29511  Redundancy Module Configuration Tool (RMCT).pdf

Embed Size (px)

Citation preview

  • RockwellAutomationSupportCenter

    29511RedundancyModuleConfigurationTool(RMCT)AccessLevel:EveryoneDateCreated:08/23/200412:00AMLastUpdated:12/03/201402:39PM

    QuestionWherecanIgetthedownloadfortheRedundancyModuleConfigurationTool?IcannotaccesstotheModuleConfigurationfor1756RMmoduleinRSLinx.

    AnswerTheRedundancyModuleConfigurationToolcanbedownloadedfromtheCompatibility/DownloadCenterundertheFirmwareDownloads.Usetheredundancymodulecatalognumberforyoursearch.(1757SRM,1756RM,1756RM2).Thetoolscanbeselectedaspartofthefirmwaredownload:

    OlderRSLinxClassicsoftwarewillpreinstallsomeversionoftheRedundancyModuleConfigurationTool(RMCT).DependinguponwhichversionofRedundantFirmwarebeingused,adifferenttoolmayberequired.

    1. ThefirststepistodeterminewhatversionRMCTiscurrentlyinstalled.IftheModuleConfigurationoptionismissingwhenrightclickingtheredundancymoduleinRSLinxcheckyourcomputer'sAdd/RemoveProgramsorProgramsandFeaturestoseeiftheRedundancyModuleConfigToolisinstalledanditsversion.

    2. ForamissingEDSfile,rightclickonthemoduleandselect'UploadEDSfilefromDevice'.Iftheuploadoptionismissing,thentheRSLinxClassicsoftwareisanolderversion.TheusercanobtainEDSfilesfromthewebsiteorinstallanewerversionofRSLinxClassicsoftware.

    IfRSLinxClassicv2.52,v2.53or2.54isinstalled,thepreinstalledversionoftheSRMConfigurationToolonlyworkswithv16redundantfirmware.TheWindowsControlPanel>Add/RemoveProgramslistcanbeusedtouninstallanexistingversion.

    3. Verifythemodulesfirmwarehasbeenflashedtothedesiredversion.DefaultfirmwarewillnotallowanEDSfileuploadormoduleconfiguration.4. IftheuserattemptstoinstallRMCTfromanetworkdrive,buttheinstallationisunsuccessfulandstatesError1309.Errorreadingfromfile\\

    ...\SRMConfig.dll.Shortenthepath,byextractingtheRMCTinstallationfilesclosertotherootoronahardlocaldrive.

    5.WheninstallingRMCTv7.2.7.0onaWindows7OS,theSetupDialogmaybehiddenbytheWindowsExplorerwindow.

    IftheRedundancyModuleConfigToolSetupV7.2.7.0dialogishiddenbehindtheWindowsExplorerwindow,simplyMinimize(ormove)theWindowsExplorerwindow.

    SimplifiedConfigurationToolSelectionVersion8.1.5.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:

    revision15revision16revision19revision20

  • Version7.3.6.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:

    revision15revision16revision19revision20

    Version7.2.7.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:

    revision13revision15revision16revision19

    Version6.2.10.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:

    revision13revision15revision16

    Version2.5.0oftheRedundancyModuleConfigurationTooliscompatiblewithrevision11redundantfirmware.

    Notes:

    1.Whenthe7.2.7.0orhigherversionofthetoolisinstalled,thepreviousversionisautomaticallyuninstalled.2. 7.2.7.0orhigherversionsofthetoolhavetoolsbackto5.2.3.0installedwithit.3. Higherrevisionsofversionssupporthigherrevisionsoffirmwareandnewer1756RM2refertothefollowingtable:

    RedundancyPackage ToolVersion ModuleFirmwareVersion

    20.55_kit4 8.02 1756RM3.003/1756RM220.00520.55_kit3 8.1.5.0 1756RM3.3/1756RM220.00420.55_kit2 8.1.5.0 1756RM3.3/1756RM220.00420.55_kit1 8.1.5.0 1756RM3.3/1756RM220.00420.54_kit1 8.1.5.0 1756RM3.3/1756RM220.00420.54Enhanced 7.3.6.0 1756RM3.3

    19.52/53_kit1 8.1.5.0 1756RM3.2/1756RM220.004

    19.52/53Enhanced 7.2.7.0 1756RM3.2

    16.081_kit2Enhanced 8.1.5.0 1756RM2.5/1756RM220.004

    16.81_kit1Enhanced 8.1.5.0 1756RM2.5/1756RM220.004

    16.8xEnhanced 6.2.10.0 1756RM2.5

    16.5xEnhanced 5.2.3.0 1756RM2.3

    16.57_kit1Standard 8.1.5.0 1757SRMv5.4/1756RM2.6/1756RM220.004

    16.56Standard 6.2.10.0 1757SRMv5.3/1756RM2.6

    16.50/16.53Standard 5.2.3.0 1757SRMv5.1

    15.5x/15.6x 5.2.3.0(3.6.4.0) 1757SRMv4.3/4.4

    13.71 5.2.3.0(2.6.4) 1757SRMv3.39

    11.72 2.50 1757SRMv3.29

    IMPORTANTForuserssupportingbothv11.xandv13.xRedundancySystemsIfyouconnectyourcomputertoaControlLogixRedundancySystemrevision11.xorearlier,donotusethe6.2.10,5.2.3,3.6.4or2.6.4versionoftheSRMConfigurationtooltomonitoranSRMmoduleolderthanrevision3.37.UsingoneoftheseversionsofthetoolwiththeolderSRMscouldcausethemoduletofault.

    Comments(0)

    Thisanswerhasnocomments

    PostaComment

    ProductTreeforThisAnswer(expand/collapse)

    DISCLAIMERThisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjectorsubjectsandisnotanexhaustivetreatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteisnotintendedtoconstituteapplication,design,softwareorotherprofessionalengineeringadviceorservices.Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshouldconsultaqualifiedprofessionaladvisor.

    ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACYOFANYOFTHEDATACONTAINEDINTHISWEBSITEANDMAYMAKECHANGESTHERETOATANYTIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALLINFORMATIONCONVEYEDHEREBYISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGESOFANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,EVENIFROCKWELLAUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.

  • ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDINRESPECTOFTHEINFORMATION(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHEIMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,MERCHANTABILITY,ANDNONINFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,thisdisclaimermaynotapplytoyou.

    ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.