARGED AREA OF PLASTICCABLE FOR OVERLAPPINGEACH SECTION

5" PLASTIC CABLE GUARD

VENTILATOR BOOTCN 323437

10/26/10 DANNA GUINN ELKINS

VENTILATOR BOOT INSTALLATION,

ALL 500 AND 1000 KCM PRIMARY RISERS

6"

GRADE

R

0

3

2

1

APPR.REVISED BY CK'D

2 BANDS

4/11/11 DANNA BURLISON ELKINS

600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY0

2

1

APPR.REVISED BY CK'D

SECTION A-A

INSTALL U-GUARD ANDCENTER TERMINALS INBACK QUARTER OF POLE

GROUND BRAIDS

3

A

NOTES:

1. INSTALL LAG SCREWS IN EACH HOLE OF MOLDING.

3. SEE DWG. 21.08-07B FOR BILL OF MATERIALS.

2. SEE DWG. 21.08-08 FOR FAULT INDICATOR DETAILS.

2

1

4

#6 SD BC

CONNECTOR

X

4. WHEN INSTALLED PROPERLY, THE LC SHIELD GROUND BRAID HAS TWO LEADS. USE ONE TO DO THE CROSSBOND AND THE OTHER TO CONNECT TO THE NEUTRAL.

SEE NOTE 4

12" MAX. APPLIES TO600 AMP LC SHIELD

#2 BOLTED CONNECTOR

H-BLOCK

(GROUNDING NOT SHOWN FOR CLARITY)

PRIMARY CABLE ONLY

3

XX

XX

X

XX

XX

XX

XX

XX

XX

5. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10' SECTION OF CABLE GUARD.

21.08-07A

DEF

X

DEPDEMDEC

11/18/15 DANNA BURLISON ADCOCK

#2 SD BC

H-BLOCK

ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F

21.08-07BDWG.

600 AMP TERMINAL POLE, CABLE RISER ASSEMBLY R

0

3

2

1

APPR.REVISED BY CK'D

NOTES:

1. SEE DWG. 21.08-07B FOR BILL OF MATERIALS.

2. MATERIAL ITEMS SUCH AS CABLE GUARDS, CONNECTORS, ETC. WILL CHANGE FOR OTHER CABLE SIZES. SEEDWGS. 21.05-05A, 21.05-05B AND 26.06-10A.

4321 CRIS1UGPVC50WF

BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE 500MCM

VENT BOOTTERM KIT, 500 KCMIL

U-GUARD, 10'-5"CABLE GRIP, 2 X 2-1/2"

DESCRIPTION

CABGRP2X250FTRM500AL615KITFCRISVENTBOOTF 1

333

MACRO UNIT

TMP3P500FM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

4321 CRIS1UGPVC50WF

BILL OF MATERIALS - TERMINAL POLE RISER THREE-PHASE 1000MCM

VENT BOOTTERM KIT, 1000 KCMIL

U-GUARD, 10'-5"CABLE GRIP, 2 X 2-1/2"

DESCRIPTION

CABGRP3X250FTRM1KAL615KITFCRISVENTBOOTF 1

333

MACRO UNIT

TMP3P1KFM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

4/11/11 DANNA BURLISON ELKINS

21.08-08DWG.

NOTES:

AND CABLE NEUTRAL

AND PLASTIC WIRE TIETO POLE WITH STAPLECOIL LEADS AND SECURE

SEE DETAIL "B"

BETWEEN TERMINATORBE INSTALLEDSENSOR UNIT MUST

UNDER STAPLEPLASTIC WIRE TIE

CONDUCTOROVER FAULT INDICATORDO NOT STAPLE

BELOW TERMINATORIMMEDIATELY

WATER STOP

INSTALL FCI

FAULTED CIRCUIT INDICATOR,

600 AMP TERMINAL POLE

1. CROSS BOND ALL 600A TERMINATORS PER DWG. 21.08-07A.

DETAIL "B"

1

DETAIL "A"

SEE DETAIL "A"

R

GROUND BRAID

0

3

2

1

APPR.REVISED BY CK'D

TIE, CABLE, PLASTIC MARKER, 'ZIP'INDICATOR, FAULT, 3 PH, LG, DISBRACKET, OH, FAULT, IND, MOUNTINGSTAPLE, GALVANIZED, 1/4" X 1-1/2"SCREW, LAG, 1/4" X 2"

BILL OF MATERIALS

CATALOGDESCRIPTION

014111015271

FCIOLD12N3PFF 070284323457443303

1

31132

QTYPERCU

NUMBERCOMPATIBLE

UNITQTY

REQ'D

X X X X X X XXXX

XX

XX

XX XX

4/11/11 DANNA BURLISON ELKINS

NEUTRAL

4" MAX

10/26/10 DANNA GUINN ELKINS

SECONDARY RISER POLE

12"

36"

0

2

1

APPR.REVISED BY CK'D

2

1 CRIS1UGPVC_F

BILL OF MATERIALS

ITEM

014111

GRIP, CABLE (VARIES WITH WIRE SIZE)

SCREW, LAG, 1/4" X 2"GUARD, CABLE (VARIES WITH WIRE SIZE)

DESCRIPTION

-CABGRP_F -1

3

QTY

1115

PERCU

NUMBERMACRO UNIT

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

-

NOTES:

1. INSTALL LAG SCREW IN EVERY HOLE.2. IF DIRECT BURIED CABLE, INSTALL CABLE GUARD 12" BELOW GROUND LEVEL.3. IF CABLE IS INSTALLED IN 4" OR 6" CONDUIT, USE APPROPRIATE VENTILATOR BOOT. FOR 5" U-GUARD, USE

4. SEE DWGS. 21.05-05A AND 21.05-05B FOR GUARD AND GRIP SIZES.

1

2

5. USE APPROPRIATE H-BLOCK, BOLT-ON OR INSULINK CONNECTORS FOR SECONDARY TO SECONDARY ORSECONDARY TO TRANSFORMER CONNECTIONS. SECONDARY PEDESTAL CONNECTORS ARE NOTAPPROVED FOR THESE APPLICATIONS.

3

#6 SD BCSEE NOTE 6

6. INSTALL GROUND WIRE (IF REQUIRED) ON OUTSIDE OF CABLE GUARD.7. INSTALL CABLE GUARD ON QUARTER OF POLE.8. ON CONCRETE POLES, INSTALL 3 S.S. BANDS PER 10' SECTION OF CABLE GUARD.

11/10/11 ROBESON BURLISON ELKINS

5/24/12 DANNA

CU CRISVENTBOOTF, ITEM # 323437. FOR 3" U-GUARD, USE CU CRISVENTBOOT3F , ITEM # 9220239095.

9. ORIENT U-GUARD WITH BELL ENDS ON BOTTOM. WHEN INSTALLING VENTILATOR BOOT, INSTALL U-GUARDOVER THE FIRST STEP OF THE VENTILATOR BOOT.

BURLISON ELKINS

ON 3" AND 5" U-GUARD,INSTALL CABLE PROTECTORCU CRISPROT35F

21.09-01

DEF

X

DEPDEMDEC11/18/15 DANNA BURLISON ADCOCK

TERMINAL POLE, SUBSTATION PILASTER0

2

1

APPR.REVISED BY CK'D

DETAIL 'A'CLUSTER MOUNT BRACKET DETAIL

NOTES:

1. SEE DWG 21.10-01B FOR BILL OF MATERIALS.2. GROUND ON POLE PROVIDED BY SUBSTATION CONSTRUCTION.

GROUND BRAIDS

SEE DETAIL 'A'

4

5

6

2

8

SEE NOTE 2

18"

1

GROUND PROVIDEDBY SUBSTATIONCONSTRUCTION3

3

X

XX

XX

XX

XX

XX

XX

XX

X

7

THREE-PHASETERMINATORBRACKETITEM # 9220197866

3. BOND U-GUARD TO POLE. USE 3 BANDS ON EACH 10' U-GUARD SECTION. USE 2 BANDSON VENTILATOR BOOT.

7

8/10/10 DANNA GUINN ELKINS

3/8/12 BURLISON BURLISON ELKINS

PILASTER POLEITEM # 328732

9INSTALL CABLE PROTECTORCU CRISPROT35F

21.10-01A

DEF

X

DEPDEMDEC11/18/15 DANNA BURLISON ADCOCK

4. BOND BRACKET TO POLE GROUND.

21.10-01BDWG.10/12/10 DANNA GUINN ELKINS

TERMINAL POLE, SUBSTATION PILASTER R

0

1

APPR.REVISED BY CK'D

NOTES:

1. SEE DWG 21.10-01A FOR DESIGN SPECIFICATIONS.

2

3

87654321 CRIS1UGPVC50CF

BILL OF MATERIALS

CATALOG

-

LUG, 2-HOLE, ARRESTER TYPELUG, 2-HOLE, 795

ARRESTER, LIGHTNING, RP, 10KVBKT AND MISC MAT FOR PILASTER POLE TERMINATIONTERMINATOR, 1000 KCM, 15KVGUARD, VENT, CABLE BOOT, 4" - 5"

CABLE GUARD, PVC, 5" X 10', CONCRETE/STEEL POLEGRIP, SINGLE EYE, 2-1/2" X 3"

DESCRIPTION

CABGRP3X250F -CRISVENTBOOTF -TRM1KAL615KITF -BKTTMP1000KPF -

ARUGTP10F -KLC2HUF -

KLC2H79ALF -33

13

3132

QTY

11

11

1111

PERCU

NUMBERMACRO UNIT

TMP3P1KPFM

CUITEMNO.

COMPATIBLE UNIT

QTYREQ'D

3/8/12 BURLISON BURLISON ELKINS

9 PILASTER POLEPCC18PILASTERF 3287321 1-

10/5/12 BURLISON BURLISON ADCOCK

TERMINAL POLE

SUBSTATION PILASTER, DOUBLE CIRCUIT0

2

1

APPR.REVISED BY CK'D

3

10/12/10 DANNA GUINN ELKINS

NOTES:

GROUND BRAIDS

18"

GROUND PROVIDEDBY SUBSTATIONCONSTRUCTION

2. BAND U-GUARD TO POLE. USE 3 BANDS ON 10' U-GUARD SECTION. USE 2 BANDS ON VENTILATORBOOT.

1. SEE DWG. 21.01-01B FOR BILL OF MATERIAL. ORDER QUANTITY OF 2 OF MACRO UNIT.

BANDING DETAIL

U-G

UARD

POLE

U-G

UARD

BAND EACH U-GUARDSECTION DIRECTLY TOPOLE

PILASTER POLEITEM # 328732

3/8/12 BURLISON BURLISON ELKINS

INSTALL CABLE PROTECTORCU CRISPROT35F

21.10-01C

DEF

X

DEPDEMDECDANNA BURLISON ADCOCK11/18/15

3. BOND BRACKET TO POLE GROUND.

21.10-02DWG.

NOTES:

VENTILATED BOOT

CONSTRUCTION TOSUBSTATION

FOR ADDITIONAL SPACE.SUBSTATION DEPT.REQUIRED CONTACTIF REGULATORS ARE

TERM. LUG

TERM. LUG

795 AAC

AMPAC WEDGE

2. INSTALL VENTILATED BOOT ON ALL FEEDER TERMINATIONS.

10/12/10 DANNA GUINN ELKINS

SUBSTATION CONNECTIONS,

STANDARD TWO-BANK SUBSTATION

CN 155464

CN 165277

CN 155328

8' MINIMUM

R

0

3

2

1

APPR.REVISED BY CK'D

PROVIDE GROUND

SUBSTATION GROUND GRID

1. DISTRIBUTION CONSTRUCTION WILL INSTALL 795 AAC CONDUCTORS FROM UG TERMINATION TO THE CIRCUIT BREAKER LINE DISCONNECT AND TO THE BYPASS SWITCH. DISTRIBUTION CONSTRUCTION WILL ALSO MAKE CABLE NEUTRAL CONNECTION TO THE GROUND (NEUTRAL) PROVIDED BY SUBSTATION CONSTRUCTION ON THE PILASTER POLE.

21.10-03DWG.

SUBSTATION BUS

AND MAKE CONNECTIONTO BUS AND CONNECT

DISTRIBUTION PERSONNELWILL INSTALL CONDUCTOR

VENTILATED BOOT

795 JUMPER

4 HOLE LUG

SUBSTATION PERSONNELTO DRILL TERMINAL MOUNTING HOLES ONBUS WORK

PER STATION GENERAL LAYOUT

10/12/10 DANNA GUINN ELKINS

SUBSTATION CONNECTIONS,

HIGH DENSITY SUBSTATION

4'-0" 4'-0"

R

0

3

2

1

APPR.REVISED BY CK'D

NEUTRAL (GROUND).CABLE NEUTRAL TO POLE

GROUND GRID

#6 SD BC

GROUNDBRAID

#6 SD BC

# 2 BC CROSS BOND

SEE NOTE 2

NOTES:

1. INSTALL VENTILATED BOOT ON ALL FEEDER TERMINATIONS.

2. CONNECT EACH INDIVIDUAL GROUNDING BRAID FROM TERMINATOR TO THE NEUTRAL.

SUBSTATION CONSTRUCTIONTO PROVIDE NEUTRAL ON POLE