621-1779-1-PB

Embed Size (px)

Citation preview

  • 7/28/2019 621-1779-1-PB

    1/5

    Advances in Electrical Engineering Systems (AEES) 152Vol. 1, No. 3, 2012, ISSN 2167-633XCopyright World Science Publisher, United Stateswww.worldsciencepublisher.org

    Dissolved Gas Analysis as a Diagnostic Tools for Early

    Detection of Transformer Faults

    Sherif S. M. Ghoneim1, 2

    , IEEE Member, Sayed A. Ward3

    1Canal Suez University, Suez, Egypt

    2Taif University-Taif- KSA

    3Benha University- Benha- Egypt

    E-mail:[email protected]

    Abstract- Transformers is a device on which cost effective supply of electricity mostly depends. Hence, to manage the

    life of transformers, to reduce failures and to extend the life of transformer, some measures are being adopted. Dissolved

    gas-in-oil analysis (DGA) is a common practice in transformer fault diagnosis. Some classical methods that depend on

    gases concentration in transformers oils are used to interpret transformer faults such as Dornenberg, Rogers, Duvaltriangle and key gases methods. These methods in some cases did not give the same results; therefore, an expertise

    method is developed to give the fault type according to the dissolved gases concentration in oil. A software code isdesigned using logic functions to get the type of the faults in transformers. Comparing the results from this software with

    the real laboratory cases as well as some cases in literatures is developed. The results explain the validation of software

    to detect the fault in transformer.

    Key words: Dissolved gases analysis; Transformer oil; Interpretation of transformer faults.

    1. Introduction

    The cost of unplanned outages can be reduced by theearly detection of such internal faults in transformer. The

    interpretation of transformer faults using dissolved gases

    analysis is produced using some techniques that assumedby Dornenberg, Rogers, Duval triangle and key gases

    methods [1-5].Dissolved gas analysis is the most important test in

    determining the condition of a transformer. It is the first

    indicator of a problem and can identify deterioratinginsulation and oil, over heating hot spots, partial discharge

    and arcing. Dissolved gas analysis is made on the basis of

    the standard IEC60599 [6] and IEEEC 57-104TM [7]

    standards. A four condition DGA guide to classify risks totransformers with no previous problems has been published

    in the standard IEEE C57- 104TM.Several artificial intelligence methods such as Fuzzy

    Logic and Artificial Neural Network (ANN) were

    developed as a technique to interpret the faults in

    transformer [8-15].

    In this paper an expertise method based upon the

    dissolved gases analysis (DGA) techniques is developed.

    Based on the interpretation of the classical techniques to

    the cause of transformer faults according to the gases

    concentration in oil transformer, an expertise system is

    suggested to give the cause of the transformer fault with

    the aid of logic functions that is used as in Fuzzy andNeural Network. A lot of real cases of analyzing the

    dissolved gases were collected and used to illustrate the

    validity of the proposed expertise method. In addition,

    some cases from previous literatures were used to

    compare their results with the proposed methods results.

    2. Classical methods to diagnose transformer

    faults

    When thermal or electrical stresses, which affect theinsulating oil and cellulose material in transformers, are

    higher than the normal permissible value, then certain

    combustible gases, referred as fault gases, started to be

    produced inside the transformer. The most significant

    fault gases produced by oil decomposition are H2

    (Hydrogen), C2H6 (Ethane), C2H4 (Ethylene) and C2H2(Acetylene) as well as Carbon monoxide (CO) and carbon

    dioxide (CO2) which produce from decomposition of

    insulated paper (Cellulose). The type of the faults[corona, arcing discharge (both electrical faults) and

    overheating (thermal fault)] as well as their severity, play

    an important role in producing different combustible

    gases.

    Based on DGA, many interpretative methods have

    been introduced to diagnose the nature of the incipient

    deterioration occurred in transformer.

    Over the years, several techniques have been

    developed to facilitate the diagnoses of fault gases such as

    Dornenberg method [5], Roger's ratio method [3], Key

    gases method [5, 16], and Duval Triangle method [4] as

    well as the recently developed techniques such as neural

    network and fuzzy logic.

    http://www.worldsciencepublisher.org/http://www.worldsciencepublisher.org/mailto:[email protected]:[email protected]:[email protected]:[email protected]://www.worldsciencepublisher.org/
  • 7/28/2019 621-1779-1-PB

    2/5

    Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 153

    2.1. Key gases method

    The key gas method interprets the incipient faults in

    transformer according to some significant gases to assign

    four typical fault types. These gases are called key

    gases [5] which are shown in Fig. 1.

    Overheated Cellulose

    0

    20

    40

    60

    80

    100

    CO H2 C H4 C2H6 C2H2 C2H2

    Gases

    %

    (a)

    Overheated Oil

    0

    20

    40

    60

    80

    100

    C O H2 C H4 C 2H6 C2H2 C2H2

    Gases

    %

    (b)

    Arc ing in Oil

    0

    20

    40

    60

    80

    100

    CO H2 CH4 C2H6 C2H2 C2H2

    Gases

    %

    (c)

    Corona in Oil

    0

    20

    40

    60

    80

    100

    CO H2 CH4 C2H6 C2H2 C2H2

    Gase s

    %

    (d)

    Fig. 1: Key gas method and four typical faults

    2.2. Dornenburg ratio method

    The Dornenburg method utilizes four calculated gas

    ratios to indicate a single fault type from three general

    fault types. This procedure requires significant levels of

    the gases to the present in order for the diagnosis to be

    valid. The four ratios and their diagnosis values are given[17]. Dornenburg method uses five individual gases or

    four-key gas ratios, which are:-

    R1=CH4/H2,

    R2=C2H2/C2H4,

    R3=C2H2/CH4,

    R4=C2H6/C2H2.

    A flow chart that describes step by step procedure to

    identify the reason behind transformer faults, is found in

    [5].

    2.3. Roger's ratio method

    This method was further modified into an IEC standard

    [3], [18]. The original Rogers ratio method uses four gas

    ratios which are CH4/H2, C2H6/CH4, C2H4/C2H6 and

    C2H2/C2H4 for diagnosis. The refined Rogers method

    uses two tables: one defined the code of the ratio, and the

    other defined the diagnosis rule. The ratio C2H6/CH4only indicated a limited temperature range of

    decomposition, but did not assist in further identification

    of fault. Therefore, in IEC standard 599, the further

    development of Roger's ratio method, was deleted.

    Roger's ratio method and IEC 599 have gained popularity

    in industrial practices. However, it may give no

    conclusion in some cases. This is the "no decision"problem.

    2.4. Duval triangle method

    The Duval Triangle was first developed in 1974[19].

    Three hydrocarbon gases only (CH4, C

    2H

    4and C

    2H

    2) are

    only used. These three gases are generated as a result of

    increasing the level of energy necessary to generate gasesin transformers in service. Figure 2 indicates the Triangle

    method. In addition to the 6 zones of individual faults

    (PD, D1, D2, T1, T2 or T3), an intermediate zone DT has

    been attributed to mixtures of electrical and thermal faultsin the transformer.

    D1 D2 DT

    T3

    T2

    T1

    PD

    %CH

    4

    %C2H2

    %C2H

    4

    Fig.2: Duval triangle as a diagnostic tool to detect the incipient faults in

    transformer.

    (T1 the zone of low thermal fault

  • 7/28/2019 621-1779-1-PB

    3/5

    Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 154

    tree is developed which contains the information between

    different faults types. Every fault type takes a number to

    help us to get the main cause of the transformer fault.

    This is shown in Figure 3.

    Fault type

    No Fault0

    Fault1

    No Fault Identify2

    Discharge7

    Thermal3

    Partial8

    Arcing11

    Low9

    High10

    Low12

    High13

    300 and

    700oC6

    Thermal Cellulose14

    Fig. 3: Decision fault tree

    A software code in excel sheet is developed using the

    logic function to get transformer fault from the four

    classical method that mentioned before, the resultsdepend on the combustible gases that arise when fault

    occurs in transformer. After determining the fault type

    from these methods, the program decides the incipientfault type.

    Figure 4 explain the form of the excel sheet that is used to

    explain the main fault in transformer and Figure 5

    illustrates the final report.

    Fig. 4: The excel sheet that use to give the main cause of transform fault

    Fig. 5: The final report

    Figure 6 illustrates the flow chart that used to determine

    the main cause of the fault using if statement and logicfunctions. It depends on the code from the decision tree

    fault.

    Fig. 6: Flow chart to determine the main cause of the transformer fault

    4. Fault Type in Transformers According to

    Gas Concentration

    Some oil samples are taken from real transformers which

    are in operation to carry out the study. In table 1, the

    results by the expertise method with that take from the

    chemical lab is explained. Figure 7 shows the results ofcase 1 as in table 1.

  • 7/28/2019 621-1779-1-PB

    4/5

    Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 155

    Table 1: Comparison between the expertise method results and lab

    results

    CASE 1 2 3 4 5

    H2 191 154 36 86 10

    CH4 47 11 245 187 24

    C2H2 0.0001 3 0.0001 0.0001 0.0001

    C2H4 15 8 332 363 24

    C2H6 43 14 144 136 372

    CO 634 487 538 26 343

    CO2 6623 3395 2326 198 2583

    LAB.

    RES.

    Therm.

    300-700oC

    Disch. of

    highenergy

    Therm.

    >700oC

    Therm.

    >700oC

    Thermal

    300-700oC

    EXP.

    METH.

    Med.

    thermal

    fault

    High

    arcing

    discharge

    High

    thermal

    fault

    High

    thermal

    fault

    Med.

    thermal

    fault

    Fig. 7: Software results for case 1

    It is seen from the table that, when the C 2H2 is

    increased above 2, the expected fault in transformer is

    arcing discharge as in case 2. In cases 1 and 3, the

    dominant gases are CH4 and C2H6, hence the expected

    fault is medium thermal fault. The high thermal fault is

    expected when CH4 and C2H4 are the dominant gases.

    The results explain that the reliability of the expertise

    method to detect the actual fault in transformer as thelaboratory does.

    5. Comparison between the Expertise

    Method and other Methods in Literatures

    Table 2 shows that the comparison between the results

    from the software code based on expertise method and the

    results from other methods in literatures.

    Figure 8 shows the result from the software code forsample 2 in [20].

    Table 2 explains also the reliability and validation of

    the proposed expertise method for detecting the inceptionfaults in transformer based on DGA.

    Table 2: Comparison between the expertise method results and results

    in literatures

    CASE Sample 2 in

    [20]

    Example 2

    in [21]

    Case in [11] Case III in

    [22]

    H2 59 206 769 127

    CH4 93 42 999 24

    C2H2 1 221 31 81

    C2H4 6 82 1599 32

    C2H6 89 16 234 0.0001

    CO 736 334 - 0.0001

    CO2 1519 3432 - 2024

    LAB.RES.

    Therm.decomp.

    ArcingDisch.

    Thermal faultwith

    temp.>700oC

    Arcing notinvolve

    cellulose

    EXP.

    METH.

    Low therm.

    fault

    High

    arcingdisch.

    High thermal

    fault

    High

    arcingdisch.

    Fig. 8: Software results for sample 2 in [3]

    6. Conclusions

    The results from different cases under study reveal that

    the proposed technique (expertise method) is reliable to

    use as a diagnostic tools to detect the fault in transformer

    in its early stage. The conclusions from the real cases

    explain that the nature of the insulating materials involved

    in the fault and the nature of the fault itself affect on

    distribution of dissolved gases. Based on The results from

    the software code and the lab results, we see that the

    software code is reliable to diagnosis the transformer fault

    based on the gas concentrations. The results from thesoftware code have a good agreement with the previous

    conventional methods for the fault detection in

    transformers.

    References

    [1] E. Dornenburg, and W. Strittmater, Monitoring Oil CoolingTransformers by Gas Analysis, Brown Boveri Review, vol. 61, pp.

    238-274, 1974.

    [2] IEC Publication 599, Interpretation of the Analysis of Gases inTransformers and Other Oil-Filled Electrical Equipment in Service, First

    Edition, 1978.

  • 7/28/2019 621-1779-1-PB

    5/5

    Sherif S. M. Ghoneim & Sayed A. Ward, AEES, Vol. 1, No. 3, pp. 152-156, 2012 156

    [3] R. R. Rogers, IEEE and IEC Codes to Interpret Incipient Faults in

    Transformers, Using Gas in Oil Analysis, IEEE Trans. on ElectricalInsulation, vol. 13, no. 5, pp. 349-354, 1978.

    [4] M. Duval, Dissolved Gas Analysis: It Can Save Your Transformer,

    IEEE Electrical Insulation Magazine, vol. 5, no. 6, pp. 22-27, 1989.[5] ANSI/IEEE Std C57.104-1991, IEEE Guide for The Interpretation of

    Gases Generated in Oil-Immersed Transformers, IEEE Power

    Engineering Society, 1992.

    [6] Mukund Hazeeb, S. K. Chand, B. N. De Bhowmick, M. M.Goswami, - Dissolved Gas Analysis Some case studies, Power Grid

    Corporation of India Limited.[7] CIGRE WG A2.18 Guide for Life Management Techniques for

    Power Transformers, 20th January, 2003.

    [8] Fbio R. Barbosa, Otaclio M. Almeida, Arthur P. S. Braga, CceroM. Tavares, Mrcio A. B. Amora, Francisco A. P., Artificial Neural

    Network Application In Estimation Of Dissolved Gases In Insulating

    Mineral Oil From Physical-Chemical Datas For Incipient FaultDiagnosis, IEEE Trans. Power Del., vol. 6, no. 2, pp. 601-607, Apr.

    1991.

    [9] CS Chang,CW Lim,Q Su, Fuzzy-Neural Approach for DissolvedGas Analysis of Power Transformer Incipient Faults", Australasian

    Universities Power Engineering Conference (AUPEC 2004) 26-29

    September 2004, Brisbane, Australia.[10] Diego Roberto Morais and Jacqueline Gisle Rolim,"A Hybrid

    Tool for Detection of Incipient Faults in Transformers Based on theDissolved Gas Analysis of Insulating Oil", IEEE Transactions on PowerDelivery, Vol. 21, No. 2, April 2006.

    [11] Rahmat-Allah Hooshmand, Mahdi Banejad, Fuzzy LogicApplication in Fault Diagnosis of Transformers Using Dissolved Gases",

    Journal of Electrical Engineering & Technology, Vol. 3, No. 3, pp.

    293~299, 2008.[12] Rahmatollah Hooshmand, Mahdi Banejad," Application of Fuzzy

    Logic in Fault Diagnosis in Transformers using Dissolved Gas based on

    Different Standards", World Academy of Science, Engineering and

    Technology 17 2006.[13] J. P. Lee, D. J. Lee, S. S. Kim, P. S. Ji and J.Y. Lim," Dissolved

    Gas Analysis of Power Transformer Using Fuzzy Clustering and Radial

    Basis Function Neural Network", Journal of Electrical Engineering &Technology, Vol. 2, No. 2, pp. 157~164, 2007.

    [14] N.A. Muhamad, B.T. Phung, T.R. Blackburn, K.X Lai,"

    Comparative Study and Analysis of DGA Methods for Transformer

    Mineral Oil", Journal of Electrical Engineering & Technology, Vol. 2,No. 2, pp. 157~164, 2007.

    [15] Mang-Hui Wang," A Novel Extension Method for TransformerFault Diagnosis", IEEE Transactions on Power Delivery, Vol. 18, No. 1,

    January 2003.

    [16] J.P. Gibeault, On-line monitoring of key fault gases in transformeroil. Operational experience accumulated over the years, SYPROTEC

    INC., August 1997.

    [17] R.D.Stebbins, J.J.Kelly. S.D.Myers,''Power Hansformer FaultDiagnosis', 1997 IEEE PESWM, Panel Session, New York, Feb.6, 1997.

    [18] IEC Publication 60599, Interpretation of the analysis of gases intransformer and other oil med electrical equipment in &, Geneva,

    Switzerland, 1999.[19] M. Duval, Fault Gases Formed in Oil-Filled Breathing EHV

    Power Transformers- The Interpretation Of Gas Analysis Data, IEEE

    PAS Conf. Paper No C 74 476-8, 1974.

    [20] Sayed A. Ward Evaluating Transformer Condition Using DGA OilAnalysis, 2003 Annual Report Conference on Electrical Insulation and

    Dielectric Phenomena.[21] J. BILBAO, et. al. "Expertise Method to Diagnose Transformer

    Conditions", WSEAS/IASME Conferences, Corfu, Greece, August 17-

    19, 2004.[22] Joseph B. DiGiorgio, "Dissolved Gas Analysis of Mineral Oil

    Insulating Fluids" , Northern Technology and testing,

    http://www.nttworldwide.com.

    http://www.nttworldwide.com/http://www.nttworldwide.com/http://www.nttworldwide.com/