16-QMP-05-3B 02 12.04.12 CLIENT COMMENTS INCORPORATED AND REISSUED FOR USE AKJ BPN TBY 01 29.03.12 CLIENT COMMENTS INCORPORATED AND REISSUED FOR USE AKJ ARUS TBY 00 21.02.12 ISSUED FOR USE AKJ ARUS TBY Rev. Date Description Prpd. Chkd. Appd. Triune Energy Services Pvt. Ltd. New Delhi TECHNICAL SPECIFICATION FOR HV VARIABLE FREQUENCY DRIVE SYSTEM Std. / Doc. Number Rev. 9579-02-TS-102 0 Sheet 1 of 30 CHAPTER 4 TECHNICAL SPECIFICATION FOR HV VARIABLE FREQUENCY DRIVE SYSTEM

4.VFD SPEC. REV.1

  • Upload
    wado11

  • View
    79

  • Download
    6

Embed Size (px)

DESCRIPTION

Variable Speed Drive Specification

Citation preview

  • 16-QMP-05-3B

    02 12.04.12 CLIENT COMMENTS INCORPORATED

    AND REISSUED FOR USE

    AKJ BPN TBY

    01 29.03.12 CLIENT COMMENTS INCORPORATED

    AND REISSUED FOR USE

    AKJ ARUS TBY

    00 21.02.12 ISSUED FOR USE AKJ ARUS TBY

    Rev. Date Description Prpd. Chkd. Appd.

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR

    HV VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 1 of 30

    CHAPTER 4

    TECHNICAL SPECIFICATION

    FOR

    HV VARIABLE FREQUENCY DRIVE

    SYSTEM

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 2 of 35

    1. Scope

    The equipment listed below shall be supplied in accordance with the requirements specified in this document, equipment data sheet, specification applicable codes and standards and other documents attached/ referred herein.

    Sl. No.

    Quantity STATION Description

    1. 2 SET KHOPOLI

    6.6kV, 3phase, minimum 18 pulse variable speed drive (VSD) system suitable for 2 Nos. New Pump Motor of 2750kW (Estimated rating) and 1 No. Existing 750kW (Refer Attach Motor Data Sheet for Detail) including Dry type VSD transformer. VSD Set/System shall be complete with the following as per attached system configuration:

    1. One No. Synchronous Panel. 2. One No. Common Drive Logic Panel. 3. One Set. of Down Stream Breakers Panel Board

    (Consists of 9 Nos. of Breakers). 4. Interconnecting Power & Control Cables required for the

    above VSD System. 5. 3 Nos. of Local Control panels. 6. Addition/ Modification of Existing 6.6kV Switchboard. 7. Any required change in control scheme.

    Note: Both VFDs shall have option for cross-selection of motor according to the pump which is under operation as per attached system configuration. Same VFD shall be suitable for both rating of motor i.e. 2750kW & 750kW.

    2 1 SET

    For each rating

    - Special Tools and Tackles required for the erection, testing, commissioning, operation and maintenance of Complete System at Khopoli.

    3 1 SET

    For each rating

    - Recommended Commissioning Spare Parts for Complete System at each location Khopoli.

    4 1 SET

    For each rating

    - Mandatory Spares as per vendor recommendation for Complete System at each location Khopoli.

    5 1 SET

    For each rating

    - Recommended 2 year operation & maintenance Spare (Vendor to submit unit rate separately for the same)

    Notes: 1. Vendor to visit site (At Khopoli) before submitting offer and analyze required 6.6kV switchgear

    modification/addition as per attached system configuration and indicate the same in their offer. All the required modifications/additions due to addition of VFD system in the 6.6kV switchboard are in the scope of vendor. Vendor to check and indicate interface requirement with UCP Panel and Station PLC. All interface requirements and any changes in control scheme are in the scope of vendor.

    2. Vendors scope of work includes design, engineering, manufacturing, shop testing, inspection of bought out items and supply of all electrical equipments.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 3 of 35

    3. Pumps shall be fed from VSD system which includes input converter transformer. Protection and Metering for VSD system shall be as per attached specifications for VSD system and referred codes and standards.

    4. VSD panel shall be located in the sub-station. Vendor to indicate requirement of Air-conditioned room for the same (If any). However, equipment shall be suitable for operation even during failure of Air-Condition.

    5. With reference to limits of harmonics as per IEEE 519, the harmonics are to be controlled at 6.6kV bus. The overall power factor of the drives at 100% load shall not be less than 0.99

    6. Any other accessory, fixing hardware, switches etc. which shall be required for satisfactory operation and completeness shall be provided by vendor.

    7. Type test certificates and utility consumption list shall be submitted with the offer. 8. Inspection and Testing at works shall be as per VSD specification.

    9. Final Documentation: A. Vendor to furnish Hard Copy and electronic files of all the documents indicated for final

    documentation in addition of hard copy. B. Vendor to furnish all drawings and documents either in MS Word, MS Excel, Autocad, Microstation

    stored in electronic media. C. Final documentation shall be provided along with hard copies in compact disc compatible with

    standard PC based application. D. All operating and maintaining instructions in electronic media or in scanned images converted in

    electronic media. Final documentation shall be provided in CD with proper index along with hard copies. ORDER OF PRECENDENCE: 1. Statutory Rules and Regulations 2. This Requisition 3. Equipment Data Sheet 4. Standard specification 5. Codes and Standards

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 4 of 35

    1.0 SCOPE

    These specification covers design, manufacturing, testing at works, packing and

    supply of High Voltage (6.6KV), AC Variable Frequency Drive system along with

    bypass isolators. The VFD system shall be compatible with Squirrel Cage

    Induction Motor as specified in specification no. 9579-02-TS-101 and complete

    with converter, converter input transformer (if required), DC link reactor with

    associated auxiliaries, harmonic filters (if required), isolators, field mounted local

    control panel etc. as detailed below.

    2.0 GENERAL

    The Vendor shall be responsible for engineering and functioning of the complete

    system, meeting the requirement of this specification and data sheets. This shall

    include but not be limited to inverter sizing, input transformer sizing, transformer

    impedance selection, vector group, input and output harmonic filter(if required)

    design and sizing, output dv/dt filter sizing, isolator rating, motor cable selection/

    sizing and motor sizing / selection.

    3.0 SITE CONDITIONS

    3.1 The VFD and all other associated equipments shall be suitable for operating

    satisfactorily in humid and highly corrosive atmosphere prevailing in refineries

    and other petroleum installations.

    Ambient temperature: 5 to 50 0C.

    Humidity: 95%

    Altitude: less than 1000m above MSL.

    3.2 The AC drive (with or without in built converter transformer) & isolators shall be

    installed indoors in a non-hazardous room, as specified in data sheet. Motor shall

    be installed outdoors in hazardous area as specified in datasheet. The vendor

    shall furnish the required clearances in VFD room including layout, earthing

    requirement and the required capacity of AC, if any, for efficient and reliable

    operation of the VFD.

    3.3 VFD system shall be designed for continuous duty as per nameplate rating under

    the specified ambient conditions.

    4.0 APPLICABLE CODES AND STANDARDS

    4.1 The equipment shall comply with the requirements of latest revision of following

    standards issued by BIS (Bureau of Indian Standards), unless otherwise specified.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 5 of 35

    The offered equipment shall comply with latest editions of following standards.

    The vendor shall clearly bring out in the offer the applicable standard for every

    feature of the offered component, if different from the following standards.

    IS-3700 : Essential ratings and characteristic of semi-conductor devices

    IS-3715 : Letter symbols for semi-conducting devices

    IS-4411 : Code of designation of semi-conducting devices

    IS-5001 : Guide for preparation of drawings for semi-conductor devices

    IS-5469 : Code of practice for the use of semi-conductor junction devices

    IS-6297 : Transformers and indicators for electronic equipment

    IS-8789 : Performance parameters for motors

    IS-12729 : Switchgear and control gear for voltages exceeding 1000V- General

    requirements

    IS-13408 : Code of practice for the selection, installation and maintenance of

    electrical apparatus for use in potentially explosive atmospheres

    IEC 146 : Semi Conductor converters

    IEC 297 : Dimension of panels and racks

    IEC 326 :General requirements and measuring methods for printed wiring

    boards

    IEC 352 : Solder less wrapped connection

    IEEE 444 : Protection standards for converters

    IEEE 519 : Harmonic control & reactive compensation of static power

    converters

    DIN 41488 : Electrical engineering dimensions

    In case Indian standards are not available for any particular equipment,

    standards issued by IEC/BS/VDE/ IEEE/NEMA/UL/FM/CE or equivalent agency

    shall be applicable.

    5.0 GENERAL REQUIREMENTS

    5.1 The offered equipment shall be brand new with state of art technology and proven

    field track record. No prototype equipment shall be offered.

    5.2 The VFD model offered shall be from the existing VFD model series in the regular

    manufacturing range of the manufacturer. Along with the offer the Vendor should

    submit the supply record and satisfactory performance record for 8000 Hr

    running of the VFD supplied in India or abroad in a hydrocarbon industry

    (Preferably in a petroleum oil pipeline).

    5.3 Vendor shall ensure availability of spare parts and maintenance support services

    for the offered equipment for at least for 15 years from the date of supply. The

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 6 of 35

    offered VFD manufacturer should have their maintenance service & spares supply

    network in India to provide quick maintenance service & Spares supply support.

    The vendor shall indicate the source for supply of spares & Maintenance service

    location in India.

    5.4 Vendor shall ensure proper coordination with the driven equipment supplier in

    selection / sizing of offered variable frequency drive system.

    6.0 TECHNICAL REQUIREMENT

    6.1 Performance Requirement

    6.1.1 The system shall be fully digital, Microprocessor based, energy efficient, and shall

    provide very high reliability, high power factor, low harmonic distortion and low

    vibration and wear and noise. It shall be easy to install in minimum time and

    expense and no special tools shall be required for routine maintenance.

    6.1.2 The system shall be designed to deliver the motor input current and torque for the

    complete speed torque characteristics of the driven equipment, with maximum

    input supply voltage variation of +10% and frequency variation of +3%. The

    system shall be suitable for the load characteristics and the operational duty of

    the driven equipment.

    6.1.3 It shall be capable of withstanding the thermal and dynamic stresses and the

    transient mechanical torque, resulting from short circuit. Any damage resulting

    from such a short circuit or internal fault shall be limited to the component

    concerned.

    6.1.4 The drive system shall be designed to operate in one or more of the following

    operating modes as to suit characteristics of the driven equipment or specified in

    the data sheet:

    a. Variable torque changing as a function of speed i.e. speed squared

    b. Constant torque over a specific speed range.

    c. Constant power over a specific speed range where the torque decreases when speed increases.

    d. Any other as specified in data-sheet

    6.1.5 The drive controller shall be equipped with microprocessor based digital regulator

    with programmable functions. The power control regulator logic shall provide for

    an acceleration / deceleration current limit curve and shall be capable of field

    adjustments without shutting the system down. Linear acceleration and

    deceleration shall be separately programmable from 0.1 second to 20 second.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 7 of 35

    6.1.6 The system shall be suitable for single quadrant operation and the speed variation

    shall be within range 10-110% with speed set accuracy of +1% of rated maximum

    speed and steady state regulation of +0.5% of rated speed.

    The total harmonic distortion (THD) of the voltage and current at inverter output

    shall be as per IEC 61800-4 and it shall be considered in the design of the motor.

    6.1.7 Harmonics at the supply side of the drive system i.e. at primary of the main input

    transformer shall be restricted within the maximum allowable levels of current

    and voltage distortion as per recommendations in the latest edition of IEEE-519.

    Harmonic studies shall be conducted with maximum and minimum system fault

    level, cable capacitance, system equipment reactance etc. The studies shall

    highlight but not be limited to maximum load current, expected resonant

    frequencies, need of harmonic filters, sequence of switching of filters, voltage wave

    form etc.

    6.1.8 Unless otherwise specified, the overload capacity of the controller shall be 150% of

    rated current of motor for one minute for constant torque applications, and 115 %

    of rated current for one minute for variable torque applications at rated voltage. If

    the motor load exceeds the limit, the drive shall automatically reduce the

    frequency and voltage to the motor to guard against overload. If load demand

    exceeds the current limit for more than 1 minute, the drive shall shut down to

    prevent over heating of the motor and damage to the drive.

    6.1.9 During operation, the system shall be capable of developing sufficient torque

    under all load conditions to respond to a 20% alteration in speed set point within

    a time limit up to 60 seconds.

    6.1.10 The integrator action of the speed set point alteration shall be independently

    adjustable for both an upward and a downward alteration. The minimum time

    interval between set point adjustments by the distributed control system shall be

    considered as 10 seconds.

    6.1.11 The drive shall trip in case the speed exceeds 110% of the maximum operational

    speed or reduces to 95% of the minimum operational speed for more than 10

    seconds.

    6.1.12 Maximum noise level from the drive at 1-meter distance, under rated load with all

    normal cooling fans operating shall not exceed 85 dBA.

    6.1.13 Variable frequency drive shall be arranged so that it can be operated in an open

    circuit mode, disconnected from the motor for startup adjustments and

    troubleshooting / maintenance.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 8 of 35

    6.1.14 VFD should have by-pass system for running of motor on DOL in case of any

    problem in VFD. By-pass system should be provided with 3 vacuum contactors of

    6.6 KV voltage level & suitable current rating corresponding to Motor & VFD

    rating. All the three contactors shall have Mechanical & Electrical interlocks. Also,

    Contactors should have Electrical interlock with VFD. Vendor is to furnish the

    detailed scheme, catalogue & datasheet of contactor, interlock details etc. with

    VFD for owner approval.

    6.1.15 Voltage at Motor Neutral shall be maintained at ground potential for the total

    operating condition.

    6.1.16 Motor space heater supply for approximate rating of 240 V, 400 Watts is to be

    provided in VFD Panel interlocked with VFD Run command i.e. when Motor is

    running, motor space heater shall be OFF and when Motor is stopped, motor

    space heater shall be ON. In case of bypass mode operation of Motor, a contact

    shall be taken from Bypass Mechanism so that logic for Space heater is ensured

    i.e. heater is ON when Motor is stopped and vice-versa.

    6.2 Control Requirement

    6.2.1 The system shall operate on constant v/f supply with required boost capability in

    low frequency mode of operation.

    6.2.2 Short time voltage dips up to 20% of nominal voltage (e.g. in case of a large motor

    start up connected to the same bus as VFD) shall not cause the control system to

    stop functioning and shall not trip the drive system.

    6.2.3 The system shall also be equipped with a facility which will restart the system in

    case of voltage dip over 20% of power interruptions for min. 2 seconds, with

    recovery of the voltage to its nominal value, with a facility to block the automatic

    restart if required by the operator. Upon restart the converter shall be capable of

    synchronizing onto a rotating motor and develop full acceleration torque within 10

    seconds.

    6.2.4 The system shall be suitable for number of starts as per the specifications of the

    Motor in chapter-3.

    6.2.5 The power controller shall be controlled to always start the motor in the forward

    direction. Logic shall be provided to prevent the motor from being started in the

    reverse direction.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 9 of 35

    6.2.6 The drive motor shall be speed controlled corresponding to 4-20 mA or 0-10V

    reference input signal, the drive shall automatically run at constant speed as at

    80-110% of the last speed reference available prior to the loss of signal.

    6.2.7 It shall be possible to vary the speed of the drive in either Local or Remote mode.

    Local / Remote selection shall be from VFD panel unless otherwise specified.

    a. With the selector switch in Local mode, the operator shall be able to set the

    speed through keypad, mounted on front of the drive panel.

    b. With the selector switch in Remote mode, speed of the motor shall be

    controlled from a 4-20 mA signal, from owners PLC/SCADA system. The

    relationship between the speed, torque and the reference signal (4-20mA)

    within the operational speed shall be linear. Necessary equipment required for

    interfacing with PLC/SCADA shall also be provided in the drive panel.

    6.2.8 The required provision for the interface with remote PLC/SCADA located at control

    room shall be through hardwiring of interface signals (DI/DO/AI/AO) with

    potential free contacts and transducers. Also, provision for MODBUS

    communication (RS 485) from VFD to Owners control panel shall be made

    available. Vendor shall provide protocol details, mapping and addresses to be

    taken by Owners panel.

    6.3 Panel Construction

    6.3.1 The drive shall be suitably housed in sheet steel panels fabricated with 2 mm

    thick cold rolled sheet steel. The panel shall be suitable for indoor installation. The

    panel shall be free standing, dust and vermin proof with degree of enclosure

    protection as IP-4X. The maximum and minimum operating height shall be 1800

    mm and 300 mm respectively.

    6.3.2 The cable entry shall be from the bottom of the panel and bolted un-drilled gland

    plate shall be provided. Clamp type terminals shall be used for connection of all

    wire up to 10 mm2 and terminal for higher sizes shall be bolted type suitable for

    cable lugs. Minimum space for power cable termination shall be 600 mm clear

    from bottom of the cable gland plate.

    6.3.3 Bus bars shall be of electrolytic copper/aluminium, colour coded separately for AC

    and DC system. All the live parts shall be sleeved / shrouded to ensure complete

    safety to personnel intending to carry out routine inspection by opening the panel

    doors. All the equipment inside the panel and on the doors shall be provided with

    suitable nameplate.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 10 of 35

    6.3.4 The panel shall include suitable semi conducting power devices (Diodes /

    IGBT/IGCT/SGCT) modules with protective devices, reactors (if required), filters (if

    required), control circuit, control accessories, indication and annunciation etc. The

    construction of the panel shall provide effective protection against electromagnetic

    emissions and shall be the design requirement of integrated standards.

    6.3.5 Upstream breaker ON/OFF/TRIP indications and remote breaker closing and trip

    push button shall be provided on the front door.

    6.3.6 Safety interlock shall be provided so that power cabinet cant be opened unless the

    upstream breaker is disconnected, safety-grounding switch is closed and DC link

    capacitor is discharged.

    6.3.7 All the switches, component and accessories, which are essential for normal and

    emergency operation, shall be mounted on the door and shall be operable

    externally. All the analogue instruments, where provided, shall be switchboard

    type, back connected, 96 mm x 96 mm. Scale shall have red mark indicating

    maximum permissible operating rating.

    6.3.8 Panels except power cell chamber shall be provided with illuminating lamp with

    switch and fuse. 5/15A, 240V power socket with switch and fuse shall be

    provided. Each panel shall have space heater with switch fuse/MCB and variable

    setting thermostat.

    6.3.9 Copper earth bus of minimum size 30 x 6 mm upto short circuit withstand

    capacity of 31.5 KA and 50 x 6 mm for a short circuit withstand capacity above

    31.5 KA shall be provided in the panel with provision for connection to Owners

    plant earth grid. All the non-metallic components / parts shall be connected to the

    main earth bus bar. Separate earth bus bar and stud for electronic control system

    shall be provided.

    6.3.10 All the metal parts shall be treated so as to ensure efficient anti-corrosive

    protection. Hardwares shall be zinc passivated or electro-galvanized. Panel

    enclosure and structure supports shall be thoroughly cleaned and degreased to

    remove mill scale and rust etc. External surface shall be prepared for final

    painting shade of RAL 7032 (Siemens grey) as per DIN.

    6.3.11 All panels shall be of same height so as to form a uniform line-up, to give good

    aesthetic appearance.

    6.3.12 All the control wiring shall be enclosed in plastic / metal channel. Each wire shall

    be identified at both ends by self-sticking wire marker tapes or PVC ferrules.

    Power and control wiring inside the panel shall be done with BIS approved, PVC

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 11 of 35

    insulated, fire retardant, copper conductor wire 1.5 mm2 size wire shall normally

    be used provided the control fuse rating is 10 Amps or less and 2.5 mm2 size for

    control fuse rating 16 A & above for electrical circuits and 0.5 mm2 for electronic

    circuits. All wires shall be ferruled and terminals shall be properly numbered,

    minimum 20% spare terminal shall be provided.

    6.3.13 All electronic modules and components shall be accessible from front of panel

    only. Modular assemblies for both the system control electronic equipment and

    power electronic equipments shall be used.

    6.3.14 All low voltage compartment and cabling shall be electrically and physically

    separated from the high voltage compartment.

    6.3.15 Suitable removable type hooks shall be provided for lifting the panel.

    6.3.16 Suitable transparent insulating material shall be used for covering live

    components.

    6.3.17 Drive keypad, operator control panel required for control, monitoring and

    measurements shall be supplied and installed outside the panel on the front door.

    It shall be accessible for operation without opening the front door and shall be

    non-removable type.

    6.3.18 All equipment shall be complete with cable glands, lugs etc. and cable glands shall

    be double compression type.

    6.3.19 DC link capacitor and pre-charging and discharging circuit shall preferably be

    mounted in the rear of the panel.

    6.4 Cooling

    6.4.1 The drive panel shall be naturally air cooled as per manufacturers standards. If

    unavoidable, forced type-cooling system shall be provided. Vendor shall ensure

    that the panel dimensions and flow paths have been designed for continuous

    running at the specified ambient without over hearting & suggest the cooling

    system to be provided in VFD room considering heat generation in VFD & 50 deg

    Cent ambient temp.

    6.4.2 For fan cooled drives, redundant cooling fans (N+1) shall be provided. In case

    the redundant fan is not possible to be mounted, same shall be supplied

    loose.

    6.4.3 Necessary starter shall be provided with in the VFD panels for the Ventilation fans

    and any other auxiliary motors etc. The system provided shall be interfaced with

    drive starting and shut down such that safety interlocks such as Start Permissive

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 12 of 35

    from cooling system to drive and trip signal from cooling system to drive in case of

    cooling system failure etc. shall be incorporated in the overall sequence logic.

    6.5 Equipment / Component Specification

    6.5.1 Motor

    The motor shall be designed, constructed and tested in accordance with the

    owners specification / data sheet (refer specification no. 9579-02-TS-101) for high

    voltage induction motor, in addition to the following requirements:

    a. The motor shall be suitable for operation with a solid state power supply

    consisting of an adjustable frequency inverter for speed control and DOL.

    b. The motor shall be suitable for the current waveforms produced by the power

    supply including the harmonics generated by the drive.

    c. The motor shall be designed to operate continuously at any speed over the

    range (10-110%) of rated speed unless otherwise specified in data sheet.

    d. The permitted voltage variation should take into account the steady state

    voltage drop across the AC drive and all other system components upstream

    of the motor.

    e. The motor shall be constructed to withstand torque pulsations resulting from

    harmonics generated by the solid-state power supply.

    f. The motor insulation shall be designed to accept the applied voltage

    waveform, within the Vpeak and dv/dt limits as per IEC-61800-4.

    g. The drive manufacturer shall be solely responsible for proper selection of the

    motor for the given load application and the output characteristics of the

    drive.

    For detailed motor specification and data sheet refer specification no. 9579-02-TS-

    101.

    6.5.2 Converter Transformer

    a) The converter transformer, if provided, shall be copper wound dry type.

    Insulation class of dry type transformer shall be H with temperature rise of

    body limited to 75C. Dry type transformer shall preferably be mounted inside

    the drive system panel. The impedances of converter input transformers with

    more than one secondary winding for minimum 18 pulse systems shall be

    selected to ensure equal load / current sharing between the secondary

    windings, the converters and the motor windings under all operational

    conditions including starting and restarting.

    b) The transformation ratio, impedances, taps and secondary voltage shall be

    chosen by the drive vendor to optimize system performance.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 13 of 35

    c) The transformer shall be designed, manufactured and tested in accordance

    with latest applicable Indian standards or equivalent international standards.

    d) Transformer for operation with converters shall be suitable for operation with

    non-sinusoidal wave shape and DC components under normal and abnormal

    conditions of the system without exceeding the temperature.

    6.5.3 Power Converter

    a. The static power converter shall consist of a line side converter for operation as

    a rectifier and a load side power converter for operation as a fully controller

    inverter. Power converter shall be fast switching, most efficient and low loss

    type.

    b. The converter shall be co-ordinated with the transformers. The converter shall

    be able to withstand a three phase short circuit current until interrupted by

    normal breaker operation.

    c. Adequate short circuit and over voltage protection shall be provided for the

    converter and inverter system.

    d. All power converter devices shall include protective devices, snubber networks

    and dv/dt networks as required.

    e. The current rating of the converters semi-conductor components shall not be

    less than 120% of the nominal current flowing through the elements at full

    load of the VFD through the whole speed range. If the parallel connection of

    semi conductor is applied, the above current rating shall not be less than

    140% of the above values.

    f. All power diodes shall be of silicon type with minimum VBO rating at 2.5 times

    the rated operating voltage.

    g. The power converter circuit shall be designed so that motor can be powered at

    its full nameplate rating continuously without exceeding its rated temperature

    rise nor reducing its service factor due to harmonic currents generated by the

    inverter operation.

    h. The conversion devices and associated heat sinks shall be assembled such that

    individual devices can be replaced without requiring the use of any special

    precautions / tools.

    i. The cooling system of the electronic components, if provided, shall be

    monitored and necessary alarms shall be provided to prevent any

    consequential damage to the power control devices.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 14 of 35

    j. All power controller devices shall be protected with high speed semiconductor

    grade fuse. I2t particulars of the power controller devices and the fuses shall be

    supplied along with the calculations in support of the selection of fuses.

    k. Offered system shall also take in account the distance between drive panel and

    motor and system shall include all material and accessories to make system

    suitable for a distance of 350 m unless otherwise specified in the data sheet.

    6.5.4 Output filter

    Vendor shall ensure that converter design is in such a way that both voltage and

    current harmonics are within the limits as specified in IEEE-519. Output filter

    shall be provided, if required. Output filter capacitors shall be provided with

    discharge circuits to ensure that all residual stored charge is reduced to less than

    50 V DC within 30 seconds after a loss of AC voltage. All capacitor shall be

    maintenance free and self-healing type.

    The VFD system shall inherently protect motor from high voltage dv/dt stress,

    independent of cable length to motor. Output filter shall be an integral part of the

    VFD system and included within the VFD enclosure.

    6.5.5 DC Link Reactor (For CSI drive)

    Smoothing reactors for the DC link shall be designed to sufficiently decouple the

    rectifier and inverter portion of the converter and to limit fault currents in this

    circuit.

    Unless otherwise specified, the reactor shall be air-cooled or fan cooled typed

    located within the panel.

    Reactor shall be suitable for operation with the non-sinusoidal current wave

    shapes and DC components under all operational conditions of the system without

    exceeding its temperature limits.

    6.6 PROTECTION, CONTROL METERING AND INDICATION / ANNUNCIATION

    REQUIREMENTS

    6.6.1 The manufacturer shall provide all the necessary system control, protection, alarm

    equipment and metering for the entire drive system and its auxiliary equipment

    and its description shall be furnished along with the offer including the details of

    the system built-up.

    6.6.2 Automatic sequence control shall include start-up of cooling system, auxiliary

    system of the motor, interlock checking, automatic start and run-up of drive,

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 15 of 35

    planned and emergency shutdown. The same shall be processed through

    microprocessor based system.

    6.6.3 All protection, metering, indication, alarm, annunciation and fault diagnostic as

    required, shall be available at PLC over communication network (RS-485).

    Necessary communication module shall be provided in VFD accordingly.

    6.6.4 Operator Control Panel.

    a. Each drive shall be equipped with a front mounted operator control panel

    consisting of a backlit alphanumeric display and a keypad with keys for

    parameterization and adjusting parameter which shall not be limited to start /

    stop, local / remote, auto / manual, increase / decrease, menu navigation and

    protection and measurement parameter selection etc. Display shall consist of

    minimum 2 lines of 16 characters- LCD type.

    b. All parameters names, fault messages, warnings and other information shall

    be displayed in complete English words or Standard English abbreviations to

    allow the user to understand what is being displayed without the use of a

    manual or cross-reference table. This shall also be used for the modification of

    all electrical values, configuration parameters, drive menu parameters,

    application and activity function access, faults, local control, adjustment

    storage, self test and diagnostics. Keypad shall be operable with password for

    changing the protection setting, safety interlock etc. However the parameters

    such as measurements, setting, mode of drive etc. shall be allowed to be

    viewed without any password.

    c. Operator console shall have facility / port to connect external hardware such

    as Lap-Top etc. Console shall have facility for upload and download of all

    parameter settings from one drive to another identical drive for start up and

    operation.

    d. Drive system control shall also have facility to receive tripping signal from

    upstream breaker for tripping and also provision for closing upstream breaker

    after all required process parameters are achieved.

    e. User-friendly software for operation and fault diagnostic shall be loaded in the

    drive system panel before commissioning.

    6.6.5 Protective features

    The system offered shall incorporate adequate protective features, properly

    coordinated for the drive control and for motor but not limited to the following:

    i) Converter transformer: short circuit, over current, earth fault & winding

    temperature high

    ii) Incoming and outgoing line surge protection with suitably designed surge

    diverter.

    iii) Under / over voltage protection

    iv) Phase loss, phase reversal protection

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 16 of 35

    v) Programmable over current protection and under load protection

    vi) Inverter fault.

    vii) Over frequency/speed operation.

    viii) Ventilation loss.

    ix) Over temperature of equipment

    x) Specific motor protection, including motor winding, bearing temperatures,

    over current, overload, negative phase sequence, locked rotor and earth

    fault protections etc.

    xi) System earth fault protection.

    xii) Speed reference loss

    6.6.6 Control

    The following minimum controls shall be provided as a part of the Operator

    Control Panel or through separate switches on the front panel door.

    i) Start / stop(in local/remote mode)

    ii) Speed control (Raise / lower)

    iii) Acknowledge/Accept/ Test Push Button for annunciation

    iv) Auto / Manual / Test Mode select

    v) Emergency stop

    vi) Trip-Remote Breaker

    vii) Local Remote

    viii) Sequential Switching of filters

    6.6.7 Indications

    Vendor shall provide indications as required for normal operation and for easy

    maintenance, which shall not be limited to the following indications.

    i) Motor running

    ii) Motor stopped

    iii) VFD System Fault

    iv) System ready to start

    v) Motor zero speed

    vi) AC mains ON

    vii) Motor over speed

    viii) VFD ON

    ix) Remote breaker trip

    x) Owners speed reference fail

    xi) Input Isolator ON

    xii) Input Isolator OFF

    xiii) Output Isolator ON

    xiv) Output Isolator OFF

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 17 of 35

    xv) Bypass Isolator ON

    xvi) Bypass Isolator OFF

    xvii) Motor Space heater ON

    xviii) Motor Space heater OFF

    xix) Rectifier output ON

    xx) Motor Zero Speed

    Above indications may be provided as a part of the operator control panel, i.e. door

    mounted keypad or through indicating lamps / LEDS in VFD/Isolator Panel.

    Potential free contacts of items i-iv shall be wired separately for remote indications

    in Owners SCADA systems.

    6.6.8 Metering

    Digital display of the following parameters shall be as a part of the Operator

    Control Panel, selectable by the operator.

    i) Input AC voltage

    ii) Input AC frequency

    iii) Input AC Current

    iv) Output voltage

    v) Output current VFD

    vi) Output frequency

    vii) Motor speed

    viii) Hour Run

    ix) Necessary transducer shall be provided with 4-20mA output for indicating motor speed and motor current in Owners SCADA system.

    x) KW monitoring

    xi) KWh monitoring

    xii) Power factor

    xiii) Drive Thermal State

    6.6.9 Audio-visual annunciations

    a. Audio-visual window annunciations shall be provided on the front of the panel.

    All annunciations as required for normal and satisfactorily operation of the

    drive system shall be included as per vendor standards. These annunciations

    can be part of operator console panel.

    b. Vendor shall include audio-visual alarm as required for normal operation and

    maintenance of the system but not be limited to the following.

    i) Rectifier fuse failure

    ii) Main AC failure

    iii) Inverter fuse failure

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 18 of 35

    iv) Inverter overload

    v) Inverter high temperature

    vi) Cooling system failure

    vii) Motor failed to start

    viii) Transformer failure

    ix) Communication and measurement system unhealthy

    x) Motor Temperature High

    xi) Harmonic Filters Monitoring

    Common potential free contacts shall be provided for above annunciations and

    these shall be wired up to terminal block for owners use for remote alarm and

    monitoring.

    Alarm accept / reset push button is to be provided on the front door of the panel.

    6.7 Fault Diagnostic

    Fault diagnostic shall be built into the system to supervise the operation and

    failure of the system. The information regarding failure of any of the system

    including shut down of the system shall be available for a period of minimum 7 4

    days (96 hours) after a shut down even though no supply would be available to

    the system. The system may be totally de-energized for maintenance or otherwise.

    It shall be possible to retrieve the record of events prior to tripping of the system

    or de-energization. Auxiliary supply to the system components or to the

    electronics (firmware) for the diagnostics / display shall be taken care by the

    manufacturer for this purpose.

    6.8 External Power supply for auxiliary and Control Circuit

    Auxiliary power supply for devices external to VFD module, space heater supply

    for motor, VFD panel space heater, auxiliary power supply for transformers,

    cubicle lamps etc. shall operate on 240 volts single phase AC provided by Owner.

    All control circuit shall operate at 110V DC (Provided by owner).

    Vendor shall include supply of all control transformers, protective devices,

    required accessories etc. and any other control supply voltage as required for the

    system shall be derived from the power supply made available by owner.

    6.9 Reliability features

    The expected lifetime of the drive system shall be 20 years. The system including

    all individual components forming part of the system shall have an availability of

    minimum 0.997 and a minimum MTBF of 40,000 Hours.

    6.10 Maintenance features

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 19 of 35

    The controller design shall incorporates the following maintenance features:

    - Modular construction.

    - All components shall be easily accessible.

    - Standard diagnostics to aid maintenance personnel. These shall include LED

    or alphanumeric displays, test or measurement points.

    6.11 Painting

    All metal surfaces shall be thoroughly cleaned and degreased. Fabricated

    structure shall be pickled and then rinsed to remove any trace of acid. The under

    surface shall be prepared by applying a coat of paint and coat of yellow zinc

    chromate primer. After preparation of the under surface, the board shall be spray

    painted with two coats of final paint. Colour shade shall be RAL 7032 (Siemens

    grey) as per DIN.

    The finished panels shall be dried in stoving ovens in dust free atmosphere. Panel

    finish shall be free from imperfection like pin holes, orange peels, runoff paints

    etc. All unpainted steel parts shall be cadmium plated or suitably treated to

    prevent rust formation.

    7.0 CDL PANEL AND SYNCHRONOUS PANEL

    CDL or Common Drive Logic Panel functions as a common interface between

    VFD1, VFD2, Upstream and Downstream Breakers, Unit Control Panel (UCP)-A,B

    & C and Synchronous Panel.

    Main Functions of the CDR Panel are:

    Controls the VFD Start-up & Shutdown Sequence.

    Receives Commands & Provides Feedback to UCP and Station PLC

    Controls the downstream breaker line-up as per the VFD & Motor combination

    selection.

    Helps in Breaker Control during Synchronous change-over.

    Synchronous panel takes voltage sample from downstream breaker of each VFD,

    Upstream breaker of bypass and synchronize the VFD output with mains.

    8.0 INSPECTION, TESTING AND ACCEPTANCE

    8.1 All tests shall be carried out at the manufacturers works under his care and

    expense. The tests shall be witnessed by an inspector of Owner or of an agency

    authorized by the owner. Prior notice of minimum 4 weeks shall be given to the

    inspector for witnessing the tests.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 20 of 35

    8.2 The routine test shall be conducted on all the drive system. However type test

    shall be performed on one system of each rating and type. For the purpose of

    testing, drive system shall include input transformer, switchgears, converter,

    filters etc. as defined in clause 1.0.

    8.3 The Routine and Type tests to be performed on the drive system shall be as

    follows:

    8.3.1 Routine tests

    a. Visual Inspection

    It involves checking of the various equipments / components fault diagnostic

    unit, wiring, terminals, earthing ratings etc. in line with the approved drawings

    and visual inspection shall not be limited to the following:

    i) Dimensions and door layout vis--vis the approved drawings.

    ii) Degree of Protection of Cubicles.

    iii) Simulation facility of control signals for testing purposes.

    iv) Memory function of fault diagnostic.

    v) Interface capability

    vi) Voltage / current rating of power semi conductor elements.

    vii) Cable termination size and number of terminals, cable supporting etc.

    viii) Accessibility of components.

    ix) External signals and indication / alarm signals on converter.

    x) Earthing of cubicles and cubicle doors.

    b. Insulation test

    c. Checking of auxiliary devices

    d. Checking the protective devices

    e. Checking of control and functional requirements

    f. Automatic restart / re-acceleration

    g. Test capability to restart the system and resynchronize converter onto running

    motor after a voltage interruption.

    h. Light load and functional test

    i. Load Duty test

    8.3.2 Type Tests

    a. Efficiency

    b. Temperature rise

    c. Torque pulsation

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 21 of 35

    d. EM Immunity

    e. EM Emission

    f. Line side voltage and current distortion content

    g. Power factor

    h. Audible noise

    i. High voltage test on transformer

    j. Speed loop test capability to ride through voltage less than 80%.

    k. Total Harmonic Distortion at input side

    l. Allowable full load current Vs Speed

    m. Dynamic Performance

    n. Current limit and Current loop test

    Type test certificate from Independent Testing Agency for similar equipment can

    be accepted for a, b, c, d & e as mentioned above.

    8.3.3 Additional tests on transformers/other auxiliaries shall be carried out as per the

    applicable codes/standards.

    9.0 CERTIFICATIONS

    The Variable Frequency Drive shall have test certification from internationally

    recognized test house i.e. CE/UL/FM/IEC/CSA/NEMA or equivalent. The VFD

    and associated equipment shall have test certificates issued by recognized

    independent test house (CIMFR/BASEEFA/LCIE/UL/FM or equivalent). All

    indigenous motors shall conform to Indian Standards and shall be certified by

    Indian testing agencies. All motors (indigenous and imported) shall also have valid

    statutory approvals as applicable for the specified location.

    10.0 PACKING AND DESPATCH

    The equipment shall be divided into several shipping sections for protection and

    ease of handling during transportation. The equipment shall be properly packed

    for transportation by ship / rail or trailer. The equipment shall be wrapped in

    polyethylene sheets before being placed in wooden crates / cases to prevent

    damage to the finish. Crates / cases shall have skid bottoms for handling. Special

    notations such as Fragile, The side up, Weight, Owners particulars, PO Nos.

    etc. shall be clearly marked on the package together with other details as per

    purchase order.

    The equipment may be stored outdoors for long periods before installation. The

    packing should also be suitable for outdoor storage areas with heavy rains / high

    ambient temperature unless otherwise agreed.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 22 of 35

    11.0 Software of PLC of VFD

    A copy of PLC software of the VFD along with any hardware / software key is to be

    provided on DVD / CD on placement of purchase order as a backup for

    maintenance of the VFD.

    License software (both run time and works) to be supplied.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 23 of 35

    13.0 DRAWINGS AND DOCUMENTATION

    Following drawings and documents in English language shall be furnished as per the schedule mentioned hereunder. It is mandatory for vendor to take approval of all post PO documents/drawings before proceeding with manufacturing of VFD and its By-pass system.

    S. N.

    Drawing/ Document Time of submission No. of

    sets

    1 Technical particulars/ catalogues for the offered system and the detailed description

    To be submitted

    Two

    2 Block diagram of the system Along with the technical bid Two

    3 Complete technical details of each equipment / component

    Along with the technical bid Two

    4 GA layout showing overall dimensions Along with the technical bid Two

    5 Single line diagram and control schematic showing equipment rating

    Along with the technical bid Two

    6 The detailed scheme, catalogue & datasheet of isolator, interlock details with VFD

    Along with the technical bid Two

    7 List of spares for 2 years of maintenance Along with the technical bid Two

    8

    Reference list along with PO copies and performance certificates from end user in India only to whom such system (VFD of same make & similar design for same or higher rating) has been supplied.

    Along with the technical bid Two

    9 Detail of cooling system to be provided in VFD room

    Along with the technical bid Two

    10 Copy of drive system certifications as per clause no. 8.0

    Along with the technical bid Two

    11

    Details of after sales (Service) network in India with addresses, contact numbers, manpower details and level of expertise (in terms of drive rating etc.) available.

    Along with the technical bid Two

    12 BOM of cables in case converter transformer is mounted outside VFD Panel

    Along with the technical bid Two

    13 Block diagram of the system On placement of purchase order Two

    14 Complete technical details of each equipment / component

    On placement of purchase order Two

    15 G.A. layout showing overall dimensions On placement of purchase order Two

    16 Single line diagram and control schematic showing equipment rating , interlocks, control and power cable scheduling etc.

    On placement of purchase order Two

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 24 of 35

    17 Protection co-ordination diagram On placement of purchase order Six

    18 Torque / speed/ current / power factor of the system

    On placement of purchase order Six

    19 Foundation/mounting drawing of VFD, Transformer, Bypass Isolator etc.

    On placement of purchase order Six

    20 Special installation requirements for the VFD system and cables

    On placement of purchase order Six

    21 Operation and Maintenance manuals On placement of purchase order Three

    22

    Terminal details for wiring to external station control panel including Potential free contacts, DI, DO, AI & AOs separately.

    On placement of purchase order Three

    23 QAP for all independent equipments for VFD system.

    On placement of purchase order Three

    24 Detailed document on control philosophy

    On placement of purchase order Six

    25 Detailed Single Line Diagram Along with the technical bid Two

    26 Suggestive Sub-station Equipment Layout Along with the technical bid Two

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 25 of 35

    14.0 DATA SHEET FOR HV VARIABLES SPEED DRIVES

    DATA FURNISHED BY OWNER

    Sl. no

    FEATURES Description

    1. BASIC REQUIREMENTS

    i. Required rated output capacity : * (As per motor ratings / Pump

    Load)

    ii. Torque requirement : As per pump requirement

    iii. Load/driven equipment details : Horizontal Centrifugal pumps

    iv. Load torque details : Centrifugal pumps

    v. Drive system : One drive for each pump

    vi. Reacceleration of motor : As per Operational requirements of

    Pump specifications

    2. SITE CONDITIONS

    a) Location : As per SOR

    b) Design Ambient temperature : 5- 500C

    c) Altitude : Less than 1000m above mean sea

    level

    d) Humidity (max) : 95%(relative)

    e) Location : Indoor

    f) Installation area for VFD : Indoor

    g) Installation area for motor &

    LCP

    : Hazardous zone-2, gas group-

    IIA/IIB, Temperature class-T3,

    Tropical, dusty, corrosive.

    3 INPUT POWER SUPPLY

    SYSTEM CONDITIONS

    a) No. of phases : Three

    b) AC input voltage : 6.6KV

    c) Voltage fluctuation : 10%

    d) Rated frequency : 50 Hz

    e) Frequency fluctuation : 3%

    f) System fault level : 25 KA (1 sec.)

    4 SYSTEM REQUIREMENTS

    a) Speed range required : As per Pump requirement

    b) Speed reference signal : 4-20mA

    c) Operation in case of loss of

    reference signal : Last speed reference/ a set speed

    lower than previous reference /

    either of above as per manufactures

    standard.

    d) Acceleration time : As per clause 6.1.5

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 26 of 35

    Sl. no

    FEATURES Description

    e) Deceleration time : As per clause 6.1.5

    f) Communication facility between

    Owners control system and

    drive

    : Required

    g) Harmonic study : Required

    h) Braking : Flux braking/ DC injection

    braking/ either of the above

    i) Converter transformer : Dry type

    j) Output voltage of VFD system : 6.6KV, three phase (without using

    any output transformer)

    k) Type of converter/rectifier : Minimum 18 Pulse

    l) Harmonic filters on supply bus : Vendor shall ensure that converter

    design is in such a way that both

    harmonics V&I harmonics are

    within limits as specified in IEEE-

    519

    m) Power factor improvement

    feature as part of harmonic

    filters

    : Vendor shall ensure that converter

    design is in such a way, so that

    minimum PF at input of each VFD

    is 0.99 lag for the varying load of

    10% to 110%

    5 CONTROL LOCATION

    a) Local/Remote operation : Required

    b) Local/Remote selector switch

    location

    : At VFD panel

    c) Speed raise/Lower signal : At VFD panel

    d) Distance of VFD panel from

    Motor

    : 350m (maximum)

    6 COMMUNICATION

    On communication network

    (compatible RS 485 port) the

    following details shall be

    available

    a) Protection features : Yes

    b) Indication : Yes

    c) Metering : Yes

    d) Annunciation : Yes

    e) Diagnostic : Yes

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 27 of 35

    15.0 TECHNICAL DATA TO BE FURNISHED BY MANUFACTURER

    (To be submitted separately for each location)

    1. Make : Siemens / ABB / Rockwell / Yaskawa /

    Hitachi

    2. Model No. : *

    3. Rating of drive panel

    a) Output in amperes : * (to be provided)

    b) Rating expressed at

    (torque)

    : *

    c) Rating declared at

    (temp.)

    : 50 Deg C

    d) Switching frequency at

    declared rating

    : * Hz

    4. Applicable code / standards : CSA,UL,IEC,NEMA,ANSI,IEEE,CE/equivalent

    5. Drive type : CSI/VSI

    6. Speed range : 10% to 110% of rated motor speed

    7. Speed reference signal type : 4-20mA

    8. Input power supply ratings : 3 Phase 6.6Kv

    9. Voltage : 6600 V + 10%

    10. Frequency : 50 Hz + 3%

    11. Output voltage at 10% input voltage full speed, full

    load

    : 6600 v

    12. Overload capability of

    converter

    a) 115% In( for variable

    torque) for

    : *

    13. Overall efficiency of drive

    (excl. motor) at

    a) 100% load : *

    b) 75% load : *

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 28 of 35

    c) 50% load : *

    14. Overall power factor of drive (excl. motor) at

    :

    a) 100% load : *

    b) 75% load : *

    c) 50% load : *

    15. AC Output :

    a) Rated frequency range : *

    b) Accuracy of frequency : *

    16. Dynamic response :

    a) Speed fluctuation band : *

    b) Speed recovery time after 100% torque step

    : *

    17. Waveform distortion factor (% harmonics) in output / input waveform.

    : *

    (Number of harmonics and magnitude of each harmonic generated shall be furnished)

    18. Output short ckt. Capability and duration

    : *

    19. Controls At Drive level

    (Please answer as provided / not provided

    a) System start : *

    b) System stop : *

    c) Speed raise : *

    d) Speed lower : *

    e) Drive frequency setting : *

    h) Remote bkr.trip : *

    i)Electronic Ramp function : *

    j) Speed and current

    controller

    : *

    k) Drive ready to start signal : *

    l) Ammeter : On digital operator or separate digital type

    m) Speed indicator : On digital operator or separate digital type

    20. a)Diodes / IGBT : *

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 29 of 35

    /IGCT/SGCT configuration

    Number and Ratings

    b)Total No. of diodes / IGBT

    /IGCT / SGCT

    Number and Ratings

    : *

    21. Cooling system :

    i) Type : Fan forced cooling

    ii) Redundancy in cooling

    units

    : *

    22. a)Type of feed-back for

    speed control

    : Open loop Vector

    b)Speed control accuracy : *

    23. List of controls provided at the front of panel (As per specification)

    : Yes / No

    24. List of status measuring devices provided at the front of panel (as per specification

    : Yes / No

    25. List of status indication and annunciation provided (as per specification)

    : Yes / No

    26. Type of electronic card mounting arrangement

    : *

    27. DIMENSION

    a) Length : *

    b) Height : *

    c) Depth : *

    d) Weight of cubicle : *

    (Dimensional details of all panels shall be furnished).

    28. Degree of protection for

    enclosure

    : * (Minimum IP 4X)

    29. Paint shade : As per specification

    30. Heat output of Panel : *

    31. Whether Air conditioning is required for these panels

    : *

    32. Control supply voltage and Aux. Power requirement

    : 415 V, 3 phase, 4 Wire

    33. Converter Transformer (If :

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 30 of 35

    applicable)

    a) Make : *

    b) Type of transformer : Dry type

    c) KVA Rating : *

    d) Voltage ratio : *

    e) Vector group : *

    f) Taps : *

    g) Insulation class : F (Min) for dry type transformer.

    f) Impedance : *

    g) Efficiency : > 98%

    h) Weight : *

    i) Winding RTDs /

    Thermistors

    : Minimum 1 per phase

    g) Overall dimension

    (L&BXH)

    : *

    h) Transformer accessories : *

    * data to be filled up & furnished with the offer

    Note:

    1. If synchronous and de-synchronous transfers are required it shall be in "bumpless

    close transition" only. Open transition is not acceptable.

    2. Motor to be protected from all the electrical faults by VFD when it is in VFD mode and

    by "DOL Feeder" when it is in DOL mode.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 31 of 35

    16.0 COMPLIANCE / EXCEPTIONS AND DEVIATIONS FOR OFFERED VFD

    NAME OF BIDDER:

    Bidder to stipulate here exceptions and deviations to Bidding Document, if any,

    separately for technical clauses in respect of the specifications.

    Sl.

    No.

    Clause

    No.

    Accepted

    (Tick one)

    Deviation proposed by Bidder if No for column no. 3

    1 2 3 4

    1. 1.0 Yes / No

    2. 2.0 Yes / No

    3. 3.0 Yes / No

    4. 4.0 Yes / No

    5. 5.0 Yes / No

    6. 6.0 Yes / No

    7. 7.0 Yes / No

    8. 8.0 Yes / No

    9. 9.0 Yes / No

    10. 10.0 Yes / No

    11. 11.0 Yes / No

    12. 12.0 Yes / No

    13. 13.0 Yes / No

    14. 14.0 Yes / No

    Note:

    1. If the space is not sufficient, separate sheets to be attached as per this format.

    2. Bidder to note that clause no. 16.0 has been included in the Bidding document solely

    for the convenience of the Bidder so as to facilitate them to list out the deviations /

    exceptions both of technical and commercial nature from / to the bidding document.

    Owner will not recognise any deviations / exception (s) in respect of the specifications

    which is not listed at clause no. 16.0.

    3. Offers without fully filled clause no. 16.0 may be summarily rejected.

    (SIGNATURE OF BIDDER)

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 32 of 35

    15.0 List of the VFD Manufacturer or their Indian Representative

    Sl No VFD Manufacturer

    Indian Office / Representative

    1(a)

    1(b)

    Siemens

    Pittsberg

    USA

    Siemens

    Nasik, India

    Siemens Ltd.

    IIADT

    Post Box 85

    Thane Belapur Road

    Thane 400601

    Maharashtra

    2 Asea Brown Boveri

    Turgi

    Swizerland

    Asea Brown Boveri Limited,

    Drive Division

    Kosbahalli road,

    Nelemangla

    Bangalore

    Karnataka

    3 Rockwell Automation

    Cambridge

    Canada

    Rockwell Automation India Pvt Ltd

    A-66, Sector-64

    Noida-201301

    UP

    4 Yaskawa Electric Corporation

    YUKUHASHI

    Japan

    Larsen & Toubro Ltd

    Control & automation Business Unit

    Automation campus

    A-600, TTC Industrial Area

    Shil-Mahape Road

    Navi Mumbai - 400710

    5 HITACHI

    NOTE: Make of 6.6kV Downstream Breaker Panel, CDL Panel and Synchronization Panel

    shall be Siemens/ABB/Schneider Electric/L&T.

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 33 of 35

    TECHNICAL DATA SHEET

    FOR EXISTING

    HT MOTOR AT KHOPOLI

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 34 of 35

    PARAMETERS DESCRIPTION

    Motor Condition Existing

    Duty Centrifugal Pump

    Output, kW 750

    Volts, V 6600

    Phases 3

    Locked Rooter Torque 90% of F.L. torque

    Enclosure TEFV

    Frame XD40010

    Poles 2

    Speed, RPM 2988

    Full Load Current, Amp 76.5

    Frequency, Hz 50

    Temperature Rise 75OC by resistance

    Starting Current 636% of F.L. Current

    Protection IPW55

    Cooling Air-Cooled

    Mounting Foot

    Pull Out Torque 250% of Full Load Torque

    Stator Winding Diamond Coils Star Connected

    Net Weight, kg. 4875

    Bearing (DE/NDE) Roller/Ball & Roller

    Direction of Rotation Clock-Wise

    Starting DOL

    Lubrication Shell Alvania 3

    Main Terminal Arrangement

    No. of terminals 3 entry from below Peebles flameproof containing Phase Segregated type 15A

    Connections (Terminals/Phase) U V W/L1 L2 L3

    Space Heater Rating 240W, 240V, 1 Phase FLP terminal box

    Stator Winding RTDs Six platinum Resistors, wired to separate

    terminal box

    BASEEFA Certificate No. EX811075

    Insulation Class F

    Stator Connection Star

    Power Factor 0.89

  • 16-QMP-05-3B

    W

    ord

    Triune Energy Services Pvt. Ltd.

    New Delhi

    TECHNICAL SPECIFICATION FOR HV

    VARIABLE FREQUENCY DRIVE

    SYSTEM

    Std. / Doc. Number Rev.

    9579-02-TS-102 0

    Sheet 35 of 35

    SYSTEM CONFIGURATION:

    Proposed (2750KW)

    Proposed (2750KW)

    Existing (750KW)