    RTU560

    Data Sheet CT/VT Interface 560CVT10

    Doc-No.: 1KGT 150 623 V001 1 1

    CT/VT Interface 560CVT10

    Application

    The Current/Voltage Transducer Interface(CT/VT interface) is used for measuring ana-log AC input signals from three independentphases with 3 or 4 wire connections. Foreach phase voltage, current and power aremeasured directly, and a number of other pa-rameters derived from these in software. Theresults are transmitted to the RTU560.

    There are several versions available:

    Auxiliary Voltage (LO):3 current-, 3 voltage inputs (In1A)3 current-, 3 voltage inputs (In5A)4 current-, 4 voltage inputs (In1A)4 current-, 4 voltage inputs (In5A)

    Auxiliary Voltage (HI):4 current-, 4 voltage inputs (In1A)4 current-, 4 voltage inputs (In5A)

    Characteristics

    The CT/VT interface is a microprocessor-based Intelligent Electronic Device (IED) in-tended for current, voltage, power and en-ergy measurement.Distorted input waveforms with harmonics tothe 15th are therefore detected accurately.

    Additional functionality to provide functionsas fault current detection, minimum andmaximum logging and analog high and lowlimit supervision is available.

    The fault current is measured up to 20 timesnominal current. Therefore the current inputswithstand 50 times nominal current for 1 s.

    The CT/VT interface is equipped with one binaryoutput which can be used to indicate e.g. alarmfor over current.

    All CT/VT interfaces are mounted in the RTU cabi-net. Current and voltage inputs are connected viatransformer only (see Figure 1).

    The CT/VT interfaces are designed for mountingon DIN rails 35 mm.

    Meter OperationThe following metered parameters are available:

    Instantaneous Meter Values

    Measured by true RMS conversion and transmis-sion to the RTU560 of following values:

    Phase - Neutral Voltage 1N, 2N, 3N, Average

    Phase -Phase Voltage 1-2, 2-3, 3-1, Average

    Current Phase 1, 2, 3

    Fault Current Phase 1, 2, 3, N

    Active Power, Phase 1, 2, 3, Total

    Reactive Power, Phase 1, 2, 3, Total

    Apparent Power, Phase 1, 2, 3, Total

    Power Factor, Phase 1, 2, 3, Average

    Frequency,

    Phase Rotation

    Voltage / Current Harmonic Distortion (THD,

    current and voltage phase 1,2 and 3)

    Derived Meter Values

    calculation of Active, Apparent and ReactiveEnergy accumulated values (intermediate andend of period readings, delivery and con-sumption)

    calculation of Ampere Hours accumulatedvalues (intermediate and end of period read-ings, delivery and consumption)

    Neutral current (with 3 wire connection)

  • 8/9/2019 560CVT ABB

    2/6

    RTU560

    Data Sheet CT/VT Interface 560CVT10

    2 Doc.-No.: 1KGT 150 623 V001 1

    Functionalities

    With a powerful diagnostic tool the operator

    is able to fulfil below described tasks. As op-tion the related date can be transferred overthe communication link to the RTU and thecontrol system.

    Communications over RS485 port withModbus RTU Protocol

    User Mapping to speed up communica-tion

    Logging of Minimum and Maximum Val-ues

    Event Logging

    Trend logging (option)

    Waveform Capturing and phaseranalysis:

    Harmonic analysis for power quality analysis(up to 15th harmonic):

    Relay output for configurable alarm

    Configurable alarms for over voltage, overfrequency, over current and so on

    Fault current detection (Option)

    - configurable flexcurve for overcurrentalarm (in the same as IEC, ANSI curves)

    -

  • 8/9/2019 560CVT ABB

    3/6

    RTU560

    Data Sheet CT/VT Interface 560CVT10

    Doc-No.: 1KGT 150 623 V001 1 3

    Wiring

    Fig. 1: 3 phase with 3 wire connection Fig. 2: 3 phase with 4 wire connection

  • 8/9/2019 560CVT ABB

    4/6

    RTU560Data Sheet CT/VT Interface 560CVT10

    4 Doc.-No.: 1KGT 150 623 V001 1

    Technical Data

    In addition to the RTU560 general data, the fol-lowing applies:

    Input Channels

    VoltageU1, U2, U3, U4

    Range:10 ... 300V AC3 Phase, 3 or 4 WireLoad :

  • 8/9/2019 560CVT ABB

    5/6

    RTU560Data Sheet CT/VT Interface 560CVT10

    Doc-No.: 1KGT 150 623 V001 1 5

    Mechanical Layout

    Width 134.8 mm

    Height 70.3 mm

    Depth 149.5 mm

    Height 70.3 mm

    Enclosure for DIN Rail 35 mm

    Environmental Conditions

    Operating Tempera-ture

    -25 to +60 C

    Storage Temperature -40 to +80 C

    Relativehumidity

    10 95 %non condensing

    Ordering in formation

    560CVT10 R00011In = 1A, 3 voltage, 3current, Version LO

    1KGT 018900R0011

    560CVT10 R00015In = 5A, 3 voltage, 3current, Version LO

    1KGT 018900R0015

    560 CVT10 R0021In= 1A, 4 voltage, 4current, Version LO

    1KGT 018900R0021

    560 CVT10 R0025In= 5A, 4 voltage, 4current, Version LO

    1KGT 018900R0025

    560 CVT10 R0041In= 1A, 4 voltage, 4current, Version HI

    1KGT 018900R0041

    560 CVT10 R0045In= 5A, 4 voltage, 4current, Version HI

    1KGT 018900R0045

  • 8/9/2019 560CVT ABB

    6/6

    RTU560Data Sheet CT/VT Interface 560CVT10

    6 Doc.-No.: 1KGT 150 623 V001 1

    Note:We reserve the right to make technical changes or modifythe con-tents of this document without prior notice. With re-gard to purchase orders, the agreed particulars shall prevail.

    ABB AG does not accept any responsibility whatsoever forpotential errors or possible lack of information in this docu-ment.We reserve all rights in this document and in the subjectmatter and illustrations contained therein. Any reproduction,disclosure to third parties or utilization of its contents - inwhole or in parts - is forbidden without prior written consentof ABB AG.