BHEL, Hardwar 6.1-0100-99/1
Steam Turbine Technical Data Description Construction, Speed & Steam Pressure Load
Rated Load 600 MW
Maximum Load under valve wide open (VWO) condition 629.2 MW
Construction
Three cylinder reheat condensing turbine
Single flow HP Turbine with 14 reaction stages Type : H30-100-2
Double flow IP Turbine with 10 reaction stages per flow Type : M30-63
Double flow LP Turbine (2 no.s) with (5 drum + 3 module) stages per flow
Type : N30-4x6.3
2 Main Stop and Control valves (HP casing mounted) Type : EV 320-1
2 Reheat Stop and Control Valves (Floating) Type : IV 560
1 Swing Check Valve in cold reheat line DN-800 Make : BHEL, Trichy
2 LP Bypass Stop and Control Valves with actuators & HPSU (High pressure EHA based)
Make: CCI Switzerland
Extraction Swing Check Valves
Extraction 1 : No valve
Extraction 2 : 2 Swing Check Valve with actuator and 2 Swing Check Valve without actuator
DN 600 Make : BHEL, Trichy
Extraction 3 : 2 Swing Check Valve with actuator and 2 Swing Check Valve without actuator
DN 500 Make : BHEL, Trichy
Extraction 4.1 : 2 Swing Check Valves with actuator DN 500 Make : BHEL, Trichy
Extraction 4.2 : 2 Swing Check Valves with actuator DN 500 Make : BHEL, Trichy
Extraction 5 : 1 Swing Check Valve with actuator and 1 Swing Check Valve without actuator
DN 400 Make : BHEL, Trichy
Extraction 6 : No valve
Extraction 7 : 1 swing check valve with actuator and 1 swing check valve without actuator
DN 250 Make : BHEL, Trichy
BHEL, Hardwar 6.1-0100-99/2
Speed
Rated speed 50.0 c/s
Speed limitation in load and station operation
Max. Speed, no time limitation
Min. Speed, no time limitation
Permissible for maximum 2 hours during the life of LP blading Speed below Speed above
51.5 c/s
47.5 c/s
47.5 c/s 51.5 to 60 c/s
Speed exclusion range at operation without load * 7 to 47.5 c/s
Standard over speed trip setting Max. 55.5 c/s
* This speed range should be passed through in one smooth operation to avoid endangering the blades due to resonance
Steam Pressures
Rated ♦ Long time operation♣ Short time operation♥ Unit
Initial Steam 170.0 178.5 203.9 ata
Before 1st HP drum stage 158.6 171.8 171.8 ata
HP cylinder exhaust 42.9 49.4 51.5 ♠ ata
IP cylinder stop valve inlet 38.7 44.8 46.3 ♠ ata
Extraction 7 65.8 73.6 73.6 ata
Extraction 6 42.9 49.4 51.5 ata
Extraction 5 19.2 22.6 22.6 ata
Extraction 4 7.6 9.15 9.15 ata
Extraction 3 2.56 3.12 3.12 ata
Extraction 2 0.967 1.21 1.21 ata
Extraction 1 0.392 0.49 0.49 ata
LP cylinder exhaust 0.1033 0.31 0.31 ata
♦ These values correspond to 600 MW load with 3 % make-up and 0.1033 ata back pressure with all heaters in service and rated steam conditions.
♠ The safety valves must be set so that short time values are not exceeded. ♣ Long time operation: Upper limit value, permissible without time limit. ♥
Short time operation: Permissible momentary value. The aggregate duration of such swings must not exceed 12 hours in any one year
All pressures are absolute pressures
BHEL, Hardwar 6.1-0100-99/3
Low vacuum trip, standard setting
Electrical low vacuum trip 0.3 bar
Electrical low vacuum trip bypass operation 0.6 bar
Seal steam supply system
Pressure in seal steam header (above atmospheric) 35 mbar
Axial shift
Alarm ± 0.5 mm
Trip ± 1.0 mm
Direction of rotation
Anti clock wise when viewed from Front Pedestal towards the Generator