SD Engineering Sdn BhdElectrical Calculation
Ac and DC UPS complete with Battery sizing
Battery and load specification
Batery type Nickel-Cadmium alkaline
Nominal (operational) Voltage 24 Volt
Maximum Voltage 26.4 Volt
(24V + 10%)
Minimum Voltage 21.6 Volt
(24V - 10%)
Nominal Voltage/cell V/cell 1.2
Recommended Battery float charge V/cell 1.4
( Based on Saft-Nife thr value is 1.4V/cell )
Quantity of cell required (N) 19 (round-up figure)
(Maximum voltage/Float voltage)
End voltage(per cell) 1.15 (nearest figure is 1.14)
(Min voltage/number of cell)
Continous load (Acont.) 35.1 Ampere (refer to load tabulation)
Design criteria
Temperature correction factor @25oC 1
Design Margin or spare capacity 1.10 ( 10% additional)
Ageing factor due to the battery deteriorate 1.25 ( 25% additional)
Computation
9323-RPT-EL-002
7/28/2019 24vdc Ups Battery Sizing
2/4
SD Engineering Sdn BhdElectrical Calculation
Ac and DC UPS complete with Battery sizing
Battery sizing S=N
Uncorrected cell size (AH) = Max
S=2
N = number of period in load profile
p = period being analysed
Ap = Ampere required for period "P"
T = time (minute/hour or second)
KT = AH capacity at standard rating/Amp that cell supply in time T
From the graph compute the uncorrected battery size in Ampere hour
A0 0 ampere
A1 100.1 ampere
A2 35.1 ampere
KT1=128/102 1.2549
T1 at 45 minute and A1
KT2= 8.3/45.2 0.1836
T2 at (T1-next time duration) minute
& A2 .
Therefore computed uncorrected cell size 113.68 Ampere-Hour
Corrected battery size(AHcorrect) = 156.31 Ampere-Hour
AHcorrect = AH max. uncorrect x temperature correction factor x design margin x ageing factor
Manufacturer's Data
Based on Saft-Nife battery is SBH157 157 AH
Physical battery cell sizing 349mm(H) x 195mm(W) x 252mm(L)-(2 cell per block)
Number of cell 19
Proposed battery rack 3 tiers
Propose battery arrangement
Charger sizing
1000
800
t
1
)1p(p }{ KAAsp
p
=
=
--
9323-RPT-EL-002
7/28/2019 24vdc Ups Battery Sizing
3/4
SD Engineering Sdn BhdElectrical Calculation
Ac and DC UPS complete with Battery sizing
Calculation Procedure
Maximum system voltage per cell( V1max) = Maximum system voltage/ number of cell
V1max = 1.4 volt
This is the maximum volt, the battery are allowed to be charged during high rate or float charge
Based on Saft-Nife battery high the rate charge voltage level is between 1.45 to 1.75V/cell
It assumed that battery banks are allowed for the high rate charge it is assumed that the charger shall
be size to cater for the short duration of charging.
Recommended high rate charge (Ahr) 94.2 Ampere
0.4 C5A for 2.5Hr and 0.2C5A for 2.5Hr
Charger size( AC )=Ahr+ Cont.load (Acont.) 129 Ampere
Manufacturer's Standard size 150 Ampere
Input Power (P)=KxVnxIn 4752 watt @ 3 phase 415V source
Vn = nominal charger output voltage
In = max charger output current
K = Constant factor @ 24V 1phase 2.64
K = Constant factor @ 24V 3 phase 1.32
Battery Charger physical sizing
(all dimension in mm unless specified)
H=1630
D=490
W=670
9323-RPT-EL-002
7/28/2019 24vdc Ups Battery Sizing
4/4
SD Engineering Sdn BhdElectrical Calculation
Ac and DC UPS complete with Battery sizing
9323-RPT-EL-002