8/22/2019 25kV KonNx Coupler.pdf
1/36
Worry Free High Voltage Couplers
WMEA Conference, San AntonioNovember 19, 2009Presented by Nick Turner of KonNx Inc.
8/22/2019 25kV KonNx Coupler.pdf
2/36
KONNX
AUSPROOFHeadquarters, Factory, and
Global Distribution in
Gladstone, Queensland, Australia
KonNx IncOffice, Warehouse and North American
Distribution
Denver, Colorado
8/22/2019 25kV KonNx Coupler.pdf
3/36
Computer Network from
Design to Manufacture
CNC Equipped Machine Workshop
Non-Ferrous Foundry
KONNX
8/22/2019 25kV KonNx Coupler.pdf
4/36
Final product totally
manufactured andready for use
Basic raw materialsreceived
8/22/2019 25kV KonNx Coupler.pdf
5/36
The Development
Of The
Cable Coupler Systems
KONNX
8/22/2019 25kV KonNx Coupler.pdf
6/36
PERFORMANCE RECORD OF COUPLERS IN SERVIC
PERFORMANCE RECORD OF COUPLERS IN SERVICPERFORMANCE RECORD OF COUPLERS IN SERVIC
1
2 3
45
6
8/22/2019 25kV KonNx Coupler.pdf
7/36
What made them fail?
Goal: Engineer out all the ways a
high voltage coupler can fail.
8/22/2019 25kV KonNx Coupler.pdf
8/36
RESEARCHING COUPLERS GLOBELYRESEARCHING COUPLERS GLOBELYRESEARCHING COUPLERS GLOBELY
Designs
around the World
8/22/2019 25kV KonNx Coupler.pdf
9/36
Initial FindingsInitial Findings
Quick Fix Solutions i.e. Teflon
Electrical Type Tests For Connector
Lower Than Requirement For Cable
makin cou ler weak link
Low voltage High voltage
8/22/2019 25kV KonNx Coupler.pdf
10/36
THE ULTIMATE TESTTHE ULTIMATE TESTTHE ULTIMATE TEST
SHORTSHORT
8/22/2019 25kV KonNx Coupler.pdf
11/36
8/22/2019 25kV KonNx Coupler.pdf
12/36
8/22/2019 25kV KonNx Coupler.pdf
13/36
Air Trapped Inside Coupler Enclosure
Phase To Phase Flashover
AIR AND PARTIAL DISCHARGEAIR AND PARTIAL DISCHARGEAIR AND PARTIAL DISCHARGE
AIR
PARTIAL DISCHARGE
Existing couplers tested with results exceeding
20,000 pico-coulombs (pC).
Extruded mining cable specifications call for
an average 5 pico-coulombs.
8/22/2019 25kV KonNx Coupler.pdf
14/36
SOLUTIONSSOLUTIONSSOLUTIONS
Remove Air with Silicon Rubber Insert Insulating Material Developed to ExtinguishInsulating Material Developed to Extinguish
TrackingTracking
SiliconSiliconInsertInsert
InsulatingInsulating
MaterialMaterial
8/22/2019 25kV KonNx Coupler.pdf
15/36
NO TRIPS OR ANY SIGNS OF FAULTNO TRIPS OR ANY SIGNS OF FAULTNO TRIPS OR ANY SIGNS OF FAULT
8/22/2019 25kV KonNx Coupler.pdf
16/36
ANALYSISANALYSISANALYSIS
Silicon Rubber Insulating Material
Stepping Stone
8/22/2019 25kV KonNx Coupler.pdf
17/36
PHASE SEGREGATION BY EARTHPHASE SEGREGATION BY EARTHPHASE SEGREGATION BY EARTH
PHASE
PHASE
PHASE
Mining Industry Standard
EARTH
EARTH
EARTH
EARTH
8/22/2019 25kV KonNx Coupler.pdf
18/36
A Phase to GroundFault was created
with conductive
paint
Earth Star Placed
Between Phases
A Through Fault Test was then performed on this solution
to see how it would perform in the field
FIRST SOLUTIONFIRST SOLUTIONFIRST SOLUTION
8/22/2019 25kV KonNx Coupler.pdf
19/36
REASON FOR FAILUREREASON FOR FAILUREREASON FOR FAILURE
PHASE 1
EARTH
PHASE 2
PHASE 3
8/22/2019 25kV KonNx Coupler.pdf
20/36
FINDING A SUCCESSFUL SOLUTIONFINDING A SUCCESSFUL SOLUTIONFINDING A SUCCESSFUL SOLUTION
.
Equipotential
Lines Good
Earth StarEarth Star
Equipotential LinesEquipotential Lines
Crushed UpCrushed Up
Individually ScreenedIndividually Screened
CableCable
EquipotentialEquipotential
Lines GoodLines Good
8/22/2019 25kV KonNx Coupler.pdf
21/36
ALL TYPE TESTS PERFORMED WEREALL TYPE TESTS PERFORMED WERE
WITHIN CABLE SPECIFICATIONSWITHIN CABLE SPECIFICATIONS
COUPLERS HOMOGENEOUS
WITH CABLE
COUPLERS HOMOGENEOUSCOUPLERS HOMOGENEOUS
WITH CABLEWITH CABLE
EARTHEARTHCROSS SECTION
8/22/2019 25kV KonNx Coupler.pdf
22/36
CurrentCurrent
Contacts are of an eight fingerdesign.
Heat treated locking ring to
maintain contact pressure.
Continuous rating of 800A
TYPE TESTS PERFORMED ON NEW DESIGN
Temperature Rise at 800A Passed
Through Fault Test:20kA for 0.3 sec Passed
20kA for 0.3 sec Passed
20kA for 1.0 sec Passed
8/22/2019 25kV KonNx Coupler.pdf
23/36
Voltage Type Tests PassedVoltage Type Tests Passed
50kV for 1 min
35kV for 6 hours
125kV 10 Pos. Shots and 10 Neg. Shots
Impulse Voltage
A/C High Voltage Withstand
Partial Discharge
10pC Prior to 6 hour high voltage withstand
0.6pC After 6 hour high voltage withstand
8/22/2019 25kV KonNx Coupler.pdf
24/36
ComparisonComparison
Coupler Now As Good As The CableCoupler Now As Good As The Cable
8/22/2019 25kV KonNx Coupler.pdf
25/36
From Partial Solution to theFrom Partial Solution to the
Complete SolutionComplete Solution
8/22/2019 25kV KonNx Coupler.pdf
26/36
Water IngressionWater Ingression
Cable GlandsCable Glands
Existing round O-ring seal
Square section silicon face
seals with a life of 30 yrs
Tested to IP 68 Standard
KonNx gland incorporates adjustments to
maintain tension on cable over time.
Design will tighten on cable if tension on
cable is applied.
Glands are design specifically for cable sizes.
IEC 60529
8/22/2019 25kV KonNx Coupler.pdf
27/36
Special Cold Pour Developedwith 3M
8/22/2019 25kV KonNx Coupler.pdf
28/36
BiBi--Sexual DesignSexual Design
All male couplers.
Guide pins assist alignment.
All Silicon 800amp
female/female Phase
connectors w/Rockwell
hardened lock rings
MSHA Compliance.
8/22/2019 25kV KonNx Coupler.pdf
29/36
Tools & CouplingTools & Coupling
Enclosed slide hammers.
Earth pilot attachment.
Coupling tool.
After together use four bolts to
secure
8/22/2019 25kV KonNx Coupler.pdf
30/36
Integrated Handling System ForIntegrated Handling System For
Surface Mining ApplicationsSurface Mining ApplicationsAssists with opening and closing couplers
One man operation
Able to relocate couplers while energized.
Protection for the joint.
Roll-over.
Skid wear pads.
Cable clamp at each end.
No tools required
8/22/2019 25kV KonNx Coupler.pdf
31/36
8/22/2019 25kV KonNx Coupler.pdf
32/36
8/22/2019 25kV KonNx Coupler.pdf
33/36
Eliminating risk of phase to phase faults. Reducing the risk of phase to ground faults
Fully integrated handling systems.
Couplers do not limit the power supply to machines
(All couplers cont inuously rated at 800 amps)
Eliminates need for male/female cable orientation
We listen to our customers and keep improving our products Increase in expected life of coupler.
Over 1000 of our couplers in service since 1992 with no problems
Research & DevelopmentResearch & Development
5% of annual incomeLatest Development is integrated Fiber Optics
Benefits to the Mining Industry
8/22/2019 25kV KonNx Coupler.pdf
34/36
Track RecordTrack Record 25kV couplers operating in Australian mines since 1992.
In excess of 2000 couplers in Australia, South Africa,
South America, North America and Asia
Specified 25kV coupler byBHP Bill iton.
Rio Tinto.
Xstrata Coal.
Anglo American Coal
Arch MineralsCline Resources
Signal Peak Energy
8/22/2019 25kV KonNx Coupler.pdf
35/36
Specified 15kv Couplers by:
GCC Energy
Prairie States Energy Project
ICG
Consol Energy
Specified 8kV Couplers by:
BHP San Juan Mine
Arch Minerals
Signal Peak Energy
Patriot Coal
FMC Chemicals
Track RecordTrack Record
8/22/2019 25kV KonNx Coupler.pdf
36/36
KonNx