12
Making Electric Power Safer, More Reliable, and More Economical ® Features and Benefits SEL-2440 Discrete Programmable Automation Controller DPAC ® Powerful control and I/O. Protocol Processing Security Programmable Automation Engine (2 ms processing) Sequential Events Recorder Serial Ethernet Switch MAC Ethernet IRIG-B OUT IRIG-B IN Input Processor (1 ms) Microsecond Timer Output Relays (4 ms) 32 Discrete Inputs (typical) 16 Discrete Outputs (typical) 7 ms Delay 2 $960 for 48 Digital I/O Points = $20 Per Point! Distributed I/O Right Out of the Box Preprogrammed register maps Select protocol and address via switches behind front panel Fast and Powerful 2 ms processing interval 7 ms from input to output: auxiliary relay speed Events timed to the microsecond A Great Communicator and Interpreter Supported Protocols Serial Ethernet DNP3 Modbus ® MIRRORED BITS ® communications SEL Fast Message IEC 61850 Convenient Maintenance and Support Removable terminal blocks with positive retention Continuous self-monitoring diagnostics LEDs for system status, every I/O point, and communications port Front-panel management port SEL Quality, Standards, and Global Support 2000 Vac/2500 Vdc HiPot • 8 kV contact/15 kV air ESD tested • IEEE C37.90-1989 • IEEE 1613-2003 standard • IEC 60255 protective relay standards

2440 Flyer A5 - static.selinc.com

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Making Electric Power Safer, More Reliable, and More Economical ®

Features and Benefits

SEL-2440 Discrete Programmable Automation Controller

DPAC®

Powerful control and I/O.

Protocol Processing

Security

ProgrammableAutomation

Engine(2 ms processing)

Sequential Events Recorder

SerialEthernet

Switch

MAC

EthernetIRIG-BOUT

IRIG-BIN

Inpu

t Pro

cess

or (1

ms)

Mic

rose

cond

Tim

er

Outp

ut R

elay

s (4

ms)

32DiscreteInputs

(typical)

16DiscreteOutputs(typical)

7 ms Delay

2

■$960for48DigitalI/OPoints=$20PerPoint!

■DistributedI/ORightOutoftheBox • Preprogrammed register maps • Select protocol and address via switches behind front panel

■FastandPowerful • 2 ms processing interval • 7 ms from input to output: auxiliary relay speed • Events timed to the microsecond

■AGreatCommunicatorandInterpreter

Supported Protocols Serial EthernetDNP3 ✔ ✔

Modbus® ✔ ✔

Mirrored Bits® communications ✔

SEL Fast Message ✔

IEC 61850 ✔

■ConvenientMaintenanceandSupport • Removable terminal blocks with positive retention • Continuous self-monitoring diagnostics • LEDs for system status, every I/O point, and communications port • Front-panel management port

■SELQuality,Standards,andGlobalSupport • 2000 Vac/2500 Vdc HiPot • 8 kV contact/15 kV air ESD tested • IEEE C37.90-1989 • IEEE 1613-2003 standard • IEC 60255 protective relay standards

2

Easy Setup

UnPACk AnD InSPECt wIrE It

PowEr UP AnD vErIFy StAtUSSEt ProtoCol AnD ADDrESS USIng DIP SwItChES

vErIFy ContACt StAtUS wIth mAStEr

SEL-2440

OUT

+ +

PORT 2PORT 1

ETH 1 ETH 2

IN

IRIGPOWERALARM

OUT201 OUT202 OUT203 OUT204

IN101 IN102 IN103 IN104 IN105 IN106 IN107 IN108 IN109 IN110 IN111 IN112 IN113 IN114 IN115 IN116

IN301 IN302 IN303 IN304 IN305 IN306 IN307 IN308 IN309 IN310 IN311 IN312 IN313 IN314 IN315 IN316

B0

1

B0

2

B0

3

B0

4

B0

5

B0

6

B0

7

B0

8

B0

9

B10

B1

1

B12

B13

B14

B15

B16

B17

B18

B19

B2

0

B2

1

B2

2

B2

3

B2

4

B2

5

B2

6

B2

7

B2

8

B2

9

B3

0

B3

1

B3

2

B3

3

B3

4

B3

5

B3

6

Z0

1

Z0

2

Z0

3

Z0

5

Z0

6

Z0

7

Z0

8

OUT205 OUT206 OUT213 OUT214 OUT215 OUT216

A09

GND

OUT207 OUT208 OUT209 OUT210 OUT211 OUT212

A0

1

A0

2

A0

3

A0

4

A0

5

A0

6

A0

7

A0

8

A0

9

A10

A1

1

A12

A13

A14

A15

A16

A17

A18

A19

A2

0

A2

1

A2

2

A2

3

A2

4

A2

5

A2

6

A2

7

A2

8

A2

9

A3

0

A3

1

A3

2

C0

1

C0

2

C0

3

C0

4

C0

5

C0

6

C0

7

C0

8

C0

9

C10

C1

1

C12

C13

C14

C15

C16

C17

C18

C19

C2

0

C2

1

C2

2

C2

3

C2

4

C2

5

C2

6

C2

7

C2

8

C2

9

C3

0

C3

1

C3

2

SEL-2440

SCADA

SEL-2440 DoneJob ®

SEL-2440

1 2

3 4

5

SEL-2440

Press lamp test for: • LED status • Port address check • Time-code check

3

Distributed I/o Expandable to thousands of Points

Simplify Settings, Analysis, and Design Using acSELErator® Software

SEL-2411 SEL-2411 SEL-2411

. . .

. . .

. . .

RTAC

DPAC

PAC

SEL-2440 SEL-2440

SEL-2440 SEL-2440

Serial or Ethernet Communications

SEL-3530Real-TimeAutomationController

or computer,communications processor,direct SCADA link, RTU replacement

DiscreteProgrammableAutomationController

ProgrammableAutomationController

SEL-2440

SEL-7XX

SEL-2411

SEL-3XX SEL-4XX

Reports Updates IEC 61850SettingsHMI Events

4

how can SEl deliver all these features for only $960?

By leveraging successful designs for relays and automation controllers with world-class manufacturing. And not by cutting corners on quality.

what if I burn out a relay contact in a DPAC?

First, SEL has a ten-year, no-questions-asked warranty. If you burn out a contact, SEL will repair your DPAC usually within 72 hours. Second, the DPAC is entirely connectorized, so you can easily remove it from service without removing any wires from the connectors. Because of the low price, having a spare on hand for only $960 is affordable. Simply download your settings to the spare and insert the connectors for a fast, simple, and economical repair.

Can I expand the I/o of the DPAC?

Yes! The base product typically has 32 inputs and 16 outputs. Want some more? You can add two SEL-2505 Remote I/O Modules (8 in/8 out), one per serial port, for a total of 32 more points. . .for a grand total of 80 I/O points! But, the DPAC is so cost effective to begin with, it’s usually most economical to buy another DPAC! Remember, it’s $20 per point for protection quality I/O.

where is the DPAC designed and made?

It is designed and manufactured in our factory in Pullman, Washington. The DPAC firmware was developed by SEL in Pullman too.

Can I hook two DPACs back-to-back? what kind of performance can I get?

You may be familiar with our SEL-2505 Modules. They communicate 8 points in each direction, so that 8 inputs at one end are 8 outputs at the other, and vice versa. You can do exactly this with 8 inputs and 8 outputs of each DPAC and still have your other I/O. End-to-end delay is about 7 ms. Or, you can use IEC 61850 GOOSE messaging and the Ethernet ports to communicate any desired combination of I/O points; e.g., 16 inputs to 16 outputs one way and 8 inputs to 8 outputs going back.

how can I apply the DPAC in my system?

You can use it as a standalone controller or digital concentrator. Or, you can use the DPAC as a host or I/O expansion for the SEL-2411 Programmable Automation Controller (PAC) that also supports low-level dc or ac analog inputs. For automation and control applications, you can use the SEL-3530 RTAC or our embedded computers. You can also connect your DPAC to SEL-2020, -2030, -2032 communications processors via our SEL protocols, or easily integrate with your existing SCADA infrastructure with DNP3 and Modbus® protocols over Ethernet or serial connections.

this is a new product for me. how can SEl assist me?

If you are already familiar with the SEL-2411 PAC, then you will be right at home with the DPAC. They have the same roots. The DPAC is actually easier, because it doesn’t need to handle analog signals. If you have never used an SEL device, then now is the time! We have field application engineers around the world who are ready to assist you with your designs at no charge. Or, our systems engineering team can develop a detailed custom design for you in accordance with your needs at reasonable fees. Or, if your local consultant wants help, we are prepared to support him or her as well.

your literature stresses that you guarantee performance to various standards. what does this mean?

The design engineers at SEL understand these standards, and they know that their designs must not only comply but also have margin beyond the standard. For instance, standards require a dielectric strength test (HiPot) of 2000 Vac. SEL adds margin onto the standard and requires the product pass at 2500. . .for a 25 percent margin above the standard! This requires careful attention to clearances, spacing, and many other parameters. Unfortunately, there are many devices, costing much more and having (understandably) weaker warranties, that say their products are “designed to” the standards. . .whatever that means. Be assured that when SEL mentions a standard, we meet it! Not only “designed to.” Not only “tested to.” But “tested to and passed with margin!” Standards exist for a reason: these devices are put to work in hostile environments, and you and we need to sleep at night, knowing we have taken every step possible to reasonably assure performance in the substation environment for many years.

Frequently Asked Questions

5

Be Sure your Discrete I/o System measures Up to SEl Safety, reliability, and Economy

DESIgn SEl othErS ImPortAnCE

Positive retention of connectors � no

Control wiring is stiff and heavy. Connectors without positive retention can come off, causing failure or misoperation of your control system.

2000 V all circuits to ground � ??

Faults can stress power supply and I/O to high voltages. Flash-over can destroy I/O and cause misoperations.

2000 V circuit-to-circuit � ?? Adjacent circuits can have different references.

HiPot routine test � ??

Every SEL device is HiPot tested in manufacturing before it goes out the door. Others may not be and may fail during HiPot testing of your panels.

Utility-rated power supply � no

SEL makes its own power supplies, which have a 600-year MTBF. Others may use commercial supplies, as found in computers.

AC/DC inputs � no

SEL inputs are dual-rated. Others are typically dc only. AC-rated inputs are needed for monitoring ac loads and volt-age transformers.

Level-sensitive inputs � no

SEL input thresholds are near one-half the battery voltage to prevent false assertions. Others may use “universal” inputs, with thresholds as low as 12 V, which may misoperate on battery grounds, transients, and switching events.

—40˚ to +85˚C � no

The SEL DPAC will work in outdoor cabinets and when air conditioning fails. Others probably won’t.

Vibration � ?? Designed and tested to work in vibration-prone environments.

Tested to IEEE C37.90 � ??

SEL type tests all products. Others may say only “designed to. . .” Type tests prove secure, reliable performance.

ProtoColS

DNP3 and Modbus® � no

SEL recognizes that different applications require one or the other, so we provide both at no additional cost.

IEC 61850 � noSEL supports the international standard for communications and integration in substations.

SEL Fast Message � no Enables easy additions to SEL communications processors.

SEL Mirrored Bits® communications � no Provides high-speed, secure,

point-to-point communication.

SEL Messenger Points � no

Receive station alarms and event notification by telephone with the SEL-3010 Event Mes-senger.

CommUnICAtIonS SEl othErS ImPortAnCE

SErIAl

EIA-232 �1 no

MOV protection, 5 Vdc pass-through for transceivers, and demodulated IRIG-B pass-through.

EIA-485 � ?? MOV protection.

Fiber V-pin connector � ??Improves communications reli-ability and far less susceptible to noise.

Fiber ST® connector � ??Improves communications reli-ability and far less susceptible to noise.

EthErnEt

Dual 10/100BASE-T with integrated switch � no

Integrated switch allows easy daisy-chaining of IP-based devices.

Dual 100BASE-FX Ethernet with integrated switch � no

Improves communications reli-ability and far less susceptible to noise.

DEmoDUlAtED IrIg-B

IRIG-B input and output � noIRIG-B input and output connec-tors allow easy daisy-chaining of devices.

Microsecond accurate timing � no Time-critical events, such as breaker mechanism operations.

ProCESSIng CAPABIlItIES

Math and logic � no Provides local control and processing.

Scheduling and timing of outputs � no

Enable scheduling of outputs based on month, day, hour, and minute variables.

Logic processing interval to less than 2 ms � no Fast deterministic processing

interval.

Command line response processing � no

All programming and control can be accomplished from a command line.

SECUrIty

Strong passwords � noSupports alpha, numeric, and special characters up to 12 characters in length.

Port enable/disable � no Set security levels on a per port basis, and turn off unused ports.

wArrAnty AnD SUPPort

No-hassle, ten-year, worldwide warranty � no Best in the industry.

Free worldwide technical support � no SEL maintains more than 80

offices in over 15 countries.

PrICE PEr DIgItAl I/o PoInt

$20 per point � no Others may charge up to $60 per point.

Management and setup port.

48 status LEDs, one for every I/O point.

Continuous display of network activity with communications port activity LEDs.

Powerful 32-bit microcontroller delivers relay-speed I/O, logic, and communications.

LEDs also show port address and IRIG time code after lamp test.

All connectors have positive retention, so wires and cables cannot pull off.

Industry-leading, worldwide, ten-year warranty.

Diagnostic LEDs.

Digital outputs.

Lamp test, port address check, and time-code check.

All outputs are rated for utility grade per IEEE C37.90, eliminating the need for interposing relays.

delivers relay-speed I/O, logic, delivers relay-speed I/O, logic, and communications.and communications.

I/O labels match status LEDs.

Widest operating temperature range (—40˚ to +85˚C), use indoors and in outdoor cabinets.

Supports DNP3, Mirrored Bits® communications, SEL Fast Messages, Modbus®, and IEC 61850 protocols.

Remove two screws to access configuration switches.

All digital inputs are rated for ac and dc and time-stamped to 1 μs accuracy.

Wide-range universal power source,

19.2—275 Vdc, and

19.2—264 Vac.

Demodulated IRIG-B input synchronizes the microsecond timer to absolute time and drives the demodulated IRIG-B output.

Alarm contact alerts you to self-test failure, communications access, and settings changes.

Two standard EIA-232 serial ports, with EIA-485 and fiber options available for one serial port.

Standard 10/100BASE-T Ethernet ports with integrated switch eliminate the need for an external switch.

For simple I/O applications, the SEL-2440 can be configured with switch settings—no computer or software required.

SEL rugged power supply has an MTBF of 600 years.

All input thresholds are near ½ nominal voltage to avoid false assertions during faults and battery grounds.

+85°C—40°C

Industry standard 2U height.

8

Applications

SubstationRTU/PLCSystem

SubstationSecurity

SEL-2440

Station and YardLighting

AudibleAlarm

VisibleAlarm

FenceSensors

MotionSensors

Panel/CabinetSensors

DoorSensors

SCADA

SEL-3010

Cell PhoneSEL-2440

SEL-2440 SEL-2440 SEL-2440

Substation IEDs

DNP3

IRIG-B

DNP3

IRIG-B

DNP3

IRIG-B

IRIG-BSEL-3530 SEL-2407®

Lock

outs

Over

curr

ent A

larm

s

Brea

ker T

rips

Tem

p Al

arm

s

Flui

d Le

vel A

larm

s

Pres

sure

Ala

rms

SEL-2440 SEL-2440 SEL-2440

Cont

rol

Cont

rol

9

Applications

AddDiscreteI/OtoLegacySystems

TransformerProtection

BuildHigh-DensityDiscreteI/O

SEL-734

SEL-734 SEL-2411

SEL-2032

RTUsMeters and

Monitors

Relays and IEDs

CommunicationsProcessor

SEL Protocols

DNP3

SerialCommunications

SEL-2440

SEL-2440

SEL-2440

SEL-2411SEL-2411

SEL-3530

SEL-2725

SEL-2725 SEL-2725 SEL-2725 SEL-2725

Ethernet Communications

Modbus® TCP,DNP3, orIEC 61850

Real-TimeAutomationController

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440SEL-2440

SEL-2440

SEL-787

SCADAIEC 61850

Digital I/O

CT, PT, AI, RTDs

SEL-2440

10

Applications

BayController

MASTER STATION

DNP3, Conitel 2020,Harris 5000/6000,

Recon, etc.

Other DeviceOther Device

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

SEL-2440

ETHERNET SWITCH

SEL-2411

SEL-2411

SEL-3332

Other DeviceOther Device

Analog Inputs/Outputs

Digital Inputs/Outputs

DNP3, Modbus®, IEC 60870-5-103,SEL Fast Messaging

CONTROL ENCLOSURE

FIBER OPTIC

SUBSTATION YARD

SEL-2440 SEL-2440

SEL-2440

SEL-2411

SEL-3530

SEL-451-4

SEL-421

SEL-487B

ETHERNET SWITCH

MASTER STATION

GOOSE Message 1, 2, 3

GOOSE Message 1, 2, 3

GOOSE Message 1, 2, 3

GOOSE Message 1

GOOSE Message 3

GOOSE Message 2

Digital Inputs/Outputs

Analog Inputs/Outputs

Digital Inputs/Outputs

DigitalInputs/Outputs

High-DensitySubstationI/O

11

Applications

LockoutRelayContactMultiplier

ExchangeHigh-SpeedMirrored Bits®Communications

ProtocolConverter

DNP3

SEL Fast Message

Fast

Mes

sage

IEC 61850

IEC

6185

0

SEL MIRRORED BITS®

SEL-2030

SEL-351

SEL-421

SEL-2440 DPAC

MIR

RORE

D BI

TS

SCADA

SCADA

MIRRORED BITS

48 I/O SEL-

2505

SEL-

2505

SEL-2440

Busbar

52 52 52 52

SEL-2440IN01

OUT2OUT1 OUT3 OUT4

SEL-587Z

SEL-9510

52-1 52-2 52-3 52-4

87 Trip

SupervisoryControl

Pullman, Washington USATel: +1.509.332.1890 • Fax: +1.509.332.7990 • www.selinc.com • [email protected]

© 2008—2010 by Schweitzer Engineering Laboratories, Inc. PF00188 • 20101007

UniversalPowerSupplyRatings 120/230 Vac 24/48/125/250 Vdc Range 19.2—275 Vdc 19.2—264 Vac

OptionalFeaturesDual 100BASE-FX fiber Ethernet

Serial module communications (Port 2) options

EIA-485

Fiber-optic, 200 μm V-pin connector

Fiber-optic, 62.5 multimode ST® connector

IEC 61850 communications

Conformal coating

ProgrammableAutomationandLogic32 logic variables

32 math variables

32 timers

32 counters

32 remote control points

128 remote analog points

32 latching points

StandardsIEEE C37.90-1989

IEC 60255 and 6100

IEEE 1613-2003

Dimensions2U rack-mount 88.1 mm H x 482.6 mm W x 158.1 mm D

(3.47 x 19.00 x 6.23 in)

2U panel-mount 124.5 mm H x 502.9 mm W x 158.1 mm D

(4.90 x 19.80 x 6.23 in)

DIN rail-mount 171.1 mm H x 447.0 mm W x 89.4 mm D

(6.74 x 17.60 x 3.52 in)

Surface-mount 171.1 mm H x 482.6 mm W x 89.4 mm D

(6.74 x 19.00 x 3.52 in)

StandardFeatures32 digital ac and dc inputs

16 digital outputs (12 Form A and 4 Form C)

Dual copper 10/100BASE-T Ethernet port with integrated switch

Dual EIA-232 serial ports (Port 2 and Port 3)

Demodulated IRIG-B input and output

Front USB configuration port

Form C alarm output contact

LEDs for communications status and port activity

StandardProtocolsSEL protocols

SEL Mirrored Bits communications

SEL ASCII and Fast Message

SEL Messenger Points

Modbus serial and Modbus TCP/IP

DNP3 and DNP LAN/WAN

I/OConfigurationsInputs Outputs

Standard Configuration 32 16 Option 1 16 32 Option 2 48 0

DigitalInputRatingsOptoisolated

MOV protection

Level sensitive inputs

300 V input maximum

DigitalOutputRatingsPickup time <5 ms

6 A continuous carry

30 A make per IEEE C37.90

MOV protection

general Specifications

Electrostatic Shock (15 kV)

Vibration (15 g Shock)

Heat (+85°C)

Cold (—40°C)

SEL-2440 DPAC Discrete Programmable Automation Controller