Upload
bansalr
View
222
Download
0
Embed Size (px)
Citation preview
7/28/2019 2v73 Application
1/18
THE RELAY SPECIALISTS
relay monitoring systems pty ltd www.rmpl.com.au
7/28/2019 2v73 Application
2/18
2V73
High Impedance Differential Relay
7/28/2019 2v73 Application
3/18
2V73
High Impedance Differential Relay
The 2V73 relay provides high speeddifferential protection for various items of
power system plant including generators,busbars, motors & the individual windings ofpower transformers.
It is also suitable for restricted earth faultprotection applications.
7/28/2019 2v73 Application
4/18
2V73
High Impedance Differential Relay
The relay measuring element is basically anattracted armature unit of simple & rugged
construction powered from a bridge rectifier.
Relay stability can be set in steps (25-115V in 15Vsteps or 25-325V in 50V steps), by using the front
panel mounted selector switch. A capacitor isconnected in series with the operating coil to makethe relay insensitive to the DC component of faultcurrent.
7/28/2019 2v73 Application
5/18
External Fault
A DCB
2500A 4500A 3000A
5000A
10000A
F1
15 kA
5A 9A 6A 20A
No current
through
relay
EXTERNAL FAULT of 15 kA
RELAY CURRENT = 5 + 9 + 6 - 20 = 0A
7/28/2019 2v73 Application
6/18
External Fault Assuming
CT Not Saturated
10.2A 30.6A10.2A10.2A
7/28/2019 2v73 Application
7/18
External Fault Causing
CT Saturation
If CT saturation occurs it is most l ikely to affect
CT with heaviest loading.
Unbalance current caused by CT saturation wil l
flow through secy winding of saturated CT and
through relay.
To obtain a relay operating voltage in excess of
the resultant voltage the relay is required to be a
HIGH IMPEDANCE.
Note this is a relative term i.e. high impedance
relative to impedance of saturated CT path
7/28/2019 2v73 Application
8/18
Stability Setting
For CT Saturation Condition
10.2A
30.6A
10.2A10.2A
82.6V
RL
2 ohms
RCT
0.7 Ohm
7/28/2019 2v73 Application
9/18
Internal BUS Fault
A DCB
2500A 4500A 3000A 5000A
F215 kA
5A 9A 6A 10A
30A
through
relay
INTERNAL FAULT of 15 kA
Relay Current = 5 + 9 + 6 + 10 = 30A
7/28/2019 2v73 Application
10/18
2V73
Operating Current
The primary operating current is given by: I op = n ( IR + N I
)
IR = Relay operating current & Metrosil current at setting voltageas per the table below.
I
= CT magnetizing current at setting voltage (A)
n = CT turns ratioN = Number of connected CTs
The operating currents shown in the following tables are for both3 inch & 6 inch Metrosils connected to the 2V73 as per the wiringdiagram.
Range A(Volts)
25 75 125 175 225 275 325
Nominal(mA)
15 15 15 15 17 21 29
13 13 13 13 13 15 18
to to to to to to toLimits(mA)
16 17 17 20 27 39 61
7/28/2019 2v73 Application
11/18
2V73
Operating Current
Range B(Volts)
25 40 55 70 85 100 115
Nominal(mA)
14 14 14 14 14 14 14
13 13 13 13 13 13 13
to to to to to to toLimits
(mA) 16 16 16 17 17 17 17
Should the natural effective operating current after applying theabove formula be lower that desired, it can be raised to therequired level by adding a shunt resistor across the differentialrelay input circuit.
7/28/2019 2v73 Application
12/18
2V73
BUS Protection
(Single Phase Representation)
12
8
14
10
Flag resetvoltage free
contact
Magnetic flagoption only
Flag auxiliary
Flag auxiliary
28
24
22
26
Tripoutput 2
Tripoutput 1
5
6 Vs
L1 L2 NL3
P2P1
P2P1
7/28/2019 2v73 Application
13/18
2V73
Restricted Earth Fault Application
12
8
14
10
Magnetic flagoption only
Flag resetvoltage free
contact
Flag auxiliary
Flag auxiliary
28
24
22
26
Trip
output 2
Tripoutput 1
5
6 Vs
P2P1
P2
P1
7/28/2019 2v73 Application
14/18
2V73
Metrosil
An external Metrosil unit having a non-linear
resistance characteristic is required foreach phase element to limit the peakvoltage appearing across the secondarydifferential circuits under internal fault
conditions.
7/28/2019 2v73 Application
15/18
1M123
BUS Bar Protection Rack
3 x 2V73 Single phase high impedance differential relays1 x 2V75 3 phase Metrosil module1 x 2HSM High speed multi trip relay1 x 4M800 4U 19 inch sub rack frame
7/28/2019 2v73 Application
16/18
2V73
Metrosil Selection
Refer 2V75 Metrosil Module
Type Specification Rated Energy Part No.6 3 600A/S3/I/S887 33kJ 2105C58001
6 1 600A/S1/S887 33kJ 2105C58002
3 3 300A/S3/I/S3063 8kJ 2105C58006
3 1 300A/S1/S646 8kJ 2105C58004
7/28/2019 2v73 Application
17/18
Customer Generated Ordering Code
Generate the required ordering code as follows: e.g. 2V73 BAA
OrderCodeGeneral
Type1 2 3
2V73 -
1 SETTING RANGE
A 25-325V AC in 50V stepsB 25-115V AC in 15V steps
2 RATED FREQUENCY
A 50 HzB 60 Hz
3 FLAG TRIP INDICATION
A Mechanical flag no flag auxiliary requiredB Magnetic flag 24 to 150V DC auxiliaryC Magnetic flag 140 to 300 V DC auxiliary
7/28/2019 2v73 Application
18/18
2V73
Additional Information
Technical Bulletin User Guide Software downloads
Auto Cad Mounting Drawings Price & Availability
www.rmspl.com.au/2V73.htm
Test Manuals
www.rmspl.com.au/search.asp
Other Products
www.rmspl.com.au/Products.htm