The 2H34 Series relay is a frequency monitoringrelay with four stages of adjustable frequencypick up & drop out points.
Each frequency set point can be set for under or
over frequency operation & has an independenttime delay driving an output relay.
An undervoltage lockout is used to disable thefour frequency outputs when the voltage fallsbelow a preset level.
2H34Four Stage Frequency Relay
Frequency Stages
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 4/26
Inputs: Single pole 63.5 or 110V ACSetting stages: 4 independent stages
Operating range: 40 to 60 HzSetting range: 41 to 59Hz in 0.05Hz stepsMeasurement resolution: 0.01Hz at 50Hz
Accuracy: +/-0.03Hz (70 to 121V) at 50HzHysterisis: 0.05 to 0.5Hz in 0.05Hz stepsOver frequency function: PU at set point
DO at set point – hysterisis +/-0.03HzUnder frequency function: PU at set point
DO at set point + hysterisis +/-0.03Hz
2H34Frequency Set Points
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 5/26
The 2H34 allows for a separate time range for each of the
four frequency stage set points.
Setting range: 0.1 to 100s in 0.05s steps.Minimum operate time: 0.1s typicalTiming error: <20ms + 0.1% of time delay setting
Frequency ElementTime Delay Setting
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 6/26
Each setting stage can also have a rate of change of frequencythreshold, df/dt, established.
Each dF/dt stage has an independent time delay but drives thesame output relay as the frequency stage.
Two logic options are available to control how the output contactresponds to the frequency and dF/dt pick up as follows:
OR either frequency of dF/dt will trigger thelogic stage output contact.
AND both the frequency and dF/dt must pickLogic up to activate the stage output relay.
2H34Rate of Change Of Frequency
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 7/26
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 8/26
2H34dF/dt Sampling Engines
To allow dF/dt setting flexibility while
remaining within the constraints described inTable 1, two dF/dt sampling engines (A & B)are provided:
dF/dt activation: Set to ON or OFFSample time A: 2 to 5 cycles in 1 cycle stepsdF/dt rejection A: 2 to 18Hz/s in 0.1Hz/s stepsSample time B: 2 to 5 cycles in 1 cycle stepsdF/dt rejection B: 0.2 to 18Hz/s in 0.1Hz/s steps
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 9/26
2H34dF/dt Set Points
Four independent dF/dt elements are provided. When this
function is activated the dF/dt pick up is used to initiate anindependent dF/dt timer.
Setting stages: 4 independent stages
Setting range: 0.13 to 9.0Hz/s in 0.1Hz/s stepsdF/dt function: PU at set point
DO at set point – hysterisis
dF/dt engine: Select dF/dt sampling engine A or B
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 10/26
The 2H34 allows for a separate time range for each of thefour dF/dt stage set points:
Setting range: 0.00 to 100s in 0.02s steps.Timing error: <20ms + 0.1% of the time delay setting
2H34dF/dt Time Delay Setting
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 11/26
2H34dF/dt Setting Criteria
Sample time(Cycles) 2 3 4 5
Maximum setting(Hz/s) 9 7 6 5
Minimum setting(Hz/s) 0.70 0.50 0.20 0.13
Minimum timedelay setting 40ms 60ms 80ms 100ms
dF/dt Measurementtime 100ms 160ms 200ms 240ms
Hysterisis(Hz/s) 0.24 0.12 0.07 0.05
Accuracy at 50Hz(Hz/s) +/-0.2 +/-0.1 +/-0.07 +/-0.05
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 12/26
The 2H34 Series relay also provides a number of independent voltage stages:
An undervoltage lockout is available to disable the four frequency outputs when the voltage falls below a presetlevel;
An undervoltage alarm stage with independent outputcontact;
An over voltage alarm stage with independent outputcontact.
2H34Voltage Stages
Voltage Alarm / Lockout Stages
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 13/26
Summary of Output Stages
2H34Four Stage Frequency Relay
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 14/26
Front Panel Settings & Indicators
SET page
DATA page
Diagnostics page4 Stage trip status LED’sFlash when timing, solid when timed out
Relay disabled LED
Under voltage alarm LED
Relay healthy LED
Relay service LED
RS232 configuration port
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 15/26
Compact draw out case- Screw terminals- CT shorting available
Micro MATRIXProtection & Control Relay Platform
High accuracy
Simple calibration
Temperature compensation
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 16/26
Self supervision- Power supply- Software watchdog
Scaleable I/O
Front accessible opto-isolated programming port
Single PC programsuits all models
Micro MATRIXProtection & Control Relay Platform
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 17/26
Firmware control & upgrades
Separate BIOS &application software levels
Micro MATRIXProtection & Control Relay Platform
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 18/26
Micro MATRIXProtection & Control Relay Platform
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 19/26
uMATRIXwinPC Configuration Screen
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 20/26
Front Panel Layout
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 21/26
Menu Structure
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 22/26
Typical uMATRIX Platform PCB’s
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 23/26
uMATRIX Platform HMI PCB
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 24/26
2H34 Terminals
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 25/26
Customer Generated Ordering Code Generate the required ordering code as follows: e.g. 2H34 BBB
1 2 32H34
1 AUXILIARY SUPPLY RANGE
A 20-70V DC
B 40-275V AC / 300V DC
2 RELAY INITIATE INPUT
Opto-isolated input A 24-80V AC/DCB 75-150V AC/DCC 150-300V AC/DC
3 REMOTE FLAG RESET INPUT
Opto-isolated input A 24-80V AC/DCB 75-150V AC/DCC 150-300V AC/DC
REQUEST DEFAULT APPLICATION SOFTWARE
A 2H34AUMX Frequency OR dF/dt output logic functionB 2H34BUMX Frequency AND dF/dt output logic function
7/27/2019 2h34 Application
http://slidepdf.com/reader/full/2h34-application 26/26
2H34Additional Information
Technical BulletinUser GuideSoftware downloads
Auto Cad Mounting DrawingsPrice & Availability
www.rmspl.com.au/2H34.htm
Test Manuals
www.rmspl.com.au/search.asp
Other Products
www.rmspl.com.au/Products.htm