3 Fulfillment of Grid Code

  • Upload
    natyac

  • View
    232

  • Download
    0

Embed Size (px)

Citation preview

  • 8/13/2019 3 Fulfillment of Grid Code

    1/21

    Fulfillment of Grid Code Requirements in

    the area served by UCTE by Combined

    Cycle Power Plants

    Dieter Diegel,Steffen Eckstein

    Ulrich Leuchs,Oldrich Zaviska

    Siemens AG, Power Generation , Germany

    Abstract:

    The continental European power system is the result of synchronous interconnection of the

    electricity networks of the separate transmission system operators (TSOs) involved. To

    ensure smooth operation of the system and to enable grid disturbances to be controlled, a

    number of technical rules and recommendations need to be followed in operation of this

    system.

    The rules and recommendations of the Union for the Coordination of Transmission of

    Electricity (UCTE) form a common basis for this, providing minimum requirements to be

    met for grid operation on this system which is operated in overall synchronism These rules

    NextOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    2/21

    profitability for the system. For the TSOs to be able to meet their responsibilities,

    transmission system users must comply with the technical minimum requirements and rulesspecified in the relevant Grid Codes.

    The paper discusses the requirements of national Grid Codes for primary and secondary

    control and the extent to which they can be fulfilled by combined cycle power plants

    (CCPPs).

    Examples are given of the restrictions that apply for modern gas turbines, and of the way in

    which Grid Code or customer requirements can be met for combined cycle plants.

    1. Introduction

    In the past year, the UCTE and regional TSO associations responsible for national Grid Codes

    have had very good reason to focus on compliance with and fulfillment of the requirements

    that they have set forth.

    There were the blackout events in Italy, Denmark/southern Sweden and the USA/Canada,

    which resulted in major economic losses.

    Even the variability of the causes involved illustrates that the complexity of a reliable energy

    supply system presents ever greater challenges and requires more and more a coordinated

    approach.

    Not least of all, grid operators are being challenged to make ever larger power reserves

    available, to achieve improved distribution of these power reserves within the interconnected

    power system and to develop new and better load shedding concepts for response to

    disturbances.

    There are various reasons for the size and uniformity of the power reserves. On the one hand,

    it is necessary for conventional power plants to provide control reserves corresponding to the

    entire output supplied by energy producers which operate without any frequency-control

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    3/21

    power system, which was originally envisioned primarily as a source of mutual assistance and

    optimization, is more and more becoming a commercial marketplace.Not least of all, the expanded physical size of the interconnected power system and the

    variability with which the interconnections mesh are also new challenges. Due to limited

    transmission capacity, reliable provision of control power within the interconnected power

    system requires uniform distribution of this control power over the generating units involved.

    In the future, transmission system operators must pay even closer attention to compliance

    with requirements when the generating units are connected and must also use test programs to

    verify the necessary flexibility of these units for grid operation.

    Power plant manufacturers are working intensively in close co-operation with companies that

    operate the generating units to comply with these ever more intricate rules.

    These companies have a vested interest in ensuring a reliable energy supply even in the event

    of grid disturbances, especially if they are responsible for supplying power to large urban

    areas with many industrial plants.

    Back in the 1980s, the Power Generation Group of Siemens AG was already gaining vast

    experience with special grid requirements, in particular relating to steam power plants.

    As gas turbines have gone on-line in single or combined cycle (Siemens GUD) power plants,

    which represent a growing market share, Siemens has been gaining worldwide experience

    with these machines since the ending of the 1980s.

    This experience also aids us in meeting the newly defined requirements for these types of

    power plants.

    2. Common Grid Requirements for Active Power control of CCPPs

    Frequency Stability

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    4/21

    If the power generation is greater than power demand, generators connected to the grid system

    speed up.If the power generation is less than power demand, generators connected to the grid system

    slow down. When power generation and power demand are back in balance, the frequency

    stabilizes.

    For correct operation of the transmission system it is necessary to hold the frequency within

    defined narrow limits. Minor deviations from the frequency reference value (50/60Hz) or

    absence of any such deviations show that there is a balance of generation and power demand.

    Faults in the system resulting from loss of power plants, shutdown of loads, short circuits, etc.

    result in deviations and gradients of varying magnitudes. These faults can result in instability

    of the grid or even in grid outage. It is possible to distinguish:

    - Faults within the anticipated range, controlled by provision of reserve power.

    Those faults result in frequency fluctuations that remain within a control band defined by

    the grid operator e.g. at UCTE = +/-200 mHz.

    It must be possible to ride out loss of the largest generator in the system without frequency

    moving outside the control band. This operation will be described in the subsection

    Frequency Control.

    - Serious system faults that are counteracted by disconnection from the interconnected

    system and measures such as load shedding.

    Fast decreases in frequency in the case of serious system faults can not be counteractedsolely by measures on the generating side. Protection devices are implemented which

    switch off loads (load shedding) in case of a specific underfrequency.

    In the case of fast decreases in frequency where the frequency remains above a

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    5/21

    Primary control is the automatic, stabilizing action of active power controls for the turbine-

    generators interconnected in the synchronous three-phase grid. This type of control acts in the

    time frame of seconds using turbine speed control.

    Secondary controltakes effect after about 30 seconds and acts in the time frame of minutes.

    The local Grid Codes in each country generally specify minimum requirements.

    Purchaser-specific requirements that go beyond the respective Grid Codes are, however, often

    specified in order to achieve competitive advantages on deregulated power trading markets.

    Specifications :

    For example: England/ Wales: NGC Grid Code, Connection Conditions, Appendix 3

    (minimum requirements):

    Plant Operating Ranges:

    If there is a contractual agreement with the TSO, frequency control takes place above a

    minimum generation MG of 65% registered capacity. In case of grid disturbances with

    increasing frequency the control must be able to reduce the generation dynamically down

    to a designed minimum operating level DMLO of 55%.

    For example: Spain : RED ELCTRICA DE ESPAA, P.O.7.1.

    Frequency control band !P = +/- 1.5 % of registered capacity

    The required frequency dependent load change is to be demonstrated 10 seconds after the

    start of a frequency simulation ramp of +/- 0.2 Hz per 30 seconds.

    (It should be noted that these requirements apply to the overall power plant. In combined-

    cycle plants, the ST does not participate in frequency regulation, so the GT has to provide

    1.5 times the response).

    Operating frequency demanded by the grid system

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    6/21

    The regulator must guarantee stable operation of the unit for an indefinite time, for any

    frequency between 47.5 Hz and 51.5 Hz and any load between the load of the auxiliary

    service and the maximum power that can be generated by the unit .

    Allowable power dip on rising/falling system frequency

    Requirement:

    Many Grid Codes contain a requirement to avoid excessive active power dips on fallingsystem frequency. Gas turbines, in particular, tend to respond to frequency reductions with

    pronounced output changes that depend on the ambient temperature.

    Specifications:

    For example: Greece : RAE, CC7.3.1.1.1.

    operate continuously at normal rated output at transmission system frequencies in the range

    49.5 Hz to 50.5 Hz

    Load rejection / island operation

    Requirement :

    In many Grid Codes the requirements above are compulsory.

    Load rejection

    Various electrical causes such as frequency under a minimum limit, stability problems and too

    low grid voltage can cause the circuit breaker to open and disconnect the power plant from the

    grid during operation. After opening of the circuit breaker house load is still supplied (about 5

    to 10 MW). This is called load rejection to house load. If opening of the generator breaker

    takes place in response to a system fault there is then a load rejection to 0 MW

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    7/21

    A blanket requirement for stable operation of a single generator in all possible island

    configurations cannot be met. If there is a requirement for the generating unit to continue in

    stable operation, a purchaser-specific automation concept must be drawn up. For this purpose

    detailed information and technical data on the purchaser's requirements and the possible

    configurations of the island system are necessary.

    Specifications :

    German Transmission Code 2003

    1. Load rejection on house load

    The generating unit must be designed to control the load rejection to house load .

    from each permissible operating point.

    2. (Grid) island operation capability

    Each generating unit must be capable of controlling the frequency under the condition

    that the respective generation shortage is not more than the primary operating reserve.

    In case of generating surplus the generating unit must be able to reduce output down

    to minimum generation.

    Control of a short circuit close to the power plant

    Requirement :

    The short circuit clearance protection will control failures in the system in a time frame of

    approximately 100 ms. If this is unsuccessful, a back-up protection feature then acts in a time

    frame of 100 to 250ms to maintain stable and undisturbed load operation. The requirement to

    overcome a short circuit in the system applies both to the generator voltage control and to the

    turbine frequency/load control.

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    8/21

    Even though the UCTE has developed a number of technical and organizational rules printed

    in the UCTE Operation Handbook, the responsibility of the national TSOs must still bedetermined in their own guidelines.

    Because grid structures vary in different countries (e.g., in the distribution of generating units

    over the area of the country) and due to the way in which the interfaces to the other

    transmission systems are defined and thus to the way in which energy is exchanged with these

    other systems over the interconnected power lines, it is necessary to define specificrequirements.

    Non-UCTE nations (such as Ireland) are second to none in terms of the requirements placed

    Fig. 1 : UCTE members

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    9/21

    4. Control Strategy of SIEMENS Combined Cycle Power Plants

    The range within which a GUDpower plant can contribute to grid frequency regulation is a

    function of the power plant operating mode and the associated overall conditions. Interaction

    between the operating modes of all of the relevant components, such as the gas turbine, heat-

    recovery steam generator and steam turbine, must be taken into account, especially where

    dynamic processes are involved.

    In the GUDprocess, Siemens gas turbines should operate within the largest possible load

    range with nearly constant turbine outlet temperatures, with NOX requirements taken into

    account here. The turbine outlet temperature controller regulates the compressor air mass flow

    to a specified fuel/air ratio. In other words, the air mass flow rate through the compressor

    must be adjusted according to the flow of fuel entering through the control valves. An

    adjustable row of inlet guide vanes, driven by an actuator, is located at the compressor inlet.

    OTC temp. IGV position

    1

    0.5

    11

    0 5

    1

    HP steam press.HP valve opening

    Valve

    Temp.IGV

    Speed-/Admiss.controller

    ST controller

    GT controller

    Speed/Load &OTC temp. lim.controller

    OTC temp.(IGV)controller

    Gas turbineHRSG Steam turbine

    Generator

    IGV

    G

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    10/21

  • 8/13/2019 3 Fulfillment of Grid Code

    11/21

    In order to hold back a required control reserve, a GUDpower plant must operate in the

    part-load range. The gas turbine is then operated under load-controlled with a subordinate

    speed controller. The unit is controlled based on a specified unit load setpoint. As soon as the

    grid frequency goes outside of a set insensitivity band, the frequency influence then acts on

    the unit power setpoint, changing this and the speed controller corrects the lift setpoint (for

    the fuel valves and inlet guide vanes). Unit output is regulated to correspond to the new

    requirement. In the event of overfrequency the load is reduced and in the event of

    underfrequency the load is increased.

    With these dynamic processes, the speed/load controller of the gas turbine provides for an

    optimum and stable combustion process.

    5. The Excellence of SIEMENS CCPPs in Frequency Response

    Now that an explanation has been provided as to the general conditions and the requirements

    of the transmission system operators on the one hand and the Siemens power plant control

    strategy on the other hand, the results of a number of tests will be used to illustrate how

    Siemens GUDpower plants respond to particular events during grid operation.

    The following points will be explored on the basis of tests:

    Primary control in the event of underfrequency

    Primary control in the event of overfrequency

    Load rejection by a gas turbine from base load to house load

    Load rejection by a gas turbine to islanding mode

    Fig. 3 : GT Control, Speed(Frequency)/ Load Controller Principle

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    12/21

    N tP iO ti

  • 8/13/2019 3 Fulfillment of Grid Code

    13/21

    Primary control in the event of overfrequency

    In response to overfrequency simulated by a ramp function of +0.2 Hz within 10 seconds, the

    GUD reduces the power output.

    Load rejection by a gas turbine from base load to house load

    Riding out a load rejection from base load to house load using a gas turbine entails holding

    speed below the overspeed trip limit without throttling the fuel valves so far that flameout

    occurs.

    Fig. 5 : Primary Frequency Response on Overfrequency

    -14

    -12

    -10

    -8

    -6

    -4

    -2

    0

    -5 0 5 10 15 20 25 30 35

    0

    0,05

    0,1

    0,15

    0,2

    0,25

    Measured power response

    UCTE / Spain requirement

    Greece requirement

    England requirement

    Frequency injection

    Frequency deviation [Hz]

    Time [s]

    Power response [% on RC]

    NextPreviousOptions

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    14/21

    Fig. 6 shows load rejection to house load initiated by opening the circuit breaker at a plant

    located in Italy.

    Load rejection by a gas turbine to islanding mode

    Load rejection to islanding mode is gaining in significance. This is a trend that has become

    more apparent since the blackout events of last year. Fig. 17 shows load and frequency curves

    for plant in Germany during load rejection from part load to islanding mode.

    6. Participation of ST in Primary Control

    It was primarily contractual agreements that led to the realization that only by involving the

    steam turbine could the power output requirements be met.

    Fig. 7 : Load Rejection to Island

    20

    40

    60

    80

    100

    120

    140

    160

    -1,00 0,00 1,00 2,00 3,00 4,00 5,00 6,00 7,00 8,00

    Time [s]

    49,9

    50

    50,1

    50,2

    50,3

    50,4

    50,5

    50,6

    GT power

    GT frequency

    Frequency [Hz]Power [MW]

    opening of circuit breaker for island operation

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    15/21

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    16/21

    The block diagram of the new control module is shown in Fig. 9. The charging of thermal

    storage is initiated by switching from natural variable-pressure mode to modified variable-

    pressure mode. This changes the setpoints in the unit control module such that the turbine

    inlet valves begin to throttle accordingly. At the end of the throttling process the storage has

    been charged and the steam section is operating in modified variable-pressure mode, ready for

    the steam turbine to participate in primary control.

    The grid frequency is compared to a frequency setpoint, with the frequency deviation (f)

    used to generate a frequency-dependent setpoint component (SETP) and perform a dynamic

    analysis (SETP_DYN). The SETP_DYNparameter is used to generate control signals in the

    unit coordination control system, with static weighting applied for the steam turbine control

    system. The statically weighted signals are used to correct the steam turbine setpoints and the

    control deviations, causing the desired release of reserve capacity within seconds via the

    control valves.

    500

    470

    460

    450

    PUNIT(MW)

    PUNIT

    PGT(MW)

    PGT

    PST

    PGT = P UNIT

    operation with active STbase load 450 MW

    50

    40

    30

    20

    10

    0

    50

    40

    30

    20

    10

    NextPreviousOptions

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    17/21

    reserve capacity. Once the reserve capacity has been made available, the steam section is

    automatically returned to modified variable-pressure mode.

    Shifting part of the primary control power to the steam turbine provides two important

    advantages over the concept used previously:

    The desired level of primary control power can be held ready at higher base load (by reducing

    the gas turbine contribution by the magnitude of the steam turbine contribution).

    Simultaneously, the dynamic characteristics of the unit are improved through temporary

    activation of the steam process (increases in steam turbine output can be implemented at the

    fast positioning speed that is a feature of the turbine inlet valves).

    A comparison of the two concepts for releasing reserve capacity is shown in Fig. 10.

    At present, a control concept is being developed for primary control using the ST in the range

    of small frequency deviations (up to about 50 mHz). The gas turbine in this case is called

    upon for large frequency dips and for secondary control. This concept will mobilize the

    advantages to be gained by shifting a part of the primary control reserve to the steam turbine.

    Controlled access to the ST control power contribution in the range of small frequency

    deviations substantially improves the dynamic characteristics of the unit and ensures a gas

    turbine operating mode that minimizes life-limiting effects.

    7. Conclusion

    Over its many years of experience in the power plant business, the Siemens Power Generation

    Group has kept pace with the new demands for involving the generating units in frequency

    control within the interconnected power system.

    A steady stream of new and innovative approaches to existing and proven control concepts

    helps us meet the requirements of the transmission system operators. The complexity of a

    NextPreviousOptions

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    18/21

    8. References

    Activating the steam side increases base load capacity. Modern Power Systems,

    January 2002

    Advanced primary control with combine cycle power plants. Proceeding of the 3rd

    International Conference Electric Power Quality and Supply Reliability, Sept. 4-6,

    2002, Haapsalu, Estonia

    Einsatz der Dampfturbine eines GUD-Kraftwerkes zur Primrregelung. EPE

    Electric Power Engineering 2003, 5thInternational Scientific Conference, Jan 28-29,

    2003, Visalaje, Czech Republic

    ESB Grid Code / requirement, Ireland

    Frequency Response Capability of Combined-Cycle Power Plants 12th Conference

    of the Electric Power Supply Industry Cepsi 02-06 November 1998

    GRTN, TRANSMISSION AND DISPATCHING CODE / requirement, Italy

    NGT Grid Code / requirement, England/Wales

    RAE Grid Code / requirement, Greece

    RED ELCTRICA DE ESPAA Grid Code / requirement, Spain

    Siemens Power Journal 2/2000

    Siemens Power Journal online May 2002

    Transmission Code 2003 / requirement, Germany

    UCTE Operation Handbook, www.ucte.org

    UNE Grid Code / requirement, Morocco

    NextPreviousOptions

    NextPreviousOptions

    http://www.ucte.org/http://www.ucte.org/http://www.ucte.org/http://www.ucte.org/
  • 8/13/2019 3 Fulfillment of Grid Code

    19/21

    Page 19 of 21

    Appendix 1, Requirements of various TSOs

    UCTE Members RC= registered capacity

    Country / Grid Code Primary Control

    Controlband/Deadband/Dynamics

    Secondary Control

    Controlband / Dynamics

    Additionals

    UCTE OpHB

    Policy 1

    Load frequency

    control(final draft 1.9E,

    31.12.2003)

    based on

    UCPTE*-Ground

    Rules

    of 01.06.98

    Primary control bandaccording to the control zone.

    Deadband < 10 mHz Dynamics: primary operating

    reserve / 30 s linear according

    to control zone.

    At !f = -0.2 Hz provision offull primary operating reserve

    Value of 8%/min for oil / gaspower plants will be used as

    an aid and are not required. The tracking-speed can be

    set from 50 to 200 s.

    Germany

    Transmission

    Code 2003

    Primary control band +/-2%of RC

    Fully available at !f = 200mHz after 30 s for 15 min.

    Gradient 2% / 3 0s Deadband < +/-10 mHz

    Not a must

    Right to participate insecondary frequency control

    after compliance with

    prequalification

    Load rejection to house load supply must be controlled. Primary reserve additional to speed of load change and

    secondary reserve

    Grid Island Mode:control band: increase !P = +1.5%

    load decrease until minimum load reached

    details must be discussed between

    grid and plant operators Load dip due to falling frequency restricted according

    to Figures 2.1 und 2.2

    p

    NextPreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    20/21

    Page 20 of 21

    Country / Grid Code Primary Control

    Controlband/Deadband/Dynamics

    Secondary Control

    Controlband / Dynamics

    Additionals

    Spain

    RED Grid Code Primary control band +/-1.5%

    of RC

    Fully available at !f = 200mHz after 30s for 15 min.

    Deadband < +/-10 mHz Droop must be adjustable

    Not a must:

    A condition for participationin secondary control by

    generators is a respective

    Qualification of OS

    Italy

    GRTN GridCode

    CA, CC und

    11

    StandardCEI 11-32

    Primary control band +/-3% oRC

    Fully available at !f = 200mHz after 30s for 15 min.

    Deadband < +/-10 mHz Droop 2 8%, must be

    adjustable

    Specific agreement

    SC-band = +/-6% of theactive plant power with 8%

    /min of the GT part of the

    combined cycle

    The primary and secondary control windows areindependent from each other. The overall control

    window is the sum value of the two.

    Islanded Mode: correct operation in an islanded grid.... restore the frequency on the island at rated value of

    +/-0.25%..

    Greece

    RAE

    Grid Code

    Primary control band +/-3%of RC in the load range of 50

    97% RC, then linear

    decrease.

    Fully available at !f = 200

    mHz after 30 s for 15 min. Deadband < +/-10 mHz Droop must be adjustable

    according to the requirements

    of HTSO

    Secondary operating reservenot less than 3% of RC in a

    load range of 50 97% RC,

    then linear decrease

    Remain synchronized with the grid at frequency 47.5 to49.5 Hz and 51.5 to 52.5 Hz for a duration of 60

    minutes

    Remain synchronized with the grid at frequency 52.5 to53 Hz for a duration of 5 s.

    Minimum load not greater than 35% RC Load dip due to falling frequency:

    Supply of rated load in the frequency range of 49.5

    50.5 Hz.

    p

    PreviousOptions

  • 8/13/2019 3 Fulfillment of Grid Code

    21/21

    Page 21 of 21

    Non UCTE Members,

    Country / Grid Code Primary ControlControlband/Deadband/Dynamics

    Secundary ControlControlband / Dynamics

    Additionals

    Morocco UNE

    Techn. rules for

    the operation of the

    connection grid

    Spain Morocco

    Primary control band +/-2.5%of RC (expotential Ta = 10s)

    at !f = 200 mHz

    Deadband < +/-10 mHz Droop 2 6%

    The COMELEC operatingzone must be equipped with a

    grid operation system.

    Morocco is a COMELEC-member. COMELEC isbeing represented within UCTE by REE (Spain). For

    COMELEC the technical rules of UCTE are valid.

    England / Wales

    NGT Grid Code Min. requirement +/-10% RC

    10s after start of frequency

    ramp of -0.5Hz / 10 s the

    frequency response must be

    10% RC.

    Deadband < +/-15 mHz. Limited frequency control in

    case of f > 50.4Hz

    Droop 3 5% NGT normallyrequires 4%.

    Min. requirement +/-10% RC30 s after start of frequency

    ramp of 0.5Hz / 10 s the

    frequency response must be

    10% RC.

    No load decrease on frequency fall of up to 49 Hz. Target frequency correction with +/-100 mHz must be

    possible.

    Islanded ModeThere must be the ability to control an island formation

    between 55% and 100% RC.

    Load dip due to falling frequency:In the range 50.5 to 49.5 Hz continuous active power !

    In the range 49.5 to 47 Hz linear decrease in active

    power by not more than 5%.

    Ireland

    ESB Grid Code

    Primary operation reserve +/-

    5% RC in the load range 50 95% RC, then linear decrease

    allowed

    Fully available in real time atfrequency nadir between 5

    15 s

    Secondary operating reserve

    not less than 5% of RC in theload range 50 95% RC,

    with linear decrease then

    allowed.

    Fully available in the timerange of 15 90 s

    Remain synchronized with the grid at frequency 47.5 to

    52.5 Hz for a duration of 60 min Remain synchronized with the grid at frequency 47.5 -

    47 Hz for a duration of 20s.

    No load increase in the range of 49.5 50.5 Hz Minimum load not < 50% RC for CC and not < 35%

    RC for steam turbine plant.