5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
1/25
Applications & ToolsAnswers for industry.
Cover
Configuration of Direct Starters withthe APL Channel Block FbSwtMMSin SIMATIC PCS 7
SIMATIC PCS 7 V8.0
Application Example October 2012
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
2/25
2Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
Siemens Industry Online SupportThis document is an article from the Siemens Industry Online Support. Thefollowing link takes you directly to the download page of this document:
http://support.automation.siemens.com/WW/view/en/64182525
Caution:
The functions and solutions described in this entry are mainly limited to therealization of the automation task. In addition, please note that suitable securitymeasures in compliance with the applicable Industrial Security standards must betaken, if your system is interconnected with other parts of the plant, the companysnetwork or the Internet. For further information on this issue, please refer to EntryID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404
Please also use our technical forum from the Siemens Industry Online Supportactively in this context. Add your questions, suggestions and problems and discussthem in our large forum community:
http://www.siemens.com/forum-applications
http://support.automation.siemens.com/WW/view/en/64182525http://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/50203404http://www.automation.siemens.com/WW/forum/guests/Conference.aspx?ForumID=230&Language=enhttp://www.automation.siemens.com/WW/forum/guests/Conference.aspx?ForumID=230&Language=enhttp://www.automation.siemens.com/WW/forum/guests/Conference.aspx?ForumID=230&Language=enhttp://support.automation.siemens.com/WW/view/en/50203404http://support.automation.siemens.com/WW/view/en/641825255/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
3/25
Configuration of Direct StartersV 1.0, Entry ID: 64182525 3
CopyrightS
iemensAG
2012Allrightsreserved
s
SIMATIC PCS 7 V8.0
Configuration of Direct Starterswith the APL Channel BlockFbSwtMMS in SIMATIC PCS 7
Application Example
Description of the taskand solution 1APL channel blockMotor Management
Starter (FbSwtMMS)2
Configuration 3
Links 4
History 5
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
4/25
Warranty and Liability
4Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
Warranty and LiabilityNote
The application examples are not binding and do not claim to be completeregarding configuration, equipment and any eventuality. The applicationexamples do not represent customer-specific solutions. They are only intendedto provide support for typical applications. You are responsible for ensuring thatthe described products are used correctly. The application examples do notrelieve you of the responsibility to use sound practices in application, installation,operation and maintenance. When using these application examples, yourecognize we will not be liable for any damage/claims beyond the liability clausedescribed. We reserve the right to make changes to these application examplesat any time without prior notice. If there are any deviations between therecommendation provided in this application example and other Siemenspublications (e.g. catalogs), the contents of the other documentation shall havepriority.
We accept no liability for information contained in this document.
Any claim against us based on whatever legal reason - resulting from the use ofthe examples, information, programs, engineering and performance data etc.,described in this Application Example shall be excluded. Such an exclusion shallnot apply in the case of mandatory liability, e.g. under the German Product LiabilityAct (Produkthaftungsgesetz), in cases of intent, gross negligence, or injury of life,body or health, guarantee for the quality of a product, fraudulent concealment of adeficiency or violation of fundamental contractual obligations (wesentlicheVertragspflichten). The damages for a breach of substantial contractual obligationsare, however, limited to the foreseeable damage, typical for the type of contract,except in the event of intent or gross negligence or injury to life, body or health.
The above provisions do not imply a change in the burden of proof to yourdetriment.
Any form of duplication or distribution of these application examples or excerptshereof is prohibited without the express consent of Siemens Industry Sector.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
5/25
Table of Contents
Configuration of Direct StartersV 1.0, Entry ID: 64182525 5
CopyrightS
iemensAG
2012Allrightsreserved
Table of ContentsWarranty and Liability..............................................................................................41 Description of the task and solution .............................................................6
1.1 Task..................................................................................................61.2 Solution.............................................................................................61.2.1 Main contents....................................................................................61.2.2 Restriction .........................................................................................71.2.3 Validity ..............................................................................................7
2 APL channel block Motor Management Starter (FbSwtMMS)...................82.1 Channel block....................................................................................82.2 Template.........................................................................................12
3 Configuration................................................................................................133.1 Requirement....................................................................................133.2
Importing the EDD/GSD file .............................................................13
3.3 Hardware configuration....................................................................143.4 CFC engineering .............................................................................183.5 OS-Runtime.....................................................................................24
4 Links .............................................................................................................255 History ..........................................................................................................25
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
6/25
1 Description of the task and solution
6Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
1 Description of the task and solution
1.1 TaskIn modern automation projects, not all the components are supplied by the samecompany. You often have the situation that the supplier of the process controlsystem is not the same as the supplier of the drives.
Moreover, not every customer needs the complete and extensive range offunctions for the drives, which can be retrieved by specifically tailored blocklibraries, most of them chargeable.
1.2 Solution
For the integration of the direct starter drives Siemens therefore offers a modern
motor channel block FbSwtMMS, which is part of the PCS 7 standard libraryAdvances Process Library (APL), allowing for an integration into PCS 7 of all thedrives which support the standard profiles of the technical specification Profiles forLow Voltage Switchgear Devices.
In addition, this variant is also interesting for the integration of Siemens drives suchas SIMOCODE pro. The complete performance range is not always needed.
By interconnecting the motor channel block FbSwtMMS with the APL functionblock MotRevL, the complete function range of the PCS 7 operation, monitoringand supervision is available.
The configuration, parameterization and commissioning of the drives takes place inthe usual PCS 7 environment.
1.2.1 Main contents
The integration of a directly starting drive is explained and completely configuredas an example with a SIMOCODE pro V and a prefabricated template, which isalso a part of the PCS 7 Advanced Process Library (APL).
The focus will be on the following issues:
Channel block FbSwtMMS
Structure of the standard profiles
Integration of the template
Hardware configuration
CFC engineering
Parameterization of the drives via PDM
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
7/25
1 Description of the task and solution
Configuration of Direct StartersV 1.0, Entry ID: 64182525 7
CopyrightS
iemensAG
2012Allrightsreserved
1.2.2 Restriction
This configuration instruction describes the integration of directly starting driveswhich support the standard protocol. As an example the Siemens driveSIMOCODE pro V is configured, all the other drives will be configured in exactlythe same way.
This application does not refer to the SIMOCODE library which is availableseparately for a fee and covers the complete performance range of theSIMOCODE drives.
1.2.3 Validity
This Application Example is valid for PCS 7 V 8.0 and higher.
All drives which support the standard profiles of the technical specification Profilesfor Low Voltage Switchgear Devices and for which a compatible Electronic DeviceDescription File (EDD) or a General Station Description (GSD) is available, can beintegrated in PCS 7 V8.0.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
8/25
2 APL channel block
8Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
2 APL channel blockMotor Management Starter (FbSwtMMS)With the APL channel block Motor Management Starter all direct starter driveswhich support the standard profiles of the technical specification Profiles for LowVoltage Switchgear Devices can be integrated in the PCS 7.
This enables you to integrate directly starting drives from different manufacturersinto PCS 7.
The channel block is part of the PCS 7 Advanced Process Library (APL).Therefore, there will be no further costs from buying an add-on or an externallibrary.
In addition the direct starters, wherever they come from, are configured in the sameway in the PCS 7 environment.
2.1 Channel block
The channel block was developed according to the profiles for Motor ManagementStarter, which are described in the technical specification Profiles for Low voltageSwitchgear Devices (LVSG).
The Motor Management Starter profile prescribes that the format 0 has to beused for the data to the process control system and also for the data from the
process control system.
In case of the SIMOCODE pro V, this would be the basic type 2 with 4 bytes inputand 2 bytes output data.
NOTICE The connection of field devices into the PCS 7 via PROFINET is only entirelysupported with PCS 7 V8.0 SP1.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
9/25
2 APL channel block
Configuration of Direct StartersV 1.0, Entry ID: 64182525 9
CopyrightS
iemensAG
2012Allrightsreserved
ExplanationThe 4 bytes entry data are reflected in the channel block in the two inputs PZDIn1
and PZDIn2 with one word each.The 2 bytes output data are represented with the output PZDOut1 in the block.
The input and output files are inverted as compared to the tables. In the followingscreenshot, the value 16#2400 is pending at the output PZDOut1, the value 24being the higher byte and 00 the lower byte.
The two individual bytes are read from right to left.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
10/25
2 APL channel block
10Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
ReservedReservedReservedReservedManufacturer
Specific1Manufacturer
Specific2Manufacturer
Specific3Manufacturer
Specific41
Run
ReverseOff
Run
Forward
Self
Test
Emergency
Start
Auto
Mode
Trip
ResetReserved0
89101112131415
01234567
Bits: (0-7 for byte constructions; 0-15 for word constructions)
Byte
16#2400
Higher Byte
Lower Byte
24
00
24
42
16#2400
00
00
ReservedReservedReservedReservedManufacturer
Specific1Manufacturer
Specific2Manufacturer
Specific3Manufacturer
Specific41
Run
ReverseOff
Run
Forward
Self
Test
Emergency
Start
Auto
Mode
Trip
ResetReserved0
89101112131415
01234567
Bits: (0-7 for byte constructions; 0-15 for word constructions)
Byte
16#2400
Higher Byte
Lower Byte
24
00
24
42
16#2400
00
00
In the table you can see that it is a directly starting motor, which currently runsforward in automatic mode (auto Mode and Run Forward).
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
11/25
2 APL channel block
Configuration of Direct StartersV 1.0, Entry ID: 64182525 11
CopyrightS
iemensAG
2012Allrightsreserved
Input data from the field device to the controllerTable 2-1
Bits: (0-7 for byte constructions; 0-15 for word constructions)
7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8
23 22 21 20 19 18 17 16
Byte
31 30 29 28 27 26 25 24
0 Warning FaultAutoMode
Lock-OutTime
OverloadWarning
RunForward
OffRun
Reverse
default 0 0 1 0 0 0 1 0
1Manufacturer
Specific4
Manufacturer
Specific3
Manufacturer
Specific2
Manufacturer
Specific1
Manufacturer
Specific6
Manufacturer
Specific5Reserved Reserved
2 Motor Current High (% / Is)
default Dont Care
3 Motor Current Low (% / Is)
default Dont Care
Output data from the controller to the field deviceTable 2-2
Bits: (0-7 for byte constructions; 0-15 for word constructions)
7 6 5 4 3 2 1 0Byte
15 14 13 12 11 10 9 8
0 Reserved TripReset
AutoMode
EmergencyStart
SelfTest
RunForward
OffRun
Reverse
1
ManufacturerSpecific4
ManufacturerSpecific3
ManufacturerSpecific2
ManufacturerSpecific1
Reserved Reserved Reserved Reserved
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
12/25
2 APL channel block
12Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
2.2 Template
The template provided by the Advanced Process Library (APL) represents acomplete configured CFC plan, where the APL channel block FbSwtMMS islogically interconnected with the APL function block MotRevL, thus offering aready-to-use automation solution with the following functions:
APL faceplates for PCS 7-conform operator control & monitoring.
Switching between local and remote control
Display of the current in the faceplate
The same operator control & monitoring no matter which motor manufacturer
No additional libraries required.
The template is based exclusively on the PCS 7 APL blocks, which are available asa standard from PCS 7 V8.0 onwards.
In the template, the channel block FbSwtMMS is interconnected with the motorblock MotRevL for a motor that can be switched on in forward and reverse mode.Three interlock blocks are provided for the interlocking with acknowledgment(Protect), interlocking without acknowledgement (Interlock) and the permit forswitching on (Permit).
Where to get the template and the channel blockThe channel block and the template are part of the PCS 7 V8.0 and do not requirean additional installation.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
13/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 13
CopyrightS
iemensAG
2012Allrightsreserved
3 Configuration
3.1 RequirementA prepared PCS 7 project is required, where at least the CPU, the communicationprocessor and the DP master line, and all the communication paths have alreadybeen configured.
3.2 Importing the EDD/GSD file
In the Siemens device catalog you will find a great variety of field devices. If youcannot find a field device you use in this catalog, you can install the EDD or GSDfile for your field device. After the installation, the field device will be available in thedevice catalog with an object symbol, just as you know it.
You can get the EDD or GSD file from your field device supplier almost always.
Difference between EDD and GSD filesThe General Station Description (GSD) contains DP slave transmission features ina standard form. The use of a GSD file facilitates the configuration and integrationof field devices of different manufacturers in a DP master system.
The Electronic Device Description (EDD) always contains the GSD file and addsthe device features of the field device. The EDD files are read in by theconfiguration tools, e.g. SIMATIC PDM and simplify the configuration,commissioning and maintenance of the filed devices.
NOTICE When a direct starter is to be integrated by means of a GSD file, it cannot beconfigured by means of the PDM, but only by means of a configuration tool or onsite by means of an input module.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
14/25
3 Configuration
14Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
3.3 Hardware configuration
1. Open the hardware configuration (HW Config).
2. In the device catalog, change the profile to "Standard".The device tree then only lists those field devices which support the standardprotocols.
3. In the device catalog, choose the direct starter you use, e.g. PROFIBUS DP >Additional Field Devices > Switching Devices > SIMOCODE > SIMOCODE proV (GSD V1.3).
4. Drag and drop your direct starter to the PROFIBUS master system.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
15/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 15
CopyrightS
iemensAG
2012Allrightsreserved
5. Assign the new PROFIBUS address.
6. Select the basic type 2 with 4 byte input data and 2 byte output data, and drag
and drop it to the respective slot.
7. Select the line with the input and output addresses, open Object Propertieswith the right mouse button and select Object Properties
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
16/25
3 Configuration
16Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
8. Assign the initial addresses of the input and output addresses.
NOTICE Make sure that the initial addresses of the input and output addresses begin with
the same start value.
Note The FbSwtMMS block must be incorporated in the same cycle (OB) as therespective hardware.
Assign a symbolic address9.
Select the line with the addresses again and open the Edit Symbolswindow with a click on the right mouse button.
10.Assign the symbolic names in the Symbol column.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
17/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 17
CopyrightS
iemensAG
2012Allrightsreserved
PDMWhen a motor starter is integrated via GSD, it cannot be configured by means of
PDM, but only with a separate configuration tool.
11.For the configuration via PDM, select your motor starter, in this caseSIMOCODE, and open the motor properties with the right mouse buttonObject Properties....
12.Select the tab General and activate the option box Configuration via PDM.
13.After the activation, double-click on the symbol figure of the direct starter toopen PDM. You can now configure the direct starter.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
18/25
3 Configuration
18Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
3.4 CFC engineering
1. Switch to the SIMATIC Manager.
2. Select File > Open in the menu bar.
3. In the window Open Project go to the tab Libraries and select the PCS 7AP Library V80.
4. In the PCS 7 Library V80, select the Templates folder.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
19/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 19
CopyrightS
iemensAG
2012Allrightsreserved
5. Select the ManagedMotorStarter template, open the context menu and selectCopy.
6. Go to the technical hierarchy and add the copied template with the right mousebutton by selecting paste.
7. Rename the template.
8. Open the template.
9. Select the MotRevL block, click on the right mouse button and select ObjectProperties.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
20/25
3 Configuration
20Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
10.Assign a meaningful name under Name:
Interconnect a symbolic address11.
In the CFC plan, select the input PZDIn1 of the FbSwtMMS block. Open thecontext menu with the right mouse button, and select Interconnection toAddress.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
21/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 21
CopyrightS
iemensAG
2012Allrightsreserved
12.Select the first input word of the symbolic interconnection here, in this caseIW512_SC.All the other input and output words are automatically connected by the driver
wizard.
Note The telegram type used must also be stored in the direct starter. You can make
this setting by means of the respective configuration tool or when you integratedthe EDD via PDM.
The driver wizard checks the number of input data, compares it with those storedin the device and if they dont match, it generates an error message.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
22/25
3 Configuration
22Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
13.The output Imax for the maximum motor current with reference to the nominalcurrent is interconnected with the input UserAna1 of the MotRevL. Select the input UserAna1 and open the context menu with the right mouse
button, then select Object Properties.
14.Select Value [REAL] Value, open the context menu and select Properties.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
23/25
3 Configuration
Configuration of Direct StartersV 1.0, Entry ID: 64182525 23
CopyrightS
iemensAG
2012Allrightsreserved
15.Enter a meaningful name like Imax in the entry box Identifier. This name willlater be displayed in the faceplate next to the Imax value.
Compiling and loading of the AS and OS16.Compile and load the AS.
17.Compile and load the OS.
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
24/25
3 Configuration
24Configuration of Direct Starters
V 1.0, Entry ID: 64182525
CopyrightS
iemensAG
2012Allrightsreserved
3.5 OS-Runtime
In OS Runtime you operate and monitor the field device via the usual faceplate ofthe MotRevL.
The operator always sees and operates the same faceplates, no matter how manydifferent drives of different manufacturers are integrated in the system operation.
This guarantees a uniform operating concept, a clearer structure and avoidsoperating mistakes.
Faceplate of the MotRevL
5/26/2018 64182525 Configuration of Direct Starters With FbSwtMMS En
25/25
4 Links
Configuration of Direct StartersV 1.0, Entry ID: 64182525 25
CopyrightS
iemensAG
2012Allrightsreserved
4 LinksThe following list is by no means complete and only provides a selection of
appropriate information.
Table 4-1
Topic Title
1 Reference to this document http://support.automation.siemens.com/WW/view/en/64182525
2 Siemens Industry Online Support http://support.automation.siemens.com
3 PCS 7 quick start (start page,landing page)
http://support.automation.siemens.com/WW/view/en/63481413
5 History
Table 5-1
Version Date ChangeV1.0 10/2012 First issue
http://support.automation.siemens.com/WW/view/en/64182525http://support.automation.siemens.com/http://support.automation.siemens.com/WW/view/en/63481413http://support.automation.siemens.com/WW/view/en/63481413http://support.automation.siemens.com/http://support.automation.siemens.com/WW/view/en/64182525