2.Requirements for Electrical Installations

Embed Size (px)

Citation preview

  • 7/28/2019 2.Requirements for Electrical Installations

    1/12

    2Requirements for Electrical Installations

    2.1.1 Description of Fuse Class Designations2.1.2 Maximum Peak Let-Through Current (Ip-Amperes) and ClearingI

    2t(Amperes-Squared-Seconds)2.2.1 Working Spaces [NEC Table 110.26(A)]

    2.2.2 Examples of Conditions 1, 2, and 3 (Working Spaces)2.2.3 Example of Exception 1 (Working Spaces)

    2.2.4 Example of Exception 3 (Working Spaces)

    2.2.5 Required 30-In-Wide Front Working Space (Working Spaces)2.2.6 Required Full 90-Degree Opening of Equipment Doors (Working Spaces)

    2.3.1 NEC Section 110.26(C), Basic Rule, First Paragraph (Access to WorkingSpace)

    2.3.2 NEC Section 110.26(C), Basic Rule, Second Paragraph (Access to WorkingSpace)

    2.3.3 Example of an Unacceptable Arrangement of a Large Switchboard (Access

    to Working Space)2.3.4 Example of Exception No. 1 (Access to Working Space)

    2.3.5 Example of Exception No. 2 (Access to Working Space)2.4.1 Working Space and Dedicated Electrical Space

    2.4.2 Working Space in Front of a Panelboard as Required byNEC Section 110.26

    2.4.3 Dedicated Electrical Space Over and Under a Panelboard2.5.1 Minimum Depth of Clear Working Space at Electrical Equipment

    2.5.2 Elevation of Unguarded Live Parts Above Working Space

    Section

    2.1

  • 7/28/2019 2.Requirements for Electrical Installations

    2/12

    2.1.1 Description of Fuse Class Designations

    2.2 Section Two

    TABLE 2.1.1

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    3/12

    Requirements for Electrical Installations 2.3

    2.1.2 Maximum Peak Let-Through Current(I

    p-Amperes) and Clearing I

    2t

    (Amperes-Squared-Seconds)

    TABLE 2.1.2

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    4/12

    2.2.1 Working Spaces

    2.4 Section Two

    Exception No. 1. Working space shall not be required in back or sides of

    assemblies, such as dead-front switchboards or motor control centers, wherethere are no renewable or adjustable parts, such as fuses or switches, on the

    back or sides and where all connections are accessible from locations other

    than the back or sides. Where rear access is required to work on deenergized

    parts on the back of enclosed equipment, a minimum working space of 30 in(762 mm) horizontally shall be provided.

    Exception No. 2. By special permission, smaller spaces shall be permittedwhere all uninsulated parts are at a voltage no greater than 30 V rms, 42 V

    peak, or 60 V dc.

    Exception No. 3. In existing buildings where electrical equipment is beingreplaced, condition 2 working clearance shall be permitted between dead-

    front switchboards, panelboards, or motor control centers located across the

    aisle from each other where conditions of maintenance and supervisionensure that written procedures have been adopted to prohibit equipment on

    both sides of the aisle from being open at the same time and qualified per-sons who are authorized will service the installation.

    TABLE 2.2.1

    ( 2001, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    5/12

    2.2.2 Examples of Conditions 1, 2, and 3 (Working Spaces) Distances are measured from thelive parts if the live parts are exposed, or from the enclosure front if live parts are enclosed. If any assemblies, such as switchboards

    or motor-control centers, are accessible from the back and expose live parts, the working clearance dimensions would be required at

    the rear of the equipment, as illustrated. Note that for Condition 3, where there is an enclosure on opposite sides of the working

    space, the clearance for only one working space is required.

    Requirements for Electrical Installations 2.5

    2.2.2

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    6/12

    2.2.3 Example of Exception 1 (Working Spaces)

    2.6 Section Two

    2.2.4 Example of Exception 3 (Working Spaces)

    2.2.3

    2.2.4

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    7/12

    2.2.5 Required 30-In-Wide Front Working Space (Working Spaces) The 30-inch-wide frontworking space is not required to be directly centered on the electrical equipment if it can be ensured that the space is sufficient for

    safe operation and maintenance of such equipment.

    Requirements for Electrical Installations 2.7

    2.2.5

    2.2.6 Required Full 90-Degree Opening of Equipment Doors (Working Spaces)Equipment doors are required to open a full 90 degrees to ensure a safe working space.

    2.2.6

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    8/12

    2.3.1 NECSection 110.26(C), Basic Rule, First Paragraph (Access to WorkingSpace) Section 110.25 (C), Basic Rule, first paragraph. At least one entrance is required to provide access to the workingspace around electrical equipment. The installation shown on the bottom would not be acceptable if the electrical equipment was a

    switchboard over 6 feet wide and rated 1200 amperes or more.

    2.8 Section Two

    2.3.1

    2.3.2 NECSection 110.26(C), Basic Rule, Second Paragraph (Access to WorkingSpace) Section 110.26 (C), Basic Rule, second paragraph. For equipment rated 1200 amperes or more and over 6 feet wide,one entrance not less than 24 inches wide and 6-1/2 feet high is required at each end.

    2.3.2

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    9/12

    2.3.3 Example of an Unacceptable Arrangement of a Large Switchboard (Access toWorking Space) Unacceptable arrangement of large switchboarda person could be trapped behind arcing electrical

    equipment.

    Requirements for Electrical Installations 2.9

    2.3.3

    2.3.4 Example of Exception No. 1 (Access to Working Space) The equipment locationpermits a continuous and unobstructed way of exit travel.

    2.3.4

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    10/12

    2.3.5 Example of Exception No. 2 (Access to Working Space) If the working space requiredby Section 110.26 (A) is doubled, only one entrance to the working space is required.

    2.10 Section Two

    2.3.5

    2.4.1 Working Space and Dedicated Electrical Space The two distinct indoor installation spacesrequired by Section 110.26 (A) and 110.26 (F), that is, the working space and the dedicated electrical space.

    2.4.1

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    11/12

    2.4.2 Working Space in Front of a Panelboard as Required by NECSection 110.26The working space in front of a panelboard as required by Section 110.26. This illustration supplements the dedicated equipment

    space shown in Figure 2.4.3.

    Requirements for Electrical Installations 2.11

    2.4.2

    2.4.3

    2.4.3 Dedicated Electrical Space Over and Under a Panelboard The dedicated electricalspace over and under a panelboard, as required by Section 110.26 (F) (1).

    ( 1999, NFPA)

    ( 1999, NFPA)

  • 7/28/2019 2.Requirements for Electrical Installations

    12/12

    2.5.1 Minimum Depth of Clear WorkingSpace at Electrical Equipment [NECTable 110.34(A)]

    2.12 Section Two

    TABLE 2.5.1

    2.5.2 Elevation of Unguarded LiveParts Above Working Space [NECTable 110.34(A)]

    TABLE 2.5.2

    ( 2001, NFPA)