    420KV SF6

    CIRCUIT BREAKER

    OPERATION AND TESTING

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    2/18

    CONTENT:

    Introduction

    Classification of circuit breakers

    Advantages of SF6 circuit breaker

    Technical data

    Constructional details

    Arc phenomenon

    Operating principle

    Conclusion

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    3/18

    ABSTRACT:

    This project is titled 420 KV SF6 CIRCUIT BREAKER OPERATION AND TESTING .The operation of

    420KV SF6 circuit breakers was explained. The various routine tests recommended by IEC 62271-100 standard is

    described and the results of the test are compared with the specified values.

    The first deals with the basic introduction to a circuit breaker, types of circuit breaker, the properties and

    advantages of SF6 circuit breaker, its disadvantages, technical data, constructional features of the breaker in which

    various parts of the circuit breaker are explained, It also deals with the basic working principle, arc phenomenon,

    arc extinction and modes of operation of 420 KV SF6 circuit breaker.

    The second part covers introduction to IEC 62271-100 standards and various types of tests. A list of various types

    and routine test is also included.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    4/18

    INTRODUCTION:

    With the ever-increasing demand for energy, power generation, transmission and distribution have become very

    important and circuit breaker is a vital component in the transmission system achieves greater significance.

    A circuit breaker is a device which can make or break a circuit manually or by remote control under normal

    conditions, break a circuit automatically under fault conditions and make a circuit either manually or by remote

    control after fault cleared.

    The circuit breaker serves two basic purposes:

    1. Switching during normal operating conditions for the purpose of operation

    and maintenance.

    2.Switching during abnormal conditions such as short circuit and interrupting

    fault currents.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    5/18

    CLASSIFICATION OF CIRCUIT BREAKERS:

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    6/18

    CLASSIFICATION BY LOCATION:

    Switchgear based on where it is located is classi ied as indoor and

    out-door type.

    Medium and low voltage switchgear and high voltage as

    Insulated Switchgear ( IS) are categorised as indoor type

    Where as the out- door switchgearwhich has air as an external

    insulating medium is categorised as air insulated switchgear ( IS)

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    7/18

    CLASSIFICATION BY EXTERNAL DESIGN:

    Out-door circuit breakers can be identified as either dead-tank or live-tank

    type circuit breakers, from the point of view of their physical structural

    design.

    In Dead tank circuit breaker, the switching device is located with suitable

    insulator supports inside a metallic vessel(s) at ground potential and filledwith insulating medium.

    In Live tank circuit breaker the interrupter(s) is/are located in an insulator

    bushing/s and are at a potential above the ground. The live tank circuit

    breakers are cheaper and they require less mounting space.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    8/18

    CLASSIFICATION BY INTERRUPTING MEDIA:

    Depending upon the interrupting media the circuit breakers are classified into

    Air Blast Circuit Breaker

    Oil circuit breakers

    Vacuum circuit breaker

    SF6 gas circuit breaker

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    9/18

    ADVANTAGES OF SF6

    GAS CIRCUIT BREAKERS:

    SF6 is an electro-negative gas and has a strong tendency to absorb free electrons , so it has very short arcing time.

    The dielectric strength of SF6 gas is 2 to 3 times that of air, such breakers can interrupt much larger currents.

    There is no risk of fire because SF6 gas is non-flammable.

    The SF6 circuit breakers requires low maintenance .

    Since SF6breakers are totally enclosed and sealed from atmosphere , they are particularly suitable where

    explosion hazard exists e.g coal mines.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    10/18

    TECHNICAL DATA:

    Electrical data:

    Rated voltage KV 420

    Rated insulation level

    - Lightening impulse withstand

    voltage(1.2/250us)

    KVp 1425

    - One minute power frequency

    withstand voltage

    KV 520-610

    Rated frequency HZ 50

    Rated normal current A 3150

    Rated short -circuit breakingcurrent

    KA 40

    Rated short-circuit making

    current

    KA 2.5 times rated short-circuit

    breaking current

    Rated short- circuit current

    duration

    Sec 3

    Rated duty cycle--

    O- 0.3sec-CO-3mins-CO

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    11/18

    OPERATI TI I :

    Closing time ms 100 max

    Opening time ms 22 max

    Arcing time ms 18 max

    Break time Cycles 2

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    12/18

    CONSTRUCTIONAL ETAILS:

    The main parts of the SF6 circuit breaker are:

    Interrupt assembly

    Bell-crank mechanism

    Support insulator

    Hydraulic mechanism

    Control cabinet

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    13/18

    ARC PHENOMENON:

    When short circuit occurs, a heavy current flows through the contacts of the circuit breaker before they are opened

    by the protective system.

    At the instant when the contacts begin to separate, the contact area decreases rapidly and large fault currents

    causes increased current density and hence rise in temperature.

    The heat produced in the medium between contacts is sufficient to ionise the air or vaporize and ionise the oil.

    The ionised air or vapour acts as conductor and an arc is struck between the contacts.

    The p.d between the contacts is quite small and is just sufficient to maintain the arc.

    The arc provides a low resistance path and consequently the current in the circuit remains uninterrupted so long as

    the arc persists.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    14/18

    OPERATING PRINCIPLE:

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    15/18

    CONCLUSION:

    Thus in our presentation we are explained about basic introduction of circuit breaker, classification

    of circuit breakers depending upon different consideration, technical data , advantages of SF6circuit breaker, constructional features circuit breaker, Arc phenomenon operating principle of SF6circuit breaker and the process of arc extinction.

  • 7/27/2019 420KV SF 6 CIRCUIT BREAKER .pdf

    16/18

    REFERENCES:

    TEXT OOKS:

    1.PRINCIPLES OF POWER SYSTEM - V.K.MEHTA

    ROHIT MEHTA

    2.OPERATION & MAINTANCE OF SF6 CIRCUIT BREAKER BHEL,HYD.

    WEBSITES:

    1.WWW.GOOGLE.COM

    2. WWW.BHEL.COM

    3. WWW.ABB.COM.