    TESTING OF RELZ 100 RELAYWITH

    F6150 & F6TEST SOFTWAREKAMIN DAVE (RELAY APPLICATION ENGINEER)

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    2/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    RELAY INFORMATION:

    Features:Simultaneous phase-phase and phase- earth loop impedance measurement, withindividual numerical measuring elements for each type of fault and each distancezone, ensures fast and reliable fault detection.

    Minimum operating time: 13 ms

    Typical operating time of impedance measuring function: 28 ms.

    Multiprocessor design guarantees high availability together with excellent possibiliesfor combining optional functions.

    Numerical filtering and measuring technique ensure correct performance during CTsaturation and CVT transients.

    Versatile local human machine communication (HMC) from the relay front paneltogether with two optional serial ports brings REL 100 close to the any user whereverthey may be located (in the substation, in the control centre or in the office).

    Basic version of REL 100 includes:three forward and one reverse distance zones with individual setting of reach inreactive and resistive direction as well setting of earth return compensating factor.

    switch onto fault protection.

    three-phase tripping.

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    3/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    Distance Protection:

    ----- Typical Operating Time = 28ms

    ----- Minimum Operating current = 0.2*Ir

    ----- Reset Time:Forward = 40msReverse = 60ms

    ----- Tripping mode: Three Phase / Single Phase tripping

    ----- Number of Zones: 3-forward / 1-reverse

    ----- Impedance Setting Range at Ir = 1.0AReactive reach = (0.1 150)Ohms/PhaseResistive reach:- Phase Phase = (0.1 150)Ohms/Phase- Phase Loop = (0.1 150)Ohms/Phase

    ----- Setting range of Timer = (0 10)s

    ----- Power Swing detection element: (0.1 150)Ohms

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    4/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    RELAY SETTINGS:

    CLIENT: RELIANCE ENERGY LTD-DAHANU

    SERVICE SETTING:

    ZONE:-1- EARTH FAULT UNIT:

    R1 = 15.02 OHMX1 = 15.99 OHMKN = 0.59t1 = 0ms

    PHASE FAULT UNIT:R1 = 3.85 OHM

    X1 = 15.99 OHMt1 = 0ms

    ZONE:-2 - EARTH FAULT UNIT:

    R2 = 20.4 OHMX2 = 22.41 OHMKN = 1.12t2 = 400ms

    PHASE UNIT:

    R2 = 4.8 OHMX2 = 22.41 OHM

    t2 = 400ms

    ZONE:-3 - EARTH FAULT UNIT:

    R3 = 23.81 OHMX3 = 43.97 OHMKN = 0.59t3 = 750ms

    PHASE UNIT:

    R3 = 7.97 OHMX3 = 43.97 OHMt3 = 750ms

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    5/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-1SELECT DATABASE OF RELZ100

    DOUBLE CLICK ON RELZ100

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    6/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-2HOW TO SET RELAY CHARACTERISTIC FOR TEST?

    SINGLE CLICK ON RELAY PARAMETERS

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    7/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-3OPEN EXISTING DATABASE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    8/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-4Modify your settings in Existing database

    Select zone & Press Modify button

    SELECT GENERAL & ENTER KN VALUE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    9/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-5READY MADE SHAPES ARE OPEN

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    10/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-6SINGLE CLICK ON QUAD 2 SHAPE & ENTER RELAY PARAMETERS

    ENTER R VALUE

    ENTER X VALUE & PUT ANGLE = 90 DEG.ENTER VALUES OF DIRECTIONAL LINES

    PRESS OK BUTTON & SAVE IT.

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    11/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-7

    ENTER TOLERANCES & CLOSE WINDOW

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    12/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    HOW TO ENTER IN TESTPLAN FOR TEST?

    STEP:-1SINGLE CLICK ON TESTPLAN TAB

    DOUBLE CLICK ON TEST PLAN

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    13/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-2

    NOW, TEST PLAN IS OPEN

    SELECT Z-CHAR MODULE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    14/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-3

    SINGLE CLICK ON TEST ELEMENTS

    SELECT FUNCTION NAME

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    15/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-4

    SELECT TEST METHOD CONSTANT-I, V or Z

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    16/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-5

    SELECT TRIGGER

    SELECT TRIGGER (Say, Open to Close)

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    17/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-6

    SINGLE CLICK ON TEST LINES

    SELECT ANY ONE OPTION FOR TEST;1) RADIAL LINES2) User Drawn Lines

    ENTER ANGLE BOUNDARY WITH DELTA STEP

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    18/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-7SINGLE CLICK ON TEST TAB

    SELECT FAULT TYPE

    RIGHT CLICK IN BOX; IT SHOWS ONLINE VECTOR & MEASUREMENT

    NOW, APPLY RUN COMMAND FOR TEST.

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    19/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TESTED CHARACTERISTIC ON AB FAULT

    BLUE COLOR SHOWS EXPECTED CHARACTERISTIC

    RED & GREEN POINT SHOWS; ACTUAL OPERATING POINTS

    Dotted line shows tolerances

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    20/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TEST RESULTS OF AB FAULT

    TEST VOLTAGE & CURRENT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    21/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    SELECT BC FAULT FOR TEST

    SELECT BC FAULT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    22/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TESTED CHARACTERISTIC ON BC FAULT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    23/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TEST RESULTS OF BC FAULT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    24/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    SELECT AN FAULT

    SELECT AN FAULT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    25/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TESTED CHARACTERISTIC OF AN FAULTS

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    26/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    TEST RESULTS OF AN FAULT

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    27/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    (B) TIME TEST:STEP:-1

    SELECT Z-TIME MODULE & DOUBLE CLICK ON TIMER TEST

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    28/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-2SINGLE CLICK ON TEST POINTS

    ADD POINT TO LIST BY MOUSE CLICKING ON R-X PLANE

    SELECT FAULT TYPE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    29/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    STEP:-3SELECT FAULT TYPE (Say, AB)

    SELECT FAULT TYPE

    SELECT OPTION R-X PLANE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    30/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    DOBLE ENGINEERING PVT LTD

    SAME RESULT IN Z-T PLANE

    SELECT Z-T PLANE

  • 8/6/2019 303.Testing of Relz100 With f6150-Distpro

    31/31

    India

    Knowledge Is PowerSM

    Apparatus Maintenance and Power

    Management For Energy Delivery

    THANK YOUDOBLE ENGINEERING PVT LTD