    USERS MANUAL FOR 3 IN ONE CLEAN ROOM MONITOR

    MODEL NO. AI-PRH

  • 8/9/2019 3 in 1 Monitor Manual

    2/17

    1

    Quality is not an act, it is a habit.

    1. INTRODUCTION 2

    2. APPLICATION 3

    3. CLASSIC FEATURES 3

    4. TECHNICAL SPECIFICATIONS 4

    5. FRONT PANEL DESCRIPTION 5

    6. WIRING DIAGRAM 6

    7. FLOW CHART 7

    TABLE OF CONTENT

    SR NO SUBJ ECTS PA GE NO

  • 8/9/2019 3 in 1 Monitor Manual

    3/17

    2

    Quality is not an act, it is a habit.

    1.INTRODUCTION:-

    The 3 in one clean room indicator is microcontroller based Transmitter and control instrument

    for indicating process parameters like Humidity, Temperature & Differential Pressure. The

    family includes besides the microcontroller based products as following :

    This instrument has been designed mainly to monitor very important process

    parameters using integrated sensors for humidity, temperature & differential pressure.

    Our instrument measuring ranges from 0 to 100% R.H. & 0 to 50 Deg. C customizable as

    per customer & application requirements, where it is having 3 independent 4-20mA Outputs

    one each for all 3 parameters of humidity, temperature, differential pressure.

    The front panel operation has been specially designed for user friendly operations.

    There are commands for directing mode settings, alarm settings and output settings.

    The documentation presented here describes the front panel operation in detail. The

    user is requested to go through this manual and simultaneously give commands on the panel of

    the indicator. After initial difficulties the user will find that the front panel operations are quite

    simple and easy.

    MODEL

    DIGI MAG-T

    DIGI MAG-T

    2 in 0ne

    TYPE

    mm.W C

    mm.H g

    % RH/OC

    OUTPUT

    4-20 mA

    4-20 mA

    4-20 mA,RS485

  • 8/9/2019 3 in 1 Monitor Manual

    4/17

    3

    Quality is not an act, it is a habit.

    2.APPLICATION :-

    1.HVAC System,

    2.Cold Storehouse,

    3.Factory,

    4.Clean Room,

    5.

    Warehouse,

    6.Library,

    7.Museum,

    8.Office,

    9.Machine Room And Labs.

    3.CLASSIC FEATURES :-

    1.

    Measuring Range Humidity : 0.0 to 99.9% R.H.

    2.

    Measuring Range Temperature : 0.0 to 50.0 Deg. C

    3.

    Measuring Range Differential Pressure : 0 to 100 Pascals (or as per label)

    4.

    Accuracy Humidity : +/- 1.8% R.H.

    5.

    Accuracy Temperature : +/- 0.5 Deg. C

    6.

    Accuracy Differential Pressure : +/-0.5 % F.S.

    7.

    Output : Individual 4-20mA Output for all 3 Parameters of

    Temperature, Humidity & Differential Pressure

    8.

    Resolution : 0.1Deg.C for Temperature

    0.1% R.H. for Humidity1 Pascals for Differential Pressure.

  • 8/9/2019 3 in 1 Monitor Manual

    5/17

    4

    Quality is not an act, it is a habit.

    4.Technical Specifications :

    1.

    Power Supply : 12 V.D.C., Max. Load 500 Ohms

    2.

    Signal Output : 3 x 4-20mA Individual Output for Each Temperature,

    Humidity & Differential Pressure3.

    Consumption : 22mA

    4.

    Electrical Connection : 4 Pin Screw Terminal Block (Male/Female) for

    Cables Dia 1.5 sq.mm. max. for Output 2 Pin Screw

    Terminal Block for Power Supply 12 V.D.C.

    5.

    Working Temperature : 0 to +50 Deg. C

    6.

    Environment : Air & Neutral Gases.

    7.

    Differential Pressure Connection : 2 Nos. 4 mm. Hose Nipples at top

    8.

    Cable Entry : 2 Nos. PG7 Rated Plastic Cable Gland.

    5.FRONT PANEL DESCRIPTION :

  • 8/9/2019 3 in 1 Monitor Manual

    6/17

    5

    Quality is not an act, it is a habit.

    The front panel of the instruments consists of:

    Display windows: - 3 Nos.

    LEDs : - 2 Nos.

    Keys : - 4 Nos.

    a) DISPLAY WINDOW :

    I. DIFFERENTIAL PRESSURE WINDOW: It consists of 4 displays which indicate the

    differential pressure value.

    II. HUMIDITY WINDOW:It consists of 3 displays which indicate the humidity value.

    III. TEMPERATURE WINDOW:It consists of 3 displays which indicate the temperature value.

    b) L.E.DS:

    This includes 2nos ON status of alarm 1 & alarm 2,indicates by L.E.Ds. steady indication

    for low mode &and blinking indication for high mode.

    6) WIRING DIAGRAM:

    Output connection Input connection factory fixed

    1 2 3 4 dc supply input signals

    G- ground

    T- temperature

    RH-humidity

    DP-differential pressure

  • 8/9/2019 3 in 1 Monitor Manual

    7/17

    6

    Quality is not an act, it is a habit.

    Continuously press

    buttons combinedly.

    Press to select type of

    input

    Press to adjust ZERO

    input range

    7) FLOW CHART:

    1) FLOW CHART FOR INPUT TYPE ADJUSTMENT:-

    Restart the device using RST switch

    Press SET key

    Press SET key

    Now it display ZERO

    Press SET key

    Now it display SPAN

    Press to adjust SPAN

    input range

    A

  • 8/9/2019 3 in 1 Monitor Manual

    8/17

    7

    Quality is not an act, it is a habit.

    A

    Press SET key

    Now it humidity %R.Hdisplay will blink

    Press SET key

    Now it temp oc

    display will blink

    Press SET key

    Now it display Dec 1

    Press to adjust decimal

    point of input range.

    Press to adjust

    TEMPERATUREvalue.

    Press to adjust

    HUMIDITYvalue.

    Press SET key

    Now it will go to NORMAL RUNNING MODE

  • 8/9/2019 3 in 1 Monitor Manual

    9/17

    8

    Quality is not an act, it is a habit.

    Now it displays ALARM

    Press to adjust DIFFERENTIAL

    PRESSURE OUTPUT SETTINGvalue, it

    displays ZERO.

    Press SET key

    Now it display SPAN.

    2) FLOW CHART FOR OUTPUT SETTINGS:-

    Pr ess SET key

    cont inuousl y f or 5 sec

    Press to adjust ZERO

    value.

    Press to adjust SPAN

    value.

    A

  • 8/9/2019 3 in 1 Monitor Manual

    10/17

    9

    Quality is not an act, it is a habit.

    Press SET key

    Now it display ZEROfor HUMIDITY

    Press SET key

    Now it display SPANfor HUMIDITY

    Press SET key

    Now it display ZEROforTEMPERATURE

    Press SET key

    Now it display SPANforTEMPERATURE

    Press SET key , Now it display t t for outputtype

    adjustment(4-20mA,0-20).

    A

    Press to adjust ZERO

    value.

    Press to adjust SPAN

    value.

    Press to adjust ZERO

    value.

    Press to adjust SPAN

    value.

    Press to adjust OUTPUT

    type selection.

    B

  • 8/9/2019 3 in 1 Monitor Manual

    11/17

    10

    Quality is not an act, it is a habit.

    Press SET key , Now it display SCAL for UP & DOWN

    adjustment.

    Press to adjust UP &

    DOWN type selection.

    Now it displays SCAL

    Press SET key

    Now it display OFFSETfor offset adjustment

    3) FLOW CHART FOR CALIBRATION MODE FOR DIFFERENTIAL PRESSURE:-

    B

    Press SET key

    Now it will go to NORMAL RUNNING MODE

    Pr ess key

    cont inuousl y f or 5 sec

    Press to adjust OFFSET

    value.

    A

  • 8/9/2019 3 in 1 Monitor Manual

    12/17

    11

    Quality is not an act, it is a habit.

    Press SET key

    Now it display 0v for D.P zero range.

    Feed in ovs open condition

    (+) port open

    Press SET key

    Now it display 10v for D.P 10 v range.

    Feed in 1ovs connecting pressure at

    (+) port of the device (range) as required.

    Press SET key

    Now it display SCAL.

    Press key

    Now it will go to NORMAL WORKING

    MODE.

    A

  • 8/9/2019 3 in 1 Monitor Manual

    13/17

    12

    Quality is not an act, it is a habit.

    Now it displays ALARM

    Press SET key ,Now it display AL-1ALARM 1

    settings and second display pv will blink.

    Press to select pressure (pv),

    humidity (Rh), temperature (tnp) type

    of parameter for alarm indication.

    Press SET key ,Now it display typHfor ALARM

    1 type HIGH or LOW selection.

    Press to select HIGH or

    LOW Ttype of alarm indication.

    4) FLOW CHART FOR ALARM SETTINGS:-

    Pr essSET

    key

    Cont inuousl y f or 5 sec

    B

  • 8/9/2019 3 in 1 Monitor Manual

    14/17

    13

    Quality is not an act, it is a habit.

    Press SET key ,Now it display -0.1 process

    value.

    Press SET key ,Now it display HYST hystereisis

    value.

    Press SET key ,Now it display LAT Y FOR LED

    LATCHING SETUP.

    Press to select pressure (pv),

    humidity (Rh), temperature (tnp) type

    of parameter for alarm indication.

    B

    Press to adjust ALARM

    value.

    Press to adjust

    HYSTERESISvalue.

    Press to ON and OFF the

    led latch operation.

    Press SET key ,Now it display AL-2ALARM 2

    settings and second display pv will blink.

    C

  • 8/9/2019 3 in 1 Monitor Manual

    15/17

    14

    Quality is not an act, it is a habit.

    Press SET key ,Now it display typHfor ALARM2 type HIGH or LOW selection.

    Press to select HIGH or

    LOW Ttype of alarm indication.

    Press SET key ,Now it display -0.1 process

    value.

    Press SET key ,Now it display HYST hystereisis

    value.

    Press SET key ,Now it display LAT Y FOR LED

    LATCHING SETUP.

    Press key

    Now it will go to NORMAL WORKING

    MODE.

    C

    Press to adjust ALARM

    value.

    Press to adjust

    HYSTERESISvalue.

    Press to ON and OFF the

    led latch operation.

  • 8/9/2019 3 in 1 Monitor Manual

    16/17

    15

    Quality is not an act, it is a habit.

    Now it displays ALARM

    Press for communication settings ,now it

    displays Anbt ambient adjustment.

    Press SET key ,Now it display SErL scroll mode.

    Press SET key ,Now it display baud for

    adjusting baud rate value.

    5) FLOW CHART FOR COMMUNICATION SETTINGS:-

    Pr essSET

    key

    Cont inuousl y f or 5 sec

    Press to adjust ambient

    value.

    Press to adjust baud rate

    value.

    A

  • 8/9/2019 3 in 1 Monitor Manual

    17/17

    16

    Quality is not an act, it is a habit.

    Press SET key ,Now it display s Id for station id

    adjusting .

    Press key

    Now it will go to NORMAL WORKING

    MODE.

    For any technical assistance, please feel free to contact factory at the below

    address

    Manufactured By :

    ACE INSTRUMENTS(An ISO 9001-2008 Certified Company )

    Plot No.77, Shaktipuram, Industrial Estate Kukatpally, Prashantinagar,Hyderbad 500072 .Phones: +91-40-23078848, 32901226

    Email: [email protected]: www.aceinstrumentshyd.com

    A

    Press to adjust station id

    value for communication.