Upload
jorge-bravo
View
210
Download
34
Embed Size (px)
Citation preview
MCAC-UTSM-2010-06 Contents
Contents i
Part 1 General Information ..................................................................................................... 1
Part 2 Indoor Units .................................................................................................................. 6
Part 3 Outdoor Units……………………………………………………………………………... 169
Part 4 Installation………………………………….…………………………….……..…..…….. 211
Part 5 Control……………………………………………………………………………………… 222
※The specifications, designs, and information in this book are subject to change without notice for product improvement.
UnReg
ister
ed
UnReg
ister
ed
MCAC-UTSM-2010-06 General Information
General Information 1
Part 1 General Information
1. Model Names of Indoor/Outdoor Units .......................... 2
2. External Appearance ...................................................... 3
2.1 Indoor Units ................................................................................. 3
2.2 Outdoor Units .............................................................................. 3
3. Nomenclature .................................................................. 4
4. Features ........................................................................... 5
UnReg
ister
ed
Model Names of Indoor/Outdoor Units MCAC-UTSM-2010-06
2 General Information
1. Model Names of Indoor/Outdoor Units 1.1 Indoor Units R22 (capacity multiply by 1000Btu/h)
Type Function 12 18 24 36 48 60
New Four-way cassette (compact)
Cooling only √ √
Cooling and heating √ √
Four-way cassette Cooling only √ √ √ √ √
Cooling and heating √ √ √ √ √
Duct Cooling only √ √ √ √ √ √
Cooling and heating √ √ √ √ √ √
High static pressure duct Cooling only √ √ √ √
Cooling and heating √ √ √ √
Ceiling & floor Cooling only √ √ √ √ √ √
Cooling and heating √ √ √ √ √ √
1.2 Outdoor Units Model of outdoor unit and corresponding indoor unit
Universal Outdoor unit Model Compressor type Compressor Brand Matched indoor units
Cooling Only
MOUB-12C Rotary Midea-Toshiba MCA2-12CR-Q MUB-12CR MTB-12CW-Q
MOU-18C-Q Rotary Midea-Toshiba
MCA-18CR-Q MCC-18CR-Q MCC-18CR-Q MTB-18CW-Q
MOU-24C-Q Rotary Midea-Toshiba
MCC-24CR-Q MUB-24CR-Q MTB-24CW-Q MHC-24CW-Q
MOUA-36C-R Scroll SANYO MCC1-36CR-R MUB1-36CR-R MTB-36CW-R
MOUB-36C Scroll Copeland MCC1-36CR MUB1-36CR MTB-36CW-Q MOUA-36C Scroll SANYO
MOU-36C-R Scroll Hitachi MHC-36CW-R
MOU-36C-Q Scroll SANYO MHC-36CW-Q
MOU-48C-R Rotary Hitachi
MCC2-48CR-R MUB2-48CR-R MTB-48CW-R MHC-48CW-R
MOUA-60C-R Scroll SANYO
MCC-60CR-R MUB1-60CR-R MTB-60CW-R MHC-60CW-R
Heat Pump
MOUB-12H Rotary Midea-Toshiba MCA2-12HR-Q MTB-12HW-Q MUB-12HR
MOU-18H-Q Rotary Midea-Toshiba
MCA-18HR-Q MCC-18HR-Q MUB-18HR-Q MTB-18HW-Q
MOU-24H-Q Rotary Midea-Toshiba
MCC-24HR-Q MUB-24HR-Q MTB-24HW-Q MHC-24HW-Q
MOUA-36H-R Scroll Hitachi
MCC1-36HR-R MUB1-36HR-R MTB-36HW-R MHC-36HW-R
MOUA-36H Scroll SANYO MCC1-36HR MUB1-36HR MTB-36HW-Q MHC-36HW-Q MOUB-36H Scroll Copeland
MOU-48H-R Rotary Hitachi
MCC2-48HR-R MUB2-48HR-R MTB-48HW-R MHC-48HW-R
MOUA-60H-R Scroll SANYO
MCC-60HR-R MUB-60HR-R MTB-60HW-R MHC-60HW-R
UnReg
ister
ed
MCAC-UTSM-2010-06 External Appearance
General Information 3
2. External Appearance 2.1 Indoor Units
2.2 Outdoor Units
New Four-way cassette type (compact)
Four-way cassette type
Duct type
High pressure static duct type
Ceiling & floor type
Ceiling & floor type
12,000Btu/h
18,000Btu/h
24,000Btu/h
36,000Btu/h
36,000Btu/h
48,000Btu/h
60,000Btu/h
UnReg
ister
ed
Nomenclature MCAC-UTSM-2010-06
4 General Information
3. Nomenclature 3.1 Indoor Unit
M C C - 36 H R - R
Power SupplyR 380~420V, 3ph, 50Hz-- 220`240V, 1ph, 50Hz
Control ModeW Wired control R Remote controlM Mechanical control E Eletric control
Function CodeC Cooling OnlyH Cooling & Heating
Capacity (×1000Btu/h)
Product SeriesA Time A Design B Time B DesignC Time C Design
Indoor unit Type T Duct H High static pressure duct C Cassette U Ceiling & Floor Midea
3.2 Outdoor Unit
M O U - 36 H - R
Power SupplyR 380~415V, 3ph, 50HzQ 220~240V, 1ph, 50Hz
Function CodeC Cooling OnlyH Cooling & Heating
Capacity (×1000Btu/h)
Universal Outdoor UnitO Outdoor unit U Universal
Midea
UnReg
ister
ed
MCAC-UTSM-2010-06 Features
General Information 5
4. Features 1. High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins.
2. Anti-rust, 500 hours salt spray test. 3. Low operation sound level: Well-known stable and quiet running fan motor. 4. Well-known compressor. 5. Compact design: Smaller dimension and larger stuffing capacity. 6. Universal outdoor unit design. 7. Optional air outlet grille: plastic type and wire type.
Wire type Plastic type Plastic type
8. Optional low temperature cooling module.
UnReg
ister
ed
Indoor Units MCAC-UTSM-2010-06
6 Indoor Units
Part 2 Indoor Units
Duct Type ............................................................................. 7
UnReg
ister
ed
MCAC-UTSM-2008-11 Duct Type
Duct Type 7
Duct Type
1. Features ........................................................................... 8
2. Specifications .................................................................. 9
3. Dimensions .................................................................... 16
4. Service Space ................................................................ 17
5. Wiring Diagrams ........................................................... 18
6. Capacity Tables ............................................................. 22
7. Capacity Correction Factors ........................................ 36
8. Static Pressure .............................................................. 38
9. Electric Characteristics ................................................ 39
10. Sound Levels ............................................................... 40
11. Accessories ................................................................. 41
12. The Specification of Power ........................................ 42
13. Field Wiring ................................................................. 43
UnReg
ister
ed
Features MCAC-UTSM-2010-06
8 Duct Type
1. Features 1. Optional accessories
2. Two air intake methods: from below or back
Air inlet from back standard and from bottom optional
Because the size of the plate from bottom and flange from back is same,it’s easy to change the air inlet from back to bottom by installer.
Just remove the plate from bottom and flange from back,then exchange the location and install them again
3. Water pump is optional and the maintenance is very easy
The pump can be took down very easy by screwed off the four screws.
Front boar Panel Canvas air passage Filter
UnReg
ister
ed
MCAC-UTSM-2010-06 Specifications
Duct Type 9
2. Specifications Model MTB-12CW-Q MTB-12HW-Q
Code 220070100150 220070100140
Power supply V-ph-Hz 220~240-1-50 220~240-1-50
Cooling Capacity Btu/h 12000 12000
Input W 1139 1151
Heating Capacity Btu/h — 13000
Input W — 1258
Indoor fan motor
Model YSK25-4P YSK25-4P
Input W 107/65/52 107/65/52
Capacitor uF 2UF/450V 2UF/450V
Speed(Hi/Mi/Lo) r/min 1150/800/700 1150/800/700
Indoor coil
Number of rows 2 2
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube
Φ7 Inner grooved copper tube
Coil length × height × width mm 735×252×26.7 735×252×26.7
Number of circuits 3 3
Indoor air flow(Hi/Mi/Lo) m3/h 800/610/520 800/610/520
Indoor external static pressure (Hi) Pa 40 40
Indoor noise level (sound pressure) dB(A) 36/32/25 36/32/25
Indoor unit
Dimension (W×H×D) mm 920x210x635 920x210x635
Packing (W×H×D) mm 1135x290x655 1135x290x655
Net/Gross weight kg 23/29 23/29
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ6.4/Φ12.7 Φ6.4/Φ12.7
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal)
2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
UnReg
ister
ed
Specifications MCAC-UTSM-2010-06
10 Duct Type
Model MTB-18CW-Q MTB-18HW-Q
Code 220070201280 220070201270
Power supply V-ph-Hz 220~240-1-50 220~240-1-50
Cooling Capacity Btu/h 18000 18000
Input W 1879 1886
Heating Capacity Btu/h — 20000
Input W — 1846
Indoor fan motor
Model YSK68-4P YSK68-4P
Input W 107/65/52 107/65/52
Capacitor uF 3.5UF/450V 3.5UF/450V
Speed(Hi/Mi/Lo) r/min 1150/800/700 1150/800/700
Indoor coil
Number of rows 3 3
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube
Φ7 Inner grooved copper tube
Coil length × height × width mm 735×252×40.11 735×252×40.11
Number of circuits 4 4
Indoor air flow(Hi/Mi/Lo) m3/h 1170/980/650 1170/980/650
Indoor external static pressure (Hi) Pa 70 70
Indoor noise level (sound pressure) dB(A) 43/31/27 43/31/27
Indoor unit
Dimension (W×H×D) mm 920x210x635 920x210x635
Packing (W×H×D) mm 1135x290x655 1135x290x655
Net/Gross weight kg 24/30 24/30
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ6.4/Φ12.7 Φ6.4/Φ12.7
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30 Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal) 2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic
room.
UnReg
ister
ed
MCAC-UTSM-2010-06 Specifications
Duct Type 11
Model MTB-24CW-Q MTB-24HW-Q
Code 220070301370 220070301360
Power supply V-ph-Hz 220~240-1-50 220~240-1-50
Cooling Capacity Btu/h 24000 24000
Input W 2510 2510
Heating Capacity Btu/h — 26000
Input W — 2405
Indoor fan motor
Model YSK74-4P YSK74-4P
Input W 163/93/75 163/93/75
Capacitor uF 3.5UF/450V 3.5UF/450V
Speed(Hi/Mi/Lo) r/min 1000/750/680 1000/750/680
Indoor coil
Number of rows 4 4
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube Φ7 Inner grooved copper tube
Coil length × height × width mm 735×252×53.48 735×252×53.48
Number of circuits 6 6
Indoor air flow(Hi/Mi/Lo) m3/h 1400/1100/1000 1400/1100/1000
Indoor external static pressure (Hi) Pa 70 70
Indoor noise level (sound pressure) dB(A) 44/33/29 44/33/29
Indoor unit
Dimension (W×H×D) mm 920x270x635 920x270x635
Packing (W×H×D) mm 1135x350x655 1135x350x655
Net/Gross weight kg 28/34 28/34
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ9.5/Φ15.9 Φ9.5/Φ15.9
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal)
2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
UnReg
ister
ed
Specifications MCAC-UTSM-2010-06
12 Duct Type
Model MTB-36CW-Q MTB-36HW-Q
Code 220070501660 220070501640
Power supply V-ph-Hz 220~240-1-50 220~240-1-50
Cooling Capacity Btu/h 36000 36000
Input W 3791 3804
Heating Capacity Btu/h --- 40000
Input W --- 3859
Indoor fan motor
Model YSK140-4P YSK140-4P
Input W 291/168/138 291/168/138
Capacitor uF 10uF/450V 10uF/450V
Speed(Hi/Mi/Lo) r/min 1070/790/710 1070/790/710
Indoor coil
Number of rows 4 4
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube Φ7 Inner grooved copper tube
Coil length × height × width mm 955×336×53.48 955×336×53.48
Number of circuits 8 8
Indoor air flow(Hi/Mi/Lo) m3/h 2270/1890/1650 2270/1890/1650
Indoor external static pressure (Hi) Pa 80 80
Indoor noise level (sound pressure) dB(A) 49/39/36 49/39/36
Indoor unit
Dimension (W×H×D) mm 1140x270x775 1140x270x775
Packing (W×H×D) mm 1355x350x795 1355x350x795
Net/Gross weight kg 41/46 41/46
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ9.5/Φ19 Φ9.5/Φ19
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal);
2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
UnReg
ister
ed
MCAC-UTSM-2010-06 Specifications
Duct Type 13
Model MTB-36CW-R MTB-36HW-R
Code 220070501670 220070501650
Power supply V-ph-Hz 380~420-3-50 380~420-3-50
Cooling Capacity Btu/h 36000 36000
Input W 3818 3818
Heating Capacity Btu/h --- 40000
Input W --- 3871
Indoor fan motor
Model YSK140-4P YSK140-4P
Input W 291/168/138 291/168/138
Capacitor uF 10uF/450V 10uF/450V
Speed(Hi/Mi/Lo) r/min 1070/790/710 1070/790/710
Indoor coil
Number of rows 4 4
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube Φ7 Inner grooved copper tube
Coil length × height × width mm 955×336×53.48 955×336×53.48
Number of circuits 8 8
Indoor air flow(Hi/Mi/Lo) m3/h 2270/1890/1650 2270/1890/1650
Indoor external static pressure (Hi) Pa 80 80
Indoor noise level (sound pressure) dB(A) 49/39/36 49/39/36
Indoor unit
Dimension (W×H×D) mm 1140x270x775 1140x270x775
Packing (W×H×D) mm 1355x350x795 1355x350x795
Net/Gross weight kg 41/46 41/46
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ9.5/Φ19 Φ9.5/Φ19
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal);
2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
UnReg
ister
ed
Specifications MCAC-UTSM-2010-06
14 Duct Type
Model MTB-48CW-R MTB-48HW-R
Code 220070701550 220070701540
Power supply V-ph-Hz 380~420-3-50 380~420-3-50
Cooling Capacity Btu/h 48000 48000
Input W 5224 5204
Heating Capacity Btu/h — 52000
Input W — 5034
Indoor fan motor
Model YSK170-4P YSK170-4P
Input W 356/201/152 356/201/152
Capacitor uF 10uF/450V 10uF/450V
Speed(Hi/Mi/Lo) r/min 1070/750/650 1070/750/650
Indoor coil
Number of rows 4 4
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube Φ7 Inner grooved copper tube
Coil length × height × width mm 1030×378×53.48 1030×378×53.48
Number of circuits 8 8
Indoor air flow(Hi/Mi/Lo) m3/h 3010/2410/1940 3010/2410/1940
Indoor external static pressure (Hi) Pa 100 100
Indoor noise level (sound pressure) dB(A) 49/39/36 49/39/36
Indoor unit
Dimension (W×H×D) mm 1200x300 x865 1200x300 x865
Packing (W×H×D) mm 1385x373 x920 1385x373 x920
Net/Gross weight kg 47/55 47/55
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ12.7/Φ19 Φ12.7/Φ19
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions: Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal);
2. Nominal heating capacities are based on the following conditions: Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
UnReg
ister
ed
MCAC-UTSM-2010-06 Specifications
Duct Type 15
Model MTB-60CW-R MTB-60HW-R
Code 220070801650 220070801640
Power supply V-ph-Hz 380~420-3-50 380~420-3-50
Cooling Capacity Btu/h 60000 60000
Input W 5993 6015
Heating Capacity Btu/h — 65000
Input W — 6419
Indoor fan motor
Model YSK180-4P YSK180-4P
Input W 355/223/173 355/223/173
Capacitor uF 10uF/450V 10uF/450V
Speed(Hi/Mi/Lo) r/min 1080/830/710 108/830/710
Indoor coil
Number of rows 4 4
Tube pitch(a)×row pitch(b) mm 21×13.37 21×13.37
Fin spacing mm 1.5 1.5
Fin type (code) Hydrophilic aluminum Hydrophilic aluminum
Tube outside dia.and type mm Φ7 Inner grooved copper tube Φ7 Inner grooved copper tube
Coil length × height × width mm 1030×378×53.48 1030×378×53.48
Number of circuits 8 8
Indoor air flow(Hi/Mi/Lo) m3/h 3150/2510/1990 3150/2510/1990
Indoor external static pressure (Hi) Pa 100 100
Indoor noise level (sound pressure) dB(A) 50/42/37 50/42/37
Indoor unit
Dimension (W×H×D) mm 1200x300 x865 1200x300 x865
Packing (W×H×D) mm 1385x373 x920 1385x373 x920
Net/Gross weight kg 47/55 47/55
Refrigerant type R22 R22
Design pressure MPa 2.8/1.2 2.8/1.2
Refrigerant piping Liquid side/ Gas side mm Φ12.7/Φ19 Φ12.7/Φ19
Drainage water pipe diameter mm ODΦ25 ODΦ25
Controller KJR-10B/DP(T)-E KJR-10B/DP(T)-E
Operation temperature ℃ 17-30 17-30
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. piping: 7.5m (horizontal); 2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. piping: 7.5m (horizontal) 3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic
room.
UnReg
ister
ed
Dimensions MCAC-UTSM-2010-06
16 Duct Type
3. Dimensions
Capacity (KBtu)
Outline dimension(mm)
Air outlet o pening size
Air return opening size
Size of outline dimension mounted plug
A B C D E F G H I J K L M
12/18 920 210 635 570 65 713 35 119 815 200 80 960 350
24 920 270 635 570 65 713 35 179 815 260 20 960 350
30/36 1140 270 775 710 65 933 35 179 1035 260 20 1180 490
48/60 1200 300 865 800 80 968 40 204 1094 288 45 1240 500
UnReg
ister
ed
MCAC-UTSM-2010-06 Service Space
Duct Type 17
4. Service Space Ensure enough space required for installation and maintenance.
UnReg
ister
ed
Wiring Diagrams MCAC-UTSM-2010-06
18 Duct Type
5. Wiring Diagrams MTB-12HW-Q MTB-18HW-Q
MTB-12CW-Q MTB-18CW-Q
UnReg
ister
ed
MCAC-UTSM-2010-06 Wiring Diagrams
Duct Type 19
MTB-24CW-Q
UnReg
ister
ed
Wiring Diagrams MCAC-UTSM-2010-06
20 Duct Type
MTB-24HW-Q MTB-36HW-Q
MTB-36CW-Q
UnReg
ister
ed
MCAC-UTSM-2010-06 Wiring Diagrams
Duct Type 21
MTB-36CW-R / MTB-48CW-R / MTB-60CW-R
MTB-36HW-R / MTB-48HW-R / MTB-60HW-R
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
22 Duct Type
6. Capacity Tables 6.1 Cooling Capacity MTB-12CW-Q MTB-12HW-Q High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 3.30 3.14 2.98 2.85
SC 2.44 2.41 2.38 2.39
Input 0.95 1.03 1.07 1.11
24/17ºC DB/WB
TC 3.39 3.23 3.07 2.88
SC 2.54 2.52 2.49 2.42
Input 1.00 1.07 1.12 1.17
27/19ºC DB/WB
TC 3.46 3.30 3.20 2.98
SC 2.56 2.54 2.50 2.44
Input 1.03 1.08 1.14 1.20
32/23ºC DB/WB
TC 3.52 3.39 3.33 3.07
SC 2.99 2.95 2.93 2.86
Input 1.07 1.12 1.20 1.24
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 3.16 3.01 2.86 2.73
SC 2.34 2.32 2.28 2.30
Input 0.91 0.99 1.03 1.07
24/17ºC DB/WB
TC 3.25 3.10 2.95 2.76
SC 2.44 2.42 2.39 2.32
Input 0.97 1.03 1.08 1.13
27/19ºC DB/WB
TC 3.32 3.16 3.07 2.86
SC 2.45 2.43 2.39 2.34
Input 0.99 1.05 1.10 1.16
32/23ºC DB/WB
TC 3.38 3.25 3.19 2.95
SC 2.87 2.83 2.81 2.74
Input 1.03 1.08 1.16 1.20
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 3.03 2.88 2.73 2.62
SC 2.24 2.22 2.19 2.20
Input 0.88 0.95 1.00 1.03
24/17ºC DB/WB
TC 3.12 2.97 2.82 2.65
SC 2.34 2.32 2.29 2.22
Input 0.93 1.00 1.04 1.09
27/19ºC DB/WB
TC 3.18 3.03 2.94 2.73
SC 2.35 2.33 2.29 2.24
Input 0.95 1.01 1.06 1.11
32/23ºC DB/WB
TC 3.23 3.12 3.06 2.82
SC 2.75 2.71 2.69 2.62
Input 1.00 1.04 1.11 1.16
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 23
MTB-18CW-Q MTB-18HW-Q High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 5.46 5.19 4.93 4.72
SC 4.04 4.00 3.94 3.96
Input 1.58 1.71 1.79 1.84
24/17ºC DB/WB
TC 5.62 5.35 5.09 4.77
SC 4.21 4.18 4.12 4.01
Input 1.67 1.79 1.86 1.96
27/19ºC DB/WB
TC 5.72 5.46 5.30 4.93
SC 4.24 4.20 4.13 4.04
Input 1.71 1.81 1.90 2.00
32/23ºC DB/WB
TC 5.83 5.62 5.51 5.09
SC 4.96 4.89 4.85 4.73
Input 1.79 1.86 2.00 2.07
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 5.24 4.99 4.73 4.53
SC 3.88 3.84 3.79 3.81
Input 1.53 1.66 1.73 1.78
24/17ºC DB/WB
TC 5.40 5.14 4.89 4.58
SC 4.05 4.01 3.96 3.85
Input 1.62 1.73 1.80 1.90
27/19ºC DB/WB
TC 5.50 5.24 5.09 4.73
SC 4.07 4.04 3.97 3.88
Input 1.66 1.75 1.84 1.93
32/23ºC DB/WB
TC 5.60 5.40 5.29 4.89
SC 4.76 4.69 4.66 4.54
Input 1.73 1.80 1.93 2.01
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 5.03 4.78 4.54 4.34
SC 3.72 3.68 3.63 3.65
Input 1.47 1.59 1.66 1.72
24/17ºC DB/WB
TC 5.17 4.93 4.68 4.39
SC 3.88 3.84 3.79 3.69
Input 1.56 1.66 1.73 1.82
27/19ºC DB/WB
TC 5.27 5.03 4.88 4.54
SC 3.90 3.87 3.81 3.72
Input 1.59 1.68 1.77 1.86
32/23ºC DB/WB
TC 5.37 5.17 5.08 4.68
SC 4.56 4.50 4.47 4.36
Input 1.66 1.73 1.86 1.93
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
24 Duct Type
MTB-24CW-Q MTB-24HW-Q High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.31 6.96 6.60 6.32
SC 5.41 5.36 5.28 5.31
Input 2.08 2.26 2.36 2.43
24/17ºC DB/WB
TC 7.53 7.17 6.82 6.39
SC 5.64 5.59 5.52 5.37
Input 2.21 2.36 2.46 2.59
27/19ºC DB/WB
TC 7.67 7.31 7.10 6.60
SC 5.67 5.63 5.54 5.41
Input 2.26 2.38 2.51 2.64
32/23ºC DB/WB
TC 7.81 7.53 7.38 6.82
SC 6.64 6.55 6.50 6.34
Input 2.36 2.46 2.64 2.74
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.02 6.68 6.34 6.07
SC 5.20 5.15 5.07 5.10
Input 2.02 2.19 2.28 2.36
24/17ºC DB/WB
TC 7.23 6.89 6.55 6.14
SC 5.42 5.37 5.30 5.16
Input 2.14 2.28 2.38 2.50
27/19ºC DB/WB
TC 7.37 7.02 6.82 6.34
SC 5.45 5.41 5.32 5.20
Input 2.19 2.31 2.43 2.55
32/23ºC DB/WB
TC 7.50 7.23 7.09 6.55
SC 6.38 6.29 6.24 6.09
Input 2.28 2.38 2.55 2.65
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 6.73 6.40 6.07 5.81
SC 4.98 4.93 4.86 4.88
Input 1.94 2.11 2.20 2.27
24/17ºC DB/WB
TC 6.92 6.60 6.27 5.88
SC 5.19 5.14 5.08 4.94
Input 2.06 2.20 2.29 2.41
27/19ºC DB/WB
TC 7.05 6.73 6.53 6.07
SC 5.22 5.18 5.09 4.98
Input 2.11 2.22 2.34 2.46
32/23ºC DB/WB
TC 7.18 6.92 6.79 6.27
SC 6.11 6.02 5.98 5.83
Input 2.20 2.29 2.46 2.55
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 25
MTB-36CW-Q MTB-36HW-Q High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 10.82 10.29 9.77 9.35
SC 8.00 7.92 7.81 7.85
Input 3.15 3.42 3.57 3.69
24/17ºC DB/WB
TC 11.13 10.61 10.08 9.45
SC 8.35 8.27 8.16 7.94
Input 3.34 3.57 3.72 3.91
27/19ºC DB/WB
TC 11.34 10.82 10.50 9.77
SC 8.39 8.33 8.19 8.01
Input 3.42 3.61 3.80 3.99
32/23ºC DB/WB
TC 11.55 11.13 10.92 10.08
SC 9.82 9.68 9.61 9.37
Input 3.57 3.72 3.99 4.14
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 10.38 9.88 9.37 8.97
SC 7.68 7.61 7.50 7.54
Input 3.05 3.31 3.46 3.57
24/17ºC DB/WB
TC 10.68 10.18 9.68 9.07
SC 8.01 7.94 7.84 7.62
Input 3.24 3.46 3.61 3.79
27/19ºC DB/WB
TC 10.89 10.38 10.08 9.37
SC 8.06 7.99 7.86 7.69
Input 3.31 3.50 3.68 3.86
32/23ºC DB/WB
TC 11.09 10.68 10.48 9.68
SC 9.42 9.30 9.23 9.00
Input 3.46 3.61 3.86 4.01
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 9.95 9.47 8.98 8.60
SC 7.36 7.29 7.19 7.22
Input 2.94 3.19 3.33 3.43
24/17ºC DB/WB
TC 10.24 9.76 9.27 8.69
SC 7.68 7.61 7.51 7.30
Input 3.12 3.33 3.47 3.65
27/19ºC DB/WB
TC 10.43 9.95 9.66 8.98
SC 7.72 7.66 7.53 7.37
Input 3.19 3.36 3.54 3.72
32/23ºC DB/WB
TC 10.63 10.24 10.05 9.27
SC 9.03 8.91 8.84 8.62
Input 3.33 3.47 3.72 3.86
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
26 Duct Type
MTB-36CW-R MTB-36HW-R High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 10.82 10.29 9.77 9.35
SC 8.00 7.92 7.81 7.85
Input 3.17 3.44 3.59 3.71
24/17ºC DB/WB
TC 11.13 10.61 10.08 9.45
SC 8.35 8.27 8.16 7.94
Input 3.36 3.59 3.74 3.93
27/19ºC DB/WB
TC 11.34 10.82 10.50 9.77
SC 8.39 8.33 8.19 8.01
Input 3.44 3.63 3.82 4.01
32/23ºC DB/WB
TC 11.55 11.13 10.92 10.08
SC 9.82 9.68 9.61 9.37
Input 3.59 3.74 4.01 4.16
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 10.38 9.88 9.37 8.97
SC 7.68 7.61 7.50 7.54
Input 3.07 3.33 3.48 3.59
24/17ºC DB/WB
TC 10.68 10.18 9.68 9.07
SC 8.01 7.94 7.84 7.62
Input 3.26 3.48 3.63 3.81
27/19ºC DB/WB
TC 10.89 10.38 10.08 9.37
SC 8.06 7.99 7.86 7.69
Input 3.33 3.52 3.70 3.89
32/23ºC DB/WB
TC 11.09 10.68 10.48 9.68
SC 9.42 9.30 9.23 9.00
Input 3.48 3.63 3.89 4.03
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 9.95 9.47 8.98 8.60
SC 7.36 7.29 7.19 7.22
Input 2.95 3.20 3.35 3.45
24/17ºC DB/WB
TC 10.24 9.76 9.27 8.69
SC 7.68 7.61 7.51 7.30
Input 3.13 3.35 3.49 3.67
27/19ºC DB/WB
TC 10.43 9.95 9.66 8.98
SC 7.72 7.66 7.53 7.37
Input 3.20 3.38 3.56 3.74
32/23ºC DB/WB
TC 10.63 10.24 10.05 9.27
SC 9.03 8.91 8.84 8.62
Input 3.35 3.49 3.74 3.88
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 27
MTB-48CW-R MTB-48HW-R High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 14.42 13.72 13.02 12.46
SC 10.67 10.56 10.42 10.47
Input 4.32 4.68 4.89 5.04
24/17ºC DB/WB
TC 14.84 14.14 13.44 12.60
SC 11.13 11.03 10.89 10.58
Input 4.58 4.89 5.10 5.36
27/19ºC DB/WB
TC 15.12 14.42 14.00 13.02
SC 11.19 11.10 10.92 10.68
Input 4.68 4.94 5.20 5.46
32/23ºC DB/WB
TC 15.40 14.84 14.56 13.44
SC 13.09 12.91 12.81 12.50
Input 4.89 5.10 5.46 5.67
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 13.84 13.17 12.50 11.96
SC 10.24 10.14 10.00 10.05
Input 4.17 4.53 4.73 4.88
24/17ºC DB/WB
TC 14.25 13.57 12.90 12.10
SC 10.68 10.59 10.45 10.16
Input 4.43 4.73 4.93 5.18
27/19ºC DB/WB
TC 14.52 13.84 13.44 12.50
SC 10.74 10.66 10.48 10.25
Input 4.53 4.78 5.03 5.28
32/23ºC DB/WB
TC 14.78 14.25 13.98 12.90
SC 12.57 12.39 12.30 12.00
Input 4.73 4.93 5.28 5.48
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 13.27 12.62 11.98 11.46
SC 9.82 9.72 9.58 9.63
Input 4.02 4.36 4.55 4.69
24/17ºC DB/WB
TC 13.65 13.01 12.36 11.59
SC 10.24 10.15 10.02 9.74
Input 4.26 4.55 4.74 4.99
27/19ºC DB/WB
TC 13.91 13.27 12.88 11.98
SC 10.29 10.22 10.05 9.82
Input 4.36 4.60 4.84 5.08
32/23ºC DB/WB
TC 14.17 13.65 13.40 12.36
SC 12.04 11.88 11.79 11.50
Input 4.55 4.74 5.08 5.28
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
28 Duct Type
MTB-60CW-R MTB-60HW-R High speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 16.48 15.68 14.88 14.24
SC 12.20 12.07 11.90 11.96
Input 4.98 5.40 5.64 5.82
24/17ºC DB/WB
TC 16.96 16.16 15.36 14.40
SC 12.72 12.60 12.44 12.10
Input 5.28 5.64 5.88 6.18
27/19ºC DB/WB
TC 17.28 16.48 16.00 14.88
SC 12.79 12.69 12.48 12.20
Input 5.40 5.70 6.00 6.30
32/23ºC DB/WB
TC 17.60 16.96 16.64 15.36
SC 14.96 14.76 14.64 14.28
Input 5.64 5.88 6.30 6.54
Medium speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 15.82 15.05 14.28 13.67
SC 11.71 11.59 11.43 11.48
Input 4.81 5.22 5.45 5.63
24/17ºC DB/WB
TC 16.28 15.51 14.75 13.82
SC 12.21 12.10 11.94 11.61
Input 5.10 5.45 5.68 5.97
27/19ºC DB/WB
TC 16.59 15.82 15.36 14.28
SC 12.28 12.18 11.98 11.71
Input 5.22 5.51 5.80 6.09
32/23ºC DB/WB
TC 16.90 16.28 15.97 14.75
SC 14.36 14.16 14.06 13.71
Input 5.45 5.68 6.09 6.32
Low speed
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 15.16 14.43 13.69 13.10
SC 11.22 11.11 10.95 11.00
Input 4.63 5.02 5.25 5.41
24/17ºC DB/WB
TC 15.60 14.87 14.13 13.25
SC 11.70 11.60 11.45 11.13
Input 4.91 5.25 5.47 5.75
27/19ºC DB/WB
TC 15.90 15.16 14.72 13.69
SC 11.76 11.67 11.48 11.23
Input 5.02 5.30 5.58 5.86
32/23ºC DB/WB
TC 16.19 15.60 15.31 14.13
SC 13.76 13.57 13.47 13.14
Input 5.25 5.47 5.86 6.08
Remark: TC: Total capacity ; kW SC: Sensible heat capacity ; kW Input: Input power; kW
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 29
6.2 Heating Capacity MTB-12HW-Q High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 5.20 4.20 3.44 3.12
Input 1.36 1.17 1.01 0.95
20ºC TC 5.04 4.00 3.24 3.04
Input 1.49 1.26 1.11 1.02
27ºC TC 4.72 3.76 3.04 2.96
Input 1.58 1.36 1.20 1.11
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 4.94 3.99 3.27 2.96
Input 1.31 1.13 0.97 0.91
20ºC TC 4.79 3.80 3.08 2.89
Input 1.43 1.21 1.06 0.98
27ºC TC 4.48 3.57 2.89 2.81
Input 1.51 1.31 1.15 1.06
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 4.73 3.82 3.13 2.84
Input 1.25 1.08 0.93 0.87
20ºC TC 4.59 3.64 2.95 2.77
Input 1.37 1.16 1.02 0.94
27ºC TC 4.30 3.42 2.77 2.69
Input 1.45 1.25 1.10 1.02
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
30 Duct Type
MTB-18HW-Q High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 7.80 6.30 5.16 4.68
Input 2.00 1.72 1.48 1.39
20ºC TC 7.56 6.00 4.86 4.56
Input 2.18 1.85 1.63 1.50
27ºC TC 7.08 5.64 4.56 4.44
Input 2.31 2.00 1.76 1.63
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 7.41 5.99 4.90 4.45
Input 1.92 1.65 1.42 1.33
20ºC TC 7.18 5.70 4.62 4.33
Input 2.10 1.78 1.56 1.44
27ºC TC 6.73 5.36 4.33 4.22
Input 2.22 1.92 1.69 1.56
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 7.10 5.73 4.70 4.26
Input 1.84 1.58 1.36 1.28
20ºC TC 6.88 5.46 4.42 4.15
Input 2.01 1.70 1.50 1.38
27ºC TC 6.44 5.13 4.15 4.04
Input 2.13 1.84 1.62 1.50
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 31
MTB-24HW-Q High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 9.88 7.98 6.54 5.93
Input 2.60 2.24 1.93 1.81
20ºC TC 9.58 7.60 6.16 5.78
Input 2.84 2.41 2.12 1.95
27ºC TC 8.97 7.14 5.78 5.62
Input 3.01 2.60 2.29 2.12
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 9.39 7.58 6.21 5.63
Input 2.51 2.16 1.86 1.74
20ºC TC 9.10 7.22 5.85 5.49
Input 2.74 2.32 2.04 1.88
27ºC TC 8.52 6.79 5.49 5.34
Input 2.90 2.51 2.20 2.04
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 9.00 7.27 5.95 5.40
Input 2.40 2.06 1.78 1.67
20ºC TC 8.72 6.92 5.61 5.26
Input 2.62 2.22 1.95 1.80
27ºC TC 8.17 6.50 5.26 5.12
Input 2.78 2.40 2.11 1.95
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
32 Duct Type
MTB-36HW-Q High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 15.60 12.60 10.32 9.36
Input 4.17 3.59 3.09 2.90
20ºC TC 15.12 12.00 9.72 9.12
Input 4.55 3.86 3.40 3.13
27ºC TC 14.16 11.28 9.12 8.88
Input 4.83 4.17 3.67 3.40
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 14.82 11.97 9.80 8.89
Input 4.01 3.45 2.97 2.78
20ºC TC 14.36 11.40 9.23 8.66
Input 4.38 3.71 3.26 3.01
27ºC TC 13.45 10.72 8.66 8.44
Input 4.64 4.01 3.52 3.26
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 14.20 11.47 9.39 8.52
Input 3.83 3.30 2.84 2.66
20ºC TC 13.76 10.92 8.85 8.30
Input 4.19 3.55 3.12 2.88
27ºC TC 12.89 10.26 8.30 8.08
Input 4.44 3.83 3.37 3.12
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 33
MTB-36HW-R High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 15.60 12.60 10.32 9.36
Input 4.18 3.60 3.10 2.90
20ºC TC 15.12 12.00 9.72 9.12
Input 4.57 3.87 3.41 3.13
27ºC TC 14.16 11.28 9.12 8.88
Input 4.84 4.18 3.68 3.41
Medium speed Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 14.82 11.97 9.80 8.89
Input 4.02 3.46 2.98 2.79
20ºC TC 14.36 11.40 9.23 8.66
Input 4.39 3.72 3.27 3.01
27ºC TC 13.45 10.72 8.66 8.44
Input 4.65 4.02 3.53 3.27
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 14.20 11.47 9.39 8.52
Input 3.84 3.31 2.85 2.67
20ºC TC 13.76 10.92 8.85 8.30
Input 4.20 3.56 3.13 2.88
27ºC TC 12.89 10.26 8.30 8.08
Input 4.45 3.84 3.38 3.13
UnReg
ister
ed
Capacity Tables MCAC-UTSM-2010-06
34 Duct Type
MTB-48HW-R High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 19.50 15.75 12.90 11.70
Input 5.43 4.68 4.02 3.77
20ºC TC 18.90 15.00 12.15 11.40
Input 5.94 5.03 4.43 4.07
27ºC TC 17.70 14.10 11.40 11.10
Input 6.29 5.43 4.78 4.43
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 18.53 14.96 12.26 11.12
Input 5.23 4.50 3.87 3.63
20ºC TC 17.96 14.25 11.54 10.83
Input 5.71 4.84 4.26 3.92
27ºC TC 16.82 13.40 10.83 10.55
Input 6.05 5.23 4.60 4.26
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 17.75 14.33 11.74 10.65
Input 5.01 4.32 3.71 3.48
20ºC TC 17.20 13.65 11.06 10.37
Input 5.48 4.64 4.08 3.76
27ºC TC 16.11 12.83 10.37 10.10
Input 5.80 5.01 4.41 4.08
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Tables
Duct Type 35
MTB-60HW-R High speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 24.70 19.95 16.34 14.82
Input 6.93 5.97 5.14 4.82
20ºC TC 23.94 19.00 15.39 14.44
Input 7.58 6.42 5.65 5.20
27ºC TC 22.42 17.86 14.44 14.06
Input 8.03 6.93 6.10 5.65
Medium speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 23.47 18.95 15.52 14.08
Input 6.66 5.74 4.94 4.63
20ºC TC 22.74 18.05 14.62 13.72
Input 7.28 6.17 5.43 5.00
27ºC TC 21.30 16.97 13.72 13.36
Input 7.71 6.66 5.86 5.43
Low speed
Heating Outdoor conditions
Indoor Conditions (DB) (kW) 24/18ºC DB/WB 7/6ºC DB/WB 2/1ºC DB/WB -5/-6ºC DB/WB
15ºC TC 22.48 18.15 14.87 13.49
Input 6.38 5.50 4.73 4.43
20ºC TC 21.79 17.29 14.00 13.14
Input 6.97 5.91 5.20 4.79
27ºC TC 20.40 16.25 13.14 12.79
Input 7.39 6.38 5.61 5.20
Remark: TC: Total capacity ; kW Input: Input power; kW UnR
egist
ered
Capacity Correction Factors MCAC-UTSM-2010-06
36 Duct Type
7. Capacity Correction Factors 7.1 Correction factor of indoor air-flow changing rate Cooling:
Unit Model Air flow(m3/h) Air delivery capacity correction factor
Total Sensible
MTB-12CW-Q MTB-12HW-Q
928 1.05 1.08 800 1 1 672 0.96 0.92 544 0.92 0.85
MTB-18CW-Q MTB-18HW-Q
1345 1.05 1.08 1170 1 1 995 0.96 0.92 820 0.92 0.85
MTB-24CW-Q MTB-24HW-Q
1563 1.05 1.08 1400 1 1 1237 0.96 0.92 1074 0.92 0.85
MTB-36CW-Q MTB-36HW-Q MTB-36CW-R MTB-36HW-R
2473 1.05 1.08 2270 1 1 2067 0.96 0.92 1864 0.92 0.85
MTB-48CW-R MTB-48HW-R
3266 1.05 1.08 3010 1 1 2754 0.96 0.92 2498 0.92 0.85
MTB-60CW-R MTB-60HW-R
3377 1.05 1.08 3150 1 1 2923 0.96 0.92 2696 0.92 0.85
Heating:
Unit Model Air flow(m3/h) Air delivery capacity correction factor
Total
MTB-12HW-Q
928 1.05 800 1 672 0.95 544 0.91
MTB-18HW-Q
1345 1.05 1170 1 995 0.95 820 0.91
MTB-24HW-Q
1563 1.05 1400 1 1237 0.95 1074 0.91
MTB-36HW-Q MTB-36HW-R
2473 1.05 2270 1 2067 0.95 1864 0.91
MTB-48HW-R
3266 1.05 3010 1 2754 0.95 2498 0.91
MTB-60HW-R
3377 1.05 3150 1 2923 0.95 2696 0.91
UnReg
ister
ed
MCAC-UTSM-2010-06 Capacity Correction Factors
Duct Type 37
7.2 Correction factor of the length and elevation difference of refrigerant pipe 1. Rate of change in cooling capacity
10 20 30 40 50
- 10
- 20
- 30
% 100
98 96 94 92 90
2. Rate of change in heating capacity
0
10
20
30
40
50
-10
-20
-30
20 3010 40 50 60 70 80
Pipe equivalent length L(m)
100%
Outdoor unit
99%
98%
97%
UnReg
ister
ed
Static Pressure MCAC-UTSM-2010-06
38 Duct Type
8. Static Pressure 12,000Btu/h 18,000Btu/h
Super high speed
0900600500
Mid speedHigh speed
Ext
erna
l sta
tic p
ress
ure
(Pa)
3Air volume(m /h)
Pa
90
80
70
60
50
40
30
20
10
Low speed
300 400 700 800
Super high speed
500400300200
Low speed
10
20
30
40
50
60
70
80
90
Pa
600 700 800 900 1000 1100Air volume(m /h)3
Ext
erna
l sta
tic p
ress
ure
(Pa)
High speed
Mid speed
1200
24,000Btu/h 36,000Btu/h
Super high speed
14001300
Low speed
10
20
30
40
50
60
70
80
90
Pa
800 900 1000 1100Air volume(m /h)3
Ext
erna
l sta
tic p
ress
ure
(Pa)
High speed
Mid speed
1200 1500700
2400220016001400
Low speed
10
20
30
40
50
60
70
80
90
1100Air volume(m /h)3
Ext
erna
l sta
tic p
ress
ure
(Pa)
High speed
Mid speed
36K
1200 1800 2000
Super high speed
Pa
UnReg
ister
ed
MCAC-UTSM-2010-06 Electric Characteristics
Duct Type 39
48,000Btu/h 60,000Btu/h
120
110
Super high speed
100
Pa
250022001300
48K
Mid speed
High speed
Ext
erna
l sta
tic p
ress
ure
(Pa)
3Air volume(m /h)1000
90
80
70
60
50
40
30
20
10
Low speed
1600 1900 2800 3100
120
110
Super high speed
3400
100
3100280019001600
Low speed
10
20
30
40
50
60
70
80
90
Pa
1000Air volume(m /h)3
Ext
erna
l sta
tic p
ress
ure
(Pa)
High speed
Mid speed
1300 2200 2500
9. Electric Characteristics
Model Indoor Units Power Supply
Hz Voltage Min. Max. MCA MFA
MTB-12CW-Q 50 220-240V 198V 254V 0.72 16
MTB-12HW-Q 50 220-240V 198V 254V 0.72 16
MTB-18CW-Q 50 220-240V 198V 254V 0.72 16
MTB-18HW-Q 50 220-240V 198V 254V 0.72 16
MTB-24CW-Q 50 220-240V 198V 254V 1.095 25
MTB-24HW-Q 50 220-240V 198V 254V 1.095 25
MTB-36CW-Q 50 220-240V 198V 254V 1.92 30
MTB-36HW-Q 50 220-240V 198V 254V 1.92 30
MTB-36CW-R 50 380-420V 342V 440V 1.92 30
MTB-36HW-R 50 380-420V 342V 440V 1.92 30
MTB-48CW-R 50 380-420V 342V 440V 2.33 30 MTB-48HW-R 50 380-420V 342V 440V 2.33 30 MTB-60CW-R 50 380-420V 342V 440V 2.33 30 MTB-60HW-R 50 380-420V 342V 440V 2.33 30
Remark: MCA: Min. Current Amps. (A) MFA: Max. Fuse Amps. (A)
UnReg
ister
ed
Sound Levels MCAC-UTSM-2010-06
40 Duct Type
10. Sound Levels
SuctionDischarge
Microphone
1.4m
Concealed Duct Type
DuctDuct
Model Noise level dB(A)
H M L
MTB-12CW-Q/ MTB-12HW-Q 36 32 25
MTB-18CW-Q/ MTB-18HW-Q 43 31 27
MTB-24CW-Q/ MTB-24HW-Q 44 33 29
MTB-36CW-Q/ MTB-36HW-Q 49 39 36
MTB-36CW-R/ MTB-36HW-R 49 39 36
MTB-48CW-R/ MTB-48HW-R 49 39 36
MTB-60CW-R/ MTB-60HW-R 50 42 37
UnR
egist
ered
MCAC-UTSM-2010-06 Accessories
Duct Type 41
11. Accessories
Name Quantity Shape Remark
Soundproof / insulation sheath 2
Binding tape 1
Seal sponge 1
Orifice 1 Only For R22,Cooling/Heating Unit
Except Model 12
Drain joint 1
Seal ring 1
Wire controller 1
Owner‘s manual 1
Installation manual 1
UnReg
ister
ed
The Specification of Power MCAC-UTSM-2010-06
42 Duct Type
12. The Specification of Power
MODEL (For R22,Cooling& Heating) 12~18 24 36 36-60
Power Phase 1-phase 1-phase 1-phase 3-phase
Frequency and Voltage 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz 380-415V, 50Hz
Circuit Breaker/ Fuse (A) 20/16 40/25 60/30 40/30
Indoor Unit Power Wiring (mm2) 3×2.5 3x2.5 3x4.0 5x4.0
Indoor/Outdoor Connecting Wiring
(mm2)
Ground Wiring 2.5 2.5 4.0 4.0
Outdoor Unit Power Wiring 3×2.5 3x4.0 5x4.0
Strong Electric Signal 5×2.5 3×1.5 3×1.5 3×1.5
Weak Electric Signal 2×0.75 2×0.75 2×0.75
MODEL
(For R22,Cooling only) 12~18 24 36 36-60
Power Phase 1-phase 1-phase 1-phase 3-phase
Frequency and Voltage 220-240V, 50Hz 220-240V, 50Hz 220-240V, 50Hz 380-420V, 50Hz
Circuit Breaker/ Fuse (A) 20/16 40/25 60/30 40/30
Indoor Unit Power Wiring (mm2) 3x2.5 3x2.5 3x4.0 5x4.0
Indoor/Outdoor Connecting Wiring
(mm2)
Ground Wiring 2.5 2.5 4.0 4.0
Outdoor Unit Power Wiring 3×2.5 3x4.0 5x4.0
Strong Electric Signal 3x2.5 1×1.5 1×1.5 1×1.5
Weak Electric Signal 2×0.75
UnR
egist
ered
MCAC-UTSM-2010-06 Field Wiring
Duct Type 43
13. Field Wiring
MTB-12HW-Q MTB-18HW-Q
UnReg
ister
ed
Field Wiring MCAC-UTSM-2010-06
44 Duct Type
MTB-24HW-Q MTB-36HW-Q
MTB-36HW-R MTB-48HW-R MTB-60HW-R
UnReg
ister
ed
MCAC-UTSM-2010-06 Field Wiring
Duct Type 45
MTB-12CW-Q
MTB-18CW-Q
UnReg
ister
ed
Field Wiring MCAC-UTSM-2010-06
46 Duct Type
MTB-24CW-Q
MTB-36CW-Q
UnReg
ister
ed
MCAC-UTSM-2010-06 Field Wiring
Duct Type 47
MTB-36CW-R MTB-48CW-R MTB-60CW-R
UnReg
ister
ed
错误!文档中没有指定样式的文字。 MCAC-UTSM-2010-06
48
UnReg
ister
ed