Upload
augsto-vi
View
75
Download
0
Embed Size (px)
Citation preview
RockwellAutomationSupportCenter
29511RedundancyModuleConfigurationTool(RMCT)AccessLevel:EveryoneDateCreated:08/23/200412:00AMLastUpdated:12/03/201402:39PM
QuestionWherecanIgetthedownloadfortheRedundancyModuleConfigurationTool?IcannotaccesstotheModuleConfigurationfor1756RMmoduleinRSLinx.
AnswerTheRedundancyModuleConfigurationToolcanbedownloadedfromtheCompatibility/DownloadCenterundertheFirmwareDownloads.Usetheredundancymodulecatalognumberforyoursearch.(1757SRM,1756RM,1756RM2).Thetoolscanbeselectedaspartofthefirmwaredownload:
OlderRSLinxClassicsoftwarewillpreinstallsomeversionoftheRedundancyModuleConfigurationTool(RMCT).DependinguponwhichversionofRedundantFirmwarebeingused,adifferenttoolmayberequired.
1. ThefirststepistodeterminewhatversionRMCTiscurrentlyinstalled.IftheModuleConfigurationoptionismissingwhenrightclickingtheredundancymoduleinRSLinxcheckyourcomputer'sAdd/RemoveProgramsorProgramsandFeaturestoseeiftheRedundancyModuleConfigToolisinstalledanditsversion.
2. ForamissingEDSfile,rightclickonthemoduleandselect'UploadEDSfilefromDevice'.Iftheuploadoptionismissing,thentheRSLinxClassicsoftwareisanolderversion.TheusercanobtainEDSfilesfromthewebsiteorinstallanewerversionofRSLinxClassicsoftware.
IfRSLinxClassicv2.52,v2.53or2.54isinstalled,thepreinstalledversionoftheSRMConfigurationToolonlyworkswithv16redundantfirmware.TheWindowsControlPanel>Add/RemoveProgramslistcanbeusedtouninstallanexistingversion.
3. Verifythemodulesfirmwarehasbeenflashedtothedesiredversion.DefaultfirmwarewillnotallowanEDSfileuploadormoduleconfiguration.4. IftheuserattemptstoinstallRMCTfromanetworkdrive,buttheinstallationisunsuccessfulandstatesError1309.Errorreadingfromfile\\
...\SRMConfig.dll.Shortenthepath,byextractingtheRMCTinstallationfilesclosertotherootoronahardlocaldrive.
5.WheninstallingRMCTv7.2.7.0onaWindows7OS,theSetupDialogmaybehiddenbytheWindowsExplorerwindow.
IftheRedundancyModuleConfigToolSetupV7.2.7.0dialogishiddenbehindtheWindowsExplorerwindow,simplyMinimize(ormove)theWindowsExplorerwindow.
SimplifiedConfigurationToolSelectionVersion8.1.5.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:
revision15revision16revision19revision20
Version7.3.6.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:
revision15revision16revision19revision20
Version7.2.7.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:
revision13revision15revision16revision19
Version6.2.10.0oftheRedundancyModuleConfigurationTooliscompatiblewiththefollowingredundantfirmware:
revision13revision15revision16
Version2.5.0oftheRedundancyModuleConfigurationTooliscompatiblewithrevision11redundantfirmware.
Notes:
1.Whenthe7.2.7.0orhigherversionofthetoolisinstalled,thepreviousversionisautomaticallyuninstalled.2. 7.2.7.0orhigherversionsofthetoolhavetoolsbackto5.2.3.0installedwithit.3. Higherrevisionsofversionssupporthigherrevisionsoffirmwareandnewer1756RM2refertothefollowingtable:
RedundancyPackage ToolVersion ModuleFirmwareVersion
20.55_kit4 8.02 1756RM3.003/1756RM220.00520.55_kit3 8.1.5.0 1756RM3.3/1756RM220.00420.55_kit2 8.1.5.0 1756RM3.3/1756RM220.00420.55_kit1 8.1.5.0 1756RM3.3/1756RM220.00420.54_kit1 8.1.5.0 1756RM3.3/1756RM220.00420.54Enhanced 7.3.6.0 1756RM3.3
19.52/53_kit1 8.1.5.0 1756RM3.2/1756RM220.004
19.52/53Enhanced 7.2.7.0 1756RM3.2
16.081_kit2Enhanced 8.1.5.0 1756RM2.5/1756RM220.004
16.81_kit1Enhanced 8.1.5.0 1756RM2.5/1756RM220.004
16.8xEnhanced 6.2.10.0 1756RM2.5
16.5xEnhanced 5.2.3.0 1756RM2.3
16.57_kit1Standard 8.1.5.0 1757SRMv5.4/1756RM2.6/1756RM220.004
16.56Standard 6.2.10.0 1757SRMv5.3/1756RM2.6
16.50/16.53Standard 5.2.3.0 1757SRMv5.1
15.5x/15.6x 5.2.3.0(3.6.4.0) 1757SRMv4.3/4.4
13.71 5.2.3.0(2.6.4) 1757SRMv3.39
11.72 2.50 1757SRMv3.29
IMPORTANTForuserssupportingbothv11.xandv13.xRedundancySystemsIfyouconnectyourcomputertoaControlLogixRedundancySystemrevision11.xorearlier,donotusethe6.2.10,5.2.3,3.6.4or2.6.4versionoftheSRMConfigurationtooltomonitoranSRMmoduleolderthanrevision3.37.UsingoneoftheseversionsofthetoolwiththeolderSRMscouldcausethemoduletofault.
Comments(0)
Thisanswerhasnocomments
PostaComment
ProductTreeforThisAnswer(expand/collapse)
DISCLAIMERThisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjectorsubjectsandisnotanexhaustivetreatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteisnotintendedtoconstituteapplication,design,softwareorotherprofessionalengineeringadviceorservices.Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshouldconsultaqualifiedprofessionaladvisor.
ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACYOFANYOFTHEDATACONTAINEDINTHISWEBSITEANDMAYMAKECHANGESTHERETOATANYTIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALLINFORMATIONCONVEYEDHEREBYISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGESOFANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,EVENIFROCKWELLAUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.
ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDINRESPECTOFTHEINFORMATION(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHEIMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,MERCHANTABILITY,ANDNONINFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,thisdisclaimermaynotapplytoyou.
ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.