Upload
priyadharshini-ramasamy
View
8
Download
0
Tags:
Embed Size (px)
Citation preview
FAULT LEVEL CALCULATIONS
(As per IS 13234 : 1992 &
IEC 60909 : 1995)
FAULT LEVEL AT ANY GIVEN POINT OF THE INSTALLATION IS THE MAXIMUM CURRENT THAT CAN FLOW IN CASE OF S/C AT THAT POINT
WHAT IS FAULT LEVEL?WHAT IS FAULT LEVEL?
PURPOSE OF FAULT LEVEL CALCULATIONS
• FOR SELECTING S.C.P.Ds OF ADEQUATE S/C BREAKING CAPACITY
• FOR SELECTING BUSBARS, BUSBAR SUPPORTS, CABLES & SWITCHGEARS, DESIGNED TO WITHSTAND THERMAL & MECHANICAL STRESSES BECAUSE OF S/C
• TO DO CURRENT BASED DISCRIMINATION BETWEEN CBs
FAULT LEVEL CALCULATIONS
TYPES OF FAULTS
SYMMETRICAL ASYMMETRICAL
LINE TO LINE
DOUBLE LINE TO EARTH
LINE TO EARTH
THREE PHASE FAULT
SOURCES OF SHORT CIRCUIT CURRENTS
ELECTRIC UTILITY SYSTEMS
D.G SETS
CONDENSERS
MOTORS
NATURE OF SHORT CIRCUIT CURRENT
THE SHORT CIRCUIT CURRENT WILL
CONSIST OF FOLLOWING COMPONENTS
THE AC COMPONENT WITH CONSTANT AMPLITUDE
THE DECAYING DC COMPONENT
SOURCE : UTILITY SYSTEMSOURCE : UTILITY SYSTEM
NATURE OF SHORT CIRCUIT NATURE OF SHORT CIRCUIT CURRENTCURRENT
TOP ENVELOPE
DECAYING DC COMPONENT
CURRENT
BOTTOM ENVELOPE
2√2
I K =
2 √
2 I K
''
I P
A
2√2
I K ´
TIME
WAVEFORMWAVEFORM
CALCULATION ASSUMPTIONS
TYPE OF SHORT CIRCUIT : THREE PHASE BOLTED SHORT CIRCUIT
IMPEDANCES OF BUSBAR/SWITCHGEAR/C.T. /JOINTS ARE NEGLECTED
TRANSFORMERS ARE CONNECTED TO INFINITE BUS ON H.T. SIDE
TRANSFORMER TAP IS IN THE MAX. POSITION
S/C CURRENT WAVEFORM IS A PURE SINE WAVE
DISCHARGE CURRENT OF CAPACITORS ARE NEGLECTED
WHAT ?WHAT ?
CALCULATION OF SHORT CIRCUIT CURRENT
I S/C = 1 . 05 * LINE VOLTAGE
√ 3 * ( ZTR + Z CABLE )
)
Z TR = (in ohms)
% Z * 10 * KV2
KVA
CASE STUDY
STEP 1 : SINGLE LINE DIAGRAMSTEP 1 : SINGLE LINE DIAGRAM
°°)
°°)
°°)°
°) °
°)
°°)
F1
F2
PCCPCC
MCCMCC
M2M1 M3 M4
11
21
31
50HP 100HP 30HP 150HP
°°°°°°
G
°°)
° °)
12
13
STANDBY GENERATOR1250kVA
TRANSFORMER 1600kVA
350A 300A 300A
STEP 2 : SYSTEM DATA
TRANSFORMERTRANSFORMER :: 11/0.433 KV11/0.433 KV 1600 KVA1600 KVA %R = 0.94%R = 0.94 %X = 5.46%X = 5.46 %Z = 5.54%Z = 5.54
STEP 2 : SYSTEM DATA
CABLE :CABLE : R = 0.062 R = 0.062 ΩΩ /KM/KM X = 0.079 X = 0.079 ΩΩ /KM/KMLENGTH OF CABLE, 21 TO 31= 100mLENGTH OF CABLE, 21 TO 31= 100m
INDUCTION MOTORS :INDUCTION MOTORS : M1, IM1, IrMrM = 200A = 200A
M2, IM2, IrMrM = 135A = 135A
M3, IM3, IrM rM = 135A= 135A
M4, IM4, IrM rM = 200A = 200A
STEP 3 : CALCULATION OF RT & XT
RT = 10 (%R)(SECONDARY KV)2
KVA
10 (0.94)(0.433)2
1600 = = 0.001102 OHMS
XT = 10 (%X)(SECONDARY KV)2
KVA10 (5.46)(0.433)2
1600 = = 0.006398 OHMS
STEP 4 : CALCULATION OF RL & XL
RL = 0.062 × 0.1 = 0.0062 OHMS
XL = 0.079 × 0.1 = 0.0079 OHMS
STEP 5 : CALCULATION OF ‘Z’ UP TO THE POINT OF FAULT
TOTAL ‘Z’ UP TO FAULT LOCATION F1 = √ (RT)2 + (XT)2 = √ (0.001102)2 + (0.006398)2 = 0.00649 Ω
STEP 5 : CALCULATION OF ‘Z’ UP TO THE POINT OF FAULT
TOTAL ‘Z’ UP TO FAULT LOCATION F2
= √ (RT + RL)2 + (XT + XL)2
= √ (0.007302)2 + (0.01430)2
= 0.01606 Ω
STEP 6 : CALCULATION OF RMS VALUE OF S/C CURRENT AT THE
POINT OF FAULT
IK″ AT FAULT LOCATION F1 =
c Un
√3 Z
= 1.05 × 415
√3 × 0.00649
= 38765 A OR 38.77 kA
STEP 6 : CALCULATION OF RMS VALUE OF S/C CURRENT AT THE
POINT OF FAULT
IK″ AT FAULT LOCATION F2 =
c Un
√3 Z
= 1.05 × 415
√3 × 0.01606
= 15665 A OR 15.67 kA
STEP 7 : CALCULATION OF MAKING CAPACITY AS PER
STANDARD IEC 60947-2
2.20.250< I
2.10.2520< I<=50
2.00.310< I<=20
1.70.56< I<=10
1.50.74.5<= I<=6
Multiplying factor
Power factorShort-circuit breaking
capacity (kA)
STEP 8 : CALCULATION OF PEAK VALUE OF S/C CURRENT AT THE
POINT OF FAULT
iP AT FAULT LOCATION F1 = 2.1 × 38.77 = 81.41 kA (PEAK)
iP AT FAULT LOCATION F2 = 2 × 15.67 = 31.34 kA (PEAK)
CALCULATION OF X AND R FOR GENERATOR
• The value of xd″ will be given in percentage terms.
• Calculate xd″ in ohms.• Calculate R in ohms as per data in standard:• Rg =0.15 xd″ for generators less than 1000V
• Rg =0.07 xd″ for generators up to 100MVA
• Rg =0.05 xd″ for generators 100MVA and above.• Apply correction factor and recalculate R and X.• Find Z and use in the formulae.
THANK YOU