23
TD-TSP-0004-2A (1/19) INSTRUCTIONS MAINTENANCE FOR POWER TRANSFORMER AddressNo. 23, Chung-Hwa Rd., Huko Hsiang, Hsinchu, Taiwan 303, R.O.C. URLhttp: / / ww w . s eec. c o m. t w TEL+886-3-598- 1921 FAX+886-3-597-6373

3. Maintenance Manual_TD-TSP-0004-2A.docx

Embed Size (px)

Citation preview

Page 1: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (1/19)

INSTRUCTIONSMAINTENANCE FOR

POWER TRANSFORMER

Address:No. 23, Chung-Hwa Rd., Huko Hsiang, Hsinchu, Taiwan 303, R.O.C. URL:http: / / ww w . s eec. c o m. t w TEL:+886-3-598-1921 FAX:+886-3-597-6373

Page 2: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (2/19)

1. FOREWORD

Power transformers are getting larger in their capacity to meet increasing power demand. So

emergency or unexpected power demand due to transformer trouble cause much loss of production as

well as inconvenience.

Therefore it is essential to assure trouble-free performance by a well-planned maintenance program.

Daily or periodical inspections will result in detecting abnormal conditions of a transformer and parts

before they cause any more serious troubles. A regular program of inspection should be established

and rigidly carried out for preventive maintenance of power transformers.

This instruction book describes inspection and maintenance methods to keep transformers in good

condition. As for construction, functions and handling of accessories, the corresponding instruction

book should be referred to for more detailed information.

2. REQUIREMENTS FOR INSPECTION AND MAINTENANCE

2.1 General

(1) The inspection items are classified into three categories in this instruction book.

(a) Routine inspection items (Table 1)

The routine inspection should be made, preferably daily, on every transformer in

service. Especially oil leak, oil temperature and/or winding temperature, load current,

ambient temperature and oil level in transformer should be daily checked and recorded.

(b) Periodical inspection items (Table 2)

The periodical inspection should be made each item, at least once every six months to once

every three years in order to ascertain the good performance of a transformer and its parts.

Most of the periodical inspections should be made in detail when the transformer is de-

energized.

(c) Additional inspection items (Table 3)

Some additional inspections or measurements of electrical characteristics of a transformer are

recommended as preventive maintenance actions and when any transformer trouble should be

investigated thoroughly.

(2) Repainting of radiators and transformer tanks, and exchange of parts, gaskets and bearings of

motors should be planned and prepared previously for preventive maintenance, which will result in

continuous good performance of transformers. (Refer to Table 4)

Page 3: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (3/19)

(3) If any protective relays give alarm, investigate the trouble causes according to Table 5 and Table 6.

It is essential in investigating the right causes to check whether differential relay, overcurrent

relay and/or ground fault relay have operated or not, in combination with other relays such as

Buchholz relay, sudden pressure relay and pressure relief device, which have physically

operating mechanisms.

(4) Transformer should be inspected internally whenever they have been subjected to unusually

severe operating conditions such as overloads and frequent short-circuits of outer bus or

transmission line.

(5) Any symptoms such as unusual noises, high or low oil levels, rupturing of bursting plate, etc.,

should be investigated thoroughly.

2.2 Inspection records

(1) The establishment of the report and recording of the condition and repair of the transformers is

required for a good maintenance program.

(2) A preventive maintenance system will operate satisfactorily with the following

records. (a) An equipment record

This may be simply a card, which contains the basic information of a transformer itself such

as the serial number, the location, size, etc.

(b) A repair record card

This may keep a running record as to costs of maintaining a transformer. It is the

essential diagnostic record for avoiding future difficulties.

(c)An inspection check list or inspector’s record

This may be simply a listing of the points to be checked on a transformer and the

establishment of the time that these checks should be made.

(3) Without these records it would be very difficult for a preventive maintenance program to

work, because the knowledge gained form regular inspections would be quickly lost.

2.3 Actions for safety

Always inspection and maintenance works are to be done very carefully so that their schedule should

be planned in detail in view of safekeeping of human life and equipment according to APPENDIX I.

Page 4: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (4/19)

3. INSPECTION

3.1 Routine inspection

At least item 1 should be checked daily and recorded.

Table 1

No. Items Method Action

1 Oil temperature

and winding

temperature

Read indications of dial and/or

alcohol thermometers, and winding

thermal relays, if provided. Compare

them with the data previously

obtained.

When oil and/or winding

temperature

are much higher or lower

considering load current and

ambient temperature,

Thermometers should be inspected.

Check if indication of a thermometer is

correct or not.

If the temperature is not correct,

exchange with a new one.

If oil temperature is too high due to

dust and other foreign materials on

the finned area of radiators or the

inner surface of cooling water tube

(In case of water cooler type) clean

up them.

If indication of thermometer is not

correct, check oil level in the sensor

pocket and adjust to correct the level.Load current

Ambient

temperature

Load current and ambient

temperature should be recorded at

the same time.

2(1) Oil level

See note.

Read indication of the dial oil level

gauge on the conservator with a

telescope.

Compare it with the oil level-oil

temperature curve for the

transformer. Oil level is deemed to

be normal when its difference is

within one graduation of the gauge

on the curve.

When the indicated oil level is

constant with the changing oil

temperature, inspect the dial gauge

and check the actual oil level.

If the oil level is abnormal, adjust it

according to instructions.

If the oil level shows low, in case of

rubber bag or diaphragm type,

damage of rubber bag or diaphragm is

suspected.

If oil level of OLTC is abnormal,

breaking of seal between OLTC and

transformer is suspected.

(2) in bushing Check the oil level and oil leakage

on all oil-filled bushings.

3 Oil leaks Check oil leaks visually from

radiators flanges, pipes,

transformer tank and so on.

If oil leaks are due to gasket, tighten

bolts or exchange gasket.

In case of oil leaks from welded

parts, apply adhesive material or

weld again on the leaking part.

Page 5: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (5/19)

No. Items Method Action

4 Abnormal noise

and vibration

Abnormal or unusual noise, especially

from oil pump motors and fan motors,

should be carefully

listened to.

When oil pump or fan motor is

getting noisier, exchange the

bearings with new ones.

Abnormal vibration can be checked

comparatively easily by hand.

When any supporters, pipes and other

parts are vibrating due to loose

bolts, tighten them.

5 Silica gel breather Check the breathing action in oil pot

and discoloration of silica gel visually.

Check the color of oil in oil pot.

If the breathing action is not

satisfactory, check choking such as

filter in oil pot.

If the color of silica gel became to

pink from blue (or became to dark

green from orange) from upper side

check air leaks and fix it up.

If the oil color in oil pot blackened,

replace with new oil.

6 Gas trapped in

buchholz relay

Check whether any gas trapped in

buchholz relay with telescope.

If any gas trapped in the relay, the

transformer should be stopped for

investigation including accumulated

gas analysis.

7(1) Appearance

Bolt connection

Check any looseness of bolt

connection visually.

When any loose bolts are found,

tighten them.

(2) Discoloration Check visually that all connections

are normal without any

discoloration due to local heating.

When any connections show signs

of having been hot, clean and tighten

bolts and nuts.

(3) Dust Inspect visually for dust, especially

on radiators.

Clean up dust if it may reduce

cooling capacity of radiators.

(4) Rust Inspect visually for rust, especially

on radiators.

Re-painting is recommendable once

every five years.

Anti-rust and final paint should be

applied after rubbing off rust and old

paint.

(5) Dew Inspect visually for dew in the

terminal box, control cabinets and

protective relays.

If any dew is found, dry it out, and

ensure space heaters are in use if

they are provided.

Note:In case of a self-cooled transformer, there is some difference between top and average oiltemperatures depending on loading conditions and ambient temperature. Strictly speaking, theaverage oil temperature should be referred to for checking oil level.

Page 6: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (6/19)

3.2 Periodical inspection

The recommended inspection frequency is described in parenthesis under each inspection item.

Table 2

No. Items Method Action

1 Breather silica gel

(Once every six

months)

Check the discoloration of silica gel in

breather due to moisture in breathed

air.

If the color of silica gel has turned to

pink from blue (or turned to dark

green from orange) by more than two

thirds of total quantity, dry out or

exchange it.

If the color of silica gel has turned to

pink by more than two thirds of total

quantity, dry out or exchange it.

2(1)

(2)

(3)

Insulation oil

Dielectric strength

(Every one year)

Measure dielectric strength with an oil

tester and confirm it is more than 40

kV/2.5 mm gap.

If any measured values are not

satisfactory, filtering and/or

degassing of insulating oil are

recommended. The permissible

value of OLTC oil shows in Table

4-b.

Moisture content in

oil

(Every one year)

Measure moisture content in oil with

Automatic Coulometric Karl-Fischer

Titration method and confirm that it is

satisfactory to the criteria. Criteria of

OLTC oil is show in Table 4-b.

(Criteria of Transformer oil)

TR. Voltage ≦69kV > 69kV~230kV

M. Content ≦35 ppm ≦25 ppm

TR. Voltage > 345 kV

M. Content ≦ 20 ppm

Acid value

(Every one year)

Measure acid value and judge it with

the criteria of Table 7.

3 Fan motors and/or

oil pump motors

(At least once every

two years)

(1) Measure insulation resistance of

fan motors and/or oil pump motors

with a 500V megger.

If insulation resistance is less than

2MΩ, check balancing of load

currents of three phase and dry out

the interior of fan motors.

(2) Check if temperature rise of oil

pump motors’ cases, based on oil

temperature, is less than 10 deg. C.

If it is more than 10 deg. C, check its

insulation resistance, winding

resistance and three phase balancing

of load current.

Page 7: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (7/19)

No. Items Method Action

4 In case of:Cooler

of water-cooled

type

(At least once every

two years)

(1) Analyze the characteristics of

cooling water as shown in Table 8.

(2) Check scale deposit on the inside

of the cooling tube to reduce the

water flow required, resulting in

excessive heating of a transformer

at normal load.

If any characteristics are not

satisfactory according to the criteria

shown in Table 8, shorten inspection

interval of coolers. If any heavy

scale is found on the inside of the

cooling tubes, clean them up.

5 Control panel and

terminal box and

cables. (Once

every one year)

(1) Check the water-tightness of a

control cabinet and a terminal box.

If the rubber gasket is worn out,

exchange it with a new one.

(2) Ascertain the tightness of all

control wiring connections.

Tighten the loose bolts.

(3) Operate all switches, annunciators

and lamps to observe proper

functions according to schematic

diagrams.

If any part maloperates, adjust or

exchange them with new one.

(4) Measure insulation resistance of

cable with 500V megger.

Check any crack or abrading on

cable insulation.

If such defect is found, put tape on it

or exchange it with new one.

6

(1)

(2)

Protective relays

(Once every two

years)

(1) oil temperature indicator (2) winding temperature indicator

(3) dial oil gauge (4) oil flow indicator

(5) Buchholz relay (6) gas detector

(7) sudden pressure relay (8) differential pressure relay for oil/water cooler

(9) pressure relief device (10) leak detector

Insulation

resistance

(Once every two

years)

Measure insulation resistance of

protective relays including their

wirings with a 500V megger.

When the insulation resistance is

less than 2MΩ, check dews in the

terminal box.

Operation Operation tests should be made only

when protective relays operated even

if no troubles of a transformer

occurred.

The cause of a maloperation should

be investigated by operation tests

according to instruction books for

protective relays.

7 Connections

(Occasionally)

All connections outside of a

transformer should be inspected to

see whether they are in good

conditions without any discoloration,

which indicates “hot” connection.

Any connection that shows signs of

having been hot should be

thoroughly cleaned and bolted

together tightly.

Page 8: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (8/19)

3.3 Additional inspection

The following inspections and measurements are recommended for a preventive maintenance and in investigating a transformer trouble.For preventive maintenance, items 1 and 2 are recommended.If a transformer was failed, all items (1 to 7) are recommended for the investigation on that particular occasion.

Table 3

No. Items Method Action or remarks

1 Insulation oil

Analysis of gas

dissolved in oil

After a transformer is put into service, a periodic analysis of gas dissolvedin oil is recommended at least every six months.

Using an appropriate airtight container, oil should be taken from the transformer. The dissolved gas should be extracted from the oil and analyzed.

When the quantities of combustible gases are obtained, evaluationscan be made to a probable location and type of trouble, which may be present in a transformer.

(Refer to Table 10.)

2 Insulation resistance of transformer windings

Measure the insulation resistance between a pair of windings, and between each winding and ground with a 1,000 or 2,000 volt megger at a periodical inspection.

The megger test should be made to check if the transformer is in suitable condition for operation or application of the dielectric test. Refer to Fig. 1.

The insulation resistance is subject to wide variation with temperature, humidity and cleanness of bushing porcelains.It may be low due to the leakage current through the weakest point of inferior insulation, in which case gases dissolved in oil should be analyzed.

3 Ratio test Measure the ratio of a transformer by two voltmeter methods or with a ratio tester.

If the transformer has taps, the turn ratio should be measured for all taps as well as for the full winding.

The test voltage may be between 100 and 200V at the rated frequency.

Compare the test results with those in the test report.

If it is difficult to measure because of fluctuation of voltmeter pointer or because of unbalance of a bridge circuit, more detailed investigation should be made.

4 Winding resistance Measure the winding resistance by bridge method or by drop-of-potential method. If oil pumps are provided, they should be operated during measuring winding resistance. Theoil temperature should be also recorded at the same time.

In case of low voltage and large capacity delta winding (Ex. generator transformer), there is a very difficulty to measure the winding resistance precisely and needs to pay careful consideration for judgment.

If the winding resistance, corrected to a specified temperature, is different from the data obtained previously, more detailed investigation should be made.

5 Excitation current at low voltage

Measure the excitation current at low voltage (100-200 volts) applied onthe lower voltage winding with other windings being open-circuited.

The voltage wave shape should be sinusoidal.

Note (1)

If the measured excitation current is much larger than the original dataat installation, more detailed investigation should be made.

Note (2)

Page 9: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (9/19)

No. Items Method Action or remarks

6 Impedance voltage Measure the impedance voltage at low current (5-10 amperes) applied on the higher voltage winding with lower voltage winding beingshort-circuited.

Note (3)

If the measured impedance voltage is much different from the original data at installation, more detailed investigation should be made.

7 Bushing current transformer

Excitation current and winding resistance should be measured in the same way as items 4 and 5.

Same as above 4 and 5.

Note:(1) The ammeter should be connected inside of voltmeter as shown below to avoid error due to highimpedance measurement.

(2) If the measured values satisfy an expression below, the transformer may not get serious injury such as layer shorting.

VM/IM 10

VR/IR

IR:Rated current IM:Measured current VR:Rated voltage VM:Measured voltage

(3) The shorting cable should be more than 100mm2 in its section and be as shorter as possible in its

length, to avoid measuring error.

Shorting cable

TR

(4) If those characteristic values from the item 2 to 6 are abnormally different compared the data with original data, it is recommended to carry out an internal inspection. In this case, you are kindly requested to tell us the information as APPENDIX II.

Page 10: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (10/19)

4. MAINTENANCE

Maintenance of parts and materials should be planned according to the following Table 4-a.

Table 4-a

No. Material and parts Maintenance frequency Remarks

1 Grease of fan motors Grease them up once a year, with the grease gun.

Refer to item No.6. It is no necessary when a bearing is sealed type.

2 Porcelain insulator such as bushing, lightning arrester, supporting insulator

Cleaning should be done periodically.

Interval depends on actual circumstance condition at site.

According to insulation book

3 Cooler

(1) Radiator type

Recommended cleaning frequency is once every two years.

With compressed air and/or water.

(2) Forced air type Dust and other foreign materials, accumulated on the finned area, should be blown out to maintain the efficiency of the cooler.

(3) Water cooled type Internal compartment check and cleaning should be done once every two years.

4 Paint for transformer external tank

Repainting should be done once every five years.

5 Bursting plate of transformer

Bursting plate is recommended to be replaced once every five years.

6 Bearing of fan motors and oil pump motors

Expected life is ten years.

Expected life is three years, whenbearing is sealed type. (only fanmotors)

Exchange with new ones, if a motor becomes noisy due to broken bearings.

7 (1) Gasket

(Cork-neoprene)

(2) Thermometer

(Oil, winding)

(3) Pressure relay

(Water, nitrogen, sudden pressure relay, water/oil differential pressure relay)

Expected life is ten years. Exchange with new gaskets, if oil leaks from gasket are serious.

(4) Rubber bag or diaphragm in conservator

Expected life is 15 years. If any damage of rubber bag or diaphragm is suspected, exchange with new one.

8 De-energized tap changer

Operate de-energized tap changer more than once a year when the transformer is out of service

Internal inspection is recommendable before operation of the de-energized tap changer, if the de-energized tap changer is not operated more than one year.

Note: As for maintenance of on-load tap changers, please refer to the corresponding insulation books.

Page 11: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (11/19)

OLTC diverter oil should be maintained according to Table 4-b.

Table 4-b

Location of on-load tap changer

Permissible value

Breakdown voltage Water content

Installed to line side

including delta winding≧40 kV/2.5 mm gap ≦30 ppm

Installed to neutral side ≧30 kV/2.5 mm gap ≦40 ppm

Page 12: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (12/19)

5. TROUBLE SHOOTING

5.1 Diagnosis of protective relays in operationIf any protective relay gives an alarm, investigate its causes according to the following Table 5.

Table 5

No Relay Function Cause and Action

1 Dial type thermometer The dial type thermometer indicates

the top oil temperature and highest oil

temperature experienced. It gives an

alarm when oil temperature gets

to the alarm setting (80℃ for

example).

1.Overloading

2. Insufficient efficiency of cooler

units due to dust and other

foreign materials accumulated on

the finned area or due to a heavy

scale in the water-cooling coils.

3. Maloperation of thermometer or

thermal relay due to their own

defects.

4. If indication of thermometer is not

correct, check oil level in the

sensor pocket and adjust to

correct oil level.

2 Thermal relay for oil

temperature or winding

temperature

The thermal relay detects and

indicates maximum oil or winding

temperature of a transformer.

It also has protective functions to

give an alarm or tripping signal, and

automatic functions to control cooling

system.

3 Oil flow indicator The magnetic oil flow indicator

checks the operating condition of an

oil pump. When an oil pump stops,

the pointer returns to the stop

position and the micro-switch

contact closes to give an alarm.

1.Trouble of oil pump motor

2.Trouble of wiring connection to oil pump motor

3. Radiator valves are shut off.

4. Inverse of power phase sequence.

4 Oil level gauge-dial type The dial type oil level gauge

indicates the oil level in a

conservator of an oil-immersed

transformer.

When the oil level comes down to

the bottom of a conservator, its

pointer indicates zero and give an

alarm.

1.Shortage of oil

2.Abnormally low ambient temperature in winter season

3.Oil leakage

4. Damage of rubber bag or diaphragm in conservator.

5. If oil level of OLTC is abnormal, breaking of seal between the OLTC and transformer is suspected.

Page 13: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (13/19)

5.2 Relay function

If any protective relay operates, investigate the cause of a trouble according to the following relay’s functions.First of all, dissolved gas analysis is recommended immediately for the diagnosis of the transformer.

Table 6

No Relay Function and investigation

1 Buchholz relay

(1) First stage

The first stage of a Buchholz relay detects the gas formation due to minor troubles in transformer tank.

Rubber bag or d i aph r a g m t y pe c on s e rv ato r ;

Stop operation of the transformer immediately, and carry out gas analysis of accumulated gas and dissolved gas in oil and internal inspection of the transformer because a local heating and/or arc discharge is suspected.

B r eather t y pe and/ o r n i t r og e n gas s ea l ed t y pe c on s e rv ato r ;

Check if abnormal gas are exist or not by gas analysis of the transformer gas and dissolved gas in oil.

As the result, if abnormal gas are detected, stop operation of the transformer and carry out of internal inspection.

The type and location of trouble may be predicted by gas analyses of oil. Note:

Nitrogen gas dissolved in oil could supersaturate and accumulate inthe relay and actuate the relay when oil-temperature drops rapidlyon a cold day in case of a gas-sealed transformer.

(2)Second stage The second stage of a Buchholz relay detects the rushing oil due to a serious trouble in the transformer tank.

If other protective relays, such as over-current relay of differential relay operate at the same time, a serious internal damage is suspected.

2 Sudden oil pressure relay

The sudden oil pressure relay detects the high rate of oil pressure increase in a transformer tank due to the gas generation and oil vapour caused by serious troubles. In case of correct operation, the transformer operation should be stopped.

3 Sudden pressure relay [In case of nitrogen sealed conservator]

The sudden pressure relay detects the high rate of nitrogen pressure increase in a tank due to the gas generation and oil vapour caused by serious troubles in the transformer tank.

4 Pressure relief device The pressure relief device operates when the pressure in the relief vent rises abnormally high enough to reach the pressure of approximately0.7kg/cm2 caused by serious failure in a transformer.

It also operates when the pipe of air breather is choked so as to increase the pressure in the relief vent.

6 OLTC protective relay OLTC protective relay detects some faults in diverter of on-load tap changer.

Check the following items;

1.Fault of diverter insert

2.Fault of whole of OLTC

Malfunction of OLTC relay due to normal deterioration.

7 Differential relay The differential relay detects the difference between the input current and the output current of a transformer converted by a current transformer.

It also operates sometimes with the inrush current when a transformer is excited.

8 Over current relay and ground fault relay

These relays detect faults in the electrical system including transformers.

Page 14: 3. Maintenance Manual_TD-TSP-0004-2A.docx

Insu

latio

n re

sist

ance

(M

eg o

hm

s)

TD-TSP-0004-2A (14/19)

Fig1. Allowable value of transformer insulation resistance

1200

1000

800

600

400good

300

200

150

System voltage more than 6kV Systme voltage more than 11kV Systme voltage more than 22kV Systme voltage more than 66kV

100

80

60

40poor

30

20

15

10

8

6

4

3

2

0 20 40 60 80 100 120

Transformer oil temperature (° C)

Page 15: 3. Maintenance Manual_TD-TSP-0004-2A.docx

Die

lect

ric

stre

ng

th (

kV

)

2.5m

m g

ap

/12

.5m

s

ph

ere

TD-TSP-0004-2A (15/19)

Fig2. Relation between dielectric strength and amount of water in insulating oil

50

40

30

20

10

00 10 20 30 40 50 60

Water-parts per million by weight (PPM)

Table 7. Acid value criteria

No Acid value (mg KOH/g) Action

1 Less than 0.2 Good

2 From 0.2 to 0.4 Filter or exchange with

new oil.

in earlier stage

3 More than 0.4 immediately

Table 8. Criteria of cooling water characteristics

No Test item Criteria

1 Hydrogen ion concentration (PH) 6.0 〜 8.0 at 25°C

2 Electrical conductivity Less than 500 (μΩ/cm) at 25°C

3 Chlorine ion (C1—

) Less than 100 ppm

4 Total hardness (CaCO3) Less than 150 ppm

5 — —Sulfuric acid ion (SO4 ) Less than 200 ppm

6 M-Alkalinity (CaCO3) 15 〜 60 ppm

7 Sulfur ion (S— —

) undetectable

8 +Ammonium ion (NH4 ) undetectable

9 Total iron ion (Fe+++

) Less than 0.5 ppm

10 Silica (SiO2) Less than 30 ppm

Table 9-a:Resistivity criteria of insulation oil, at 80℃

Page 16: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (16/19)

Remarks:New oil should be used added oil.

No Transformer voltage Resistivity (Ω.cm) Judgment Action

1≧400 kV ≧1E

13

goodPeriodical analysis every one year.<400 kV >5E

12

2≧400 kV ≦1E〜5E

PrecautionExchange to new oil is recommendable.<400 kV ≦5E

12〜>1E11

3≧400 kV <5E

12

Poor Exchange to new oil<400 kV ≦1E

11

Table 9-b:Power factor criteria of insulation oil, at 80℃

No Transformer voltage Power factor (%) Judgment Action

1≧400 kV ≦0.5

goodPeriodical analysis every one year.<400 kV ≦1.0

2≧400 kV 0.5〜1.5

PrecautionExchange to new oil is recommendable.<400 kV <1〜3

3≧400 kV >1.5

Poor Exchange to new oil<400 kV >3

Table 10 Combustible gas and type of fault with dissolved gas analysis of insulating oil

No Decomposed gases Type of fault

1 H2, CH4, C2H4, C2H6, C3H6, C3H8 Local heating in the oil

2C O , C O 2, H2, CH4, C2H4, C2H6, C3H6,

C3H8

Local heating in the oil impregnated solid insulation.

3 H2, CH4, C2H2, C2H4, C3H6Discharge in the oil

4 C O , C O 2, H2, CH4, C2H2, C2H4, C3H6Discharge in the oil impregnated solid insulation.

Note:Underline means a significant gas.

Page 17: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (17/19)

Table11. Combustible gas levels for maintenance

GasesThe level needed a follow-up survey

Permissible levels

C2H2 <0.5ppm 5ppm

H2 <400ppm

C2H4<100ppm

It should be evaluated by necessary and sufficient

conditions with the following two items.

C2H4:more than 100ppm

TCG:more than 700ppm

CO <300ppm

It should be evaluated by necessary and sufficient

conditions with the following two items.

CO:more than 300ppm

Ratio of CO2/CO

Normal ratio is more than 3

Abnormal ratio is less than 3

TCG

(Total Combustible Gas)<700ppm

It should be evaluated by necessary and sufficient

conditions with the following three items.

Increasing rage:70ppm/month of TCG

C2H4:100ppm

TCG:700ppm

APPENDIX I Actions for safety and quality

Page 18: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (18/19)

Table 11

No Working condition Actions for safety

1 Exterior check (1) Be careful not to approach live parts.

2 Electrical test and

remedial work

(1) De-energize the transformer by circuit breakers and line switches.

(2) Ground the line terminals of the transformer.

(3) Attach caution tags not to operate switches for circuit breakers and line

switches. See note.

(4) De-energize the control cabinets for coolers and tap changer by AC and DC

switches.

(5) Attach caution tags on switch boxes.

3 When internal

inspection is to be

made

Same as above except the following additional items.

(1) Replace nitrogen gas completely with dry fresh air, if it was filled in the

transformer.

(2) Make sure there is 18% or more oxygen to sustain life in a transformer

tank.

(3) Make sure your pockets are empty.

(4) Take off a wrist watch and any other accessories on your body.

(5) List up name and quantity of all tools to be brought into a transformer

tank.

(6) Spread out clean cloth on coil groups when repairing.

(7) Protect lamps with guards not to break them in a tank.

(8) Be careful not to drop any tool and foreign material into the transformer.

Secure all tools with hand lines. Any metallic item dropped into a

transformer must be removed to prevent serious trouble in future.

4 After inspection

work

(1) Make sure all foreign materials are clear before closing manhole and

energizing.

(2) Check the quantity of all tools brought out from a tank.

(3) Remove the grounding wires on the line terminals of the transformer.

Note:When test and remedial work must be carried out under the live conditions for any special reasons,

pay

attention to live parts to protect yourself against electrical shock.

Page 19: 3. Maintenance Manual_TD-TSP-0004-2A.docx

TD-TSP-0004-2A (19/19)

APPENDIX II Technical information to be sent to the manufacturer

Whenever you need technical advice for any troubles of parts and/or a transformer itself from Shihlin Electric

Corporation, you are kindly requested to let us know the following technical information.

(1) Name of the power station or sub-station where the transformer is in service

(2) Serial number and ratings of the transformer in trouble

(3) Name, type and serial number of the parts in trouble

(4) Detailed explanation in case of more severe troubles

a. Duration and amperes of over current

b. Overvoltage and/or surge applied on the transformer

c. Protective relays in operation

d. Load conditions (voltage, current and power factor)

e. Copies of p/s or s/s layout drawings which show location of the transformer and other electrical

equipment such as circuit-breakers, lightning arresters and line switches

f. Copies of skeleton sequence drawings for control panels

(5) Any other information available about the trouble

Your quick and detailed information is being expected, which would result in quick and more

appropriate actions for its recovery.