Upload
anonymous-m65ttcfot
View
220
Download
0
Embed Size (px)
Citation preview
7/28/2019 621-1779-1-PB
1/5
Advances in Electrical Engineering Systems (AEES) 152Vol. 1, No. 3, 2012, ISSN 2167-633XCopyright World Science Publisher, United Stateswww.worldsciencepublisher.org
Dissolved Gas Analysis as a Diagnostic Tools for Early
Detection of Transformer Faults
Sherif S. M. Ghoneim1, 2
, IEEE Member, Sayed A. Ward3
1Canal Suez University, Suez, Egypt
2Taif University-Taif- KSA
3Benha University- Benha- Egypt
E-mail:[email protected]
Abstract- Transformers is a device on which cost effective supply of electricity mostly depends. Hence, to manage the
life of transformers, to reduce failures and to extend the life of transformer, some measures are being adopted. Dissolved
gas-in-oil analysis (DGA) is a common practice in transformer fault diagnosis. Some classical methods that depend on
gases concentration in transformers oils are used to interpret transformer faults such as Dornenberg, Rogers, Duvaltriangle and key gases methods. These methods in some cases did not give the same results; therefore, an expertise
method is developed to give the fault type according to the dissolved gases concentration in oil. A software code isdesigned using logic functions to get the type of the faults in transformers. Comparing the results from this software with
the real laboratory cases as well as some cases in literatures is developed. The results explain the validation of software
to detect the fault in transformer.
Key words: Dissolved gases analysis; Transformer oil; Interpretation of transformer faults.
1. Introduction
The cost of unplanned outages can be reduced by theearly detection of such internal faults in transformer. The
interpretation of transformer faults using dissolved gases
analysis is produced using some techniques that assumedby Dornenberg, Rogers, Duval triangle and key gases
methods [1-5].Dissolved gas analysis is the most important test in
determining the condition of a transformer. It is the first
indicator of a problem and can identify deterioratinginsulation and oil, over heating hot spots, partial discharge
and arcing. Dissolved gas analysis is made on the basis of
the standard IEC60599 [6] and IEEEC 57-104TM [7]
standards. A four condition DGA guide to classify risks totransformers with no previous problems has been published
in the standard IEEE C57- 104TM.Several artificial intelligence methods such as Fuzzy
Logic and Artificial Neural Network (ANN) were
developed as a technique to interpret the faults in
transformer [8-15].
In this paper an expertise method based upon the
dissolved gases analysis (DGA) techniques is developed.
Based on the interpretation of the classical techniques to
the cause of transformer faults according to the gases
concentration in oil transformer, an expertise system is
suggested to give the cause of the transformer fault with
the aid of logic functions that is used as in Fuzzy andNeural Network. A lot of real cases of analyzing the
dissolved gases were collected and used to illustrate the
validity of the proposed expertise method. In addition,
some cases from previous literatures were used to
compare their results with the proposed methods results.
2. Classical methods to diagnose transformer
faults
When thermal or electrical stresses, which affect theinsulating oil and cellulose material in transformers, are
higher than the normal permissible value, then certain
combustible gases, referred as fault gases, started to be
produced inside the transformer. The most significant
fault gases produced by oil decomposition are H2
(Hydrogen), C2H6 (Ethane), C2H4 (Ethylene) and C2H2(Acetylene) as well as Carbon monoxide (CO) and carbon
dioxide (CO2) which produce from decomposition of
insulated paper (Cellulose). The type of the faults[corona, arcing discharge (both electrical faults) and
overheating (thermal fault)] as well as their severity, play
an important role in producing different combustible
gases.
Based on DGA, many interpretative methods have
been introduced to diagnose the nature of the incipient
deterioration occurred in transformer.
Over the years, several techniques have been
developed to facilitate the diagnoses of fault gases such as
Dornenberg method [5], Roger's ratio method [3], Key
gases method [5, 16], and Duval Triangle method [4] as
well as the recently developed techniques such as neural
network and fuzzy logic.
http://www.worldsciencepublisher.org/http://www.worldsciencepublisher.org/mailto:[email protected]:[email protected]:[email protected]:[email protected]://www.worldsciencepublisher.org/7/28/2019 621-1779-1-PB
2/5
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 153
2.1. Key gases method
The key gas method interprets the incipient faults in
transformer according to some significant gases to assign
four typical fault types. These gases are called key
gases [5] which are shown in Fig. 1.
Overheated Cellulose
0
20
40
60
80
100
CO H2 C H4 C2H6 C2H2 C2H2
Gases
%
(a)
Overheated Oil
0
20
40
60
80
100
C O H2 C H4 C 2H6 C2H2 C2H2
Gases
%
(b)
Arc ing in Oil
0
20
40
60
80
100
CO H2 CH4 C2H6 C2H2 C2H2
Gases
%
(c)
Corona in Oil
0
20
40
60
80
100
CO H2 CH4 C2H6 C2H2 C2H2
Gase s
%
(d)
Fig. 1: Key gas method and four typical faults
2.2. Dornenburg ratio method
The Dornenburg method utilizes four calculated gas
ratios to indicate a single fault type from three general
fault types. This procedure requires significant levels of
the gases to the present in order for the diagnosis to be
valid. The four ratios and their diagnosis values are given[17]. Dornenburg method uses five individual gases or
four-key gas ratios, which are:-
R1=CH4/H2,
R2=C2H2/C2H4,
R3=C2H2/CH4,
R4=C2H6/C2H2.
A flow chart that describes step by step procedure to
identify the reason behind transformer faults, is found in
[5].
2.3. Roger's ratio method
This method was further modified into an IEC standard
[3], [18]. The original Rogers ratio method uses four gas
ratios which are CH4/H2, C2H6/CH4, C2H4/C2H6 and
C2H2/C2H4 for diagnosis. The refined Rogers method
uses two tables: one defined the code of the ratio, and the
other defined the diagnosis rule. The ratio C2H6/CH4only indicated a limited temperature range of
decomposition, but did not assist in further identification
of fault. Therefore, in IEC standard 599, the further
development of Roger's ratio method, was deleted.
Roger's ratio method and IEC 599 have gained popularity
in industrial practices. However, it may give no
conclusion in some cases. This is the "no decision"problem.
2.4. Duval triangle method
The Duval Triangle was first developed in 1974[19].
Three hydrocarbon gases only (CH4, C
2H
4and C
2H
2) are
only used. These three gases are generated as a result of
increasing the level of energy necessary to generate gasesin transformers in service. Figure 2 indicates the Triangle
method. In addition to the 6 zones of individual faults
(PD, D1, D2, T1, T2 or T3), an intermediate zone DT has
been attributed to mixtures of electrical and thermal faultsin the transformer.
D1 D2 DT
T3
T2
T1
PD
%CH
4
%C2H2
%C2H
4
Fig.2: Duval triangle as a diagnostic tool to detect the incipient faults in
transformer.
(T1 the zone of low thermal fault
7/28/2019 621-1779-1-PB
3/5
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 154
tree is developed which contains the information between
different faults types. Every fault type takes a number to
help us to get the main cause of the transformer fault.
This is shown in Figure 3.
Fault type
No Fault0
Fault1
No Fault Identify2
Discharge7
Thermal3
Partial8
Arcing11
Low9
High10
Low12
High13
300 and
700oC6
Thermal Cellulose14
Fig. 3: Decision fault tree
A software code in excel sheet is developed using the
logic function to get transformer fault from the four
classical method that mentioned before, the resultsdepend on the combustible gases that arise when fault
occurs in transformer. After determining the fault type
from these methods, the program decides the incipientfault type.
Figure 4 explain the form of the excel sheet that is used to
explain the main fault in transformer and Figure 5
illustrates the final report.
Fig. 4: The excel sheet that use to give the main cause of transform fault
Fig. 5: The final report
Figure 6 illustrates the flow chart that used to determine
the main cause of the fault using if statement and logicfunctions. It depends on the code from the decision tree
fault.
Fig. 6: Flow chart to determine the main cause of the transformer fault
4. Fault Type in Transformers According to
Gas Concentration
Some oil samples are taken from real transformers which
are in operation to carry out the study. In table 1, the
results by the expertise method with that take from the
chemical lab is explained. Figure 7 shows the results ofcase 1 as in table 1.
7/28/2019 621-1779-1-PB
4/5
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 155
Table 1: Comparison between the expertise method results and lab
results
CASE 1 2 3 4 5
H2 191 154 36 86 10
CH4 47 11 245 187 24
C2H2 0.0001 3 0.0001 0.0001 0.0001
C2H4 15 8 332 363 24
C2H6 43 14 144 136 372
CO 634 487 538 26 343
CO2 6623 3395 2326 198 2583
LAB.
RES.
Therm.
300-700oC
Disch. of
highenergy
Therm.
>700oC
Therm.
>700oC
Thermal
300-700oC
EXP.
METH.
Med.
thermal
fault
High
arcing
discharge
High
thermal
fault
High
thermal
fault
Med.
thermal
fault
Fig. 7: Software results for case 1
It is seen from the table that, when the C 2H2 is
increased above 2, the expected fault in transformer is
arcing discharge as in case 2. In cases 1 and 3, the
dominant gases are CH4 and C2H6, hence the expected
fault is medium thermal fault. The high thermal fault is
expected when CH4 and C2H4 are the dominant gases.
The results explain that the reliability of the expertise
method to detect the actual fault in transformer as thelaboratory does.
5. Comparison between the Expertise
Method and other Methods in Literatures
Table 2 shows that the comparison between the results
from the software code based on expertise method and the
results from other methods in literatures.
Figure 8 shows the result from the software code forsample 2 in [20].
Table 2 explains also the reliability and validation of
the proposed expertise method for detecting the inceptionfaults in transformer based on DGA.
Table 2: Comparison between the expertise method results and results
in literatures
CASE Sample 2 in
[20]
Example 2
in [21]
Case in [11] Case III in
[22]
H2 59 206 769 127
CH4 93 42 999 24
C2H2 1 221 31 81
C2H4 6 82 1599 32
C2H6 89 16 234 0.0001
CO 736 334 - 0.0001
CO2 1519 3432 - 2024
LAB.RES.
Therm.decomp.
ArcingDisch.
Thermal faultwith
temp.>700oC
Arcing notinvolve
cellulose
EXP.
METH.
Low therm.
fault
High
arcingdisch.
High thermal
fault
High
arcingdisch.
Fig. 8: Software results for sample 2 in [3]
6. Conclusions
The results from different cases under study reveal that
the proposed technique (expertise method) is reliable to
use as a diagnostic tools to detect the fault in transformer
in its early stage. The conclusions from the real cases
explain that the nature of the insulating materials involved
in the fault and the nature of the fault itself affect on
distribution of dissolved gases. Based on The results from
the software code and the lab results, we see that the
software code is reliable to diagnosis the transformer fault
based on the gas concentrations. The results from thesoftware code have a good agreement with the previous
conventional methods for the fault detection in
transformers.
References
[1] E. Dornenburg, and W. Strittmater, Monitoring Oil CoolingTransformers by Gas Analysis, Brown Boveri Review, vol. 61, pp.
238-274, 1974.
[2] IEC Publication 599, Interpretation of the Analysis of Gases inTransformers and Other Oil-Filled Electrical Equipment in Service, First
Edition, 1978.
7/28/2019 621-1779-1-PB
5/5
Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 156
[3] R. R. Rogers, IEEE and IEC Codes to Interpret Incipient Faults in
Transformers, Using Gas in Oil Analysis, IEEE Trans. on ElectricalInsulation, vol. 13, no. 5, pp. 349-354, 1978.
[4] M. Duval, Dissolved Gas Analysis: It Can Save Your Transformer,
IEEE Electrical Insulation Magazine, vol. 5, no. 6, pp. 22-27, 1989.[5] ANSI/IEEE Std C57.104-1991, IEEE Guide for The Interpretation of
Gases Generated in Oil-Immersed Transformers, IEEE Power
Engineering Society, 1992.
[6] Mukund Hazeeb, S. K. Chand, B. N. De Bhowmick, M. M.Goswami, - Dissolved Gas Analysis Some case studies, Power Grid
Corporation of India Limited.[7] CIGRE WG A2.18 Guide for Life Management Techniques for
Power Transformers, 20th January, 2003.
[8] Fbio R. Barbosa, Otaclio M. Almeida, Arthur P. S. Braga, CceroM. Tavares, Mrcio A. B. Amora, Francisco A. P., Artificial Neural
Network Application In Estimation Of Dissolved Gases In Insulating
Mineral Oil From Physical-Chemical Datas For Incipient FaultDiagnosis, IEEE Trans. Power Del., vol. 6, no. 2, pp. 601-607, Apr.
1991.
[9] CS Chang,CW Lim,Q Su, Fuzzy-Neural Approach for DissolvedGas Analysis of Power Transformer Incipient Faults", Australasian
Universities Power Engineering Conference (AUPEC 2004) 26-29
September 2004, Brisbane, Australia.[10] Diego Roberto Morais and Jacqueline Gisle Rolim,"A Hybrid
Tool for Detection of Incipient Faults in Transformers Based on theDissolved Gas Analysis of Insulating Oil", IEEE Transactions on PowerDelivery, Vol. 21, No. 2, April 2006.
[11] Rahmat-Allah Hooshmand, Mahdi Banejad, Fuzzy LogicApplication in Fault Diagnosis of Transformers Using Dissolved Gases",
Journal of Electrical Engineering & Technology, Vol. 3, No. 3, pp.
293~299, 2008.[12] Rahmatollah Hooshmand, Mahdi Banejad," Application of Fuzzy
Logic in Fault Diagnosis in Transformers using Dissolved Gas based on
Different Standards", World Academy of Science, Engineering and
Technology 17 2006.[13] J. P. Lee, D. J. Lee, S. S. Kim, P. S. Ji and J.Y. Lim," Dissolved
Gas Analysis of Power Transformer Using Fuzzy Clustering and Radial
Basis Function Neural Network", Journal of Electrical Engineering &Technology, Vol. 2, No. 2, pp. 157~164, 2007.
[14] N.A. Muhamad, B.T. Phung, T.R. Blackburn, K.X Lai,"
Comparative Study and Analysis of DGA Methods for Transformer
Mineral Oil", Journal of Electrical Engineering & Technology, Vol. 2,No. 2, pp. 157~164, 2007.
[15] Mang-Hui Wang," A Novel Extension Method for TransformerFault Diagnosis", IEEE Transactions on Power Delivery, Vol. 18, No. 1,
January 2003.
[16] J.P. Gibeault, On-line monitoring of key fault gases in transformeroil. Operational experience accumulated over the years, SYPROTEC
INC., August 1997.
[17] R.D.Stebbins, J.J.Kelly. S.D.Myers,''Power Hansformer FaultDiagnosis', 1997 IEEE PESWM, Panel Session, New York, Feb.6, 1997.
[18] IEC Publication 60599, Interpretation of the analysis of gases intransformer and other oil med electrical equipment in &, Geneva,
Switzerland, 1999.[19] M. Duval, Fault Gases Formed in Oil-Filled Breathing EHV
Power Transformers- The Interpretation Of Gas Analysis Data, IEEE
PAS Conf. Paper No C 74 476-8, 1974.
[20] Sayed A. Ward Evaluating Transformer Condition Using DGA OilAnalysis, 2003 Annual Report Conference on Electrical Insulation and
Dielectric Phenomena.[21] J. BILBAO, et. al. "Expertise Method to Diagnose Transformer
Conditions", WSEAS/IASME Conferences, Corfu, Greece, August 17-
19, 2004.[22] Joseph B. DiGiorgio, "Dissolved Gas Analysis of Mineral Oil
Insulating Fluids" , Northern Technology and testing,
http://www.nttworldwide.com.
http://www.nttworldwide.com/http://www.nttworldwide.com/http://www.nttworldwide.com/