Web Presentation Tish Rielly, Tara McLean Do not print, save, or use this visual presentation as an official reference. This is NOT the TREC approved document. This presentation is for viewing purposes only and allows for expanding pictures and other advanced web features. There is a separate PDF document that is your official inspection report. Please see the official TREC approved PDF document that was sent by the inspector. Property Address: 2308 Woodlawn Blvd, Austin, TX 78703 Austinspect, Inc. Mark Havelka 20755 220 Racetrack Dr Austin, TX 78748 512.633.9488

2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

Web Presentation

Tish Rielly, Tara McLean

Do not print, save, or use this visual presentation as an official reference. This is NOT the TREC approveddocument. This presentation is for viewing purposes only and allows for expanding pictures and other advanced webfeatures. There is a separate PDF document that is your official inspection report. Please see the official TREC approvedPDF document that was sent by the inspector.

Property Address: 2308 Woodlawn Blvd, Austin, TX 78703

Austinspect, Inc.

Mark Havelka 20755220 Racetrack DrAustin, TX 78748

512.633.9488

Page 2: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

Table of Contents

Cover Page.................................................................1

Table of Contents........................................................2

I STRUCTURAL SYSTEMS........................................3

II ELECTRICAL SYSTEMS.......................................28

III HEATING, VENTILATION AND AIRCONDITIONING SYSTEMS .....................................36

IV PLUMBING SYSTEM...........................................40

V APPLIANCES........................................................52

VI OPTIONAL SYSTEMS .........................................58

General Summary.....................................................61

Invoice.......................................................................69

Attachments ..............................................................70

Back Page.................................................................71

Agreement ................................................................73

Report Identification: 2308 Woodlawn Blvd

Page 2 of 75REI 7-5 (05/04/2015)

Page 3: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

I. STRUCTURAL SYSTEMS

A. FoundationsType of Foundation(s): Slab, Pier and beamFoundation Performance: Foundation is performing as intended, see additional comments belowComments:(1) One or more foundation vent(s) were below ground level, which can allow water to enter thecrawlspace.

A. Item 1(Picture) A. Item 2(Picture)

(2) Standing water was observed in the crawlspace beneath the left side of the home. Water intrusion cancontribute to differential foundation movement and mold. Improve grading & drainage as needed to preventwater intrusion.

A. Item 3(Picture)

(3) No under floor insulation or moisture barrier were present in the crawlspace.

A. Item 4(Picture)

(4) Cracks were observed at one or more areas of the perimeter footing.

Report Identification: 2308 Woodlawn Blvd

Page 3 of 75REI 7-5 (05/04/2015)

Page 4: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 5(Picture) A. Item 6(Picture)

A. Item 7(Picture)

(5) Any construction debris should be removed from the crawlspace under the home.

A. Item 8(Picture)

(6) The foundation did not appear to be in need of immediate remedial leveling at the time of the visualinspection. Hairline cracks were observed at the garage floor. The rate of hairline cracks cannot bedetermined from a one-time site visual inspection and should be monitored. If the cracks advance, aqualified foundation engineer should be contacted for further evaluation.

Report Identification: 2308 Woodlawn Blvd

Page 4 of 75REI 7-5 (05/04/2015)

Page 5: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 9(Picture)

(7) Only areas of the crawlspace determined accessible by the inspector are inspected.

B. Grading & DrainageComments:(1) There was a negative slope observed towards the home in one or more areas. Proper drainage iscritical to the performance of the foundation. All grades should drop away from the structure at a rate of 6inches for every 10 feet. Improve drainage as needed so that water flows away from the home.

B. Item 1(Picture) B. Item 2(Picture)

B. Item 3(Picture)

B. Item 4(Picture) B. Item 5(Picture)

B. Item 6(Picture)

(2) It is advisable to maintain at least 3-6 inches minimum of clear area between the ground and exterior

Report Identification: 2308 Woodlawn Blvd

Page 5 of 75REI 7-5 (05/04/2015)

Page 6: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

finishes. Areas where the soil is in contact with the exterior finish are conducive to wood-destroying insectactivity.

B. Item 7(Picture)

(3) Holes (possibly from burrowing pests) were observed at the base of the steps to the abandoned rearporch.

B. Item 8(Picture) B. Item 9(Picture)

(4) One or more gutters appear to hold water and need to be re-pitched for proper drainage.

B. Item 10(Picture)

(5) Inspector cannot determine whether underground drainage systems will perform as intended. Monitorthese drains and keep them clear of debris to ensure adequate flow.

Report Identification: 2308 Woodlawn Blvd

Page 6 of 75REI 7-5 (05/04/2015)

Page 7: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

B. Item 11(Picture) B. Item 12(Picture)

(6) The landscape in some areas may require a trench or drain if water stands or puddles after heavy rain.

B. Item 13(Picture)

C. Roof Covering MaterialsTypes of Roof Covering: Metal, SlateViewed from: Ground, WindowsRoof Ventilation: Gable vents, Ridge vents, Soffit VentsComments:(1) Slate tile roofs are not walked on by the inspector, however, cracked and loose tiles were observed atthe roof covering above the rear porches. Recommend further evaluation and repair by a qualified roofingcontractor.

Report Identification: 2308 Woodlawn Blvd

Page 7 of 75REI 7-5 (05/04/2015)

Page 8: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

C. Item 1(Picture) C. Item 2(Picture)

C. Item 3(Picture)

C. Item 4(Picture)

(2) Ponding was observed at the flashing beneath the dormer windows above the garage.

C. Item 5(Picture) C. Item 6(Picture)

(3) Kick-out flashing is recommended at roof-to-wall connections to divert water away from exteriorfinishes. Have a roofer correct where needed.

Report Identification: 2308 Woodlawn Blvd

Page 8 of 75REI 7-5 (05/04/2015)

Page 9: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

C. Item 7(Picture) C. Item 8(Picture)C. Item 9(Picture) Kick out

(4) The tree limbs that are in contact with, or hanging near the roof should be trimmed.

C. Item 10(Picture)

C. Item 11(Picture)

C. Item 12(Picture)

C. Item 13(Picture) C. Item 14(Picture)

C. Item 15(Picture)

(5) Client Advisory: The roof was not safely/easily accessible due to the height off the ground with nosecondary method of access. Some items may not be discovered without access to the roof. Recommendhaving the roof and roof covering materials evaluated by a roofing contractor. The inspector cannotguarantee that the roof will be free of leaks, nor can the inspector determine the remaining service life ofthe roof covering.

Report Identification: 2308 Woodlawn Blvd

Page 9 of 75REI 7-5 (05/04/2015)

Page 10: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

D. Roof Structures and AtticsViewed from: AtticMethod used to observe attic: From entry, Walked safely accessible areasAttic Insulation: Batt, FiberglassApproximate Average Depth of Insulation: Less than 7 inchesAttic info: Scuttle hole, Walk in accessComments:(1) Rot was observed at several cupolas. Repair or replace any damaged and rotten wood. Additionaldamage may be present that was not visible to the inspector.

D. Item 1(Picture) D. Item 2(Picture)

D. Item 3(Picture)

(2) Weather-strip the attic access perimeters and insulate the access covers to reduce air infiltration andheat from the attic area.

D. Item 4(Picture)

(3) Inspector was unable to open the metal scuttle hole in the master bedroom.

D. Item 5(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 10 of 75REI 7-5 (05/04/2015)

Page 11: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(4) One or more attic access openings are undersized by today's code standards. The minimum atticaccess opening should be 22" x 30". The size of the access door above the kitchen area may inhibitservice and/or replacement of the HVAC equipment in this space.

D. Item 6(Picture) D. Item 7(Picture)

(5) No strong backs (T-bracing) were present at the roof supports above the master suite. T-bracing helpsprevent supports from bowing. Repair as needed.

D. Item 8(Picture) D. Item 9(Picture)

(6) Current building standards dictate that roof supports and purlin should be the same size as the lumberthat they support. 2x6 roof rafters are being supported by 2x4 and 1x6 supports in some areas. The roofand structure were performing as intended at the time of inspection.

D. Item 10(Picture) D. Item 11(Picture)

(7) Current code standards call for collar ties to be installed between rafters to prevent rafter spread.

Report Identification: 2308 Woodlawn Blvd

Page 11 of 75REI 7-5 (05/04/2015)

Page 12: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

D. Item 12(Picture)

(8) A bucket was observed in the attic above the master bedroom. Inspector was unable to access thisspace.

D. Item 13(Picture)

(9) Water staining was observed at the attic decking above the vestibule to the master suite.

D. Item 14(Picture) D. Item 15(Picture)

(10) Rodent traps were observed in the attic. Pest control and sealing of access points is recommended.

D. Item 16(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 12 of 75REI 7-5 (05/04/2015)

Page 13: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(11) Insulation should be properly distributed to cover all portions of the attic located above the home livingspace.

D. Item 17(Picture)

(12) Recommend additional insulation to bring attic R value to an R 30 or greater.(13) Only areas of the attic determined accessible by the inspector were inspected. Insulation, HVACducts/mechanical equipment, limited headroom, wiring (electrical, cable and alarm) and risk of ceilingdamage are examples of factors that may inhibit access.

E. Walls (Interior & Exterior)Comments:(1) Cracks were observed in the mortar at one or more areas of the masonry veneer. Mortar improvementsare recommended to prevent water penetration.

E. Item 1(Picture) E. Item 2(Picture)

E. Item 3(Picture)

E. Item 4(Picture) E. Item 5(Picture) E. Item 6(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 13 of 75REI 7-5 (05/04/2015)

Page 14: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(2) Rot was observed at the siding and/or wood trim in one or more areas. Replace or repair all damagedand rotten wood. Additional damage may be present that was not visible to the inspector.

E. Item 7(Picture) E. Item 8(Picture)

(3) The paint is failing and/or worn at one or more areas of the exterior wood. I recommend prepping andpainting at all exposed areas to prevent rot.

E. Item 9(Picture) E. Item 10(Picture) E. Item 11(Picture)

(4) Exterior finishes should be installed 2" from any hard walking surface and 4" or greater above grade.The inspected home had one or more areas that do not meet these standards. Correct/repair as needed.

E. Item 12(Picture) E. Item 13(Picture)

E. Item 14(Picture)

(5) No weep holes were present over the windows and doors installed in the masonry veneer. Weep holesare required by current code standards.

Report Identification: 2308 Woodlawn Blvd

Page 14 of 75REI 7-5 (05/04/2015)

Page 15: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

E. Item 15(Picture)

(6) Re-seal caulk at all wood trim-to-masonry connections to prevent rot and water penetration.

E. Item 16(Picture) E. Item 17(Picture)

(7) Wood trim at the overhead garage door sides had inadequate clearance from the ground and will be subjected tohigh moisture conditions from rain water. This condition may cause early trim failure along the base. Trim and seal asneeded.

E. Item 18(Picture)

(8) Trim vegetation back from walls to prevent pest intrusion.

Report Identification: 2308 Woodlawn Blvd

Page 15 of 75REI 7-5 (05/04/2015)

Page 16: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

E. Item 19(Picture) E. Item 20(Picture)

E. Item 21(Picture)

(9) Stucco (Hard Coat or EIFS) Observation and Opinions:There was a stucco-type product installed as the exterior veneer/cladding for this structure. A fullevaluation of this product is outside the scope of this inspection. At this time a general, limited, visually-based survey of the accessible exterior stucco veneer/cladding was performed without the use of anyspecialized tools or procedures. The Inspector's findings will be listed below but all possible deficiencieswill not be limited to what is included in this report.

E. Item 22(Picture)

(10) Settlement was observed at one or more interior walls.

E. Item 23(Picture) E. Item 24(Picture)

E. Item 25(Picture)

(11) Caulk around all shower/tub fixtures. It is important to keep all around wet area fixtures well sealed to

Report Identification: 2308 Woodlawn Blvd

Page 16 of 75REI 7-5 (05/04/2015)

Page 17: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

prevent water damage. Damage can be present behind these areas that is not visible to inspector. Theinspector does not perform destructive testing or investigation. Repair as needed.

E. Item 26(Picture)

F. Ceilings & FloorsComments:(1) Separation was observed at the decorative molding in the rear first-story living area.

F. Item 1(Picture)

(2) Peeling paint was observed at the ceiling near one or more supply registers. This may be an indicationof poor AC performance.

F. Item 2(Picture) F. Item 3(Picture)

(3) Temperature anomalies were observed at one or more ceiling areas. This may indicate that theseareas are inadequately insulated.

Report Identification: 2308 Woodlawn Blvd

Page 17 of 75REI 7-5 (05/04/2015)

Page 18: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

F. Item 4(Picture) F. Item 5(Picture)

(4) Depressions were observed at the floor in the master bedroom.

F. Item 6(Picture) F. Item 7(Picture)

(5) Stains were observed various carpeted areas.

F. Item 8(Picture) F. Item 9(Picture)

G. Doors (Interior & Exterior)Comments:(1) One or more dead bolts at exterior doors were keyed. Recommend thumbscrew type for fire egress.

Report Identification: 2308 Woodlawn Blvd

Page 18 of 75REI 7-5 (05/04/2015)

Page 19: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

G. Item 1(Picture) G. Item 2(Picture)

(2) Inspector was unable to operate the doors to the balcony.

G. Item 3(Picture)

(3) The stain was faded at one or more exterior doors.

G. Item 4(Picture)

(4) Inspector is unable to determine if the safety glass is present in doors with glass panes.

Report Identification: 2308 Woodlawn Blvd

Page 19 of 75REI 7-5 (05/04/2015)

Page 20: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

G. Item 5(Picture)

(5) Door stops were missing behind one or more doors. Install door stops to prevent wall damage.

G. Item 6(Picture)

(6) The rubber seals were missing at the base of several shower doors. Install seals to prevent water fromleaking to the shower exterior.

G. Item 7(Picture) G. Item 8(Picture)

(7) The shower door in the left-most second story bathroom was difficult to latch. Adjust as needed.

G. Item 9(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 20 of 75REI 7-5 (05/04/2015)

Page 21: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(8) The shower door contacts the towel bar in the left rear first story bathroom.

G. Item 10(Picture)

(9) Rot and damage were observed at the door to the attached water softener/storage shed.

G. Item 11(Picture)

(10) An auto-closing hinge is recommended at the garage entry door to ensure fire separation between thegarage and dwelling.(11) The door to the media room binds at the frame. Adjust as needed.

H. WindowsComments:(1) Re-seal caulk around one or more windows to prevent water penetration.

H. Item 1(Picture) H. Item 2(Picture)

(2) Mildew was observed at the glazing for several window panes.

Report Identification: 2308 Woodlawn Blvd

Page 21 of 75REI 7-5 (05/04/2015)

Page 22: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

H. Item 3(Picture) H. Item 4(Picture)

(3) Windows in one or more areas of the home meet the requirements for tempered/safety glass. Some ofthe code requirements are: In all bathtub/shower areas. In all stairways where windows are not protectedfrom damage. Exposed area of an individual pane is greater than 9 square feet. Bottom edge is less than18" above the floor. Top edge greater than 36" above the floor. One or more walking surfaces within 36"horizontally of the glazing. Glazing in any part of a building wall enclosing these compartments where thebottom exposed edge of the glazing is less than 60" measured vertically above any standing or walkingsurface. Recommend installing tempered glass in all required areas.

H. Item 5(Picture)

(4) Inspector was unable to open various windows throughout the home. Recommend further evaluation ofall windows by a qualified contractor.

Report Identification: 2308 Woodlawn Blvd

Page 22 of 75REI 7-5 (05/04/2015)

Page 23: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

H. Item 6(Picture) H. Item 7(Picture)

H. Item 8(Picture) H. Item 9(Picture)

H. Item 10(Picture) H. Item 11(Picture)

(5) The latch hardware was loose at one or more windows.

H. Item 12(Picture) H. Item 13(Picture)

(6) Sash cords were damaged at one or more windows.

Report Identification: 2308 Woodlawn Blvd

Page 23 of 75REI 7-5 (05/04/2015)

Page 24: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

H. Item 14(Picture)

(7) Cracked glass was observed at one window in the formal dining room.

H. Item 15(Picture) H. Item 16(Picture)

(8) The kitchen faucet interferes with operation of the window shutter.

H. Item 17(Picture)

(9) Water staining was observed at one or more window sills.

Report Identification: 2308 Woodlawn Blvd

Page 24 of 75REI 7-5 (05/04/2015)

Page 25: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

H. Item 18(Picture) H. Item 19(Picture)

(10) One or more window screens were missing or not installed at the time of the inspection.

I. Stairways (Interior & Exterior)Comments:

J. Fireplaces and ChimneysComments:(1) There was no flue damper present at the left side fireplace.

J. Item 1(Picture)

(2) Seal all cracks in fire place before use, have a fireplace specialist evaluate and repair

J. Item 2(Picture)

(3) The damper was "seized" (non-operational) at the fireplace in the basement. Recommend furtherevaluation and repair by a qualified contractor.

Report Identification: 2308 Woodlawn Blvd

Page 25 of 75REI 7-5 (05/04/2015)

Page 26: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

J. Item 3(Picture)

K. Porches, Balconies, Decks and CarportsComments:(1) Cracks were observed at one or more areas of the driveway. Seal these areas to prevent settlement offlatwork.

K. Item 1(Picture) K. Item 2(Picture)

K. Item 3(Picture)

(2) Cracked grout was observed at the floor tiles for the front porch.

K. Item 4(Picture) K. Item 5(Picture)

(3) The paint is failing and/or worn at one or more areas of the exterior wood. I recommend prepping andpainting at all exposed areas to prevent rot.

Report Identification: 2308 Woodlawn Blvd

Page 26 of 75REI 7-5 (05/04/2015)

Page 27: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

K. Item 6(Picture)

(4) Rot was observed at several rear porch columns. Replace or repair all damaged and rotten wood.Additional damage may be present that was not visible to the inspector.

K. Item 7(Picture) K. Item 8(Picture)

K. Item 9(Picture)

(5) The guardrail for the front balcony was not properly secured at the base. Repair as needed for safety.

K. Item 10(Picture) K. Item 11(Picture)

K. Item 12(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 27 of 75REI 7-5 (05/04/2015)

Page 28: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

II. ELECTRICAL SYSTEMS

Recommend further evaluation and repair of all electrical deficiencies by a licensed electrician.

A. Service Entrance and PanelsElectrical Service Conductors: Below groundComments:(1) There was insufficient clearance present at one or more electrical panels. All electrical panels shouldhave a clear area 36" deep x 30" wide x 78" high.

A. Item 1(Picture)

A. Item 2(Picture)

A. Item 3(Picture)

(2) There was no walkway or platform present in front of the distribution panel in the attic above the mastersuite. Recommend correcting for safety.

A. Item 4(Picture)

(3) Wiring was bundled in one or more electrical panels. While this is common practice, it is not allowed bytoday's electrical code.

Report Identification: 2308 Woodlawn Blvd

Page 28 of 75REI 7-5 (05/04/2015)

Page 29: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 5(Picture) A. Item 6(Picture)

(4) Label all breakers for safety.

A. Item 7(Picture)

A. Item 8(Picture) A. Item 9(Picture)

(5) Neutral (white) wires used as hot wires should be marked with black or red electrical tape for safety.

A. Item 10(Picture)

(6) Knockout cover(s) were missing at one or more electrical panels. This is a safety hazard.

Report Identification: 2308 Woodlawn Blvd

Page 29 of 75REI 7-5 (05/04/2015)

Page 30: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 11(Picture)

A. Item 12(Picture)

A. Item 13(Picture)

(7) The conduit was not secured at the base of one rear exterior distribution panel.

A. Item 14(Picture)

(8) One breaker was tripped in a distribution panel beneath the right stairway. The breaker appeared to belabeled "Temporal." Soot was observed at one automated lighting controller in "Enclosure 2." Inspectorwas unable to determine if these two devices were connected. Recommend further evaluation and repairby a licensed electrician.

A. Item 15(Picture) A. Item 16(Picture)

A. Item 17(Picture)

(9) Screws were missing at one or more distribution panels.

Report Identification: 2308 Woodlawn Blvd

Page 30 of 75REI 7-5 (05/04/2015)

Page 31: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 18(Picture)

(10) One AFCI breaker in a distribution panel beneath the right stairway did not trip when tested.

A. Item 19(Picture)

(11) The backup generator installed at the inspected property is beyond the scope of this inspection,however, damage was observed at the conduit leading from this unit.

A. Item 20(Picture) A. Item 21(Picture)

(12) Inspector was unable to locate the gas line bond wire. Current code requires all exterior meters andinterior unions to be bonded.

B. Branch Circuits, Connected Devices, and FixturesType of Wiring: RomexBranch wire 15 and 20 AMP: CopperComments:(1) All electrical junctions and terminations should be secured within junction boxes fitted with cover plates.

Report Identification: 2308 Woodlawn Blvd

Page 31 of 75REI 7-5 (05/04/2015)

Page 32: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

B. Item 1(Picture) B. Item 2(Picture)

B. Item 3(Picture)

B. Item 4(Picture) B. Item 5(Picture)

(2) Bulbs were missing or inoperable at one or more light fixtures.

B. Item 6(Picture)

B. Item 7(Picture)

B. Item 8(Picture)

B. Item 9(Picture) B. Item 10(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 32 of 75REI 7-5 (05/04/2015)

Page 33: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(3) Bulb shields were missing at one or more light fixtures. Bulb shields are recommended at all exposedbulbs.

B. Item 11(Picture) B. Item 12(Picture)

B. Item 13(Picture)

(4) There were no wet location covers installed for the light fixtures in the master shower stalls.

B. Item 14(Picture) B. Item 15(Picture)

(5) Replace any damaged outlet covers.

B. Item 16(Picture) B. Item 17(Picture)

(6) There was no electricity present at the floor outlets in the master bedroom. These outlets may becontrolled by a light switch.

Report Identification: 2308 Woodlawn Blvd

Page 33 of 75REI 7-5 (05/04/2015)

Page 34: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

B. Item 18(Picture) B. Item 19(Picture)

(7) Secure any loose electrical outlets.

B. Item 20(Picture)

(8) Replace any missing outlet covers.

B. Item 21(Picture) B. Item 22(Picture)

(9) Recommend weather resistant (bubble type) covers at all exterior electrical outlets.

B. Item 23(Picture) B. Item 24(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 34 of 75REI 7-5 (05/04/2015)

Page 35: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(10) The GFCI outlets in the garage would not trip when tested.

B. Item 25(Picture)

(11) Cloth covered wiring is still in place and possibly in use in some areas of the home. Recommendhaving a licensed electrician evaluate and update all wiring to meet today's code and safety standards

B. Item 26(Picture)

(12) The automated/remote lighting control system(s) at the inspected home are beyond the scope of thisinspection.

B. Item 27(Picture)

B. Item 28(Picture)

(13) The inspector was unable to determine uses for all light switches.(14) Today's fire safety standards call for smoke detectors in and outside of all sleeping rooms. A minimumof one detector is required for each level. All detectors should be linked in a way that when one detectorsounds they all sound. Test and maintain detectors per manufacturer specifications and replace batteriesyearly or as needed.

Report Identification: 2308 Woodlawn Blvd

Page 35 of 75REI 7-5 (05/04/2015)

Page 36: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS

Recommend further evaluation and repair of all HVAC deficiencies by a licensed HVAC contractor.

A. Heating EquipmentType of Systems: Forced Air, Heat Pump Forced Air (also provides cool air)Energy Sources: Gas, ElectricNumber of Heat Systems (excluding wood): One, EightComments:The heat pumps were not tested for proper operation due to the outside air temperature being 70 degreesor more. Doing so could damage the unit.

B. Cooling EquipmentType of Systems: Heat Pump Forced Air (also provides warm air), Air conditioner unitComments:(1) The AC for the study/left wing bedroom was inoperable. Several error messages were present at thethermostat.

B. Item 1(Picture)

(2) The AC for the right rear first story bedroom was inoperable. An error message was present at thethermostat.

B. Item 2(Picture)

(3) Rust was observed in the secondary condensate drain pan(s). Ensure that the primary condensatedrain line is free and clear and draining properly.

Report Identification: 2308 Woodlawn Blvd

Page 36 of 75REI 7-5 (05/04/2015)

Page 37: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

B. Item 3(Picture) B. Item 4(Picture)

(4) Air leakage and mildew were observed at the supply plenum connection for the left-most evaporator inthe attic above the master suite.

B. Item 5(Picture)

(5) Condensate drain lines should extend at least 3' from the foundation.

B. Item 6(Picture)

(6) HVAC systems should be serviced twice per year by a licensed professional. We cannot determine if orwhen these systems were last serviced.Condenser Manufacture Date: 2017AC Tonnage: 5, 3, 4, 3, 5, 4, 2, 5Refrigerant: HFC-410A

C. Duct Systems, Chases, and VentsComments:(1) Mildew was observed at one or more supply registers.

Report Identification: 2308 Woodlawn Blvd

Page 37 of 75REI 7-5 (05/04/2015)

Page 38: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

C. Item 1(Picture) Cedar closet

(2) Rust, condensation and excessive noise were observed at the zone dampers in the attic above themaster suite.

C. Item 2(Picture) C. Item 3(Picture)

C. Item 4(Picture)

(3) Current code standards require that ducting be secured away from insulation.

C. Item 5(Picture)

(4) Ducts should not overlap in the attic area. Overlapping ducts can compress the duct insulation andcause condensation to form between the plastic ducting and duct insulation. Repair as needed.

Report Identification: 2308 Woodlawn Blvd

Page 38 of 75REI 7-5 (05/04/2015)

Page 39: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

C. Item 6(Picture) C. Item 7(Picture)

(5) The ancillary ventilation systems at the inspected home are beyond the scope of this inspection,however, ducts were disconnected and/or constricted at several units. One unit was unplugged.

C. Item 8(Picture) C. Item 9(Picture)

C. Item 10(Picture) C. Item 11(Picture)

(6) The interior condition and cleanliness of the ductwork was not visible or accessible. Disassembly of theHVAC or removal of registers is beyond the scope of this inspection. If further evaluation is desired, alicensed HVAC contractor should be contacted.

Report Identification: 2308 Woodlawn Blvd

Page 39 of 75REI 7-5 (05/04/2015)

Page 40: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

IV. PLUMBING SYSTEM

Recommend further evaluation and repair of all plumbing deficiencies by a licensed plumber.

A. Plumbing Supply Distribution Systems and FixturesLocation of water meter: Street, Front, Right SideLocation of main water supply valve: Front, Right SideStatic water pressure reading: 80+ psiWater Source: PublicComments:(1) Remove debris from the main water supply valve and replace the damaged cover to allow access in theevent of an emergency.

A. Item 1(Picture)

(2) Water pressure was measured at over 80 psi. Excessive water pressure can damage water lines andfixtures. Pressure regulation is recommended.

A. Item 2(Picture)

(3) A constant drip was observed at the left front exterior hose bib.

Report Identification: 2308 Woodlawn Blvd

Page 40 of 75REI 7-5 (05/04/2015)

Page 41: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 3(Picture)

(4) A rusty discharge was observed at several plumbing fixtures.

A. Item 4(Picture) A. Item 5(Picture)

(5) The hot and cold water were reversed at the faucet for the Jacuzzi tub in the master bathroom. Hotshould be oriented toward the left when facing the fixture.

A. Item 6(Picture)

(6) A leak was observed at the right shower head in the master bathroom.

A. Item 7(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 41 of 75REI 7-5 (05/04/2015)

Page 42: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(7) A constant drip was observed at the shower head in the right-most second story hall bathroom.

A. Item 8(Picture)

(8) Low flow was observed at the faucet in the first story hall bathroom.

A. Item 9(Picture)

(9) The aerator screen was missing a small kitchen sink.

A. Item 10(Picture)

(10) The shower handle was not attached properly at one first story bathroom.

Report Identification: 2308 Woodlawn Blvd

Page 42 of 75REI 7-5 (05/04/2015)

Page 43: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 11(Picture)

(11) Low flow was observed at the shower in the right first story bathroom.

A. Item 12(Picture)

(12) The cold water handle at the first story right side bathroom faucet was seized.

A. Item 13(Picture)

(13) Corrosion was observed at the water supply valves under the garage sink.

A. Item 14(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 43 of 75REI 7-5 (05/04/2015)

Page 44: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(14) There was no cold water present at the faucet for the wet bar.

A. Item 15(Picture)

(15) The toilet at left side ran continuously after flushing. The tank flap seal is damaged. As a courtesy,inspector turned off the supply valve leading to this toilet.

A. Item 16(Picture) A. Item 17(Picture)

(16) A crack was observed at the toilet basin in the left rear first story bathroom.

A. Item 18(Picture)

(17) Corrosion was observed at one supply valve in the basement.

Report Identification: 2308 Woodlawn Blvd

Page 44 of 75REI 7-5 (05/04/2015)

Page 45: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 19(Picture)

(18) Insulate all exposed water lines to prevent freezing.

A. Item 20(Picture) A. Item 21(Picture)

(19) Dissimilar piping types were present at various areas of the crawlspace. These connections are proneto leaking and should be monitored.

A. Item 22(Picture)

(20) Galvanized supply lines were observed in one or more areas of the home. These lines can rust fromthe inside out and should be monitored if still in use.(21) The steam showers installed at the inspected home are beyond the scope of this inspection.

Report Identification: 2308 Woodlawn Blvd

Page 45 of 75REI 7-5 (05/04/2015)

Page 46: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

A. Item 23(Picture) A. Item 24(Picture)

(22) The water softener installed at the inspected home is beyond the scope of this inspection, however,there was no salt present in the brine tank.

A. Item 25(Picture)

A. Item 26(Picture)

(23) The water filtration system installed a the inspected home is beyond the scope of this inspection.

A. Item 27(Picture)

B. Drains, Waste, and VentsComments:(1) Cast iron drain lines may be present under the home and/or between the home and public sewersystem. Recommend a static test or drain scope to verify the integrity of the plumbing system. Theinspector does not run the amount of water during the inspection that would emulate the daily use of afamily.

Report Identification: 2308 Woodlawn Blvd

Page 46 of 75REI 7-5 (05/04/2015)

Page 47: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

B. Item 1(Picture)

(2) One drain line in the crawlspace did not appear to be sloped properly.

B. Item 2(Picture)

(3) Inspector was unable to determine the purpose of what appeared to be a plumbing vent in the atticabove the master suite. This vent should likely terminate at the home's exterior.

B. Item 3(Picture)

(4) Drain stoppers were missing or inoperable at one or more bathroom sinks.

B. Item 4(Picture) B. Item 5(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 47 of 75REI 7-5 (05/04/2015)

Page 48: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(5) The shower pan in the right-most second story bathroom did not appear to be adequately sloped todirect water toward the drain. The recommended minimum slope for a shower floor is 1/4" per foot.

B. Item 6(Picture)

(6) A hollow drip/popping noise was observed at the small sink in the kitchen. This sound may be related tothe AC condensate line that was tied-into this drain line beneath the sink.

B. Item 7(Picture)

(7) The over flow drain cover was missing at the first story right side rear bath tub.

B. Item 8(Picture)

C. Water Heating EquipmentEnergy Sources: Gas (quick recovery)Capacity (Water Heater): 40 Gallon (1-2 people), 75 Gallon, four unitsComments:(1) The water heaters at the inspected home are at the end of their useful lives. Water Heater ManufactureDate: 2003(2) The water heater did not have a thermal expansion tank installed to prevent a possible leak at the T&Por "pop-off" valve. Current code standards require an expansion tank when a pressure-reducing valve

Report Identification: 2308 Woodlawn Blvd

Page 48 of 75REI 7-5 (05/04/2015)

Page 49: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(PRV) is in place at the water supply line/system. Inspector may not be able to verify the presence of aPRV.

C. Item 1(Picture)

(3) Insulate water lines at the top of the water heater to prevent freezing.

C. Item 2(Picture)

(4) The outer burner cover was not installed at the water heater in the attic above the study.

C. Item 3(Picture)

(5) Clear debris from water heater drain pan to prevent the clogging of drain line

Report Identification: 2308 Woodlawn Blvd

Page 49 of 75REI 7-5 (05/04/2015)

Page 50: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

C. Item 4(Picture)

(6) Any hot water recirculation pumps installed at the inspected home are beyond the scope of thisinspection.

C. Item 5(Picture) C. Item 6(Picture)

(7) There was no sediment trap present at the gas supply line. (Required by current code standards.)

D. Hydro-Massage Therapy EquipmentComments:(1) The drain stopper did not seal completely at the Jacuzzi tub in the left-most second story bathroom.

D. Item 1(Picture)

(2) Inspector was unable to operate the Jacuzzi tub in the left-most second story bathroom. The coverappeared to be missing at one of the control knobs.

Report Identification: 2308 Woodlawn Blvd

Page 50 of 75REI 7-5 (05/04/2015)

Page 51: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

D. Item 2(Picture) D. Item 3(Picture)

(3) Debris was present in tub jets. Clean before use.

D. Item 4(Picture) D. Item 5(Picture)

(4) No tub motor access was found for the Jacuzzi tubs.(5) Inspector was unable to locate GFCI protection for the Jacuzzi tub. Current code standards require thatJacuzzi tubs be GFCI-protected.

Report Identification: 2308 Woodlawn Blvd

Page 51 of 75REI 7-5 (05/04/2015)

Page 52: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

V. APPLIANCES

A. DishwashersComments:(1) It is recommended that the dishwasher drain line be kept strapped/looped upward (forming a sanitarydrain loop) preventing debris from sink drain lines and garbage disposal from entering the dish washerdrain line

A. Item 1(Picture)

(2) The rinse aid doors at both dishwashers did not open during the wash cycle.

B. Food Waste DisposersComments:

C. Range Hood and Exhaust SystemsExhaust/Range hood: VentedComments:One light bulb was inoperable at the range exhaust hood.

C. Item 1(Picture)

D. Ranges, Cooktops and OvensComments:(1) The oven is in need of cleaning.

Report Identification: 2308 Woodlawn Blvd

Page 52 of 75REI 7-5 (05/04/2015)

Page 53: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

D. Item 1(Picture)

(2) The cook top is in need of cleaning.

D. Item 2(Picture)

(3) The secondary oven door (under the microwave) did not close completely. Adjust or repair as needed.

E. Microwave OvensComments:The inspector does not test for radiation leakage.

F. Mechanical Exhaust Vents and Bathroom HeatersComments:Exhaust vents should terminate to the exterior. Vent termination is not always visible

F. Item 1(Picture) F. Item 2(Picture)

G. Garage Door Operator(s)Comments:(1) Rot was observed at the center overhead garage door. Repair or replace all damaged and rotten wood.

Report Identification: 2308 Woodlawn Blvd

Page 53 of 75REI 7-5 (05/04/2015)

Page 54: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

G. Item 1(Picture)

(2) Wood separation was present at one or more garage doors.

G. Item 2(Picture)

(3) The rubber seal was incomplete at the base of one overhead door

G. Item 3(Picture)

(4) Remove or disable lock at garage overhead door with opener installed to prevent accidental damage todoor

G. Item 4(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 54 of 75REI 7-5 (05/04/2015)

Page 55: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(5) Bulbs were missing or inoperable at one or more garage door openers.

G. Item 5(Picture)

(6) The rubber belts in belt-driven overhead door openers can break easily and are not tested for downforce sensitivity. If you are concerned about the down force adjustment on your opener, an overhead doorcontractor should be contacted. Photoelectric sensors were tested, unless otherwise noted..

H. Dryer Exhaust SystemsComments:The dryer vent is in need of cleaning. Dryer vents should be cleaned every 6 months.

H. Item 1(Picture)

I. OtherComments:(1) The elevators and related equipment at the inspected home are beyond the scope of this inspection,however, they appeared to operate as intended.

I. Item 1(Picture)

I. Item 2(Picture) I. Item 3(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 55 of 75REI 7-5 (05/04/2015)

Page 56: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(2) The automatic gate at the inspected property is beyond the scope of this inspection.

I. Item 4(Picture)

(3) Water pressure pumps are beyond the scope of this inspection.

I. Item 5(Picture)

(4) The Radon system installed at the inspected home is beyond the scope of this inspection.

I. Item 6(Picture)

(5) Refrigerators, freezers wine chillers and laundry equipment are beyond the scope of this inspection.

Report Identification: 2308 Woodlawn Blvd

Page 56 of 75REI 7-5 (05/04/2015)

Page 57: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

I. Item 7(Picture) I. Item 8(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 57 of 75REI 7-5 (05/04/2015)

Page 58: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

VI. OPTIONAL SYSTEMS

A. Landscape Irrigation (Sprinkler) SystemsComments:(1) Low flow was observed Stations 1, 2, 3, 4, 5, 9, 10, 13, 16 and 17. Recommend further evaluation andrepair by a qualified contractor.

A. Item 1(Picture)

A. Item 2(Picture)

(2) Damage was observed at one sprinkler head for Station 15.

A. Item 3(Picture)

(3) Some sprinkler heads are in need of spray pattern adjustment to prevent the watering of fences, wallsand flatwork.

A. Item 4(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 58 of 75REI 7-5 (05/04/2015)

Page 59: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

(4) Inspector was unable to locate the rain sensor for sprinkler system.(5) The irrigation system is inspected in manual mode only. Inspector does not test for underground leaks.

D. Private Water Wells (A coliform analysis is recommended)Comments:The well at the inspected property is beyond the scope of this inspection, however, the pressure gaugeattached to the supply line was not functioning.

D. Item 1(Picture) D. Item 2(Picture)

D. Item 3(Picture)

E. Private Sewage Disposal (Septic) SystemComments:(1) The waste ejector (grinder) pump installed at this property is beyond the scope of this inspection.Recommend further evaluation by a qualified contractor.

E. Item 1(Picture)

(2) The sump pumps installed in the basement for the inspected home are beyond the scope of thisinspection, however, significant corrosion was observed at these systems.

Report Identification: 2308 Woodlawn Blvd

Page 59 of 75REI 7-5 (05/04/2015)

Page 60: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I = Inspected NI = Not Inspected NP = Not Present D = Deficient

I NI NP D

E. Item 2(Picture) E. Item 3(Picture)

F. OtherComments:The fountain installed at the inspected property is beyond the scope of this inspection, however, corrosionwas observed at the pump motor housing.

F. Item 1(Picture) F. Item 2(Picture)

F. Item 3(Picture)

Report Identification: 2308 Woodlawn Blvd

Page 60 of 75REI 7-5 (05/04/2015)

Page 61: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

General Summary

Austinspect, Inc.

220 Racetrack DrAustin, TX 78748

512.633.9488

CustomerTish Rielly

Tara McLean

Address2308 Woodlawn Blvd

Austin TX 78703

The following items or discoveries indicate that these systems or components do not function as intended or adverselyaffects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequentobservation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it inproper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. ThisSummary is not the entire report. The complete report may include additional information of concern to the customer. It isrecommended that the customer read the complete report.

I. STRUCTURAL SYSTEMSA. Foundations

Inspected, Deficient(1) One or more foundation vent(s) were below ground level, which can allow water to enter the crawlspace.(2) Standing water was observed in the crawlspace beneath the left side of the home. Water intrusion cancontribute to differential foundation movement and mold. Improve grading & drainage as needed to prevent waterintrusion.(3) No under floor insulation or moisture barrier were present in the crawlspace.(4) Cracks were observed at one or more areas of the perimeter footing.(5) Any construction debris should be removed from the crawlspace under the home.(6) The foundation did not appear to be in need of immediate remedial leveling at the time of the visual inspection.Hairline cracks were observed at the garage floor. The rate of hairline cracks cannot be determined from a one-timesite visual inspection and should be monitored. If the cracks advance, a qualified foundation engineer should becontacted for further evaluation.(7) Only areas of the crawlspace determined accessible by the inspector are inspected.

B. Grading & DrainageInspected, Deficient(1) There was a negative slope observed towards the home in one or more areas. Proper drainage is critical to theperformance of the foundation. All grades should drop away from the structure at a rate of 6 inches for every 10feet. Improve drainage as needed so that water flows away from the home.

Report Identification: 2308 Woodlawn Blvd

Page 61 of 75REI 7-5 (05/04/2015)

Page 62: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I. STRUCTURAL SYSTEMS(2) It is advisable to maintain at least 3-6 inches minimum of clear area between the ground and exterior finishes.Areas where the soil is in contact with the exterior finish are conducive to wood-destroying insect activity.(3) Holes (possibly from burrowing pests) were observed at the base of the steps to the abandoned rear porch.(4) One or more gutters appear to hold water and need to be re-pitched for proper drainage.(5) Inspector cannot determine whether underground drainage systems will perform as intended. Monitor thesedrains and keep them clear of debris to ensure adequate flow.(6) The landscape in some areas may require a trench or drain if water stands or puddles after heavy rain.

C. Roof Covering MaterialsInspected, Not Inspected, Deficient(1) Slate tile roofs are not walked on by the inspector, however, cracked and loose tiles were observed at the roofcovering above the rear porches. Recommend further evaluation and repair by a qualified roofing contractor.(2) Ponding was observed at the flashing beneath the dormer windows above the garage.(3) Kick-out flashing is recommended at roof-to-wall connections to divert water away from exterior finishes. Have aroofer correct where needed.(4) The tree limbs that are in contact with, or hanging near the roof should be trimmed.(5) Client Advisory: The roof was not safely/easily accessible due to the height off the ground with no secondarymethod of access. Some items may not be discovered without access to the roof. Recommend having the roof androof covering materials evaluated by a roofing contractor. The inspector cannot guarantee that the roof will be freeof leaks, nor can the inspector determine the remaining service life of the roof covering.

D. Roof Structures and AtticsInspected, Deficient(1) Rot was observed at several cupolas. Repair or replace any damaged and rotten wood. Additional damage maybe present that was not visible to the inspector.(2) Weather-strip the attic access perimeters and insulate the access covers to reduce air infiltration and heat fromthe attic area.(3) Inspector was unable to open the metal scuttle hole in the master bedroom.(4) One or more attic access openings are undersized by today's code standards. The minimum attic accessopening should be 22" x 30". The size of the access door above the kitchen area may inhibit service and/orreplacement of the HVAC equipment in this space.(5) No strong backs (T-bracing) were present at the roof supports above the master suite. T-bracing helps preventsupports from bowing. Repair as needed.(6) Current building standards dictate that roof supports and purlin should be the same size as the lumber that theysupport. 2x6 roof rafters are being supported by 2x4 and 1x6 supports in some areas. The roof and structure wereperforming as intended at the time of inspection.(7) Current code standards call for collar ties to be installed between rafters to prevent rafter spread.(8) A bucket was observed in the attic above the master bedroom. Inspector was unable to access this space.(9) Water staining was observed at the attic decking above the vestibule to the master suite.(10) Rodent traps were observed in the attic. Pest control and sealing of access points is recommended.(11) Insulation should be properly distributed to cover all portions of the attic located above the home living space.(12) Recommend additional insulation to bring attic R value to an R 30 or greater.(13) Only areas of the attic determined accessible by the inspector were inspected. Insulation, HVAC ducts/mechanical equipment, limited headroom, wiring (electrical, cable and alarm) and risk of ceiling damage areexamples of factors that may inhibit access.

E. Walls (Interior & Exterior)Inspected, Deficient(1) Cracks were observed in the mortar at one or more areas of the masonry veneer. Mortar improvements arerecommended to prevent water penetration.(2) Rot was observed at the siding and/or wood trim in one or more areas. Replace or repair all damaged and rottenwood. Additional damage may be present that was not visible to the inspector.(3) The paint is failing and/or worn at one or more areas of the exterior wood. I recommend prepping and painting atall exposed areas to prevent rot.

Report Identification: 2308 Woodlawn Blvd

Page 62 of 75REI 7-5 (05/04/2015)

Page 63: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I. STRUCTURAL SYSTEMS(4) Exterior finishes should be installed 2" from any hard walking surface and 4" or greater above grade. Theinspected home had one or more areas that do not meet these standards. Correct/repair as needed.(5) No weep holes were present over the windows and doors installed in the masonry veneer. Weep holes arerequired by current code standards.(6) Re-seal caulk at all wood trim-to-masonry connections to prevent rot and water penetration.(7) Wood trim at the overhead garage door sides had inadequate clearance from the ground and will be subjected to highmoisture conditions from rain water. This condition may cause early trim failure along the base. Trim and seal as needed.(8) Trim vegetation back from walls to prevent pest intrusion.(9) Stucco (Hard Coat or EIFS) Observation and Opinions:There was a stucco-type product installed as the exterior veneer/cladding for this structure. A full evaluation of thisproduct is outside the scope of this inspection. At this time a general, limited, visually-based survey of theaccessible exterior stucco veneer/cladding was performed without the use of any specialized tools or procedures.The Inspector's findings will be listed below but all possible deficiencies will not be limited to what is included in thisreport.(10) Settlement was observed at one or more interior walls.(11) Caulk around all shower/tub fixtures. It is important to keep all around wet area fixtures well sealed to preventwater damage. Damage can be present behind these areas that is not visible to inspector. The inspector does notperform destructive testing or investigation. Repair as needed.

F. Ceilings & FloorsInspected, Deficient(1) Separation was observed at the decorative molding in the rear first-story living area.(2) Peeling paint was observed at the ceiling near one or more supply registers. This may be an indication of poorAC performance.(3) Temperature anomalies were observed at one or more ceiling areas. This may indicate that these areas areinadequately insulated.(4) Depressions were observed at the floor in the master bedroom.(5) Stains were observed various carpeted areas.

G. Doors (Interior & Exterior)Inspected, Deficient(1) One or more dead bolts at exterior doors were keyed. Recommend thumbscrew type for fire egress.(2) Inspector was unable to operate the doors to the balcony.(3) The stain was faded at one or more exterior doors.(4) Inspector is unable to determine if the safety glass is present in doors with glass panes.(5) Door stops were missing behind one or more doors. Install door stops to prevent wall damage.(6) The rubber seals were missing at the base of several shower doors. Install seals to prevent water from leakingto the shower exterior.(7) The shower door in the left-most second story bathroom was difficult to latch. Adjust as needed.(8) The shower door contacts the towel bar in the left rear first story bathroom.(9) Rot and damage were observed at the door to the attached water softener/storage shed.(10) An auto-closing hinge is recommended at the garage entry door to ensure fire separation between the garageand dwelling.(11) The door to the media room binds at the frame. Adjust as needed.

H. WindowsInspected, Deficient(1) Re-seal caulk around one or more windows to prevent water penetration.(2) Mildew was observed at the glazing for several window panes.(3) Windows in one or more areas of the home meet the requirements for tempered/safety glass. Some of the coderequirements are: In all bathtub/shower areas. In all stairways where windows are not protected from damage.Exposed area of an individual pane is greater than 9 square feet. Bottom edge is less than 18" above the floor. Topedge greater than 36" above the floor. One or more walking surfaces within 36" horizontally of the glazing. Glazing

Report Identification: 2308 Woodlawn Blvd

Page 63 of 75REI 7-5 (05/04/2015)

Page 64: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

I. STRUCTURAL SYSTEMSin any part of a building wall enclosing these compartments where the bottom exposed edge of the glazing is lessthan 60" measured vertically above any standing or walking surface. Recommend installing tempered glass in allrequired areas.(4) Inspector was unable to open various windows throughout the home. Recommend further evaluation of allwindows by a qualified contractor.(5) The latch hardware was loose at one or more windows.(6) Sash cords were damaged at one or more windows.(7) Cracked glass was observed at one window in the formal dining room.(8) The kitchen faucet interferes with operation of the window shutter.(9) Water staining was observed at one or more window sills.(10) One or more window screens were missing or not installed at the time of the inspection.

J. Fireplaces and ChimneysInspected, Deficient(1) There was no flue damper present at the left side fireplace.(2) Seal all cracks in fire place before use, have a fireplace specialist evaluate and repair(3) The damper was "seized" (non-operational) at the fireplace in the basement. Recommend further evaluation andrepair by a qualified contractor.

K. Porches, Balconies, Decks and CarportsInspected, Deficient(1) Cracks were observed at one or more areas of the driveway. Seal these areas to prevent settlement of flatwork.(2) Cracked grout was observed at the floor tiles for the front porch.(3) The paint is failing and/or worn at one or more areas of the exterior wood. I recommend prepping and painting atall exposed areas to prevent rot.(4) Rot was observed at several rear porch columns. Replace or repair all damaged and rotten wood. Additionaldamage may be present that was not visible to the inspector.(5) The guardrail for the front balcony was not properly secured at the base. Repair as needed for safety.

II. ELECTRICAL SYSTEMSA. Service Entrance and Panels

Inspected, Deficient(1) There was insufficient clearance present at one or more electrical panels. All electrical panels should have aclear area 36" deep x 30" wide x 78" high.(2) There was no walkway or platform present in front of the distribution panel in the attic above the master suite.Recommend correcting for safety.(3) Wiring was bundled in one or more electrical panels. While this is common practice, it is not allowed by today'selectrical code.(4) Label all breakers for safety.(5) Neutral (white) wires used as hot wires should be marked with black or red electrical tape for safety.(6) Knockout cover(s) were missing at one or more electrical panels. This is a safety hazard.(7) The conduit was not secured at the base of one rear exterior distribution panel.(8) One breaker was tripped in a distribution panel beneath the right stairway. The breaker appeared to be labeled"Temporal." Soot was observed at one automated lighting controller in "Enclosure 2." Inspector was unable todetermine if these two devices were connected. Recommend further evaluation and repair by a licensed electrician.(9) Screws were missing at one or more distribution panels.(10) One AFCI breaker in a distribution panel beneath the right stairway did not trip when tested.(11) The backup generator installed at the inspected property is beyond the scope of this inspection, however,damage was observed at the conduit leading from this unit.(12) Inspector was unable to locate the gas line bond wire. Current code requires all exterior meters and interiorunions to be bonded.

Report Identification: 2308 Woodlawn Blvd

Page 64 of 75REI 7-5 (05/04/2015)

Page 65: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

II. ELECTRICAL SYSTEMSB. Branch Circuits, Connected Devices, and Fixtures

Inspected, Deficient(1) All electrical junctions and terminations should be secured within junction boxes fitted with cover plates.(2) Bulbs were missing or inoperable at one or more light fixtures.(3) Bulb shields were missing at one or more light fixtures. Bulb shields are recommended at all exposed bulbs.(4) There were no wet location covers installed for the light fixtures in the master shower stalls.(5) Replace any damaged outlet covers.(6) There was no electricity present at the floor outlets in the master bedroom. These outlets may be controlled by alight switch.(7) Secure any loose electrical outlets.(8) Replace any missing outlet covers.(9) Recommend weather resistant (bubble type) covers at all exterior electrical outlets.(10) The GFCI outlets in the garage would not trip when tested.(11) Cloth covered wiring is still in place and possibly in use in some areas of the home. Recommend having alicensed electrician evaluate and update all wiring to meet today's code and safety standards(12) The automated/remote lighting control system(s) at the inspected home are beyond the scope of thisinspection.(13) The inspector was unable to determine uses for all light switches.(14) Today's fire safety standards call for smoke detectors in and outside of all sleeping rooms. A minimum of onedetector is required for each level. All detectors should be linked in a way that when one detector sounds they allsound. Test and maintain detectors per manufacturer specifications and replace batteries yearly or as needed.

III. HEATING, VENTILATION AND AIR CONDITIONING SYSTEMSB. Cooling Equipment

Inspected, Deficient(1) The AC for the study/left wing bedroom was inoperable. Several error messages were present at the thermostat.(2) The AC for the right rear first story bedroom was inoperable. An error message was present at the thermostat.(3) Rust was observed in the secondary condensate drain pan(s). Ensure that the primary condensate drain line isfree and clear and draining properly.(4) Air leakage and mildew were observed at the supply plenum connection for the left-most evaporator in the atticabove the master suite.(5) Condensate drain lines should extend at least 3' from the foundation.(6) HVAC systems should be serviced twice per year by a licensed professional. We cannot determine if or whenthese systems were last serviced.Condenser Manufacture Date: 2017AC Tonnage: 5, 3, 4, 3, 5, 4, 2, 5Refrigerant: HFC-410A

C. Duct Systems, Chases, and VentsInspected, Deficient(1) Mildew was observed at one or more supply registers.(2) Rust, condensation and excessive noise were observed at the zone dampers in the attic above the master suite.(3) Current code standards require that ducting be secured away from insulation.(4) Ducts should not overlap in the attic area. Overlapping ducts can compress the duct insulation and causecondensation to form between the plastic ducting and duct insulation. Repair as needed.(5) The ancillary ventilation systems at the inspected home are beyond the scope of this inspection, however, ductswere disconnected and/or constricted at several units. One unit was unplugged.(6) The interior condition and cleanliness of the ductwork was not visible or accessible. Disassembly of the HVAC orremoval of registers is beyond the scope of this inspection. If further evaluation is desired, a licensed HVACcontractor should be contacted.

Report Identification: 2308 Woodlawn Blvd

Page 65 of 75REI 7-5 (05/04/2015)

Page 66: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

IV. PLUMBING SYSTEMA. Plumbing Supply Distribution Systems and Fixtures

Inspected, Deficient(1) Remove debris from the main water supply valve and replace the damaged cover to allow access in the event ofan emergency.(2) Water pressure was measured at over 80 psi. Excessive water pressure can damage water lines and fixtures.Pressure regulation is recommended.(3) A constant drip was observed at the left front exterior hose bib.(4) A rusty discharge was observed at several plumbing fixtures.(5) The hot and cold water were reversed at the faucet for the Jacuzzi tub in the master bathroom. Hot should beoriented toward the left when facing the fixture.(6) A leak was observed at the right shower head in the master bathroom.(7) A constant drip was observed at the shower head in the right-most second story hall bathroom.(8) Low flow was observed at the faucet in the first story hall bathroom.(9) The aerator screen was missing a small kitchen sink.(10) The shower handle was not attached properly at one first story bathroom.(11) Low flow was observed at the shower in the right first story bathroom.(12) The cold water handle at the first story right side bathroom faucet was seized.(13) Corrosion was observed at the water supply valves under the garage sink.(14) There was no cold water present at the faucet for the wet bar.(15) The toilet at left side ran continuously after flushing. The tank flap seal is damaged. As a courtesy, inspectorturned off the supply valve leading to this toilet.(16) A crack was observed at the toilet basin in the left rear first story bathroom.(17) Corrosion was observed at one supply valve in the basement.(18) Insulate all exposed water lines to prevent freezing.(19) Dissimilar piping types were present at various areas of the crawlspace. These connections are prone toleaking and should be monitored.(20) Galvanized supply lines were observed in one or more areas of the home. These lines can rust from the insideout and should be monitored if still in use.(21) The steam showers installed at the inspected home are beyond the scope of this inspection.(22) The water softener installed at the inspected home is beyond the scope of this inspection, however, there wasno salt present in the brine tank.(23) The water filtration system installed a the inspected home is beyond the scope of this inspection.

B. Drains, Waste, and VentsInspected, Deficient(1) Cast iron drain lines may be present under the home and/or between the home and public sewer system.Recommend a static test or drain scope to verify the integrity of the plumbing system. The inspector does not runthe amount of water during the inspection that would emulate the daily use of a family.(2) One drain line in the crawlspace did not appear to be sloped properly.(3) Inspector was unable to determine the purpose of what appeared to be a plumbing vent in the attic above themaster suite. This vent should likely terminate at the home's exterior.(4) Drain stoppers were missing or inoperable at one or more bathroom sinks.(5) The shower pan in the right-most second story bathroom did not appear to be adequately sloped to direct watertoward the drain. The recommended minimum slope for a shower floor is 1/4" per foot.(6) A hollow drip/popping noise was observed at the small sink in the kitchen. This sound may be related to the ACcondensate line that was tied-into this drain line beneath the sink.(7) The over flow drain cover was missing at the first story right side rear bath tub.

C. Water Heating EquipmentInspected, Deficient

Report Identification: 2308 Woodlawn Blvd

Page 66 of 75REI 7-5 (05/04/2015)

Page 67: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

IV. PLUMBING SYSTEM(1) The water heaters at the inspected home are at the end of their useful lives. Water Heater Manufacture Date:2003(2) The water heater did not have a thermal expansion tank installed to prevent a possible leak at the T&P or "pop-off" valve. Current code standards require an expansion tank when a pressure-reducing valve (PRV) is in place atthe water supply line/system. Inspector may not be able to verify the presence of a PRV.(3) Insulate water lines at the top of the water heater to prevent freezing.(4) The outer burner cover was not installed at the water heater in the attic above the study.(5) Clear debris from water heater drain pan to prevent the clogging of drain line(6) Any hot water recirculation pumps installed at the inspected home are beyond the scope of this inspection.(7) There was no sediment trap present at the gas supply line. (Required by current code standards.)

D. Hydro-Massage Therapy EquipmentInspected, Not Inspected, Deficient(1) The drain stopper did not seal completely at the Jacuzzi tub in the left-most second story bathroom.(2) Inspector was unable to operate the Jacuzzi tub in the left-most second story bathroom. The cover appeared tobe missing at one of the control knobs.(3) Debris was present in tub jets. Clean before use.(4) No tub motor access was found for the Jacuzzi tubs.(5) Inspector was unable to locate GFCI protection for the Jacuzzi tub. Current code standards require that Jacuzzitubs be GFCI-protected.

V. APPLIANCESA. Dishwashers

Inspected, Deficient(1) It is recommended that the dishwasher drain line be kept strapped/looped upward (forming a sanitary drain loop)preventing debris from sink drain lines and garbage disposal from entering the dish washer drain line(2) The rinse aid doors at both dishwashers did not open during the wash cycle.

C. Range Hood and Exhaust SystemsInspected, DeficientOne light bulb was inoperable at the range exhaust hood.

D. Ranges, Cooktops and OvensInspected, Deficient(1) The oven is in need of cleaning.(2) The cook top is in need of cleaning.(3) The secondary oven door (under the microwave) did not close completely. Adjust or repair as needed.

F. Mechanical Exhaust Vents and Bathroom HeatersInspected, DeficientExhaust vents should terminate to the exterior. Vent termination is not always visible

G. Garage Door Operator(s)Inspected, Not Inspected, Deficient(1) Rot was observed at the center overhead garage door. Repair or replace all damaged and rotten wood.(2) Wood separation was present at one or more garage doors.(3) The rubber seal was incomplete at the base of one overhead door(4) Remove or disable lock at garage overhead door with opener installed to prevent accidental damage to door(5) Bulbs were missing or inoperable at one or more garage door openers.(6) The rubber belts in belt-driven overhead door openers can break easily and are not tested for down forcesensitivity. If you are concerned about the down force adjustment on your opener, an overhead door contractorshould be contacted. Photoelectric sensors were tested, unless otherwise noted..

Report Identification: 2308 Woodlawn Blvd

Page 67 of 75REI 7-5 (05/04/2015)

Page 68: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

V. APPLIANCESH. Dryer Exhaust Systems

Inspected, DeficientThe dryer vent is in need of cleaning. Dryer vents should be cleaned every 6 months.

VI. OPTIONAL SYSTEMSA. Landscape Irrigation (Sprinkler) Systems

Inspected, Deficient(1) Low flow was observed Stations 1, 2, 3, 4, 5, 9, 10, 13, 16 and 17. Recommend further evaluation and repair bya qualified contractor.(2) Damage was observed at one sprinkler head for Station 15.(3) Some sprinkler heads are in need of spray pattern adjustment to prevent the watering of fences, walls andflatwork.(4) Inspector was unable to locate the rain sensor for sprinkler system.(5) The irrigation system is inspected in manual mode only. Inspector does not test for underground leaks.

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of theneed for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use;Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value ofthe property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system thatwas not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmeticitems, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties orguarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area orperform any procedure that may damage the property or its components or be dangerous to the home inspector or otherpersons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or componentthat does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment,plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspectedadverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise,contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control orremove suspected hazardous substances; Predict future condition, including but not limited to failure of components; Sincethis report is provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensedinspector to perform an inspection to meet their specific needs and to obtain current information concerning this property.

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Mark Havelka

Report Identification: 2308 Woodlawn Blvd

Page 68 of 75REI 7-5 (05/04/2015)

Page 69: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

INVOICE

Austinspect, Inc. Inc. TPCL774365220 Racetrack DrAustin, TX 78748512.633.9488Inspected By: Mark Havelka

Inspection Date: 6/26/2020Report ID:

20200626-2308-Woodlawn-Blvd

Customer Info: Inspection Property:

Tish RiellyTara McLean

Customer's Real Estate Professional:

2308 Woodlawn BlvdAustin TX 78703

Inspection Fee:

Service Price Amount Sub-TotalHome Inspection - Heated Sq Ft. 11,000-11,999 1900.00 1 1900.00Pier and beam fee 200.00 1 200.00Wood-Destroying Insect (Termite) Inspection 100.00 1 100.00Irrigation System (Sprinkler) inspection 40.00 1 40.00

Tax $0.00Total Price $2240.00

Payment Method:Payment Status:Note:

Report Identification: 2308 Woodlawn Blvd

Page 69 of 75REI 7-5 (05/04/2015)

Page 70: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

Austinspect, Inc.

220 Racetrack DrAustin, TX 78748

512.633.9488

Report Attachments

ATTENTION: This inspection report is incomplete without reading the information included herein atthese links/attachments. Note If you received a printed version of this page and did not receive a copyof the report through the internet please contact your inspector for a printed copy of the attachments.

Click on the link below for:WDI T4 - 9-1-07(TX)

Report Identification: 2308 Woodlawn Blvd

Page 70 of 75REI 7-5 (05/04/2015)

Page 71: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

Helpful Hints

• Exterior electrical outlets not working? Reset GFCI receptacle at garage wall by pushing thereset button

• Bathroom electrical outlets not working? Reset the GFCI receptacle in the other bathroom orgarage wall by pushing the reset button

• Lights or electrical outlets not working? Try resetting the breaker by turning it off and back onagain

• Smoke detectors chirping? Try changing the 9 volt battery or dusting off the smoke detector.Back up batteries should be changed yearly

• Secondary air conditioner condensate drain line dripping? Try pouring bleach down the primarycondensate line or using compressed air to free the clog

• Garage overhead door not closing with opener? Make sure nothing is in between the safetysensors, or adjust the safety sensors

• Garbage disposal jammed or inoperable? Use appropriate hex wrench or provided tool and turnin base of unit to free disposal. There is also a small red "reset" breaker on the bottom of thedisposal that may be tripped, push to reset

Additional pages may be attached to this report. Read them very carefully. This report may not becomplete without the attachments. If an item is present in the property but is not inspected, the "NI"column will be checked and an explanation is necessary. Comments may be provided by the inspectorwhether or not an item is deemed in need of repair. If there is a check in the D (Deficiency) columnbelow, additional comments will be in the repairs section (VIII) at the end of this report.

COMPANY RELATIONSHIPS/THIRD PARTY PROVIDERS.

Austinspect may have an affiliation with third-party service providers ("TPSP") in order to offer value-added services to its Clients. The company may also arrange for these TPSP to send literature or makepost-inspection contact with the Company's Clients.

The following general comments and limitations may not pertain to all houses inspected:

• The foundation inspection is limited. The inspector does not pull up floor coverings, move furniture, measureelevations or propose repairs. The inspector does not enter crawl space areas less than 18 inches. It is important tokeep soil moisture contents by foundation consistent year round.

• It is advisable to maintain at least 3 inches minimum of clear area between the ground and siding. Proper drainageis critical to the performance of the foundation. All grades should drop away from the structure at a rate of 6 inchesfor every 10 feet.

• The inspector does not speculate on the remaining life expectancy of the roof covering. The inspector does not liftor remove shingles or tiles. Inspection of fastening systems at shingle tabs are not inspected as this could damagethe shingle. Metal and clay tile roofs are not walked on as this could damage the roof covering. Only roofs that canbe safely accessed will be walked on. Some roofs may have a pitch too great to walk on without safety restraints. Inthis case the roof will be viewed with binoculars and/or from the roof edge.

• Only areas of the attic determined accessible by the inspector are inspected.• Only areas free and clear of furniture and other obstructions are inspected. Observation of these areas is related to

structural performance and water penetration only. The inspection does not include obvious damage. It isrecommended that all surfaces be kept well sealed (interior and exterior). This inspection does not cover any issues

Report Identification: 2308 Woodlawn Blvd

Page 71 of 75REI 7-5 (05/04/2015)

Page 72: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

that are considered to be environmental, such as, but not limited to, lead based paint, asbestos, radon, mold,mildew or fungus.

• Cosmetic items and obvious holes are not included in this report. It is common in the course of climate changes thatsome doors may bind mildly or the latches may need adjustment.

• Double pane window seals may be broken without having a visible amount of condensation built up between thepanes. Obviously fogged windows are noted when observed but complete inspection is not possible due to lightconditions, installed screens, dirt on surfaces and rain at time of inspection. Consult a glass installer for furtherevaluation of windows in the event of any insulated glass failure prior to closing. If the house is occupied somewindows may be inaccessible due to owner's belongings. We do not move or climb on furniture to open a window.

• The inspection does not include the adequacy of draft or condition of chimney flue tiles. If creosote buildup is noted,the flue should be cleaned by a chimney sweep for safety

• Ancillary wiring items not inspected include but are not limited to: telephone, cable, speaker, computer, photocells,low voltage, hard wiring on smoke detectors, electric gates and doors, yard and tree lighting. Intercom systems arenot inspected.

• The inspector does not check 220-volt outlets. Random testing of electrical outlets only; not all outlets are tested. Ifthe house is occupied some electrical outlets may be inaccessible due to owner's belongings.We do not move orclimb on furniture to test electrical outlets. In the event aluminum wiring is reported, a licensed electrician shouldreview it. We do not report copper clad aluminum wiring unless labeled so at the electrical panel.

• Full evaluation of gas heat exchangers requires dismantling of furnace and is beyond the scope of this inspection.Heat pump systems are not tested when ambient temperatures are above 80 degrees Fahrenheit to avoid damageto system

• Inspector does not determine the adequacy or efficiency of the system. Humidifiers, motorized dampers, electronicair filters and programmable thermostats are not inspected. Central air conditioning system is not tested whenambient temperatures are below 60 degrees Fahrenheit to avoid damage to system. Window air conditioning unitsare not tested. Effective 2006 manufactures will no longer produce repair / replacement parts for a/c units with lessthat a 13 seer rating and in the event of failure of the unit it may be necessary to replace the entire unit

• The inspection does not include gas lines or condition of plumbing lines in walls, floors, attic, ground or foundation.If foundation work has been performed on the house you are purchasing, a static plumbing test is recommended.Water wells, water-conditioning systems/softeners, solar water heating systems, freestanding appliances, and thepotability of any water supply are excluded from inspection. Clothes washing machine and icemaker hose bibs arenot tested. Water shut off valves (main or under sinks etc.) are not turned on or off under any circumstance

• The following systems, items, or components are excluded from this inspection: 1.) Drain line for clothes washingmachine, or water conditioning systems; 2.) Drain pumps or water ejection pumps, sewer clean-outs, anti-siphondevices, components that are not visible or accessible, exterior plumbing components, and fire sprinkler systems.

• Replacement of water heaters may require permit by local municipality. Inline water heaters are not tested.• It is recommended that the dishwasher drain line be kept strapped upward forming a air gap/sanitary drain loop.

This will prevent disposal debris from entering the line• The inspector does not test for radiation leakage in microwave.

• Bathroom vents should terminate to the exterior. Vent termination is not always visible

• If sprinkler system is inspected it is tested in manual mode only. Underground leaks are not inspected for

Report Identification: 2308 Woodlawn Blvd

Page 72 of 75REI 7-5 (05/04/2015)

Page 73: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

Inspection Agreement

June 26, 2020

The address of the property is: 2308 Woodlawn Blvd , Austin, TX 78703. THIS AGREEMENT by andbetween Mark Havelka (hereinafter "INSPECTOR") and Tish Rielly (herinafter "CLIENT"), collectivelyreferred to herein as "the parties." The Parties understand and voluntarily agree as follows:

1. INSPECTOR agrees to perform a visual inspection of the home/building and to provide CLIENT witha written report identifying the defects that INSPECTOR both observed and deemed material.INSPECTOR may offer comments as a courtesy, but these comments will not comprise the bargained-for report. The report is only supplementary to the seller's disclosure.

2. Unless otherwise inconsistent with this Agreement or not possible, INSPECTOR agrees to performthe inspection in accordance with the current Standards of Practice of the Texas Real EstateCommission (TREC) posted at https://www.trec.state.tx.us/pdf/inspectors/535.227-535.233.pdf.Although INSPECTOR agrees to follow TREC's Standards of Practice, CLIENT understands that thesestandards contain limitations, exceptions, and exclusions. Unless otherwise indicated below, CLIENTunderstands that INSPECTOR will NOT be testing for the presence of radon - a colorless, odorless,radioactive gas that may be harmful to humans. Unless otherwise indicated below, CLIENTunderstands that INSPECTOR will NOT be testing for mold. Unless otherwise indicated in a separatewriting, CLIENT understands that INSPECTOR will not test for compliance with applicable buildingcodes or for the presence of potential dangers arising from asbestos, lead paint, formaldehyde, molds,soil contamination, and other environmental hazards or violations.

3. The inspection and report are for the use of CLIENT only, who gives INSPECTOR permission todiscuss observations with real estate agents, owners, repairpersons, and other interested parties.INSPECTOR shall be the sole owner of the report and all rights to it. INSPECTOR accepts noresponsibility for use or misinterpretation by third parties, and third parties who rely on it in any way doso at their own risk and release INSPECTOR (including employees and business entities) from anyliability whatsoever. Any third parties who rely on the report in any way also agree to all provisions inthis Agreement. INSPECTOR'S inspection of the property and the report are in no way a guarantee orwarranty, express or implied, regarding the future use, operability, habitability or suitability of the home/building or its components. All warranties, express or implied, including warranties of merchantabilityand fitness for a particular purpose, are expressly excluded to the fullest extent allowed by law. If anystructure or portion of any structure that is to be inspected is a log home, log structure or includessimilar log construction, CLIENT understands that such structures have unique characteristics thatmake it impossible for an inspector to inspect and evaluate them by an exterior visual inspection.Therefore, the scope of the inspection to be performed pursuant to this Agreement does not includedecay of the interior of logs in log walls, log foundations or roofs or similar defects.

4. INSPECTOR assumes no liability for the cost of repair or replacement of unreported defects ordeficiencies either current or arising in the future. CLIENT acknowledges that the liability ofINSPECTOR, its agents and/or employees, for claims or damages, costs of defense or suit, attorney'sfees and expenses arising out of or related to the INSPECTOR'S negligence or breach of any obligationunder this Agreement, including errors and omissions in the inspection or the report, shall be limited toliquidated damages in an amount equal to the fee paid to the INSPECTOR, and this liability shall be

Report Identification: 2308 Woodlawn Blvd

Page 73 of 75REI 7-5 (05/04/2015)

Page 74: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

exclusive. CLIENT waives any claim for consequential, exemplary, special or incidental damages or forthe loss of the use of the home/building even if the CLIENT has been advised of the possibility of suchdamages. The parties acknowledge that the liquidated damages are not intended as a penalty but areintended (i) to reflect the fact that actual damages may be difficult and impractical to ascertain; (ii) toallocate risk among the INSPECTOR and CLIENT; and (iii) to enable the INSPECTOR to perform theinspection at the stated fee.

5. INSPECTOR does not perform engineering, architectural, plumbing, or any other job functionrequiring an occupational license in the jurisdiction where the inspection is taking place, unless theinspector holds a valid occupational license, in which case he/she may inform the CLIENT that he/she isso licensed, and is therefore qualified to go beyond this basic home inspection, and for additional fee,perform additional inspections beyond those within the scope of the basic home inspection. Anyagreement for such additional inspections shall be in a separate writing.

6. In the event of a claim against INSPECTOR, CLIENT agrees to supply INSPECTOR with thefollowing: (1) written notification of adverse conditions within 14 days of discovery; and (2) access to thepremises. Failure to comply with the above conditions will release INSPECTOR and its agents from anyand all obligations or liability of any kind.

7. The parties agree that any litigation arising out of this Agreement shall be filed only in the Courthaving jurisdiction in the County in which the INSPECTOR has its principal place of business. In theevent that CLIENT fails to prove any claims against INSPECTOR in a court of law, CLIENT agrees topay all legal costs, expenses and fees of INSPECTOR in defending said claims. CLIENT furtherunderstands that any legal action against InterNACHI itself allegedly arising out of this Agreement orINSPECTOR's relationship with InterNACHI must be brought only in the District Court of BoulderCounty, Colorado. No such action may be filed unless the plaintiff has first provided InterNACHI with 30days' written notice of the nature of the claim. In any action against INSPECTOR and/or InterNACHI,CLIENT waives trial by jury.

8. If any court declares any provision of this Agreement invalid, the remaining provisions will remain ineffect. This Agreement represents the entire agreement between the parties. All prior communicationsare merged into this Agreement, and there are no terms or conditions other than those set forth herein.No statement or promise of INSPECTOR or its agents shall be binding unless reduced to writing andsigned by INSPECTOR. No change shall be enforceable against any party unless it is in writing andsigned by the parties. This Agreement shall be binding upon and enforceable by the parties and theirheirs, executors, administrators, successors and assignees. CLIENT shall have no cause of actionagainst INSPECTOR after one year from the date of the inspection.

9. Payment of the fee to INSPECTOR (less any deposit noted above) is due upon completion of the on-site inspection. The CLIENT agrees to pay all legal and time expenses incurred in collecting duepayments, including attorney's fees, if any. If CLIENT is a corporation, LLC, or similar entity, the personsigning this Agreement on behalf of such entity does personally guaranty payment of the fee by theentity.

10. If CLIENT requests a re-inspection, the re-inspection is also subject to all the terms and conditionsset forth in this agreement.

11. This Agreement is not transferable or assignable.

Report Identification: 2308 Woodlawn Blvd

Page 74 of 75REI 7-5 (05/04/2015)

Page 75: 2308 Woodlawn Blvd / Austinspect, Inc. / Mark Havelka · Austin, TX 78748 512.633.9488 Inspected By: Mark Havelka Inspection Date: 6/26/2020 Report ID: 20200626-2308-Woodlawn-Blvd

12. Should any provision of this Agreement require judicial interpretation, the Court shall not apply apresumption that the term shall be more strictly construed against one party or the other by reason ofthe rule of construction that a document is to be construed more strictly against the party who preparedit.

Report Identification: 2308 Woodlawn Blvd

Page 75 of 75REI 7-5 (05/04/2015)