380kV CT-VT Calculation C4 Rev D 17.12.09

Embed Size (px)

Citation preview

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    1/137

    380kV CT/VT SIZING CALCULATION

    For Evaluation Only.Copyright (c) by VeryPDF.com IncEdited by VeryPDF PDF Editor Version 2.6

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    2/137

    PROJ ECT:

    ABU-HADRIYAH

    380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    INDEX

    SR. NO. SHEET NO.

    1.0 1

    1.1 1

    1.2 1

    1.3 2

    2.0 3

    2.1 3

    2.2 5

    2.3 12

    2.4 14

    2.5 15

    2.6 16

    2.7 20

    2.8 24

    2.9 25

    2.10 31

    2.11 34

    2.12 35

    2.13 35

    2.14 36

    2.15 36

    2.16 37

    2.17 38

    2.18 39

    2.19 40

    2.20 40

    2.21 41

    2.22 41

    CT: 810 B1.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522)

    CT: 810 B1.C4 :- METERING

    CT: 810 F.C2 :- BUS-BAR PROTECTION MAIN-2 (MFAC14)

    CT: 810 F.C1 :- BUS-BAR PROTECTION MAIN-1 (MCAG 14)

    CT: 811 B2.C4 :- METERING

    CT: 811 B1.C1 :- BF PROTECTION (RAICA)

    CT: 811 B1.C2 :- OHL FEEDER SET-1 PROTECTION (RED 670)

    CT: 811 B1.C3 :- OHL FEEDER SET-2 PROTECTION (MiCOM P546)

    CT: 811 B1.C4 :- METERING

    CT: 810 F.C3 :- SPARE

    DESCRIPTION

    GENERAL DESIGN CRITERIA FOR CT CALCULATION

    SYSTEM DESIGN DATA

    CT: 811 B2.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522)

    DESIGN BASIS AND REFERENCES FOR CT CALCULATION

    CT LEAD RESISTANCE CALCULATION

    CT CALCULATION FOR THE FOLLOWING CT's.

    CT: 810 B1.C1 :- BF PROTECTION (RAICA)

    CT: 810 B1.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531)

    CT: 812 B2.C1 :- BF PROTECTION

    CT: 811 B2.C2 :-OHL FEEDER SET-1 PROTECTION (REL 531)

    CT: 811 B2.C1 :- SPARE

    CT: 812 F.C1 :- BUS-BAR PROTECTION MAIN-1 (MCAG 14)

    CT: 812 F.C2 :- BUS-BAR PROTECTION MAIN-2 (MFAC14)

    CT: 812 F.C3 :- SPARE

    CT: 812 B2.C4 :- METERING

    CT: 812 B2.C3 :- OHL FEEDER SET-2 PROTECTION (7SA522)

    CT: 812 B2.C2 :- OHL FEEDER SET-1 PROTECTION (REL 531)

    BAY NUMBER: CROSS BAY C4

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    3/137

    PROJ ECT:

    ABU-HADRIYAH

    380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    3.00 42

    47

    49

    LINE VT SIZING CALCULATION

    BUS-1 VT SIZING CALCULATION

    ATTACHMENTS:

    ANNEXURE-1 CT REQUIREMENT OF RELAY

    ANNEXURE-2 VA REQUIREMENT OF RELAY

    BUS-2 VT SIZING CALCULATION

    ANNEXURE-4A 380kV GIS DATA SCHEDULE FROM AREVA

    ANNEXURE-5 MANIFA SUBSTATION ELECTRICAL LAYOUT

    ANNEXURE-6 380kV RELAYING & METERING ONE LINE DIAGRAM

    ANNEXURE-9 M&I METROSIL CATALOGUE

    ANNEXURE-3 SAUDI CABLE CATALOGUE

    ANNEXURE-4 380kV GIS CT DATA FROM AREVA

    ANNEXURE-7 LINE PARAMETER

    ANNEXURE-8 380kV CVT DATA SCHEDULE

    BAY NUMBER: CROSS BAY C4

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    4/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    1.0 GENERAL DESIGN CRITERIA FOR CT SIZING CALCULATION

    1.1 System Design Data:

    1.1.1 380kV

    1.1.2 > 17 (As per 32-TMSS-02, sh. No. 31 of 53, Annexure-4A)

    1.1.3 63000 Amps

    1.1.4 63000 Amps

    1.1.5 63kA (As per 32-TMSS-02, sh. No. 31 of 53, Annexure-4A)

    1.2 DESIGN BASIS AND REFERENCES FOR CT CALCULATION :

    1.2.1 CT secondary excitation limiting emf and other parameters of CT's are calculated

    at adopted tap setting, as shown in relaying & metering one line diagram.

    1.2.2 Lead length considered is 500 meters including safety margin.

    Refer to the attached Abuhadriyah substation electrical layout (dwg. No. EA-009912).

    Refer Annexure 5 sheet 2.

    Thus we have ensured that assumed 500m length is not exceeded by any actual length.

    500m is also used as basis for any future modifications for normal S/S life time of 35years.

    1.2.3 Safety margin of 20% is considered for protection class CT and 25% for metering class CT in the formulae

    for CT calculation as a general and where-ever applicable relay manufacturer's recommendation is followed.

    1.2.4 CT specification is considered as per PTS 07EN307 part'F', Appendix-VII and GIS vendor data.

    1.2.5 Zs (source Impedance) is calculated based on CB Interrupting capacity. The Line Impedance value will be added

    to Zs to derive the fault current (PF & EF) at zone1 end for CT excitation limiting EMF calculation. Only one way

    is considered for PF zone1 Ual calculation and 2 way CT lead length is considered for EF zone1 Ual calculation.

    CT Calculation for close in fault is done for 3 phase fault level 63kA.

    We also have assumed 3km long line in view of any future modifications in the 380kV system,

    1.2.6 Annexure-1: CT requirement of relay

    Annexure-2: VA burden requirement of relay

    Annexure-3: Saudi cable catalogue for CT lead resistance calculation

    Annexure-4: CT data from 380kV GIS vendor (TOSHIBA)

    Annexure-4A: Data Schedule for 380kV GIS

    Annexure-5: Abu-hadriyah substation electrical Layout drawing for CT/VT cable route length (dwg. No. EA-009912)

    Annexure-6: 380kV Relaying & Metering one line diagram for cross bay C4.

    Annexure-7: Line parameters

    Annexure-8: 380kV GIS Data schedule-CCVT

    Annexure-9: M&I Metrosil catalogue

    Design Fault level (CB Interr. capacity)

    System Voltage in kV

    380kV system X/R Ratio

    380kV Maximum 3 pahse fault level

    380kV Maximum P-E fault level

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    1 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    5/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    1.3 CT LEAD RESISTANCE CALCULATION :

    CT secondary lead size considered is 6 sq.mm.

    6 sq.mm copper cable resistance at 200C is 3.08 ohms/km.i.e Rdc at 20

    0C = 3.08 ohm/km (Refer Annexure-3)

    Rdc at 75C = R20(1+20(T2-T1)); at 20C = 0.004,Where = temperature co-efficient of resistance.

    Hence, Rdc at 75C = 3.08(1+0.004(75-20));

    = 3.76 ohm/km

    Consider a distance from 380kV GIS CT to relay panel as per layout attached with considerable

    (Refer Annexure-5)safe margin = 500 meter, Lead resistance calculated is,

    = 3.76 x 0.5

    = 1.88 ohms for 500 meters

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    2 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    6/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.0 CT CALCULATION AS PER RELAY/INSTRUMENT MANUFACTURER'S RECOMMENDATION

    2.1 CT: 810 B1.C1

    Protection : BF protection (50BF)

    Core : CT: 810 B1.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : CB Fail Protection (50BF)

    Relay Type / Make: "RAICA", ABB,(50BF)

    CT CALCULATION:

    2.1.1 CT Vk requirement:

    For 2000 A

    Vk Knee point voltage

    I P = Nominal ( rated) CT primary Current = 2000 amps

    T = Turn ratio = 1/2000

    I s = Nominal ( rated) CT secondary Current = 1 amps

    I F = Maximum short circuit current = 63000 amps

    IFsec = CT Secondary short circuit current in Amps. = 31.5 amps

    RCT = Internal CT secondary resistance = 3.1 ohms

    RL = Lead Resistance =2 L x Rpkm / 1000 = 1.88 ohms

    RL = Lead resistance of cable. = 1.88 Ohms

    For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL= 1.88 ohms.

    Consider length of cable = 500 meters.

    RRAICA= Relay Burden (Refer Annexure-2, Sh. No. 6) = 0.15 VA

    RRAICA= Relay resistance = RB/ Is2

    = (0.15/12) = 0.15 ohms

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    3 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    7/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Note:

    Maximum Relay burdens occur for 1ph-G fault when both phase & ground BFP O/C relay units are in series.

    2x BFP Relay Fault Detectors = 0.30 Ohms

    Total= 0.30 ohms Ground o/c relay [1ph-G loop]

    0.15 ohms phase o/c relay [3ph]

    BFP fault detectors come once main protection operates & initiate BFP. Worst case relay operation (fatest)

    is cycle & hence @ maximum peak during fully offset.

    CT Requirement considering 20% margin.

    General formulae:

    Vkrequired > 1.2xOffset for DC x Ifsecondaryx (Connected burden)

    Vkrequired > 1.2x2xIf x ( RCT+ 2RL+ 2x(RRAICA ))

    > 1.2x2x31.5 x ( 3.1 + 3.76 + 2x(0.15))

    > 541.296 Volts

    Since CT rated knee point voltage is 3700V which is greater than 541.3 volts, CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    4 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    8/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.2 CT: 810 B1.C2

    Protection : OHL feeder protection Set-1 (87L-1,21-1)

    Core : CT: 810 B1.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection Set-1 (87L-1,21-1)

    Relay Type / Make: "REL 531", ABB

    2.2.1 Line Data: (Refer Annexure-7 attached)

    Line length as per annexure attached = 44.485 km (Annexure-7)

    Line parameter for Abu-hadriyah Al-fadhili line. Refer Annexure-7 for Line parameters.

    Z1 = 0.00054+j 0.0098 p.u Base MVA 100

    Z0 = 0.00645+j 0.03112 p.u Base kV = 380

    Base Impedance calculated = (BasekV2) = 1444 ohms

    Base MVA

    Base Current calculated = (Base MVA) = 151.9 amps

    3 x Base kV

    Zline in ohms calculated; R1= 0.794 ohms

    (Base Impedance x p.u Impedance) X1= 14.15 ohms

    R0= 9.314 ohms

    X0= 44.94 ohms

    X/R = 17 Phase volt.= 219393.1 Volts

    sin(tan-1(X/R)) = 0.998 Phase Curr.=63000 Amperes

    cos(tan-1(X/R)) = 0.059

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    5 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    9/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.2.2 Source impedance:

    Xs = (Ph vol/Ph cu)xsin(tan-1

    (X/R)) Rs = (Ph vol/Ph cu)xcos(tan-1

    (X/R))

    = 380000 x sin(tan-1

    (X/R)) = 380000 x cos(tan-1

    (X/R))

    Sqrt.(3)x63000 Sqrt.(3)x63000

    = 3.48 ohms = 0.20 ohms

    Z s = 0.2 + j 3.48 ohms

    2.2.3 Line impedance:

    X1 full Line: Line length x Reactance value/km X0 full Line: Line length x Reactance value/km

    = 14.1512 ohms = 44.93728 ohms

    R1 full Line: Line length x Resistance value/km R0 full Line: Line length x Resistance value/km

    = 0.7942 ohms = 9.3138 ohms

    Z1 line = 0.7942 + j 14.15 ohms Z0 line = 9.3 + j 44.94 ohms

    2.2.4 THREE PHASE FAULT CONDITION

    Close in Fault

    Fault current = 63 kA

    X/R = 17

    Source Imp. Z1=Z2=Z0 0.2 + j 3.48 ohms

    Through fault current at the end of the line:

    For 44.485 Km line

    Impedance calculated : (Rs + R1) + j(Xs+X1)

    (Positive sequence) = (0.2+0.794) + j (3.48+14.15)

    = 0.994+j17.63 ohms

    ZT1 = 17.66 ohms

    Phase fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x17.63

    = 12424.57 Amps

    Phase fault X/R = 17.63

    0.994

    = 17.74

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    6 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    10/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Fault current calculation at the end of zone1 fault i.e 80% of line length:

    For 44.485 Km line

    Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)

    (Positive sequence) = (0.2+0.635) + j (3.48+11.32)

    = 0.84+j14.8

    ZT1 = 14.82 ohms

    Phase fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x14.82

    = 14800.04 Amps

    Phase fault X/R = 14.82

    0.835

    = 17.75

    2.2.5 SINGLE PHASE-GROUND FAULT CONDITION:

    Through fault current at the end of the line:

    For 44.485 Km line

    Impedance calculated : (3Rs+2R1+R0) +

    (Loop Impedance) j(3Xs+2X1+X0)

    = 11.5+j83.79 ohms

    ZT1 = 84.39 ohms

    Earth fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x84.39

    I0 = 2599.62 Amps

    Earth fault X/R = 83.79

    11.5

    = 7.29

    3I0 = 7798.87 Amps

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    7 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    11/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    12/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Itfdb = Maximum Primary fault current for external faults (A) = 63000 amps

    I pn = Nominal ( rated) CT primary Current = 2000 amps

    I sn = Nominal ( rated) CT secondary Current = 1 amps

    RCT = CT secondary winding resistance = 3.1 ohms

    RB = = 0.25 ohms

    RL = Lead resistance of cable.

    For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL 1.88

    Consider length of cable = 500 meters. 2RL = 3.76 ohms

    I r = = 1 amps

    f = = 60 Hz

    Imin Sat=

    X/R = = 17

    Tp = Primary time constant, (L/R)

    L/R = (X/(2x 3.14x f )/R

    .= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec

    RTFR= Burden value for TFR (Refer Annexure-2,Sh. No.7) = 0.01 VA

    Hence, total VA burden including TFR. = 0.26 VA

    Voltage developed across CT as per ABB relay catalogue.

    At 2000/1 A tap

    Considering 20% margin

    Eal > Ealreq = {I kmaxx I sn} / Ipn x 0.5 x (RCT + RL + SR / Ir 2 ) Equation-1

    As per REL 531 relay requirement, the factor 0.5( for Tc less than 120ms) is replaced with 0.53 & 0.54

    for primary time constant of 200ms and 300ms respectively.

    Ealreq = 63000 x 1 x 0.5 x ( 3.1+ 1.88 + 0.27/1^2 ) = 82.5 volts

    2000

    With 20% extra margin Ealreq = 99.0 volts

    Sat saturation detector min current

    Burden of relay

    Protection terminal rated Current

    System ratio

    System Frequency

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    9 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    13/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Eal > Ealreq = 2 x {Ikmaxx I sn} / Ipn x (RCT + RL + SR / Ir2

    ) Equation-2

    As per REL 531 relay requirement, the factor 2 ( for Tc less than 120ms) is replaced with 2.32 & 2.5

    for primary time constant of 200ms and 300ms respectively.

    Ealreq = 63000 x 1 x 2 x ( 3.1+ 1.88 + 0.27/1^2 ) = 330.1 volts

    2000

    With 20% extra margin Ealreq = 396.1 volts

    Eal > Ealreq = 0.12 x f x Isn x (RCT + RL + SR / Ir2

    ) Equation-3

    Ealreq = 0.12 x 50 x 1x(3.1+ 1.88 +0.27/12

    ) = 31.4 volts

    With 20% extra margin Ealreq = 37.7 volts

    Eal > Ealreq = (Imin sat x CT factor x Ir) / 100 x (RCT + RL + SR / Ir 2 ) Equation-4

    Ealreq = 500 x 1 x 1x(3.1+ 1.88 +0.27/12

    ) = 26.2 volts

    100

    With 20% extra margin Ealreq = 31.4 volts

    Since CT rated knee point voltage is 3700V which is greater than the required value,

    the proposed CT is adequate.

    The Voltage developed across the CT secondary for distance protection (21L) feature as per

    ABB catalogue. (Refer Annexure-1 Sh. No. 22 )

    Requirement -1

    At 2000/1 A tap

    Eal > Ealreq = {I kmaxx I sn} / Ipn x a x (RCT + RL + SR / Ir2

    ) Equation-5

    a' = 2 for primary time constant less than 50msec.

    With 20% extra margin

    Ealreq = 63000 x 1.2 x 2 x ( 3.1+ 1.88 + 0.27/1^2 ) = 538.3 volts

    2000

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    10 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    14/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Requirement -2

    Eal > Ealreq = Ikzone1x 7 x (Isn / Ipn) x (RCT + RL + SR / Ir2

    ) Equation-6

    k' = 7 for primary time constant greater than 30 msec.

    Ikzone1= Maximum primary fundamental fault current at the end of zone 1 reach.

    Considering 80% of actual line length = 14800.04 Amps

    (Refer above fault current calculation at the end of zone1 reach considering actual line length)

    At 2000/1 A tap and with 20% extra margin

    Ealreq = 14800 x 1.2 x 7 x ( 3.1+ 1.88 +0.27/12

    ) = 442.58038 volts

    2000

    Since CT rated knee point voltage is 3700V which is greater than the required value,

    the proposed CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    11 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    15/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.3 CT: 810 B1.C3

    Protection : OHL feeder protn. -Set-2 (87L-2,21-2)

    Core : CT: 810 B1.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection - Set-2 (87L-2,21-2)

    Relay Type/make : ''7SA522 ", Siemens.

    2.3.1 CT Calculation

    Where For 2000 amps

    Vk = Knee point voltage of CT 3700 Volts

    RB = Resistance of relay 7SA522 = 0.05 ohms

    Rr = Relay resistance

    RCT = CT secondary winding resistance = 3.1 ohms

    RL = Lead resistance of cable.

    For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL = 1.88 ohms

    Consider length of cable = 500 meters. 2RL= 3.76 ohms

    I P = Nominal ( rated) CT primary Current = 2000 amps

    I S = Nominal ( rated) CT secondary Current = 1 amps

    ISCC max= Maximum short circuit current-Three phase = 63000 amps

    VK CT knee point voltage specified = 3700 volts

    X/R = System ratio = 17

    I f = Maximum value of through fault current for

    stability ( multiple of Is) = I SCC max/ IP = 31.50

    ( I f )x( X/R) = 535.5

    Tp = Primary time constant, (L/R)

    L/R = (X/(2x 3.14x f )/R

    .= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    12 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    16/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    The CT should meet the following Vk requirement as per Siemens publication.

    ( Refer Annexure-1 Sh. No. 24 )

    Vk1 > {Ktd(a)xIssc max(close-in fault)/1.3xIpn} x Isn x (RB + RCT +RL) For close-in fault

    Vk2 > {Ktd(b)xIssc max(zone-1 end fault)/1.3xIpn} x Isn x (RB + RCT +RL) For zone-1 end fault

    Ktd(a) = 2' for primary time constants less than 50ms

    Ktd(b) = 5' for primary time constants less than 50ms

    Vk1 = Accuracy limiting voltage for close in fault in volts

    Vk2 = Accuracy limiting voltage for end of zone 1 line fault in volts

    IFZ1 = Maximum secondary fault current for end of zone 1 fault in amps.

    Considering actual line length as a worst case, primary fault current (A) calculated is equal 14800.04

    Amps. Hence, CT secondary fault current = 14800.04

    2000

    = 7.40 Amps.

    RB = Relay burden

    CT requirement for close-in fault condition:

    Vk1 > {Ktd(a)xIssc max(close-in fault)/1.3xIpn} x Isn x (RB + RCT +RL)

    = {2 x 63000/1.3x2000} x (0.05 + 3.1 + 1.88) = 244 volts

    Vk 2with 20 % margin = 293 volts

    Peak voltage = 413.7 Vpeak

    CT requirement for zone1 fault condition:

    Vk2 > {Ktd(b)xIssc max(zone-1 end fault)/1.3xIpn} x Isn x (RB + RCT +RL)

    = {5 x 14800/1.3x2000} x (0.05 + 3.1 + 1.88) = 143 volts

    Vk 2with 20 % margin = 172 volts

    Peak voltage = 243.0 Vpeak

    Since CT rated knee point voltage is 3700V which is greater than the required value,

    the proposed CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    13 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    17/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.4 CT: 810 B1.C4

    Protection : Metering

    Core : CT: 810 B1.C4

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : 0.2

    VA Burden 50 VA

    Thermal rating factor 200%

    Application : Metering

    Burden Calculation (Refer Annexure-2)

    a LCP

    Ammeter 0.5 VA (Assumed)

    b Revenue metering panel

    ABB, ALPHA A3R 1E-04 VA ( Refer Annexure-1 Sh. No. 18 )

    c Mosaic panel

    Watt transducer, , AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )

    Var transducer, AREVA, ISTAT300 1 VA ( Refer Annexure-1 Sh. No. 13 )

    Watt meter, PML ION6200 0.5 VA (Assumed)

    Var meter PML ION6200 0.5 VA (Assumed)

    d DSM 0.1 VA (Assumed)

    Cabling loop (500 meters)

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1));

    Consider length of wire = 500 meters. RL = 2.812 Ohms

    2RL = 5.624 VA

    Total connected burden, PBC = 9.224 VA

    Considering 25% safe margin, connected VA equals to= 11.53 VA

    CT Rated burden = 50VA

    The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    14 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    18/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.5 CT: 810 F.C3

    Protection : Spare

    Core : CT: 810 F.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : Spare

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    15 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    19/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.6 CT: 810 F.C2

    Protection : Bus-bar protection (87M2)

    Core : CT: 810 F.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    NOTE:

    Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)

    are shown below.

    Protection : Bus-bar protection (87M2)

    Core : Core 2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : Bus-Bar Protection-Main-2 (87M2)

    Relay Type / Make: "MFAC14", AREVA (Setting range: 25V-325V)

    2.6.1 CT Calculation

    The setting voltage is determined by the following relationship. (Refer Annexure-1, Sh. No.11)

    Vs > 1.2 x If x ( RCT+ 2 x RL) (20% additional margin is taken)

    Where For 3000

    IP = Nominal ( rated) CT primary Current 3000 amps

    I S = Nominal ( rated) CT secondary Current 1 amps

    IF = Maximum Fault Current = 63000 amps

    If = CT secondary fault current = 21 amps

    RCT = Internal CT secondary resistance 4.65 ohms

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    16 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    20/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    RL = Lead resistance of cable. = 1.88 Ohms

    For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL = 1.88 ohms.

    Consider length of cable = 500 meters.

    Vk = Specified knee point voltage = 5550 Volts

    Calculation of relay setting voltage:

    Vs > 1.2 x If x ( RCT+ 2 x RL)

    Vs > 1.2 x 21 x (4.65 + 3.76 )

    Vs > 211.932

    Hence select Vs = 275 Vrms

    Peak voltage = 388.91 Vpeak

    Hence, select a metrosil with setting range 25V- 325V and set at 275 volts.

    2.6.2 Metrosil requirement

    For this relay Metrosil proposed by the manufacturer has the following parameters.

    C = 900

    = 0.25

    The current drawn by metrosil at relay setting voltage is given by formulae below.

    Irms dra = 0.52((2xV')/C))1/

    where V' = voltage in (RMS Sine)

    Metrosil recommended for 25-325V relay range @ 2kVrms

    Irms dra = 0.52x((2x2000)/900)1/0.25

    = 50.72 A rms

    At voltage settingVs = 275V, Metrosil draws about 18mA

    %Error = (0.018 / Ifs ) x 100

    = (0.018 / 21 ) x 100

    = 0.086%

    Error introduce by metrosil at voltage setting Vs = 275V is 0.086% only.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    17 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    21/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Metrosil selection: (Refer Annexure-8)

    To limit voltage to 2kVrms, select metrosil same as recommended by MFAC 14 for Vs = 275V

    C = 900

    = 0.25

    As per M&I materials catalogue attached, for the above 'C' and '' characteristics, the recommended

    metrosil type is 600A/S1/S1088.

    We recommend standard metrosil as per AREVA recommandation only as the relay & scheme is by AREVA.

    CT secondary fault current calculated as above = 21 Amps.

    Hence, Metrosil withstanding capability is greater than CT secondary current.

    2.6.3 Determination of primary fault current setting:

    At 3000/1 A tap

    Taking Primary fault currrent setting as 1% of maximum fault current i.e 63000 Amps.

    1% of bus-bar fault current = 630 amps

    Primary Fault current setting Calculation

    The primary operating current or fault setting calculated as Ip= { n Im+ Ir +IM+IV}xT

    Ip = Primary fault setting

    n = number of CTs in parallel including 3 future bays = 8.0

    Im = exciting current of each CT at the relay circuit setting voltage 0.005 Amps

    RMVTP31= Resistance of CT supervision relay MVTP 31(Assumed) 90000.0 ohms

    IV = Current in MVTP11 relay, (Vs/RMVTP31) 0.003 Amps

    IM = current in metrosil at the relay circuit setting voltage 0.018 Amps

    Ir = Relay operating current as per MFAC manual for setting range 25-325V 0.03 Amps

    Where relay setting voltage is low then current in non linear resistor is ignored.

    Primary fault setting (Ip) = {n Im+ Ir +IM+IV}xT

    = 273.167

    This current is too small as compared to 63kA i.e 0.43% of 63kA.

    It is observed that the primary operating current is less than 630A.

    Hence, an external shunt resistor (Rsh) needs to be connected inorder to get a primary operating current 630A.

    Select shunt resistor to get primary operating current of say 742 Amps.

    Ip = { nIe+ Ir +IM+(Vs/Rsh)+IV}xT

    742 = {8x0.005+0.03+0.018+(275/Rsh)+0.003} x3000 0.156

    The value of external shunt resistor required is calculated as Rsh = 1759.7 ohms

    As per AREVA MCAG14 catalogue attached Annexure-2 sheet no. 4

    Select a resistor 2700 ohms and set at 1760 ohms with the short time current rating (1 seconds) of 1.3 Amps.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    18 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    22/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.6.4 Shunt resistor Wattage calculation:

    Current in shunt resistor at setting voltage Vs =275 Volts; 275 = 0.16 Amps.

    Shunt resistor Wattage 0.16x0.16x1760 Watts. 1759.7

    45.06 Watts.

    Hence, select a shunt resistor of 50 watts.

    Hence, Primary operating current calculated =

    Primary fault setting (Ip) = {n Im+ Ir +IM+IV+IRsh}T

    = 742.0 Amps.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    19 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    23/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.7 CT: 810 F.C1

    Protection : Bus-bar protection (87M1)

    Core : CT: 810 F.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Iex < 50

    Thermal rating factor 200%

    NOTE:

    Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)

    are shown below.

    Protection : Bus-bar protection (87M1)

    Core : Core 1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : Bus-Bar Protection-Main-1 (87M1)

    Relay Type / Make: "MCAG 14", AREVA (Setting range: 20%-80% of 1A)

    2.7.1 CT Requirement

    Where For 3000 A

    Vk Knee point voltage = 5550 volts

    Vs Setting Voltage

    I P = Nominal ( rated) CT primary Current = 3000 amps

    T = Turn ratio = 1/3000

    I s = Nominal ( rated) CT secondary Current = 1 amps

    I F = Maximum short circuit current = 63000 amps

    If = CT secondary fault current in amps. = 21 amps

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    20 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    24/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    RCT = Internal CT secondary resistance = 4.65 ohms

    RL = Lead resistance of cable. = 1.88 Ohms

    For 6 sq.mm copper cable, RL= 0.00308 ohm/meter at 20C.

    at 20C = 0.004, RLat 75C = RL(1+20(T2-T1)) RL = 1.88 ohms.

    Consider length of cable = 500 meters.

    RB-MCAG Relay Burden = 1.00 VA

    RRMCAG= Relay resistance = RB/ Is2 = 1.00 ohms

    The setting voltage Vs shall be calculated in order to ensure the stability of the protection in

    regard with the maximum through fault current If . The setting voltage is determined by the following eqn.

    Vs > 1.2 x If x ( RCT+ 2 x RL) (Refer Annexure-1, Sh.No.8)

    Vs > 1.2 x 21 x (4.65 + 3.76 )

    Vs > 211.932

    Hence, select Vs same as Main-2 protection 275 Vrms

    Peak voltage = 388.91 Vpeak

    2.7.2 Voltage Llimiting Resistor- Metrosiles: (Refer MCAG 14 sheet attached)

    To establish the requirement for a Metrosil the peak voltage needs to exceed 3kV.

    Hence V rms needs to be exceeded is equal to (Vpk/ root2) = 2.12 kV

    VPK= ( 2 VK ( V f -VK))1/2

    Where VPK= Peak voltage of the voltage wave form.

    Vf = If x Tx(RCT+2RL+Rsr+RRMCAG)

    Where

    V f = Maximum voltage in absence of saturation = 28547.6 volts

    VPK= ( 2x5550x (28547.6- 5550))1/2 = 15977.28 volts

    = 15.98 kVolts

    VPK is 15.98kV which is more than 3kV hence Metrosiles are required.

    Therefore select metrosil to limit the secondary voltage to 3kV peak.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    21 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    25/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Metrosil requirement

    For this relay Metrosil proposed by the manufacturer has the following parameters.

    C = 900

    = 0.25

    The current drawn by metrosil at relay setting voltage is given by formulae below.

    Irms dra = 0.52((2xV')/C))1/

    where V' = voltage in (RMS Sine)

    Metrosil recommended for 25-325V relay range @ 2kVrms

    Irms dra = 0.52x((2x2000)/900)1/0.25

    = 50.72 A rms

    At voltage settingVs = 275V, Metrosil draws about 18mA

    %Error = (0.018 / Ifs ) x 100

    = (0.018 / 21 ) x 100

    = 0.387%

    Error introduce by metrosil at voltage setting Vs = 275V is 0.086% only.

    Metrosil selection: (Refer Annexure-9)

    To limit voltage to 2kVrms, select metrosil same as recommended by MCAG14 for Vs = 275V

    C = 900

    = 0.25

    As per M&I materials catalogue attached, for the above 'C' and '' characteristics, the recommended

    metrosil type is 600A/S1/S1088.

    We recommend standard metrosil as per AREVA recommandation only as the relay & scheme is by AREVA.

    CT secondary fault current calculated as above = 21 Amps.

    Hence, Metrosil withstanding capability is greater than CT secondary current.

    2.7.3 Determination of primary fault current setting:

    Taking Primary fault currrent setting as 1% of maximum fault current i.e 63000 Amps.

    1% of bus-bar fault current = 630 amps

    Primary Fault current setting Calculation

    The primary operating current or fault setting calculated as Ip= { n Im+ Ir +IM+IV}xT

    Ip = Primary fault setting

    n = number of CTs in parallel including 3 future bays = 8.0

    Im = exciting current of each CT at the relay circuit setting voltage 0.005 Amps

    RMVTP31= Resistance of CT supervision relay MVTP 31(Assumed) 90000.0 ohms

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    22 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    26/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    IV = Current in MVTP11 relay, (Vs/RMVTP31) 0.003 Amps

    IM = current in metrosil at the relay circuit setting voltage (Assumed) ' 0.018 Amps

    Ir = Relay setting current 0.20 Amps

    Where relay setting voltage is low then current in non linear resistor is ignored.

    =

    Primary fault setting (Ip) = { n Im+ Ir +IM+IV}xT

    {(8x0.005)+0.2+0.018+0.003}x3000

    = 783.2 Amps.

    2.7.4 Determination of stabilising resistor Rsr: (Refer MCAG 14 Manual attached, Annex-1, Sh. No.10)

    Relay circuit Voltage Vs = 275.00 Volts

    Relay setting current, Is = 0.20 Amps

    Relay burden at 275V setting is considered as 1VA,

    Stabilising resistor required, Rsr = (Vs/Ir) - (Relay burden)/(Ir^2) Rs= 1350.00 ohms

    Select a resistor of range (0 -1500 ohms),0.31A continous,1.36A/3sec,1.8A/1sec as per MCAG 14 Manual.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    23 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    27/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.8 CT: 811 B1.C1

    Protection : CB fail protection

    Core : CT: 811 B1.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : CB Fail Protection (50BF)

    Relay Type / Make: "RAICA", ABB,(50BF)

    CT calculation same as CT: 810 B1.C1. Refer above CT: 810 B1.C1 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    24 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    28/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.9 CT: 811 B1.C2

    Protection : OHL feeder protn. -Set-1 (87L-1,21-1)

    Core : CT: 811 B1.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection Set-1 (87L-1,21-1)

    Relay Type / Make: "RED 670", ABB

    2.9.1 Line Data: (Refer Annexure-7 attached)

    Line length as per annexure attached = 50 km

    Z1 = 0.00055+j 0.0108 p.u Base MVA 100

    Z0 = 0.00545+j 0.0322 p.u Base kV = 380

    Base Impedance calculated = (BasekV2) = 1444 ohms

    Base MVA

    Base Current calculated = (Base MVA) = 151.9 amps

    3 x Base kV

    Zline in ohms calculated; R1= 0.794 ohms

    (Base Impedance x p.u Impedance) X1= 15.6 ohms

    R0= 7.87 ohms

    X0= 46.5 ohms

    X/R = 17 Phase volt.= 219393.1 Volts

    sin(tan-1(X/R)) = 0.998 Phase Curr.=63000 Amperes

    cos(tan-1(X/R)) = 0.059

    2.9.2 Source impedance:

    Xs = (Ph vol/Ph cu)xsin(tan-1

    (X/R)) Rs = (Ph vol/Ph cu)xcos(tan-1

    (X/R))

    = 380000 x sin(tan-1

    (X/R)) = 380000 x cos(tan-1

    (X/R))

    Sqrt.(3)x63000 Sqrt.(3)x63000

    = 3.48 ohms = 0.20 ohms

    Z s = 0.2 + j 3.48 ohms

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    25 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    29/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.9.3 Line impedance:

    X1 full Line: Line length x Reactance value/km X0 full Line: Line length x Reactance value/km

    = 15.5952 ohms = 46.4968 ohms

    R1 full Line: Line length x Resistance value/km R0 full Line: Line length x Resistance value/km

    = 0.7942 ohms = 7.8698 ohms

    Z1 line = 0.7942 + j 15.6 ohms Z0 line = 7.8698 + j 46.5 ohms

    2.9.4 THREE PHASE FAULT CONDITION

    Close in Fault

    Fault current = 63 kA

    X/R = 17

    Source Imp. Z1=Z2=Z0 0.2 + j 3.48 ohms

    Through fault current at the end of the line:

    1) For 50 Km line

    Impedance calculated : (Rs + R1) + j(Xs+X1)

    (Positive sequence) = (0.2+0.794) + j (3.48+15.6)

    = 0.994+j19.08 ohms

    ZT1 = 19.11 ohms

    Phase fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x19.11

    = 11483.02 Amps

    Phase fault X/R = 19.08

    0.994

    = 19.20

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    26 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    30/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Fault current calculation at the end of zone1 fault i.e 80% of line length:

    1) For 50 Km line

    Impedance calculated : (Rs+0.8R1) + j(Xs+0.8X1)

    (Positive sequence) = (0.2+0.635) + j (3.48+12.5)

    = 0.84+j16

    ZT1 = 16.02 ohms

    Phase fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x16.02

    = 13693.21 Amps

    Phase fault X/R = 15.98

    0.835

    = 19.14

    2.9.5 SINGLE PHASE-GROUND FAULT CONDITION:

    Through fault current at the end of the line:

    1) For 50 Km line

    Impedance calculated : (3Rs+2R1+R0) +

    (Loop Impedance) j(3Xs+2X1+X0)

    = 10.08+j88.12 ohms

    ZT1 = 88.69 ohms

    Earth fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x88.69

    I0 = 2473.58 Amps

    Earth fault X/R = 88.12

    10.08

    = 8.74

    3I0 = 7420.73 Amps

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    27 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    31/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Fault current calculation at the end of zone1 fault i.e 80% of line length:

    1) For 50 Km line

    Impedance calculated : (3Rs+0.8x2R1+R0) +

    (Loop Impedance) j(3Xs+0.8x2X1+X0)

    = 8.18+j72.5 ohms

    ZT1 = 72.96 ohms

    Earth fault current = Ph. Volt / Ph. Imp.

    = 380000

    Sqrt.(3)x72.96

    = 3007.03 Amps

    Earth fault X/R = 72.50

    8.18

    = 8.86

    3I0= = 9021.097278 Amps

    2.9.6 CT Requirement : ( As per Annexure-1, Sh. No.2)

    Eal > Ealreq = {I kmaxx I sn} / Ipn x (RCT + RL + SR / Ir2

    ) Equation-1

    Eal > Ealreq = 2 x {I tmaxx I sn} / Ipn x (RCT + RL + SR / Ir2) Equation-2

    Eal > Ealreq = Itfdb x (Isn / Ipn) x (RCT + RL + SR / Ir2

    ) Equation-3

    Where,

    Ikmax = Maximum Primary fundamental frequency fault current for internal close-in faults (A)

    Itfdb = Maximum Primary fundamental frequency fault current for external faults (A) that

    passes through two CT's (A).

    Here for one and half breaker scheme Ikmax is equal to Itfdb.

    Ipn = The rated primary CT current (A)

    Isn = The rated secondary CT current (A)

    Ir = The rated current of the protection IED (A)

    SR = The burden of IED 670 a current input channel (VA). SR = 0.25 VA/channel.

    Where, For 2000 amps

    Ealreq=

    Eal = = 3700 volts

    I K max= Maximum short circuit current-Three phase = 63000 amps

    Itfdb = Maximum Primary fault current for external faults (A) = 63000 amps

    I pn = Nominal ( rated) CT primary Current = 2000 amps

    Required secondary e.m.f.

    Rated equivalent secondary e.m.f.= Vk

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    28 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    32/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    I sn = Nominal ( rated) CT secondary Current = 1 amps

    RCT = CT secondary winding resistance = 3.1 ohms

    RB = = 0.25 ohms

    RL = Lead resistance of cable.

    For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL 1.88

    Consider length of cable = 500 meters. 2RL = 3.76 ohms

    I r = = 1 amps

    f = = 60 Hz

    Imin Sat=

    X/R = = 17

    Tp = Primary time constant, (L/R)

    L/R = (X/(2x 3.14x f )/R

    .= ( 17 / 2x 3.14x 60) x 1000 = 45.09 msec

    RTFR= Burden value for TFR (Refer Annexure-2,Sh. No.7) = 0.01 VA

    Hence, total VA burden includong TFR = 0.26 VA

    Voltage developed across CT as per ABB relay catalogue (Refer Annexure-1 Sh. No.2 )

    At 2000/1 A tap

    Considering 20% margin

    Eal > Ealreq = {I kmaxx I sn} / Ipn x (RCT + RL + SR / Ir2

    ) Equation-1

    Ealreq = 63000 x 1 x ( 3.1+ 1.88 + 0.26/1^2 ) = 224.3 volts

    2000

    With 20% extra margin Ealreq = 269.1 volts

    Eal > Ealreq = 2 x {I tmaxx I sn} / Ipn x (RCT + RL + SR / Ir2

    ) Equation-2

    Ealreq = 63000 x 1 x 2 x ( 3.1+ 1.88 + 0.26/1^2 ) = 448.6 volts

    2000

    With 20% extra margin Ealreq = 538.3 volts

    System Frequency

    Sat saturation detector min current

    System ratio

    Burden of relay

    Protection terminal rated Current

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    29 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    33/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    At 2000/1 A tap

    Eal > Ealreq = Itfdb x (Isn / Ipn) x (RCT + RL + SR / Ir2

    ) Equation-3

    Ealreq = 63000 x 1x(3.1+ 1.88 +0.26/12

    ) = 224.3 volts

    2000

    With 20% extra margin Ealreq = 269.1 volts

    Since CT rated knee point voltage is 3700V which is greater than the required value,

    the proposed CT is adequate.

    The Voltage developed across the CT secondary for distance protection (21L) feature as per

    ABB catalogue. (Refer Annexure-1 Sh. No. 3 )

    Requirement -1

    At 2000/1 A tap

    Eal > Ealreq = {I kmaxx I sn} / Ipn x a x (RCT + RL + SR / Ir2

    ) Equation-5

    a' = 2 for primary time constant less than 50msec.

    With 20% extra margin

    Ealreq = 63000 x 1.2 x 2 x ( 3.1+ 1.88 + 0.26/1^2 ) = 538.3 volts

    2000

    Requirement -2

    Eal > Ealreq = Ikzone1x k x (Isn / Ipn) x (RCT + RL + SR / Ir2

    ) Equation-6

    k' = 6 for primary time constant greater than 30 msec.

    Ikzone1= Maximum primary fundamental fault current at the end of zone 1 reach.

    At 2000/1 A tap and with 20% extra margin

    Ealreq = 13693.21 x 1.2 x 6 x ( 3.1+ 1.88 +0.26/12

    ) = 350.98 volts

    2000

    Since CT rated knee point voltage is 3700V which is greater than the required value,

    the proposed CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    30 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    34/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.10 CT: 811 B1.C3

    Protection : OHL feeder protn. -Set-2 (87L-2,21-2)

    Core : CT: 811 B1.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection - Set-2 (87L-2,21-2)

    Relay Type/make : ''MiCOM P546", Areva.

    2.10.1CT Calculation

    Where For 2000 amps

    Vk = Knee point voltage of CT 3700 Volts

    RB = Resistance of relay P543 = 0.04 ohms

    Rr = Relay resistance

    RCT = CT secondary winding resistance = 3.1 ohms

    RL = Lead resistance of cable.

    For 6 sq.mm copper cable, RL= 3.08 ohm/kmeter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1)) RL = 1.88 ohms

    Consider length of cable = 500 meters. 2RL= 3.76 ohms

    I P = Nominal ( rated) CT primary Current = 2000 amps

    I S = Nominal ( rated) CT secondary Current = 1 amps

    ISCC max= Maximum short circuit current-Three phase = 63000 amps

    VK CT knee point voltage specified = 3700 volts

    X/R = System ratio = 17

    I f = Maximum value of through fault current for

    stability ( multiple of Is) = I SCC max/ IP = 31.50

    ( I f )x( X/R) = 535.5

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    31 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    35/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    The CT should meet the following Vk requirement as per Areva publication.

    ( Refer Annexure-1 Sh. No. 5 - 6 )

    Vk1 > K xI n x (RB + RCT +RL) (equation -1) for through fault condition

    Vk2 > KRPAxIFZ1x (1+X/R)x(RB + RCT +RL+Rr) (equation -2) for zone1 fault condition

    Vk3 > Kmax x IFmaxx (RB + RCT +RL+Rr) (equation -3) for close-up fault

    Vk1 = Accuracy limiting voltage for line through fault condition in volts

    Vk2 = Accuracy limiting voltage for end of zone 1 line fault in volts

    Vk2 = Accuracy limiting voltage for close in fault in volts

    IFZ1 = Maximum secondary fault current for end of zone 1 fault in amps.

    For 50kM line length , primary fault current (A) calculated is equal to = 13693.21

    Amps. Hence, CT secondary fault current = 13693.21

    2000

    = 6.85 Amps.

    KRPA = Fixed dimensioning factor for zone 1 fault and always = 0.6 (Refer Annex-1, Sh. No. 7)

    Kmax = Fixed dimensioning factor for close in fault and always = 1.4 (Refer Annex-1, Sh. No. 7)

    RB = Relay burden

    Where K is dimensioning factor and depends upon the maximum value of through fault current(as a multiple of In)

    and primary system X/R ratio.

    For three end current differential schemes relay set at Is1=20%, Is2=2In, K1=30% and K2=100%,

    K' is calculated as below. (Refer Annex-1, Sh. No. 6)

    For through fault condition the fault current and X/R calculated above are

    IF = 11483.02 Amps. (Primary); X/R = 19.20

    CT secondary fault currect calculated = 5.74

    If x X/R = 110.24

    If, If x X/R < 1000xIn,

    K> 40 + 0.35 x (If x X/R)

    K> 40 + 0.35x(110.24)

    K> 78.584

    As per AREVA relay catalogue, K > 78.584

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    32 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    36/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    CT requirement for through fault condition:

    Vk = K x I n x ( RB+ RCT +2RL )

    .= 78.584 x 1 x ( 0.04 + 3.1 + 3.76 ) = 542 volts

    Vk with 20 % margin = 651 volts

    Peak voltage = 920.2 Vpeak

    CT requirement for zone1 fault condition:

    Vk2 > KRPAxIFZ1x (1+X/R)x(RB + RCT +RL+Rr)

    = 0.6 x6.85 x (1+19.14) x (0.04 + 3.1 + 1.88) = 415 volts

    Vk 2with 20 % margin = 498 volts

    Peak voltage = 704.8 Vpeak

    CT requirement for close-up fault condition:

    Vk3 > Kmax x IFmax x (RB+ RCT +RL+Rr)

    = 1.4 x 63000/2000 x (0.04 + 3.1 + 1.88) = 221 volts

    Vk 2with 20 % margin = 266 volts

    Peak voltage = 375.7 Vpeak

    Since, the CT rated knee point voltage is greater than the calculated value, the proposed CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    33 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    37/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.11 CT: 811 B1.C4

    Protection : Metering

    Core : CT: 811 B1.C4

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : 0.2

    VA Burden 50 VA

    Thermal rating factor 200%

    Application : Metering

    Burden Calculation (Refer Annexure-2)

    a LCP

    Ammeter 0.5 VA (Assumed)b Energy metering panel

    NEXUS/1262 3.2 VA (Refer Annex-2, Sh. No. 8)

    c Mosaic panel

    Watt transducer, , AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)

    Var transducer, AREVA, ISTAT300 1 VA (Refer Annex-2, Sh. No. 13)

    Watt meter, PML ION6200 0.5 VA (Assumed)

    Var meter PML ION6200 0.5 VA (Assumed)

    d DSM 0.1 VA (Assumed)

    Cabling loop (500 meters)

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RL at 75C = RL(1+20(T2-T1));

    Consider length of wire = 500 meters. RL = 2.812 Ohms

    2RL = 5.624 VA

    Total connected burden, PBC = 12.42 VA

    Considering 25% safe margin, connected VA equals to= 15.53 VA

    CT Rated burden = 50VA

    The total connected burden is less than the CT rated burden i.e 50VA. Hence the CT is adequate.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    34 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    38/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.12 CT: 811 B2.C4

    Protection : Metering

    Core : CT: 811 B2.C4

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : 0.2

    VA Burden 50 VA

    Thermal rating factor 200%

    Application : Metering

    CT calculation same as CT: 810 B1.C4. Refer above CT: 810 B1.C4 for detailed calculation.

    2.13 CT: 811 B2.C3

    Protection : OHL feeder protn. -Set-2 (87L-2,21-2)

    Core : CT: 811 B2.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection - Set-2 (87L-2,21-2)

    Relay Type/make : ''7SA522", Siemens.

    CT calculation same as CT: 810 B1.C3. Refer above CT: 810 B1.C3 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    35 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    39/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.14 CT: 811 B2.C2

    Protection : OHL feeder protn. Set-1 (87L-1,21-1)

    Core : CT: 811 B2.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection Set-1 (87L-1,21-1)

    Relay Type / Make: "REL 531", ABB

    CT calculation same as CT: 810 B1.C2. Refer above CT: 810 B1.C2 for detailed calculation.

    2.15 CT: 811 B2.C1

    Protection : spare

    Core : CT: 811 B2.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : spare

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    36 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    40/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.16 CT: 812 F.C1

    Protection : Bus-bar protection (87M1)

    Core : CT: 812 F.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Iex < 50

    Thermal rating factor 200%

    NOTE:

    Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)

    are shown below.

    Protection : Bus-bar protection (87M1)

    Core : Core 1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : Bus-Bar Protection-Main-1 (87M1)

    Relay Type / Make: "MCAG 14", AREVA (Setting range: 20%-80% of 1A)

    CT calculation same as above for 87M1. Refer above CT: 810 F.C1 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    37 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    41/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.17 CT: 812 F.C2

    Protection : Bus-bar protection (87M2)

    Core : CT: 812 F.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Iex < 50

    Thermal rating factor 200%

    NOTE:

    Typical bus-bar protection CT's core detail for adjacent cross bay's(3 nos. including future bays)

    are shown below.

    Protection : Bus-bar protection (87M2)

    Core : Core 2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Ie < 50

    Thermal rating factor 200%

    Application : Bus-Bar Protection-Main-2 (87M2)

    Relay Type / Make: "MFAC 14", AREVA (Setting range: 25V-325V)

    CT calculation same as above CT: 810 F.C2. Refer above CT: 810 F.C2 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    38 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    42/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.18 CT: 812 F.C3

    Protection : Spare

    Core : CT: 812 F.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 4.65 Ohms at 3000A tap.

    Knee point voltage, Vk Vk > 5550 V at 3000A tap

    CT excitation current at 3000A tap in mA Iex < 50

    Thermal rating factor 200%

    Application: Spare

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    39 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    43/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.19 CT: 812 B2.C4

    Protection : Metering

    Core : CT: 812 B2.C4

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : 0.2

    VA Burden 50 VA

    Thermal rating factor 200%

    Application : Metering

    CT calculation same as CT: 811 B1.C4. Refer above CT: 811 B1.C4 for detailed calculation.

    2.20 CT: 812 B2.C3

    Protection : OHL feeder protn. -Set-2 (87L-2,21-2)

    Core : CT: 812 B2.C3

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection - Set-2 (87L-2,21-2)

    Relay Type/make : ''MiCOM P546", Areva.

    CT calculation same as CT: 811 B1.C3. Refer above CT: 811 B1.C3 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    40 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    44/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    2.21 CT: 812 B2.C2

    Protection : OHL feeder protn. Set-1 (87L-1,21-1)

    Core : CT: 812 B2.C2

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms ) < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : OHL feeder protection Set-1 (87L-1,21-1)

    Relay Type / Make: "RED 670", ABB

    CT calculation same as CT: 811 B1.C2. Refer above CT: 811 B1.C2 for detailed calculation.

    2.22 CT: 812 B2.C1

    Protection : BF protection (50BF)

    Core : CT: 812 B2.C1

    CT Ratio : 3000-2500-2000-1500-1250-1000-750 /1A

    Class of Accuracy : TPS

    CT Secondary resistance at 75C, RCTohms < 3.1 Ohms at 2000A tap.

    Knee point voltage, Vk Vk > 3700 V at 2000A tap

    CT excitation current at 2000A tap in mA Ie < 75

    Thermal rating factor 200%

    Application : CB Fail Protection (50BF)

    Relay Type / Make: "RAICA", ABB,(50BF)

    CT calculation same as CT: 810 B1.C1. Refer above CT: 810 B1.C1 for detailed calculation.

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    41 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    45/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    3

    3.1 VT LEAD RESISTANCE CALCULATION :

    VT secondary lead size considered is 4 sq.mm.

    4 sq.mm copper cable resistance at 200C is 4.61 ohms/km.i.e Rdc at 20

    0C = 4.61 ohm/km

    Rdc at 75C = R20(1+20(T2-T1)); at 20C = 0.004,Where = temperature co-efficient of resistance.

    Hence, Rdc at 75C = 4.61(1+0.004(75-20));

    = 5.62 ohm/km

    Consider a distance from 380kV GIS CT to relay panel as per layout attached with considerable

    safe margin = 500 meter, Lead resistance calculated is,

    = 5.62 x 0.5

    = 2.81 ohms for 500 meters

    380kV ABU HADRIYAH- MANIFA LINE-2

    CCVT Details :

    Core-1 Core-2

    VT Ratio : 380kV/3/110V/3-110V 380kV/3/110V/3-110V

    Class : 0.2/3P 0.2/3P

    VA Burden : 100 100

    Vector group : Star-Star Star-Star

    Voltage Factor : 1.2 Cont., 1.2 Cont.,

    1.9 for 30 sec 1.9 for 30 sec

    Calculation of VT burden :

    Calculation of Lead burden:

    RL = Lead resistance of wire.

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RLat 75C = RL(1+20(T2-T1)), RL= 2.81 ohms

    Calculation of Lead current at rated burden :(IVT) = 0.1939 Amperes

    Lead current is calculated considering Total VA burden.

    Hence, Lead current calculated =100/63.5 = 0.19 Amperes

    RB= Lead burden, 2xRLx (IVT 2) = 0.2112 VA

    RB=(2 x 2.81 x 0.1939 x 0.1939)

    380kV VT SIZING CALCULATION

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    42 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    46/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Core-1 :

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RXBA 4 1 2 2

    RED670 1 0.1 0.1

    TR2000 1 0.01 0.01

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    1 0.2 0.2

    RXBA 4 1 2 2

    Total VA = 12.31 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 12.52 VA

    .=(VA Connected +VA Lead)

    The Burden calculated considering 25% safety margin = 15.7 VA

    Since, the connected burden is less than 100VA,the VT burden is adequate.

    FFR (98L2) (Ref.) for 25AR (Annexure-2 Sh. No.9)

    DSM Assumed

    FFR (98) 25AR/A811 FOR AF-2 (Annexure-2 Sh. No.9)

    Relays / Instruments

    FFR (98L) A811/A812 (Annexure-2 Sh. No.9)

    Line set-1 protection (Annexure-2 Sh. No.2)

    Transient Fault Recorder (Annexure-2 Sh. No.7)

    FFR (98) (Meas.) for set-1 protection (Annexure-2 Sh. No.9)

    FFR (98) (Ref.) for set-2 protection (Annexure-2 Sh. No.9)

    FFR (98) (Ref.) for Energy meter (Annexure-2 Sh. No.9)

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    43 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    47/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Core-2:

    Relay type Quantity Unit burdenTotal burden

    (VA)

    KVAS100 1 0.02 0.02

    KVAS100 1 0.02 0.02

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    MICOMP546 1 0.02 0.02

    KVAS100 1 0.02 0.02

    KVAS100 1 0.02 0.02

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    KVAS100 1 0.02 0.02

    RAEDA1 3 4.4 13.2

    Transducer Panel

    Voltage transducer for SCADA ISTAT300 1 0.1 0.1

    Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1

    Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1

    ION6200 1 0.5 0.5

    ION6200 1 0.5 0.5

    ION6200 1 0.5 0.5

    Energy metering panel

    Nexus/1262 1 5+3.2 8.2

    RAEDA1 1 4.4 4.4

    RXBA 4 1 2 2

    LCP

    RAEDA1 1 4.4 4.4

    ION6200 1 0.5 0.5

    Total VA = 46.62 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 46.83 VA

    .=(VA Connected +VA Lead)

    The Burden calculated considering 25% safety margin = 58.5 VA

    Since, the connected burden is less than 100VA,the provided VT burden is adequate.

    Under voltage relay

    Under voltage relay

    Voltmeter

    FFR (98L2) (Meas.) / 25AR (Annexure-2 Sh. No.9)

    FFR (98B2) (Meas.) / A812 (Annexure-2 Sh. No.9)

    FFR (98) (Meas.) / A811 (Annexure-2 Sh. No.9)

    (Annexure-2 Sh. No. 13)

    (Annexure-2 Sh. No. 13)

    (Annexure-2 Sh. No. 13)

    Wattmeter, PML

    VARmeter, PML

    Energy meter

    (Annexure-2 Sh. No. 11)

    25MC/A812 (Annexure-2 Sh. No.10)

    Assumed

    Assumed

    Voltmeter, PML

    Assumed

    FFR (98) (Meas.) for revenue meter

    (Annexure-2 Sh. No. 8)

    (Annexure-2 Sh. No. 11)

    (Annexure-2 Sh. No. 11)

    Assumed

    (Annexure-2 Sh. No.9)

    (Annexure-2 Sh. No.10)

    FFR (98L) (Meas.) A811/A812 (Annexure-2 Sh. No.9)

    FFR (98) (Ref.) for set-1 protection (Annexure-2 Sh. No.9)

    25AR / A812 (Annexure-2 Sh. No.10)

    25AR / A811

    Relays / Instruments

    25MC/A811

    FFR (98) (Meas.) for 67N-2 (Annexure-2 Sh. No.9)

    Line set-2 protection (Annexure-2 Sh. No.3)

    (Annexure-2 Sh. No.10)

    25AR / A811 FOR AF-2 (Annexure-2 Sh. No.10)

    (27L2), Under voltage relay

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    44 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    48/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    3.3 380kV ABU HADRIYAH- AL-FADHILI LINE-2

    CCVT Details :

    Core-1 Core-2

    VT Ratio : 380kV/3/110V/3-110V 380kV/3/110V/3-110V

    Class : 0.2/3P 0.2/3P

    VA Burden : 100 100

    Vector group : Star-Star Star-Star

    Voltage Factor : 1.2 Cont., 1.2 Cont.,

    1.9 for 30 sec 1.9 for 30 sec

    Calculation of VT burden :

    Calculation of Lead burden:

    RL = Lead resistance of wire.

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RLat 75C = RL(1+20(T2-T1)), RL= 2.81 ohms

    Calculation of Lead current at rated burden :(IVT) = 0.1954 Amperes

    Lead current is calculated considering Total VA burden.

    Hence, Lead current calculated =100/63.5 = 0.20 Amperes

    RB= Lead burden, 2xRLx (IVT 2) = 0.2147 VA

    RB=(2 x 2.81 x 0.1954 x 0.1954)

    Core-1 :

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RXBA 4 1 2 2

    REL 531 1 0.2 0.2

    TR2000 1 0.01 0.01

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    1 0.2 0.2

    RXBA 4 1 2 2

    Total VA = 12.41 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 12.62 VA

    .= (VA Connected + VA Lead)

    The Burden calculated consider ing 25% safety margin = 15.8 VA

    Since, the connected burden is less than 100VA,the VT burden is adequate.

    FFR (98L) (Ref.) for 25MC 810 (Annexure-2 Sh. No.9)

    DSM Assumed

    FFR (98) (Ref.) for 67N-2 (Annexure-2 Sh. No.9)

    FFR (98) (Ref.) for Energy meter (Annexure-2 Sh. No.9)

    FFR (98L2) (Ref.) for 25AR (Annexure-2 Sh. No.9)

    Line set-1 protection (Annexure-2 Sh. No.15)

    Transient Fault Recorder (Annexure-2 Sh. No.7)

    FFR (98) (Meas.) for 67N-1 (Annexure-2 Sh. No.9)

    Relays / Instruments

    FFR 98-25AR/A811 FOR MAIN-2 (Annexure-2 Sh. No.9)

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    45 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    49/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Core-2:

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RASC 1 0.25 0.25

    RASC 1 0.25 0.25

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    7SA522 1 0.1 0.1

    RASC 1 0.25 0.25

    RASC 1 0.25 0.25

    RAEDA1 3 4.4 13.2

    RXBA 4 1 2 2

    Transducer Panel

    Voltage transducer for SCADA ISTAT300 1 0.1 0.1

    Watt meter Watt transducer for SCADA ISTAT300 1 0.1 0.1

    Var meter Var transducer for SCADA ISTAT300 1 0.1 0.1

    PML 1 0.5 0.5

    PML 1 0.5 0.5

    PML 1 0.5 0.5

    Revenue metering panel

    ELESTER 1 0.0173 0.0173

    RAEDA1 1 4.4 4.4

    RXBA 4 1 2 2

    LCP

    FVS-U-

    DC121 4.4 4.4

    PML 1 0.5 0.5

    Total VA = 35.42 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 35.63 VA

    .= (VA Connected + VA Lead)

    The Burden calculated consider ing 25% safety margin = 44.5 VA

    Since, the connected burden is less than 100VA,the provided VT burden is adequate.

    FFR (98) (Meas.) for revenue meter (Annexure-2 Sh. No.9)

    Under voltage relay Assumed

    Voltmeter Assumed

    VARmeter Assumed

    Revenue meter (Annexure-2 Sh. No. 18)

    Under voltage relay (Annexure-2 Sh. No. 11)

    (Annexure-2 Sh. No.13)

    (Annexure-2 Sh. No.13)

    (Annexure-2 Sh. No.13)

    Voltmeter Assumed

    Wattmeter Assumed

    25AR / A810 (Annexure-2 Sh. No.17)

    27-L2 Under voltage relay (Annexure-2 Sh. No. 11)

    FFR (98B1) (Meas.) /A810 (Annexure-2 Sh. No.9)

    25AR / A811 FOR MAIN-2 (Annexure-2 Sh. No.17)

    FFR (98) (Ref.) for 67N-1 (Annexure-2 Sh. No.9)

    FFR (98) (Meas.) for 67N-2 (Annexure-2 Sh. No.9)

    Line set-2 protection (Annexure-2 Sh. No.16)

    Relays / Instruments

    25MC/A811 (Annexure-2 Sh. No.17)

    25MC/A810 (Annexure-2 Sh. No.17)

    FFR (98L) (Meas.) A810/A811 (Annexure-2 Sh. No.9)

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    46 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    50/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    3.4 380kV BUS1-VT (Refer Annexure-4A)

    VT Details :

    Core-1 Core-2

    VT Ratio : 380kV/3/110V/3-110V 380kV/3/110V/3-110V

    Class : 0.2/3P 0.2/3P

    VA Burden : 100 100

    Vector group : Star-Star Star-Star

    Voltage Factor : 1.2 Cont., 1.2 Cont.,

    1.9 for 30 sec 1.9 for 30 sec

    Calculation of VT burden :

    Calculation of Lead burden:

    RL = Lead resistance of wire.

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RLat 75C = RL(1+20(T2-T1)), RL= 2.81 ohms

    Calculation of Lead current at rated burden :(IVT) = 0.0945 Amperes

    Lead current is calculated considering Total VA burden.

    Hence, Lead current calculated =100/63.5 = 0.09 Amperes

    RB= Lead burden, 2xRLx (IVT 2) = 0.0502 VA

    RB=(2 x 2.81 x 0.0945 x 0.0945)

    Core-1 :

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    Total VA = 6 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 6.05 VA

    .=(VA Connected +VA Lead)

    Considering 25% safety margin for any additional FFR relay required.

    The Burden calculated considering 25% safety margin = 7.6 VA

    Since, the connected burden is less than 100VA,the VT burden is adequate.

    FFR (98B1) (Meas.) 25AR/810 (Annexure-2 Sh. No.9)

    FFR (98B1) (Meas.) 25AR/807 (Annexure-2 Sh. No.9)

    FFR (98B1)-25MC/A810 (Annexure-2 Sh. No.9)

    Relays / Instruments

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    47 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    51/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Core-2:

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RASC 1 0.25 0.25

    KVAS100 1 0.02 0.02

    RASC 1 0.25 0.25

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RASC 1 0.25 0.25

    RASC 1 0.25 0.25

    TR2000 1 0.01 0.01

    1 0.2 0.2

    Transducer panel

    Voltage transducer for SCADA ISTAT300 1 0.1 0.1

    PML 1 0.5 0.5

    LCC

    PML 1 0.5 0.5

    Total VA = 8.33 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 8.38 VA

    .=(VA Connected +VA Lead)

    Considering 25% safety margin for any additional FFR relay required.

    The Burden calculated considering 25% safety margin = 10.5 VA

    Since, the connected burden is less than 100VA,the provided VT burden is adequate.

    25MC/A804 (Annexure-2 Sh. No.17)

    25MC/A807 (Annexure-2 Sh. No.10)

    25MC/A810 (Annexure-2 Sh. No.17)

    98B1-25MC/810 (Annexure-2 Sh. No.9)

    25AR / A807 (Annexure-2 Sh. No.17)

    98B1-25AR/807 (Annexure-2 Sh. No.9)

    98B1-25AR/810

    DSM Assumed

    (Annexure-2 Sh. No.9)

    25AR / A810

    Transient Fault Recorder (Annexure-2 Sh. No.7)

    Voltmeter

    AssumedVoltmeter

    Relays / Instruments

    (Annexure-2 Sh. No.17)

    (Annexure-2 Sh. No.13)

    Assumed

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    48 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    52/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    3.5 380kV BUS2-VT

    VT Details : (Refer Annexure-4A)

    Core-1 Core-2

    VT Ratio : 380kV/3/110V/3-110V 380kV/3/110V/3-110V

    Class : 0.2/3P 0.2/3P

    VA Burden : 100 100

    Vector group : Star-Star Star-Star

    Voltage Factor : 1.2 Cont., 1.2 Cont.,

    1.9 for 30 sec 1.9 for 30 sec

    Calculation of VT burden :

    Calculation of Lead burden:

    RL = Lead resistance of wire.

    For 4 sq.mm copper cable, RL= 0.00461 ohm/meter at 20C.

    at 20C = 0.004, RLat 75C = RL(1+20(T2-T1)), RL= 2.81 ohms

    Calculation of Lead current at rated burden :(IVT) = 0.0945 Amperes

    Lead current is calculated considering Total VA burden.

    Hence, Lead current calculated =100/63.5 = 0.09 Amperes

    RB= Lead burden, 2xRLx (IVT 2) = 0.0502 VA

    RB=(2 x 2.81 x 0.0945 x 0.0945)

    Core-1 :

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    Total VA = 6 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 6.05 VA

    .=(VA Connected +VA Lead)

    Considering 25% safety margin for any additional FFR relay required.

    The Burden calculated considering 25% safety margin = 7.6 VA

    Since, the connected burden is less than 100VA,the VT burden is adequate.

    Relays / Instruments

    FFR (98B2) (Meas.) 25AR/806 (Annexure-2 Sh. No.9)

    FFR (98B2) (Meas.) 25AR/812 (Annexure-2 Sh. No.9)

    FFR (98B2)-25MC/A812 (Annexure-2 Sh. No.9)

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    49 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    53/137

    PROJECT:

    ABU-HADRIYAH 380/115 kV BSP

    DOCUMENT TITLE:

    380 kV CT/VT SIZING CALCULATION

    DOCUMENT NUMBER:

    EA-086959

    Core-2:

    Relay type Quantity Unit burdenTotal burden

    (VA)

    RASC 1 0.25 0.25

    RASC 1 0.25 0.25

    KVAS100 1 0.02 0.02

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RXBA 4 1 2 2

    RASC 1 0.25 0.25

    KVAS100 1 0.02 0.02

    TR2000 1 0.01 0.01

    1 0.2 0.2

    Transducer panel

    Voltage transducer for SCADA ISTAT300 1 0.1 0.1

    PML 1 0.5 0.5

    LCC

    PML 1 0.5 0.5

    Total VA = 8.1 VA per phase

    Hence, total required burden of VT (Meters/relays plus lead burden) = 8.15 VA

    .=(VA Connected +VA Lead)

    Considering 25% safety margin for any additional FFR relay required.

    The Burden calculated considering 25% safety margin = 10.2 VA

    Since, the connected burden is less than 100VA,the provided VT burden is adequate.

    25MC/A806

    Voltmeter Assumed

    (Annexure-2 Sh. No.7)

    DSM Assumed

    (Annexure-2 Sh. No.13)

    Voltmeter Assumed

    (Annexure-2 Sh. No.17)

    25MC/A809 (Annexure-2 Sh. No.17)

    25MC/A812 (Annexure-2 Sh. No.10)

    Relays / Instruments

    (Annexure-2 Sh. No.9)

    98B2-25AR/806 (Annexure-2 Sh. No.9)

    98B2-25MC/812

    98B2-25AR/812 (Annexure-2 Sh. No.9)

    25AR / A806 (Annexure-2 Sh. No.17)

    25AR / A812 (Annexure-2 Sh. No.10)

    Transient Fault Recorder

    BAY NUMBER:

    CROSS BAY C4

    Sheet No.

    50 of 50

    ABU-HADRIYAH CONTRACT No.

    3-083300.01

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    54/137

    Annexure-: CT Requirement of Relay Page 1

    ANNEXURE-1

    CT requirements of relay

    Sr No. Description Make Type Page No.

    1 Line differential protection main-1 ABB RED670 2

    2 Line differential protection main-2 AREVA MICOMP546 5

    3 Busbar differential protection AREVA MCAG14 8

    4 Busbar differential protection AREVA MFAC14 11

    5 CT circuit supervision relay AREVA MVTP11 15

    6 Breaker failure protection relay ABB RAICA 16

    7 Transient fault recorder ROCHESTER TR2000 17

    8 Line differential protection main-1 ABB REL531 20

    9 Line differential protection main-2 SIEMENS 7SA522 24

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    55/137

    Annexure-: CT Requirement of Relay Page 2

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    56/137

    Annexure-: CT Requirement of Relay Page 3

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    57/137

    Annexure-: CT Requirement of Relay Page 4

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    58/137

    Annexure-: CT Requirement of Relay Page 5

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    59/137

    Annexure-: CT Requirement of Relay Page 6

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    60/137

    Annexure-: CT Requirement of Relay Page 7

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    61/137

    Annexure-: CT Requirement of Relay Page 8

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    62/137

    Annexure-: CT Requirement of Relay Page 9

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    63/137

    Annexure-: CT Requirement of Relay Page 10

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    64/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    65/137

    Annexure-: CT Requirement of Relay Page 12

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    66/137

    Annexure-: CT Requirement of Relay Page 13

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    67/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    68/137

    Annexure-: CT Requirement of Relay Page 15

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    69/137

    Annexure-: CT Requirement of Relay Page 16

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    70/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    71/137

    Annexure-: CT Requirement of Relay Page 18

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    72/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    73/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    74/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    75/137

    Annexure-: CT Requirement of Relay Page 22

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    76/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    77/137

    Annexure-: CT Requirement of Relay Page 24

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    78/137

    Annexure-: VA Requirement of Relay Page 1

    ANNEXURE-2

    VA burden requirements of relay

    Sr No. Description Make Type Page No.

    1 Line differential protection main-1 ABB RED670 2

    2 Line differential protection main-2 AREVA MICOMP546 3

    3 Busbar differential protection AREVA MCAG4 4

    4 CT circuit supervision relay AREVA MVTP11 5

    5 Breaker failure protection relay ABB RAICA 6

    6 Transient fault recorder ROCHESTER TR2000 7

    7 Energy Meter Electro Ind. NEXUS1262 8

    8 Fuse failure relay ABB RXBA4 9

    9 Synchro check relay AREVA KVAS100 10

    10 Undervoltage relay ABB RAEDA1 11

    11 Line differential protection main-1 ABB REL531 12

    12 Transducer AREVA ISTAT300 13

    13 Line differential protection main-1 ABB REL531 14

    14 Line differential protection main-2 SIEMENS 7SA522 16

    15 Synchro check relay ABB RASC 17

    16 Revenue Meter ELSTER A3 ALPHA 18

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    79/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    80/137

    Annexure-: VA Requirement of Relay Page 3

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    81/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    82/137

    Annexure-: VA Requirement of Relay Page 5

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    83/137

    Annexure-: VA Requirement of Relay Page 6

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    84/137

    Annexure-: VA Requirement of Relay Page 7

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    85/137

    Annexure-: VA Requirement of Relay Page 8

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    86/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    87/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    88/137

    Annexure-: VA Requirement of Relay Page 11

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    89/137

    Annexure-: VA Requirement of Relay Page 12

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    90/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    91/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    92/137

    Annexure-: VA Requirement of Relay Page 15

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    93/137

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 17.12.09

    94/137

    Annexure-: VA Requirement of Relay Page 17

  • 7/24/2019 380kV CT-VT Calculation C4 Rev D 1